Unit 2
Unit 2
2
Please read this disclaimer before proceeding:
This document is confidential and intended solely for the educational purpose of
RMK Group of Educational Institutions. If you have received this document
through email in error, please notify the system manager. This document
contains proprietary information and is intended only to the respective group /
learning community as intended. If you are not the addressee you should not
disseminate, distribute or copy through e-mail. Please notify the sender
immediately by e-mail if you have received this document by mistake and delete
this document from your system. If you are not the intended recipient you are
notified that disclosing, copying, distributing or taking any action in reliance on
the contents of this information is strictly prohibited.
3
22EC401 CONTROL ENGINEERING
Department : ECE
Batch/Year : 2023-2027/II
Created by : Mr. A. Sivakumar AP/ECE
Ms. K. Jeevitha AP/ECE
4
Table of Contents
S.No Title Page No
1 Course Objectives 6
5 CO - PO/PSO Mapping 11
6 Lecture Plan 12
8 Lecture Notes 17
9 Assignments 83
15 Assessment Schedule 99
5
1. Course Objectives
6
2.Pre Requisites
(Course Names with Code)
7
3. SYLLABUS
8
UNIT IV STABILITY AND COMPENSATOR DESIGN
Characteristics equation – Routh Hurwitz criterion- Root locus
construction – Effect of Lag, lead and lag-lead compensation on
frequency response - Design of Lag, lead and lag lead compensator
using bode plots.
LIST OF EXPERIMENTS
8. Sketch the root locus of the given transfer function and locate the
closed loop poles for different values of open loop gain (K) using
MATLAB.
9
4. Course outcomes
10
CO
5.CO- PO/PSO Mapping
PO10
PO11
PO12
PSO1
PSO2
PSO3
PO4
PO1
PO2
PO3
PO5
PO6
PO7
PO9
P08
CO6 CO5 CO4 CO3 CO2 CO1
√ √ √ √ √ √ √ √ √ √ √ √
√ √ √ √ √ √ √ √ √ √ √ √
√ √ √ √ √ √ √ √ √ √ √
√ √ √ √ √ √ √ √ √ √ √
√ √ √ √ √ √ √ √ √ √ √
√ √ √ √ √ √ √ √ √ √ √ √
11
6.Lecture Plan
UNIT II TIME RESPONSE ANALYSIS
Taxonomy
pertaining
Proposed
Delivery
Mode of
Periods
Actual
No. of
Date
level
S.No
date
CO
Topic
12
7.Activity based learning
Activity 1
13
7.Activity based learning –Crossword Puzzle
UNIT II
1. A conditionally stable system exhibits poor stability at
__________ values of open loop gain.(From Left to
Right)
14
7.Activity based learning –Crossword Puzzle
UNIT II
15
Unit II Crossword puzzle Answers
Questions Answers
1 Reduced
2 Smaller
3 Transient
4 Two
5 Ramp
6 Stable
7 No
8 Simple
9 Linear
10 Decays
16
8.LECTURE NOTES
2.INTRODUCTION
We can analyze the response of the control systems in both the time
domain and the frequency domain. Let us now discuss about the time response
analysis of control systems.
In control system, input varies from one instant to another instant. Based
on input, the system produces the output. The behavior of the system under such
condition is described by its dynamic response or time response
2.1 DEFINITION OF TIME RESPONSE
The time response of the system is the output of the system as a function
of time when subjected to a given input. In time response analysis basically system
is tested in time instead of frequency.
The time response of a system consists of two parts
Transient Response
Steady State Response
Therefore, Total Time Response = Transient Response + Steady State Response
Mathematically, we can write the time response C(t) as
17
Fig . 2.1 Response of a System
18
Impulse Input
The impulse signal has zero amplitude everywhere except at the origin.
Mathematically it is represented as,
ᵟ(t) =1 t=0
=0 t≠0 -----(2.4)
Laplace transform of unit step signal ᵟ(t) is
L[ᵟ(t)] = 1
Parabolic Input Fig.2.4 Unit impulse
Signal
The instantaneous value of a parabolic signal varies a square of time from an initial
value of zero at t=0
r(t) = A𝑡 2 t≥0
=0 t<0 -----(2.5)
L[r(t)] = 𝐿[𝑡 2 ] =
1 Fig.2.5 Parabolic Signal
𝑠3
System can be modeled in different ways. In that transfer function is one of the
methods.
The transfer function is obtained by differential equations governing the system. The
input-output relationship of linear time invariant system is defined by the transfer
function.
𝑛 𝑚
𝑘
𝑑 𝑐 𝑡 𝑏𝑘 𝑑𝑘 𝑟 𝑡
𝑎𝑘 =
𝑑𝑡𝑘 𝑑𝑡𝑘
𝑘=0 𝑘=0
19
𝑑𝑛 𝑐 𝑡 𝑑 𝑛−1 𝑐 𝑡 𝑑𝑐 𝑡
𝑎𝑛 𝑛
+ 𝑎𝑛−1 𝑛−1
+ ⋯ + 𝑎1 + 𝑎0 𝑐(𝑡)
𝑑𝑡 𝑑𝑡 𝑑𝑡
𝑑𝑚 𝑟 𝑡 𝑑 𝑚−1 𝑟 𝑡 𝑑𝑟 𝑡
= 𝑏𝑚 + 𝑏𝑛−1 + ⋯ + 𝑏1 + 𝑏0 𝑟(𝑡)
𝑑𝑡 𝑚 𝑑𝑡 𝑚−1 𝑑𝑡
The type number is specified for loop transfer function G(s)H(s). The number of
poles of the loop transfer function lying at the origin decides the type number of the
system. In general, if N is the number of poles at the origin then the type number is
N.
20
The loop transfer function can be expressed as a ratio of two polynomials in s.
K = Constant
21
We know that the transfer function of the closed loop control system has unity
negative feedback as
𝐶(𝑠) 𝐺(𝑠)
𝑅(𝑠)
= 1+𝐺(𝑠) ---(2.8)
1
Substitute G(s)= in equation (2.8)
𝑠𝑇
1
𝐶(𝑠) 𝑠𝑇 1
= =
𝑅(𝑠) 1 + 1 𝑠𝑇 + 1
𝑠𝑇
The power of s is one in the denominator term. Hence, the above transfer
function is of the first order and the system is said to be the first order system.
Where,
C(s) is the Laplace transform of the output signal c(t),
R(s) is the Laplace transform of the input signal r(t), and
T is the time constant.
Consider the unit step signal as an input to first order system.
𝑠𝑜, r(t)=u(t)
Apply Laplace transform on both the sides.
1
𝑅(𝑠) = ---(2.9)
𝑠
1
Consider the equation, 𝐶(𝑠) = (𝑠𝑇+1)𝑅(𝑠) ---(2.10)
1
Substitute 𝑅(𝑠) = in equation(2.10)
𝑠
1 1 1
𝐶(𝑠) = ( )( ) =
𝑠𝑇 + 1 𝑠 𝑠(𝑠𝑇 + 1)
Do partial fractions of C(s).
1 𝐴 𝐵
𝐶(𝑠) = 𝑠(𝑠𝑇+1) = 𝑠 + 𝑠𝑇+1 ---(2.11)
1 𝐴(𝑠𝑇 + 1) + 𝐵𝑠
⇒ =
𝑠(𝑠𝑇 + 1) 𝑠(𝑠𝑇 + 1)
On both the sides, the denominator term is the same. So, they will get cancelled by
each other. Hence, equate the numerator terms.
1 = 𝐴(𝑠𝑇 + 1) + 𝐵𝑠
22
By equating the constant terms on both the sides, you will get A = 1.
Substitute, A = 1 and equate the coefficient of the s terms on both the sides.
0 = 𝑇 + 𝐵 ⇒ 𝐵 = −𝑇
The value of the unit step response, c(t) is zero at t = 0 and for all negative values
of t. It is gradually increasing from zero value and finally reaches to one in steady
state. So, the steady state value depends on the magnitude of the input.
23
2.6 TIME RESPONSE ANALYSIS OF SECOND ORDER
SYSTEM
Consider the following block diagram of closed loop control system. Here,
2
𝜔𝑛
an open loop transfer function, is connected with a unity negative
𝑠(𝑠+2𝛿𝜔𝑛 )
feedback.
We know that the transfer function of the closed loop control system having unity
negative feedback as
𝐶(𝑠) 𝐺(𝑠)
=
𝑅(𝑠) 1 + 𝐺(𝑠)
2
𝜔𝑛
Substitute 𝐺(𝑠) = in the above equation.
𝑠(𝑠+2𝛿𝜔𝑛 )
𝜔2𝑛
𝐶(𝑠) ( ) 𝜔2
----(2.13)
𝑠(𝑠+2𝛿𝜔𝑛 )
= 𝜔𝑛2 = 𝑠2 +2𝛿𝜔𝑛 𝑠+𝜔2
𝑅(𝑠) 1+( ) 𝑛 𝑛
𝑠(𝑠+2𝛿𝜔𝑛 )
𝜔𝑛 —natural frequency
Damping ratio
𝐴𝑐𝑡𝑢𝑎𝑙 𝐷𝑎𝑚𝑝𝑖𝑛𝑔
𝐷𝑎𝑚𝑝𝑖𝑛𝑔 𝑅𝑎𝑡𝑖𝑜 = 𝐶𝑟𝑖𝑡𝑖𝑐𝑎𝑙 𝐷𝑎𝑚𝑝𝑖𝑛𝑔 ----(2.14)
The power of ‘s’ is two in the denominator term. Hence, the above transfer function
is of the second order and the system is said to be the second order system.
24
The roots of characteristic equation are -
−2𝜔𝛿𝑛 ± (2𝛿𝜔𝑛 )2 − 4𝜔𝑛2 −2(𝛿𝜔𝑛 ± 𝜔𝑛 𝛿 2 − 1)
𝑠= =
2 2
⇒ 𝑠 = −𝛿𝜔𝑛 ± 𝜔𝑛 𝛿 2 − 1 ---(2.16)
𝜔2
(ii)Consider the equation, 𝐶(𝑠) = (𝑠2 +2𝛿𝜔𝑛 𝑠+𝜔2 )𝑅(𝑠)
𝑛 𝑛
25
2.6.1 RESPONSE OF UN-DAMPED SECOND ORDER SYSTEM FOR
A UNIT STEP INPUT
Consider the unit step signal as an input to the second order system.
Laplace transform of the unit step signal is,
1
𝑅(𝑠) =
𝑠
We know the transfer function of the second order closed loop control system is,
𝐶(𝑠) 𝜔𝑛2
= 2
𝑅(𝑠) 𝑠 + 2𝛿𝜔𝑛 𝑠 + 𝜔𝑛2
Substitute, δ=0 in the transfer function.
𝐶(𝑠) 2
𝜔𝑛
= 2 2
𝑅(𝑠) 𝑠 +𝜔𝑛
1
Substitute, 𝑅(𝑠) = in above equation.
𝑠
𝜔𝑛2 1 𝜔𝑛2
𝐶(𝑠) = ( )( ) =
𝑠 2 + 𝜔𝑛2 𝑠 𝑠(𝑠 2 + 𝜔𝑛2 )
Apply inverse Laplace transform on both the sides.
𝑐(𝑡) = (1 − cos(𝜔𝑛 𝑡))𝑢(𝑡) ---(2.17)
So, the unit step response of the second order system when δ = 0 will be a
continuous time signal with constant amplitude and frequency.
26
1
Substitute, 𝑅 𝑠 = 𝑠 in the equation(2.18).
𝜔𝑛2 1 𝜔𝑛2
𝐶(𝑠) = ( )( ) =
(𝑠 + 𝜔𝑛 )2 𝑠 𝑠(𝑠 + 𝜔𝑛 )2
Do partial fractions of C(s).
𝜔2 𝐴 𝐵 𝐶
𝐶(𝑠) = 𝑠(𝑠+𝜔𝑛 2 = 𝑠 + 𝑠+𝜔 + (𝑠+𝜔 2 ---(2.19)
𝑛) 𝑛 𝑛)
27
2.6.3 RESPONSE OF UNDER DAMPED SECOND ORDER SYSTEM FOR A
UNIT STEP INPUT.
Consider the transfer function of the second order closed loop control system is,
𝐶(𝑠) 𝜔𝑛2
= 2
𝑅(𝑠) 𝑠 + 2𝛿𝜔𝑛 𝑠 + 𝜔𝑛2
𝜔2
⇒ 𝐶(𝑠) = 𝑠2 +2𝛿𝜔𝑛 𝑠+𝜔2 𝑅(𝑠) ---(2.21)
𝑛 𝑛
1
Substitute, 𝑅 𝑠 = 𝑠 in the above equation.
𝜔𝑛2 1 𝜔𝑛2
𝐶 𝑠 = =
(𝑠 + 𝛿𝜔𝑛 )2 + 𝜔𝑛2 (1 − 𝛿 2 ) 𝑠 𝑠(𝑠 2 + 2𝛿𝜔𝑛 𝑠 + 𝜔𝑛2 )
Do partial fractions of C(s)
𝜔2 𝐴 𝐵𝑠+𝐶
𝐶(𝑠) = 𝑠(𝑠2 +2𝛿𝜔𝑛 2 = 𝑠 + 𝑠2 +2𝛿𝜔 2 ---(2.22)
𝑛 𝑠+𝜔𝑛 ) 𝑛 𝑠+𝜔𝑛
1 𝑠 + 2𝛿𝜔𝑛
𝐶 𝑠 = − 2
𝑠 𝑠 + 2𝛿𝜔𝑛 𝑠 + 𝜔𝑛2
1 𝑠 + 2𝛿𝜔𝑛 1 𝑠 + 2𝛿𝜔𝑛
𝐶 𝑠 = − 2 2 = −
2
𝑠 𝑠 + 2𝑠𝛿𝜔𝑛 + 𝜔𝑛 + (𝛿𝜔𝑛 ) − (𝛿𝜔𝑛 ) 2 𝑠 (𝑠 + 𝛿𝜔𝑛 )2 + 𝜔𝑛2 (1 − 𝛿 2 )
1 (𝑠+𝛿𝜔𝑛 ) 𝛿 𝜔𝑛 1−𝛿 2
𝐶(𝑠) = 𝑠 − − ( ) ---(2.23)
(𝑠+𝛿𝜔𝑛 )2 +(𝜔𝑛 1−𝛿 2 )2 1−𝛿 2 (𝑠+𝛿𝜔𝑛 )2 +(𝜔𝑛 1−𝛿 2 )2
1 (𝑠 + 𝛿𝜔𝑛 ) 𝛿 𝜔𝑑
𝐶(𝑠) = − 2 2 − ( 2)
𝑠 (𝑠 + 𝛿𝜔𝑛 ) + 𝜔𝑑 1 − 𝛿 2 (𝑠 + 𝛿𝜔𝑛 )2 + 𝜔𝑑
28
Apply inverse Laplace transform on both the sides.
𝛿
𝑐(𝑡) = (1 − 𝑒 −𝛿𝜔𝑛 𝑡 cos(𝜔𝑑 𝑡) − 𝑒 −𝛿𝜔𝑛 𝑡 sin(𝜔𝑑 𝑡))𝑢(𝑡)
1− 𝛿2
𝑒 −𝛿𝜔𝑛 𝑡
𝑐(𝑡) = (1 − (( 1 − 𝛿 2 )cos(𝜔𝑑 𝑡) + 𝛿sin(𝜔𝑑 𝑡)))𝑢(𝑡)
1− 𝛿2
If 1 − 𝛿 2 = sin 𝜃 then ‘δ’ will be cos(θ). Substitute these values in the above
equation.
𝑒 −𝛿𝜔𝑛 𝑡
𝑐 𝑡 = 1− sin 𝜃 cos 𝜔𝑑 𝑡 + cos 𝜃 sin 𝜔𝑑 𝑡 𝑢 𝑡
1 − 𝛿2
𝑒 −𝛿𝜔𝑛 𝑡
𝑐(𝑡) = (1 − ( )sin(𝜔𝑑 𝑡 + 𝜃))𝑢(𝑡) ---(2.24)
1−𝛿 2
1−𝛿 2
Where 𝜃 = 𝑡𝑎𝑛−1 ( )
𝛿
So, the unit step response of the second order system is having damped oscillations
(decreasing amplitude) when ‘δ’ lies between zero and one.
Fig. 2.11 Response of a under damped system for unit step input
29
Problems on Second order System
Solution :
4
Given that G s = 𝑠(𝑠+5) 𝑎𝑛𝑑 𝐻 𝑠 = 1
𝐶(𝑠) 𝐺(𝑠)
The closed loop transfer function, =
𝑅(𝑠) 1+𝐺 𝑠
4
𝐶(𝑠) 𝑠(𝑠+5) 4 4
= 4 = 𝑠2 +5𝑠+4 =
𝑅(𝑠) 1+ 𝑠+4 (𝑠+1)
𝑠(𝑠+5)
4
The response in s-domain,𝐶 𝑠 = 𝑅(𝑠) 𝑠+4 (𝑠+1)
1
Since the input is step input , 𝑅 𝑠 = 𝑠
1 4
Then 𝐶 𝑠 = ×
𝑠 𝑠+4 (𝑠+1)
4 𝐴 𝐵 𝐶
By partial fraction expansion, we can write 𝐶 𝑠 = 𝑠 = 𝑠 + 𝑠+4 + 𝑠+1
𝑠+4 (𝑠+1)
The response in the time domain c(t) is obtained by taking inverse Laplace
transform of C(s).
1 −4
1
Response in time domain 𝑐 𝑡 = 𝐿−1 𝐶 𝑠 = 𝐿−1 3
+ 𝑠+4 3
+ 𝑠+1
𝑠
1 4
𝑐 𝑡 = 1 + 𝑒 −4𝑡 − 𝑒 −𝑡
3 3
Result:
1 4
The Response in time domain , 𝑐 𝑡 = 1 + 𝑒 −4𝑡 − 𝑒 −𝑡
3 3
30
2. A Positional control system with velocity feedback is shown in fig. What is the
response of the system for unit step input.
Solution:
100
Given that G s = 𝑠(𝑠+2) 𝑎𝑛𝑑 𝐻 𝑠 = 0.1𝑠 + 1
𝐶(𝑠) 𝐺(𝑠)
The closed loop transfer function,𝑅(𝑠) = 1+𝐺 𝑠 𝐻(𝑠)
100 100
𝐶(𝑠) 𝑠(𝑠 + 2) 𝑠(𝑠 + 2) 100
= = = 2
𝑅(𝑠) 1 + 100 𝑠 𝑠 + 2 + 100(0.1𝑠 + 1) 𝑠 + 2𝑠 + 10𝑠 + 100
(0.1𝑠 + 1)
𝑠(𝑠 + 2) 𝑠(𝑠 + 2)
100
=
𝑠 2 + 12𝑠 + 100
Here, 𝑠 2 + 12𝑠 + 100 is the characteristic polynomial.
The roots of the characteristics polynomial are,
−12± 144−400 12±𝑗16
s1,s2 = =− = −6 ± 𝑗8.
2 2
The roots are complex conjugate. The system is under damped and so the response
of the system has damped oscillations.
100
The response in s-domain,𝐶 𝑠 = 𝑅(𝑠) 𝑠2 +12𝑠+100
1
Since the input is step input , 𝑅 𝑠 = 𝑠
1 100 100
Then 𝐶 𝑠 = × =
𝑠 𝑠2 +12𝑠+100 𝑠(𝑠2 +12𝑠+100)
100 𝐴 𝐵𝑠 + 𝐶
= +
𝑠(𝑠 2 + 12𝑠 + 100) 𝑠 (𝑠 2 +12𝑠 + 100)
31
On equating the coefficients of constant term 𝐴100 = 100 , 𝐴 = 1
On equating the coefficients of 𝑠 2 term 𝐴 + 𝐵 = 0 , 𝐵 = −1
On equating the coefficients of 𝑠 term 12𝐴 + 𝐶 = 0 , 𝐶 = −12
1 𝑠+6 6 1 𝑠+6 6 8
= − − = − −
𝑠 (𝑠 + 6)2 +82 (𝑠 + 6)2 +82 𝑠 (𝑠 + 6)2 +82 8 (𝑠 + 6)2 +82
The response in the time domain 𝑐(𝑡) is obtained by taking inverse Laplace
transform of 𝐶(𝑠).
1 𝑠+6 6 8
Response in time domain 𝑐 𝑡 = 𝐿−1 𝐶 𝑠 = 𝐿−1 − (𝑠+6)2 +82 − 8 (𝑠+6)2 +82
𝑠
6
𝑐 𝑡 = 1 − 𝑒 −6𝑡 𝑐𝑜𝑠8𝑡 − 𝑒 −6𝑡 𝑠𝑖𝑛8𝑡
8
6
𝑐 𝑡 = 1 − 𝑒 −6𝑡 (𝑐𝑜𝑠8𝑡 + 𝑒 −6𝑡 𝑠𝑖𝑛8𝑡)
8
Result:
6
The response in time domain𝑐 𝑡 = 1 − 𝑒 −6𝑡 (𝑐𝑜𝑠8𝑡 + 𝑒 −6𝑡 𝑠𝑖𝑛8𝑡)
8
3. The response of the servomechanism is 𝑐 𝑡 = 1 + 0.2𝑒 −60𝑡 − 1.2𝑒 −10𝑡 when
subjected to a unit step input. Obtain an expression for closed loop transfer
function. Determine the un-damped natural frequency and damping ratio.
Solution:
Given that 𝑐 𝑡 = 1 + 0.2𝑒 −60𝑡 − 1.2𝑒 −10𝑡
On taking Laplace transform of c(t) we get,
1 600
=
𝑠 𝑠 + 60 (𝑠 + 10)
32
1
Since the step input R(s)= 𝑠 ,
600 600
𝐶 𝑠 =𝑅 𝑠 = 𝑅(𝑠) 2
𝑠 + 60 𝑠 + 10 𝑠 + 70𝑠 + 600
Therefore, the closed loop transfer function of the system is given by
𝐶(𝑠) 600
= 2
𝑅(𝑠) 𝑠 + 70𝑠 + 600
The damping ratio and natural frequency is obtained by comparing the system
transfer function with standard form of second order transfer function.
𝐶(𝑠) 𝜔𝑛2 600
= 2 2 = 2
𝑅(𝑠) 𝑠 + 2𝛿𝜔𝑛 𝑠 + 𝜔𝑛 𝑠 + 70𝑠 + 600
On comparing we get,
𝜔𝑛2
= 600
𝜔𝑛 = 600
𝜔𝑛 = 24.49 rad/sec
2𝛿𝜔𝑛 = 70
70 70
𝛿 = 2𝜔 = 2×24.49 = 1.43
𝑛
Result:
𝐶(𝑠) 600
The closed loop transfer function of the system is given by =
𝑅(𝑠) 𝑠2 +70𝑠+600
𝑁𝑎𝑡𝑢𝑟𝑎𝑙 𝑓𝑟𝑒𝑞𝑢𝑒𝑛𝑐𝑦 𝑜𝑓 𝑂𝑠𝑐𝑖𝑙𝑙𝑎𝑡𝑖𝑜𝑛 , 𝜔𝑛 = 24.49 rad/sec
𝐷𝑎𝑚𝑝𝑖𝑛𝑔 𝑅𝑎𝑡𝑖𝑜 𝛿 = 1.43
4. Determine the unit step response of a the control system shown in figure.
Solution:
10 𝑠
Given that 𝐺 𝑠 = 𝑠(𝑠+3)
H(s)= 10 +1
𝐶(𝑠) 𝐺(𝑠)
The closed loop transfer function,𝑅(𝑠) = 1+𝐺 𝑠 𝐻(𝑠)
10
𝐶(𝑠) 10 10
Therefore
𝑠(𝑠+3)
= = =
𝑅(𝑠) 1+
10
( +1)
𝑠
𝑠(𝑠+3) 10
𝑠 𝑠+3 +1)
+10(
𝑠
10
𝑠2 +3𝑠+𝑠+10
𝐶(𝑠) 10
= 2
𝑅(𝑠) 𝑠 + 4𝑠 + 10
10
The response in s-domain 𝐶 𝑠 = 𝑅(𝑠) 𝑠2 +4𝑠+10
33
1
For the step input 𝑅 𝑠 =
𝑠
1 10 10
𝐶 𝑠 = =
𝑠 𝑠 2 + 4𝑠 + 10 𝑠( 𝑠 2 + 4𝑠 + 10)
10 𝐴 𝐵𝑠+𝐶
By partial fraction expansion, we can write 𝐶 𝑠 = 𝑠 (𝑠2 +4𝑠+10) = 𝑠 + (𝑠2 +4𝑠+10)
10 𝐴 𝐵𝑠 + 𝐶
= + 2
𝑠2
𝑠( + 4𝑠 + 10) 𝑠 (𝑠 +4𝑠 + 10)
10 = 𝐴(𝑠 2 + 4𝑠 + 10) + 𝑠(𝐵𝑠 + 𝐶)
10 = 𝐴𝑠 2 + 𝐴4𝑠 + 𝐴10 + 𝐵𝑠 2 + 𝐶𝑠
The response in the time domain c(t) is obtained by taking inverse Laplace
transform of C(s).
1 𝑠+2 2 6
Response in time domain 𝑐 𝑡 = 𝐿−1 𝐶 𝑠 = 𝐿−1 − (𝑠+2)2 +6 −
𝑠 6 (𝑠+2)2 +6
2
𝑐 𝑡 = 1 − 𝑒 −2𝑡 𝑐𝑜𝑠 6𝑡 − 𝑒 −2𝑡 𝑠𝑖𝑛 6𝑡
6
2
𝑐 𝑡 = 1 − 𝑒 −2𝑡 𝑐𝑜𝑠 6𝑡 + 𝑠𝑖𝑛 6𝑡 𝑢(𝑡)
6
Result:
2
The response in time domain , 𝑐 𝑡 = 1 − 𝑒 −2𝑡 𝑐𝑜𝑠 6𝑡 + 𝑠𝑖𝑛 6𝑡 𝑢(𝑡)
6
34
2.7 TIME DOMAIN SPECIFICATIONS
Fig.2.12 Damped oscillatory response of second order system for unit step input
35
Delay Time
It is the time required for the response to reach half of its final value from
the zero instant. It is denoted by td.
Consider the step response of the second order system for t ≥ 0, when ‘δ’ lies
between zero and one.
𝑒 −𝛿𝜔𝑛 𝑡
𝑐(𝑡) = 1 − ( )sin(𝜔𝑑 𝑡 + 𝜃)
1 − 𝛿2
The final value of the step response is one.
Therefore, at t=td , the value of the step response will be 0.5. Substitute, these
values in the above equation.
𝑒 −𝛿𝜔𝑛 𝑡𝑑
𝑐 𝑡𝑑 = 0.5 = 1 − sin 𝜔𝑑 𝑡𝑑 + 𝜃
1 − 𝛿2
𝑒 −𝛿𝜔𝑛 𝑡𝑑
⇒ sin 𝜔𝑑 𝑡𝑑 + 𝜃 = 0.5
1 − 𝛿2
1+0.7𝛿
𝑡𝑑 = ---(2.25)
𝜔𝑛
Rise Time
It is the time required for the response to rise from 0% to 100% of its
final value. This is applicable for the under-damped systems. For the over-damped
systems, consider the duration from 10% to 90% of the final value. Rise time is
denoted by tr.
At t = t1 = 0, c(t) = 0.
The unit step response of a second order system for under damped is
𝑒 −𝛿𝜔𝑛 𝑡
𝑐(𝑡) = 1 − ( )sin(𝜔𝑑 𝑡 + 𝜃)
1 − 𝛿2
At 𝑡 = 𝑡𝑟 , 𝑐 𝑡 = 𝑐 𝑡𝑟 = 1
𝑒 −𝛿𝜔𝑛 𝑡𝑟
𝑐(𝑡𝑟 ) = 1 = 1 − ( )sin(𝜔𝑑 𝑡𝑟 + 𝜃)
1 − 𝛿2
36
𝑒 −𝛿𝜔𝑛 𝑡𝑟
⇒( )sin(𝜔𝑑 𝑡𝑟 + 𝜃) = 0
1 − 𝛿2
𝑒 −𝛿𝜔𝑛 𝑡𝑟
Since ⇒ ≠ 0 the term sin(𝜔𝑑 𝑡𝑟 + 𝜃) = 0
1−𝛿 2
sin(𝜔𝑑 𝑡𝑟 + 𝜃) = 0
When 𝜃 = 0, 𝜋, 2𝜋, 3𝜋 …,sin 𝜃 = 0
𝜔𝑑 𝑡𝑟 + 𝜃 = 𝜋
𝜋−𝜃
⇒ 𝑡𝑟 = ---(2.26)
𝜔𝑑
1 − 𝛿2
𝑊ℎ𝑒𝑟𝑒, 𝜃 = 𝑡𝑎𝑛−1 𝑎𝑛𝑑 𝜔𝑑 = 𝜔𝑛 1 − 𝛿 2
𝛿
From above equation, we can conclude that the rise time 𝑡𝑟 and the damped
frequency 𝜔𝑑 are inversely proportional to each other.
Peak Time
It is the time required for the response to reach the peak value for the
first time. It is denoted by tp. At t=tp, the first derivate of the response is zero.
We know the step response of second order system for under-damped case is
𝑒 −𝛿𝜔𝑛 𝑡
𝑐 𝑡 =1− sin 𝜔𝑑 𝑡 + 𝜃
1 − 𝛿2
Differentiate c(t) with respect to ‘t’.
d𝑐(𝑡) 𝑒 −𝛿𝜔𝑛 𝑡 −𝛿𝜔𝑛 𝑒 −𝛿𝜔𝑛 𝑡
= −( 2
)𝜔𝑑 cos(𝜔𝑑 𝑡 + 𝜃) − ( )sin(𝜔𝑑 𝑡 + 𝜃) ---(2.27)
d𝑡 1−𝛿 1−𝛿 2
d𝑐(𝑡)
Substitute,𝑡 = 𝑡𝑝 and = 0 in the equation(2.27)
d𝑡
𝑒 −𝛿𝜔𝑛 𝑡𝑝
0 = −( )[𝜔𝑑 cos(𝜔𝑑 𝑡𝑝 + 𝜃) − 𝛿𝜔𝑛 sin(𝜔𝑑 𝑡𝑝 + 𝜃)] ---(2.28)
1−𝛿 2
1 − 𝛿 2 cos(𝜔𝑑 𝑡𝑝 + 𝜃) − 𝛿sin(𝜔𝑑 𝑡𝑝 + 𝜃) = 0
⇒ sin(𝜃)cos(𝜔𝑑 𝑡𝑝 + 𝜃) − cos(𝜃)sin(𝜔𝑑 𝑡𝑝 + 𝜃) = 0
⇒ sin(𝜃 − 𝜔𝑑 𝑡𝑝 − 𝜃) = 0
37
When 𝜃 = 0, 𝜋, 2𝜋, 3𝜋 …,sin 𝜃 = 0
⇒ 𝜔𝑑 𝑡𝑝 = 𝜋
𝜋
𝑡𝑝 = 𝜔 ---(2.29)
𝑑
From the above equation, we can conclude that the peak time 𝑡𝑝 and the damped
frequency 𝜔𝑑 are inversely proportional to each other.
Peak Overshoot
Peak overshoot Mp is defined as the deviation of the response at peak
time from the final value of response. It is also called the maximum overshoot.
Mathematically, we can write it as
𝑐(𝑡𝑝 )−𝑐(∞)
%𝑃𝑒𝑎𝑘 𝑜𝑣𝑒𝑟𝑠ℎ𝑜𝑜𝑡 , %𝑀𝑝 = × 100 ---(2.30)
𝑐(∞)
38
𝛿𝜋
−
𝑀𝑝 = 1 + 𝑒 1−𝛿 2 −1
𝛿𝜋
−
⇒ 𝑀𝑝 = 𝑒 1−𝛿2 × 100
𝛿𝜋
−
Percentage peak overshoot %𝑀𝑝 = 𝑒 1−𝛿2 × 100% ----(2.32)
From the above equation, we can conclude that the percentage of peak
overshoot %Mp will decrease if the damping ratio δ increases.
Settling time
It is the time required for the response to reach the steady state and stay
within the specified tolerance bands around the final value. In general, the tolerance
bands are 2% and 5%. The settling time is denoted by ts.
The response of the second order system has two components. They are
𝑒 −𝛿𝜔𝑛 𝑡
Decaying exponential component,
1−𝛿 2
Sinusoidal component,sin(𝜔𝑑 𝑡 + 𝜃)
In this the decaying exponential term dampens (or) reduces the oscillations
produced by sinusoidal component. Hence the settling time is decided by
exponential component.
𝑒 −𝛿𝜔𝑛 𝑡𝑠
The settling time for 2% tolerance band, at 𝑡 = 𝑡𝑠 , = 0.02
1−𝛿 2
𝑒 −𝛿𝜔𝑛 𝑡𝑠
The settling time for 5% tolerance band, at 𝑡 = 𝑡𝑠 , = 0.05
1−𝛿 2
𝛿𝜔𝑛 𝑡𝑠 = 3
3
𝑡𝑠 = 𝛿𝜔 ----(2.34)
𝑛
39
The settling time for 5% tolerance band is –
3
𝑡𝑠 = = 3𝜏
𝛿𝜔𝑛
The settling time for 2% tolerance band is –
4
𝑡𝑠 = = 4𝜏
𝛿𝜔𝑛
1
Where, τ is the time constant and is equal to .
𝛿𝜔𝑛
Both the settling time ts and the time constant τ are inversely proportional to the
damping ratio δ.
Both the settling time ts and the time constant τ are independent of the system
gain. That means even the system gain changes, the settling time ts and time
constant τ will never change.
Problems on time domain specifications
1.The open loop transfer function of servo system with unity feedback is given by
10
𝐺(𝑠) = 𝑠+2 (𝑠+5) .Determine damping ratio, un-damped natural frequency of
oscillation. What is the percentage overshoot of the response to a unit step input?
Solution :
10
Given that 𝐺(𝑠) = 𝑠+2 (𝑠+5)
H(s)=1
Characteristic equation is given as 1+G(s)H(s)=0
Substitute G(s) and H(s) in above equation
10
1+ =0
𝑠 + 2 (𝑠 + 5)
𝑠 + 2 𝑠 + 5 + 10
=0
𝑠 + 2 (𝑠 + 5)
𝑠 2 + 7𝑠 + 20 = 0
Comparing the above equation with 𝑠 2 + 2𝛿𝜔𝑛 𝑠 + 𝜔𝑛2 = 0, we get
𝜔𝑛2 = 20
2𝛿𝜔𝑛 = 7
7 7
𝐷𝑎𝑚𝑝𝑖𝑛𝑔 𝑅𝑎𝑡𝑖𝑜, 𝛿 = 2𝜔 = 2×4.4.72 = 0.7826
𝑛
40
𝛿𝜋
−
Percentage overshhot %𝑀𝑝 = 𝑒 1−𝛿 2 × 100%
0.7826𝜋
−
= 𝑒 1−0.78262
× 100%
%𝑀𝑝 = 1.92%
Result:
Natural frequency, 𝜔𝑛 = 4.472 rad/sec
𝐷𝑎𝑚𝑝𝑖𝑛𝑔 𝑅𝑎𝑡𝑖𝑜, 𝛿 = 0.7826
Percentage overshhot %𝑀𝑝 = 1.92%
2.The feedback system is described by the following transfer function 𝐺(𝑠) =
12
and H(s)=Ks. The damping factor of the system is 0.8.Determine the
𝑠2 +4𝑠+16
overshoot of the system and the value of K.
Solution :
12
Given that 𝐺(𝑠) = 𝑠2 +4𝑠+16
H(s)=Ks
Characteristic equation is given as 1+G(s)H(s)=0
Substitute G(s) and H(s) in above equation
12
1+ 2 Ks=0
𝑠 + 4𝑠 + 16
𝑠 2 + 4𝑠 + 16 + 12𝐾𝑠
=0
𝑠 2 + 4𝑠 + 16
𝑠 2 + (4 + 12𝐾)𝑠 + 16 = 0
Comparing the above equation with 𝑠 2 + 2𝛿𝜔𝑛 𝑠 + 𝜔𝑛2 = 0, we get
𝜔𝑛2 = 16
𝜔𝑛 = 4rad/sec
2𝛿𝜔𝑛 = 4 + 12K
Substitute 𝛿 = 0.8 𝑎𝑛𝑑 𝜔𝑛 = 4rad/sec in above equation
2 × 0.8 × 4 = 4 + 12K
K=0.15
𝛿𝜋
−
Percentage overshhot %𝑀𝑝 = 𝑒 1−𝛿 2 × 100%
0.8𝜋
−
= 𝑒 1−0.82
× 100%
%𝑀𝑝 = 1.5%
Result:
K=0.15
Percentage overshhot %𝑀𝑝 = 1.5%
41
3.The unity feedback system is characterized by an open loop transfer function
𝐾
𝐺(𝑠) = 𝑠(𝑠+10). Determine the gain K, so that the system will have a damping ratio
0.5 for this value of K. Determine peak overshoot and time at peak overshoot for a
unit step input.
Solution:
𝐾
Given that 𝐺 𝑠 = , H(s)=1
𝑠(𝑠+10)
𝐶(𝑠) 𝐺(𝑠)
The closed loop transfer function,𝑅(𝑠) = 1+𝐺 𝑠
𝐾
𝐶(𝑠) 𝐾 𝐾
Therefore
𝑠(𝑠+10)
= 𝐾 = = 𝑠2 +10𝑠+𝐾
𝑅(𝑠) 1+ 𝑠 𝑠+10 +𝐾
𝑠(𝑠+10)
The value of K can be evaluated by comparing the system transfer function with
standard form of second order transfer function.
𝐶(𝑠) 𝜔𝑛2 𝐾
= 2 2 = 2
𝑅(𝑠) 𝑠 + 2𝛿𝜔𝑛 𝑠 + 𝜔𝑛 𝑠 + 10𝑠 + 𝐾
On comparing we get,
𝜔𝑛2 = K
𝜔𝑛 = 𝐾
2𝛿𝜔𝑛 = 10
Put 𝛿 = 0.5 𝑎𝑛𝑑 𝜔𝑛 = 𝐾, 2 × 0.5 × 𝐾 = 10
𝐾 = 10
The value of gain , K =100 , 𝑇ℎ𝑒𝑛 𝜔𝑛 = 10rad/sec
𝛿𝜋
−
Percentage overshhot %𝑀𝑝 = 𝑒 1−𝛿 2 × 100%
0.5𝜋
−
= 𝑒 1−0.52 × 100%
%𝑀𝑝 = 16.3%
𝜋 𝜋 𝜋
𝑃𝑒𝑎𝑘 𝑡𝑖𝑚𝑒 𝑡𝑝 = = = = 0.363sec
𝜔𝑑 𝜔𝑛 1 − 𝛿 2 10 1 − 0.52
𝑃𝑒𝑎𝑘 𝑡𝑖𝑚𝑒 𝑡𝑝 = 0.363sec
Result :
Percentage overshhot %𝑀𝑝 = 16.3%
𝑃𝑒𝑎𝑘 𝑡𝑖𝑚𝑒 𝑡𝑝 = 0.363sec
42
4. The open loop transfer function of a unity feedback system is given by 𝐺(𝑠) =
𝐾
, where K and T are positive constant. By what factor should the amplifier
𝑠(𝑠𝑇+1)
gain K be reduced, so that the peak overshoot of unit step response of the system
reduced from 75% to 25%.
Solution:
𝐾
Given that 𝐺 𝑠 = 𝑠(𝑠𝑇+1)
H(s) = 1
𝐶 𝑠 𝐺 𝑠
The closed loop transfer function,𝑅 = 1+𝐺
𝑠 𝑠
𝐾 𝐾
𝐶 𝑠 𝑠(𝑠𝑇+1) 𝐾 𝐾 𝑇
= 𝐾 =𝑠 = 𝑠2 𝑇+𝑠+𝐾 = 1 𝐾
𝑅 𝑠 1+ 𝑠𝑇+1 +𝐾 𝑠2 + 𝑠+
𝑠(𝑠𝑇+1) 𝑇 𝑇
Expression for 𝛿 𝑎𝑛𝑑 𝜔𝑛 can be obtained by comparing the transfer function with the
standard from of second order equation
𝐾
𝐶(𝑠) 𝜔𝑛2 𝑇
= 2 =
2
𝑅(𝑠) 𝑠 + 2𝛿𝜔𝑛 𝑠 + 𝜔𝑛 1 𝐾
𝑠2 + 𝑇 𝑠 + 𝑇
𝐾 𝐾
𝜔𝑛2 = , then 𝜔𝑛 =
𝑇 𝑇
1 1
2𝛿𝜔𝑛 = 𝑇, then 𝛿 = 2 𝐾𝑇
The peak overshoot is reduced by increasing the damping ratio and the damping
ratio is increased by reducing the gain.
𝑊ℎ𝑒𝑛 𝑀𝑝 = 0.75, 𝐿𝑒𝑡 𝛿 = 𝛿1 𝑎𝑛𝑑 𝐾 = 𝐾1
𝑊ℎ𝑒𝑛 𝑀𝑝 = 0.25, 𝐿𝑒𝑡 𝛿 = 𝛿2 𝑎𝑛𝑑 𝐾 = 𝐾2
𝛿𝜋
−
Peak overshoot , 𝑀𝑝 = 𝑒 1−𝛿 2
𝛿𝜋
Taking natural logarithm on both sides ln 𝑀𝑝 =
1−𝛿 2
(𝛿𝜋)2
On squaring on both sides we get, (ln 𝑀𝑝)2 = 1−𝛿 2
1
Substituting the value of 𝛿 = 2 𝐾𝑇
in above expression
1 2
𝜋 𝜋2
2
(ln 𝑀𝑝) = 4KT =
1 4KT − 1
1 − 4KT
43
𝜋2 𝜋2
4KT − 1 = , 4KT = +1
(ln 𝑀𝑝)2 (ln 𝑀𝑝)2
1 𝜋2
K= +1
4𝑇 ln 𝑀𝑝 2
1 𝜋 2 + ln 𝑀𝑝 2
K=
4𝑇 ln 𝑀𝑝 2
1 𝜋 2 + ln 𝑀𝑝 2
𝑊ℎ𝑒𝑛 𝑀𝑝 = 0.75, 𝑎𝑛𝑑 𝐾 = 𝐾1, 𝐾1 =
4𝑇 ln 𝑀𝑝 2
1 𝜋2 + ln 0.75 2
𝐾1 = 4𝑇 ln 0.75 2
9.952 30.06
𝐾1 = 0.331𝑇 = 𝑇
1 𝜋 2 + ln 𝑀𝑝 2
𝑊ℎ𝑒𝑛 𝑀𝑝 = 0.25, 𝑎𝑛𝑑 𝐾 = 𝐾2, 𝐾2 =
4𝑇 ln 𝑀𝑝 2
1 𝜋2 + ln 0.25 2
𝐾2 = 4𝑇 ln 0.25 2
11.79 1.53
𝐾2 = 7.68𝑇 = 𝑇
30.06
𝐾1
= 𝑇 = 19.6
𝐾2 1.53
𝑇
𝐾1 = 19.6𝐾2
To reduce the peak overshoot from 0.75 to 0.25, K should be reduced by 19.6 times
approximately.
Result:
The value of gain, K should be reduced approximately 20 times to reduce the peak
overshoot from 0.75 to 0.25
44
10
5. A unity feedback control system has an open loop transfer function 𝐺(𝑠) = .
𝑠 𝑠+2
Find the rise time, percentage overshoot, peak time, and settling time for a step
input of 12 units.
Solution:
10
Given that 𝐺 𝑠 = 𝑠(𝑠+2)
H(s) = 1
𝐶(𝑠) 𝐺(𝑠)
The closed loop transfer function,𝑅(𝑠) = 1+𝐺 𝑠
10
𝐶(𝑠) 10 10
Therefore
𝑠(𝑠+2)
= 10 = =
𝑅(𝑠) 1+ 𝑠 𝑠+2 +10 𝑠2 +2𝑠+10
𝑠(𝑠+2)
By comparing the system transfer function with standard form of second order
transfer function.
𝐶(𝑠) 𝜔𝑛2 10
= 2 =
𝑅(𝑠) 𝑠 + 2𝛿𝜔𝑛 𝑠 + 𝜔𝑛2 𝑠 2 + 2𝑠 + 10
On comparing we get,
𝜔𝑛2 = 10
𝜔𝑛 = 10 = 3.16𝑟𝑎𝑑/𝑠𝑒𝑐
2𝛿𝜔𝑛 = 2
Put 𝜔𝑛 = 3.16,
2 × 𝛿 × 3.16 = 2
2
𝛿= = 0.316
2 × 3.16
𝜔𝑑 = 𝜔𝑛 1 − 𝛿 2 = 3.16 1 − 0.3162 = 3rad/sec
1 − 𝛿2 1 − 0.3162
𝜃 = 𝑡𝑎𝑛−1 = 𝑡𝑎𝑛−1 = 1.249𝑟𝑎𝑑
𝛿 0.316
𝜋 − 𝜃 𝜋 − 1.249
𝑅𝑖𝑠𝑒 𝑡𝑖𝑚𝑒 𝑡𝑟 = = = 0.63sec
𝜔𝑑 3
𝛿𝜋
−
Percentage overshhot %𝑀𝑝 = 𝑒 1−𝛿 2 × 100%
0.316𝜋
−
= 𝑒 1−0.3162 × 100%
%𝑀𝑝 = 35.12%
35.12
Percentage overshhot %𝑀𝑝 = × 12units = 4.2144units
100
𝜋 𝜋 𝜋
𝑃𝑒𝑎𝑘 𝑡𝑖𝑚𝑒 𝑡𝑝 = = = = 1.047sec
𝜔𝑑 𝜔𝑛 1 − 𝛿 2 3
45
3 3
𝐹𝑜𝑟 5% 𝑒𝑟𝑟𝑜𝑟 𝑆𝑒𝑡𝑡𝑙𝑖𝑛𝑔 𝑡𝑖𝑚𝑒, 𝑡𝑠 = = = 3sec
𝛿𝜔𝑛 0.316 × 3.16
4 4
𝐹𝑜𝑟 2% 𝑒𝑟𝑟𝑜𝑟 𝑆𝑒𝑡𝑡𝑙𝑖𝑛𝑔 𝑡𝑖𝑚𝑒, 𝑡𝑠 = = = 4sec
𝛿𝜔𝑛 0.316 × 3.16
𝑹𝒆𝒔𝒖𝒍𝒕:
𝑅𝑖𝑠𝑒 𝑡𝑖𝑚𝑒 𝑡𝑟 = 0.63sec
Percentage overshhot %𝑀𝑝 = 35.12%
Percentage overshhot %𝑀𝑝 = 4.2144units (for a input of 12 units)
𝑃𝑒𝑎𝑘 𝑡𝑖𝑚𝑒 𝑡𝑝 = 1.047sec
𝐹𝑜𝑟 5% 𝑒𝑟𝑟𝑜𝑟 𝑆𝑒𝑡𝑡𝑙𝑖𝑛𝑔 𝑡𝑖𝑚𝑒, 𝑡𝑠 = 3sec
𝐹𝑜𝑟 2% 𝑒𝑟𝑟𝑜𝑟 𝑆𝑒𝑡𝑡𝑙𝑖𝑛𝑔 𝑡𝑖𝑚𝑒, 𝑡𝑠 = 4sec
6. A Positional control system with velocity feedback is shown in fig. what is the
response c(t) to the unit step input. Given that 𝛿 = 0.5. Also calculate rise time , peak
time, maximum overshoot and settling time.
Solution:
16
Given that 𝐺 𝑠 = 𝑠(𝑠+0.8)
H(s) = Ks+1
𝐶(𝑠) 𝐺(𝑠)
The closed loop transfer function,𝑅(𝑠) = 1+𝐺 𝑠 𝐻(𝑠)
16
𝐶(𝑠) 𝑠(𝑠+0.8) 16 16
Therefore 𝑅(𝑠) = 16 = = 𝑠2 +0.8𝑠+16𝐾𝑠+16
1+
𝑠(𝑠+0.8)
(Ks+1) 𝑠 𝑠+0.8 +16(𝐾𝑠+1)
𝐶(𝑠) 16
= 2
𝑅(𝑠) 𝑠 + (0.8 + 16𝐾)𝑠 + 16
The value of K and 𝜔𝑛 can be evaluated by comparing the system transfer function with
standard form of second order transfer function.
𝐶(𝑠) 𝜔𝑛2 16
= 2 2 = 2
𝑅(𝑠) 𝑠 + 2𝛿𝜔𝑛 𝑠 + 𝜔𝑛 𝑠 + (0.8 + 16𝐾)𝑠 + 16
On comparing we get,
𝜔𝑛2 = 16
𝜔𝑛 = 4 𝑟𝑎𝑑/𝑠𝑒𝑐
2𝛿𝜔𝑛 = 0.8 + 16K
46
Put 𝛿 = 0.5 𝑎𝑛𝑑 𝜔𝑛 = 4𝑟𝑎𝑑/𝑠𝑒𝑐, 2 × 0.5 × 4 = 0.8 + 16K
2 × 0.5 × 4 − 0.8
K=
16
𝐾 = 0.2
𝐶 𝑠 16
Substitute the value of 𝐾 = 0.2 in 𝑅 𝑠 = 𝑠2 + 0.8+16𝐾 𝑠+16
𝐶(𝑠) 16 16
Therefore = 2 = 2
𝑅(𝑠) 𝑠 + (0.8 + 16 × 0.2)𝑠 + 16 𝑠 + 4𝑠 + 16
16
The response in s-domain 𝐶 𝑠 = 𝑅(𝑠) 𝑠2 +4𝑠+16
1
For the step input 𝑅 𝑠 = 𝑠
1 16 16
𝐶 𝑠 = =
𝑠 𝑠 2 + 4𝑠 + 16 𝑠 (𝑠 2 +4𝑠 + 16)
16 𝐴 𝐵𝑠+𝐶
By partial fraction expansion, we can write 𝐶 𝑠 = 𝑠 (𝑠2 +4𝑠+16) = 𝑠 + (𝑠2 +4𝑠+16)
16 𝐴 𝐵𝑠 + 𝐶
= + 2
𝑠 (𝑠 2 +4𝑠 + 16) 𝑠 (𝑠 +4𝑠 + 16)
1 𝑠+2 2 1 𝑠+2 2 12
= − 2
− 2
= − 2
−
𝑠 (𝑠 + 2) +12 (𝑠 + 2) +12 𝑠 (𝑠 + 2) +12 12 (𝑠 + 2)2 +12
The response in the time domain 𝑐(𝑡) is obtained by taking inverse Laplace
transform of 𝐶(𝑠).
1 𝑠+2 2 12
Response in time domain 𝑐 𝑡 = 𝐿−1 𝐶 𝑠 = 𝐿−1 − (𝑠+2)2 +12 −
𝑠 12 (𝑠+2)2 +12
2
𝑐 𝑡 = 1 − 𝑒 −2𝑡 𝑐𝑜𝑠 12𝑡 − 𝑒 −2𝑡 𝑠𝑖𝑛 12𝑡
12
47
2
𝑐 𝑡 = 1 − 𝑒 −2𝑡 (𝑐𝑜𝑠 12𝑡 + 𝑠𝑖𝑛 12𝑡)
12
1
𝑐 𝑡 = 1 − 𝑒 −2𝑡 (𝑐𝑜𝑠 12𝑡 + 𝑠𝑖𝑛 12𝑡)
3
𝜋 − 𝜃 𝜋 − 1.047
𝑅𝑖𝑠𝑒 𝑡𝑖𝑚𝑒 𝑡𝑟 = = = 0.6046sec
𝜔𝑑 3.464
𝛿𝜋
−
Percentage overshhot %𝑀𝑝 = 𝑒 1−𝛿 2 × 100%
0.5𝜋
−
= 𝑒 1−0.52 × 100%
%𝑀𝑝 = 16.3%
𝜋 𝜋 𝜋
𝑃𝑒𝑎𝑘 𝑡𝑖𝑚𝑒 𝑡𝑝 = = = = 0.907sec
𝜔𝑑 𝜔𝑛 1 − 𝛿 2 3.464
3 3
𝐹𝑜𝑟 5% 𝑒𝑟𝑟𝑜𝑟 𝑆𝑒𝑡𝑡𝑙𝑖𝑛𝑔 𝑡𝑖𝑚𝑒, 𝑡𝑠 = = = 1.5sec
𝛿𝜔𝑛 0.5 × 4
4 4
𝐹𝑜𝑟 2% 𝑒𝑟𝑟𝑜𝑟 𝑆𝑒𝑡𝑡𝑙𝑖𝑛𝑔 𝑡𝑖𝑚𝑒, 𝑡𝑠 = = = 2sec
𝛿𝜔𝑛 0.5 × 4
Result:
1
The response in time domain , 𝑐 𝑡 = 1 − 𝑒 −2𝑡 𝑐𝑜𝑠 12𝑡 + 𝑠𝑖𝑛 12𝑡 𝑢(𝑡)
3
𝑅𝑖𝑠𝑒 𝑡𝑖𝑚𝑒 𝑡𝑟 = 0.6046sec
Percentage overshhot %𝑀𝑝 = 16.3%
𝑃𝑒𝑎𝑘 𝑡𝑖𝑚𝑒 𝑡𝑝 = 0.907sec
𝐹𝑜𝑟 5% 𝑒𝑟𝑟𝑜𝑟 𝑆𝑒𝑡𝑡𝑙𝑖𝑛𝑔 𝑡𝑖𝑚𝑒, 𝑡𝑠 = 1.5sec
𝐹𝑜𝑟 2% 𝑒𝑟𝑟𝑜𝑟 𝑆𝑒𝑡𝑡𝑙𝑖𝑛𝑔 𝑡𝑖𝑚𝑒, 𝑡𝑠 = 2sec
48
2.8 STEADY STATE ERROR
The steady state error is the value of error signal e(t), when t tends to
infinity. The steady state error is a measure of system accuracy. These errors rise
from the nature of inputs, type of system and from non linearity of system
components. The steady state performance of a stable control system is generally
judged by its steady state error to step, ramp, and parabolic inputs.
Consider the following block diagram of closed loop control system, which
is having unity negative feedback.
E(s)+E(s)G(s)H(s) =R(s)
𝑅(𝑠)
𝐸(𝑠) = 1+𝐺 ---(2.37)
𝑠 𝐻(𝑠)
𝑒𝑠𝑠 = lim s E s ,
𝑠→0
𝑠𝑅(𝑠)
𝑒𝑠𝑠 = lim 1+𝐺 𝑠 𝐻(𝑠) ---(2.39)
𝑠→0
49
2.9 STATIC ERROR CONSTANT
When a control system is excited with standard input signal, the steady
state error may be zero, constant or infinity. The value of steady state error depends
upon on the type number and the input signal .Type-0 system will have a constant
steady state error when the input is step signal. Type-1 system will have a constant
steady state error when the input is ramp signal or velocity signal. Type-2 system
will have a constant steady state error when the input is parabolic signal or
acceleration signal. For the above three cases mentioned above the steady state
error associated with one of the constant is defined as follows,
1
Therefore, 𝑒𝑠𝑠 = 1+𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡 ---(2.44)
50
Type 1 system
𝑠+𝑧1 𝑠+𝑧2 𝑠+𝑧3 … 𝑧 𝑧 𝑧
𝐾𝑝 = 𝑙𝑖𝑚 𝐺 𝑠 𝐻(𝑠)= 𝑙𝑖𝑚𝐾 𝑠 = 𝐾 𝑝1𝑝2 𝑝3 = ∞
𝑠→0 𝑠→0 𝑠+𝑝1 𝑠+𝑝2 𝑠+𝑝3 …. 1 2 3
1 1
𝑒𝑠𝑠 = 1+𝐾𝑝 = 1+∞ = 0 ----(2.45)
In system with type number 1 and above , for step input the value of 𝐾𝑝 is infinity
and so the steady state error is zero2.
Type 1 system
𝑠+𝑧1 𝑠+𝑧2 𝑠+𝑧3 … 𝑧 𝑧 𝑧
𝐾𝑣 = 𝑙𝑖𝑚 𝑠 𝐺 𝑠 𝐻(𝑠)= 𝑙𝑖𝑚 𝑠𝐾 𝑠 = 𝐾 𝑝1𝑝2 𝑝3 = 𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡
𝑠→0 𝑠→0 𝑠+𝑝1 𝑠+𝑝2 𝑠+𝑝3 …. 1 2 3
1
𝑒𝑠𝑠 = 𝐾𝑣 = 𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡 -----(2.48)
Hence in Type-1 systems when the input is unit ramp there will be a constant steady
state error.
51
Type 2 system
1 1
𝑒𝑠𝑠 = 𝐾𝑣 = ∞ = 0 ---(2.49)
In system with type number 2 and above , for unit ramp input the value of 𝐾𝑣 is
infinity and so the steady state error is zero.
𝑠𝑅(𝑠)
Steady state error ,𝑒𝑠𝑠 = lim s E s , 𝑒𝑠𝑠 = 𝑙𝑖𝑚 1+𝐺
𝑠→0 𝑠→0 𝑠 𝐻(𝑠)
𝑡2
When the input is unit parabolic, 𝑟 (𝑡) = .
2
1
Laplace Transform of r(t) is 𝑅 𝑠 = 𝑠3
1
𝑠 3 1 1 1
𝑇ℎ𝑒𝑟𝑒𝑓𝑜𝑟𝑒, 𝑒𝑠𝑠 = lim 1+𝐺 𝑠𝑠 𝐻(𝑠) = lim 𝑠2 (1+𝐺 = lim = --(2.50)
𝑠→0 𝑠→0 𝑠 𝐻 𝑠 ) 𝑠2 G s H(s) 𝐾𝑎
𝑠→0
where 𝐾𝑎 = lim 𝑠 2 G s H s
𝑠→0
Type 0 system
1 1
Therefore, 𝑒𝑠𝑠 = = =∞ ---(2.51)
𝐾𝑎 0
Type 1 system
1 1
𝑒𝑠𝑠 = 𝐾𝑎 = 0 = ∞ ---(2.52)
Type 2 system
𝑠+𝑧1 𝑠+𝑧2 𝑠+𝑧3 … 𝑧 𝑧 𝑧
𝐾𝑎 = 𝑙𝑖𝑚 𝑠 𝐺 𝑠 𝐻(𝑠)= 𝑙𝑖𝑚 𝑠 2 𝐾 𝑠2 = 𝐾 𝑝1𝑝2 𝑝3 = 𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡
𝑠→0 𝑠→0 𝑠+𝑝1 𝑠+𝑝2 𝑠+𝑝3 …. 1 2 3
52
1
𝑒𝑠𝑠 = 𝐾𝑎 = 𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡 ---(2.53)
Hence in Type-2 systems when the input is unit parabolic there will be a constant
steady state error.
Type 3 system
𝑠+𝑧1 𝑠+𝑧2 𝑠+𝑧3 … 𝑧 𝑧 𝑧
𝐾𝑎 = 𝑙𝑖𝑚 𝑠 𝐺 𝑠 𝐻(𝑠)= 𝑙𝑖𝑚 𝑠 2 𝐾 𝑠3 = 𝐾 𝑝1𝑝2 𝑝3 = ∞
𝑠→0 𝑠→0 𝑠+𝑝1 𝑠+𝑝2 𝑠+𝑝3 …. 1 2 3
1 1
𝑒𝑠𝑠 = 𝐾𝑎 = ∞ = 0 ---(2.54)
In system with type number 3 and above, for unit parabolic input the value of 𝐾𝑎 is
infinity and so the steady state error is zero.
The following table shows the steady state errors and the error constants
for standard input signals like unit step, unit ramp & unit parabolic signals
Kv 0 Constant ∞ ∞
Ka 0 0 Constant ∞
53
Steady State Error for Various Types of Input
1.A unity feedback control system has the open loop transfer function
4(1+2𝑠)
𝐺 𝑠 = . If the input to a system is a unit ramp, find steady state error.
𝑠2 (𝑠+2)
Solution:
4(1+2𝑠)
Given that 𝐺 𝑠 = , r(t) =tu(t).
𝑠2 (𝑠+2)
1
Take the Laplace Transform of r(t),we get R(s) =𝑠2
𝑠𝑅(𝑠)
𝑒𝑠𝑠 = lim
𝑠→0 1 + 𝐺 𝑠 𝐻(𝑠)
1
𝑠 2
𝑒𝑠𝑠 = lim 𝑠
4(1+2𝑠) = 0
𝑠→0 1+ 2
𝑠 (𝑠+2)
54
2. For servomechanism with open loop transfer function given below explain what
type of input signal give rise to a constant steady state error and calculate their
values.
20(𝑠 + 2)
𝐺 𝑠 =
𝑠(𝑠 + 1)(𝑠 + 3)
Solution:
20(𝑠+2)
𝐺𝑖𝑣𝑒𝑛 𝐺 𝑠 = 𝑠(𝑠+1)(𝑠+3),
40(s+2)
Kv = lim s G s H s = Kv = lim s
𝑠→0 𝑠→0 s(s+1)(s+4)
40 × 2 80 40(s+2)
𝐾𝑣 = = = 20 Ka = lim s 2 G s H s = lim s2 =0
1× 4 4 𝑠→0 𝑠→0 s(s+1)(s+4)
55
K(s+2)
4.A unity feedback system has G s = s2 Determine (i)type of the system,
(s2 +7s+12)
(ii) All error Coefficients(iii)Error for ramp input with magnitude.
Solution:
K(s+2)
Given G s = s2 and H(s) =1
(s2 +7s+12)
(i)Type of System:
Since the number of poles at the origin is 2, therefore it is Type 2 system
(ii)All error coefficients
K(s+2)
Kp = lim G s H(s) = lim 2 (s2 +7s+12) =∞
𝑠→0 s→0 s
K(s+2)
Kv = lim s G s H s = Kv = lim s
𝑠→0 𝑠→0 s2 (s2 +7s+12)
𝐾𝑣 = ∞
K(s+2)
Ka = lim s 2 G s H s = lim s2 s2 (s2 +7s+12)
𝑠→0 𝑠→0
𝐾 × 2 𝐾
𝐾𝑎 = = = 20
1 × 12 6
(iii)Error for the Parabolic input with magnitude
1 6
𝑒𝑠𝑠 = =
𝐾𝑎 𝐾
5.The unity feedback system has the forward transfer function gain 𝐺 𝑠 =
K(2s+1)
and input 𝑟 𝑡 = 1 + 6𝑡. Determine the minimum value of K if the steady
s(5s+1)(1+s)2
state error is to be less than 0.1.
Solution:
K(2s+1)
Given that: 𝐺 𝑠 = s(5s+1)(1+s)2 , H s = 1 and input, 𝑟 𝑡 = 1 + 6𝑡.
To find K:
K(2s+1)
Kp = lim G s H(s) = lim =∞
𝑠→0 s→0 s(5s+1)(1+s)2
K(2s + 1)
Kv = lim s G s H s = Kv = lim s =K
𝑠→0 𝑠→0 s(5s + 1)(1 + s)2
K(2s+1)
Ka = lim s 2 G s H s = lim s2 =0
𝑠→0 𝑠→0 s(5s+1)(1+s)2
56
Let A1 = Step input
A2 = Ramp input
A3 = Parabolic input
𝐴1 𝐴2 𝐴3
𝑇ℎ𝑒𝑟𝑒𝑓𝑜𝑟𝑒 , 𝑒𝑠𝑠 = + +
1 + Kp 𝐾𝑣 𝐾𝑎
For the given input 𝑟 𝑡 = 1 + 6𝑡. , A1 = 1, A2 = 6
1 6
𝑒𝑠𝑠 = +
1+∞ 𝐾
6
0.1 = 0 +
𝐾
𝐾 = 60
𝑡2
6. Determine K to limit the error of a system for input 𝑟 𝑡 = 1 + 8𝑡 + 18 to 0.8
2
K
having 𝐺 𝑠 𝐻(𝑠) = .
s2 s+1 (s+4)
Solution:
K 𝑡2
Given that: 𝐺 𝑠 𝐻(𝑠) = s2 and input, 𝑟 𝑡 = 1 + 8𝑡 + 18
s+1 (s+4) 2
To find K:
K
Kp = lim G s H(s) = lim =∞
𝑠→0 s→0 s2 s+1 (s+4)
K
Kv = lim s G s H s = Kv = lim s 2 =∞
𝑠→0 𝑠→0 s s + 1 (s + 4)
K K
Ka = lim s 2 G s H s = lim s2 =
𝑠→0 𝑠→0 s2 s+1 s+4 4
57
2.13 GENERALIZED ERROR COEFFICIENT OR DYNAMIC
ERROR COEFFICIENT
The generalized error coefficients determine the nature of system
response to any arbitrary input and it gives the steady state error in terms of t.
The final steady state error can be obtained by substituting as t=∞.
If the error varies with time, then the error series is used.
The error series is given by,
𝑒𝑠𝑠 = lim e(t) ---(2.55)
𝑡→∞
𝐶 𝐶 𝐶 𝐶𝑛 (𝑡)
𝑒𝑠𝑠 = 𝐶0 𝑟 𝑡 + 1!1 𝑟 𝑡 + 3!2 𝑟 𝑡 + 3!3 𝑟 𝑡 + ⋯ + 𝑟 𝑡
𝑛!
d2 F1 s
𝐶2 = lim ---(2.58)
𝑠→0 ds2
dn Fn s
𝐶𝑛 = lim ---(2.59)
𝑠→0 dsn
9
1.An open loop transfer function 𝐺 𝑠 = 𝑠+1 of unity feedback system. Evaluate the
3𝑡 2
first three coefficient error series and steady state error for input 𝑟 𝑡 = .
2
Solution:
9 3𝑡 2
Given that 𝐺 𝑠 = 𝑠+1 , 𝐻 𝑠 = 1 𝑎𝑛𝑑 𝑖𝑛𝑝𝑢𝑡 , 𝑟 𝑡 = .
2
To find F(s):
1 1 𝑠+1
𝐹 𝑠 = = =
1 + 𝐺𝐻 1 + 9 𝑠 + 10
𝑠+1
To find 𝐶0 :
𝑠+1 1
𝐶0 = lim F s = = = 0.1
𝑠→0 𝑠 + 10 10
To find 𝐶1 :
dF s
𝐶1 = lim
𝑠→0 ds
d 𝑠+1
𝐶1 = lim
𝑠→0 ds 𝑠 + 10
s + 10 × 1 − s + 1 × 1
𝐶1 = lim
𝑠→0 (s + 10)2
58
9 9
𝐶1 = lim 2
= = 0.09
𝑠→0 (s + 10) 100
To find 𝐶2 :
d2 F s d2 𝑠 + 1
𝐶2 = lim = lim
𝑠→0 ds 2 𝑠→0 ds 2 𝑠 + 10
−2
𝐶2 = lim 9 −2(𝑠 + 10)−3 = lim 9
𝑠→0 𝑠→0 (𝑠 + 10)−3
18
𝐶2 = lim − = −0.018
𝑠→0 1000
2.14 COMPONENTS OF AUTOMATIC CONTROL SYSTEM
The basic components of an automatic control system are Error detector,
Amplifier and Controller, Actuator (Power actuator), Plant and Sensor or Feedback
system. The block diagram of an automatic control system is shown in fig.
59
no error signal and the output settles at the desired value.
Generally, the error signal will be a weak signal and so it has to be
amplified and then modified for better control action. In most of the system the
controller itself amplifies the error signal and integrates or differentiates to produce
a control signal (i.e., modified error signal). The different types of controllers are P,
PI, PD and PID controllers.
2.15 CONTROLLERS
A controller is a device introduced in the system to modify the error signal
and to produce a control signal. The manner in which the controller produces the
control signal is called the control action. The controller modifies the transient
response of the system. The electronic controllers using operational amplifiers are
presented in this section.
The following six basic control actions are very common among industrial analog
controllers.
1. TWO-position or ON-OFF control action.
2. Proportional control action.
3. Integral control action.
4. Proportional-plus- integral control action.
5. Proportional-plus-derivative control action.
6.Proportional-plus-integral-plus-derivative control action.
Depending on the control actions provided the controllers can be classified as
follows.
1. Two position or ON-OFF controllers.
2. Proportional controllers. 3. Integral controllers.
4. Proportional-plus-integral controllers.
5. Proportional-plus-derivative controllers.
6. Proportional-plus-integral-plus-derivative controllers.
60
Then ON-OFF control action may be provided by a relay. There are different types of
relay. The most popular one is electromagnetic relay. It is a device which has NO
(Normally Open) and NC(Normally Closed) contacts, whose opening and closing are
controlled by the relay coil. When the relay coil is excited, the relay operates and the
contacts change their positions (i.e., NO-NC and NC-NO).
Let the output signal from the controller be u(t) and the actuating error
signal be e(t). In this controller, u(t) remains at either a maximum or minimum
value.
𝑢 𝑡 = 𝑢1 ; 𝑓𝑜𝑟 𝑒 𝑡 < 0
𝑢 𝑡 = 𝑢2 ; 𝑓𝑜𝑟 𝑒 𝑡 > 0
𝐸 𝑠 = 𝐿 𝑒 𝑡 ; 𝑈 𝑠 = 𝐿{𝑢 𝑡 }
The equation (2.60) gives the output of the P-controller for the input E(s) and
equation (2.61) is the transfer function of the P-controller. The block diagram of the
P-Controller is shown below.
61
From the equation (2.61), we can conclude that the proportional controller
amplifies the error signal by the amount Kp. Also the introduction of the controller
on the system increases the loop gain by an amount Kp. The increase in loop gain
improves the steady state, disturbance signal rejection and the relative stability and
also makes the system less sensitive to parameter variations. But increasing the gain
to very large values may lead to instability of the system. The drawback in P-
Controller is that it leads to a constant steady state error.
2.15.3 INTEGRAL CONTROLLER (I-CONTROLLER)
The integral controller is a device that produces a control signal u(t) which is
proportional to integral of the input error signal, e(t).
In I-controller, 𝑢 𝑡 ∝ 𝑡𝑑 𝑡 𝑒
∴ 𝑢 𝑡 = 𝐾𝑖 𝑡𝑑 𝑡 𝑒
𝑤ℎ𝑒𝑟𝑒, 𝐾𝑖 = 𝐼𝑛𝑡𝑒𝑔𝑟𝑎𝑙 𝑔𝑎𝑖𝑛 𝑜𝑟 𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡
On taking Laplace transform of equation above we get,
𝐸 𝑠
𝑈 𝑠 = 𝐾𝑖 ---(2.62)
𝑆
𝑈 𝑠 𝐾𝑖
∴ 𝑇𝑟𝑎𝑛𝑠𝑓𝑒𝑟 𝑓𝑢𝑛𝑐𝑡𝑖𝑜𝑛 𝑜𝑓 𝐼 − 𝑐𝑜𝑛𝑡𝑟𝑜𝑙𝑙𝑒𝑟, 𝐸 = ---(2.63)
𝑠 𝑆
The equation (2.62) gives the output of the I-controller for the input E(s) and
equation (2.63) is the transfer function of the I-controller. The block diagram of the
I-Controller is shown below
In PI-controller, 𝑢 𝑡 ∝ 𝑒 𝑡 + 𝑡𝑑 𝑡 𝑒
62
𝐾𝑝
∴ 𝑢 𝑡 = 𝐾𝑝 𝑒 𝑡 + න 𝑒 𝑡 𝑑𝑡
𝑇𝑖
𝑤ℎ𝑒𝑟𝑒, 𝐾𝑝 = 𝑃𝑟𝑜𝑝𝑜𝑟𝑡𝑖𝑜𝑛𝑎𝑙 𝑔𝑎𝑖𝑛 𝑎𝑛𝑑 𝑇𝑖 𝐼𝑛𝑡𝑒𝑔𝑟𝑎𝑙 𝑡𝑖𝑚𝑒
On taking Laplace transform of equation with zero initial conditions above we get,
𝐾𝑝 𝐸 𝑠
𝑈 𝑠 = 𝐾𝑝 𝐸 𝑠 + ---(2.64)
𝑇𝑖 𝑠
𝑈 𝑠 1
𝑇𝑟𝑎𝑛𝑠𝑓𝑒𝑟 𝑓𝑢𝑛𝑐𝑡𝑖𝑜𝑛 𝑜𝑓 𝑃𝐼 − 𝑐𝑜𝑛𝑡𝑟𝑜𝑙𝑙𝑒𝑟, 𝐸 = 𝐾𝑝 1 + 𝑇 𝑠 ---(2.65)
𝑠 𝑖
The equation (2.64) gives the output of the PI-controller for the input E(s) and
equation (2.65) is the transfer function of the PI-controller. The block diagram of the
PI-Controller is shown below
𝑈(𝑠)
∴ 𝑇𝑟𝑎𝑛𝑠𝑓𝑒𝑟 𝑓𝑢𝑛𝑐𝑡𝑖𝑜𝑛 𝑜𝑓 𝑃𝐷 − 𝑐𝑜𝑛𝑡𝑟𝑜𝑙𝑙𝑒𝑟, 𝐸(𝑠) = 𝐾𝑝 1 + 𝑇𝑑 𝑠 ---(2.67)
63
The equation (2.66) gives the output of the PD-controller for the input E(s) and
equation (2.67) is the transfer function of the PD-controller. The block diagram of
the PI-Controller is shown below
On taking Laplace transform of equation with zero initial conditions above we get,
𝐾𝑝 𝐸 𝑠
𝑈 𝑠 = 𝐾𝑝 𝐸 𝑠 + + 𝐾𝑝 𝑇𝑑 𝑠 𝐸(𝑠) ---(2.68)
𝑇𝑖 𝑠
𝑈(𝑠) 1
∴ 𝑇𝑟𝑎𝑛𝑠𝑓𝑒𝑟 𝑓𝑢𝑛𝑐𝑡𝑖𝑜𝑛 𝑜𝑓 𝑃𝐼𝐷 𝑐𝑜𝑛𝑡𝑟𝑜𝑙𝑙𝑒𝑟, 𝐸(𝑠) = 𝐾𝑝 1 + 𝑇 𝑠 + 𝑇𝑑 𝑠 ---(2.69)
𝑖
64
The equation (2.68) gives the output of the PID-controller for the input E(s) and
equation (2.69) is the transfer function of the PID-controller. The block diagram of
the PID-Controller is shown below
65
Fig.2.22 Equivalent circuit of Integrator and sign changer
On taking Laplace transform of equation with zero initial conditions above we get,
𝐸 𝑠
𝐼1 𝑠 = ---(2.71)
𝑅1
1
𝐼1 𝑠 = 𝐸 𝑠 ---(2.72)
𝑅1
1
𝐹𝑟𝑜𝑚 𝑡ℎ𝑒 𝑠𝑒𝑐𝑜𝑛𝑑 𝑙𝑜𝑜𝑝 𝑜𝑓 𝑡ℎ𝑒 𝑖𝑛𝑡𝑒𝑔𝑟𝑎𝑡𝑜𝑟 𝑖1 𝑅2 + 𝑖 1 𝑑𝑡 = −𝑢1 𝑡 ---(2.73)
𝐶2
By varying the values of R1 and R2 and the values of Kp and Ti are adjusted.
On taking Laplace transform of equation (2.73) with zero initial conditions we get,
1 𝐼1 𝑠
𝐼1 𝑠 𝑅2 + = − 𝑈1 𝑠 ---(2.74)
𝐶2 𝑠
1
∴ 𝐼1 𝑠 𝑅2 + = − 𝑈1 𝑠 ---(2.75)
𝐶2 𝑠
𝑢1 𝑡 = 𝑖2 𝑅 ---(2.78)
Substitute for i2 from equation (2.77) in equation (2.78)
𝑢(𝑡)
∴ 𝑢1 = − 𝑅 = −𝑢(𝑡) ---(2.79)
𝑅
66
On taking Laplace transform of the equation (2.79) we get,
𝑈1 𝑠 = −𝑈 𝑠 ---(2.80)
Substitute for U1(s) from equation (2.76) in equation (2.80)
𝑅2 1
− + 𝐸 𝑠 = −𝑈 𝑠
𝑅1 𝑅1 𝐶2 𝑠
𝑅2 1
+ 𝐸 𝑠 = 𝑈 𝑠
𝑅1 𝑅1 𝐶2 𝑠
𝑈 𝑠 𝑅2 1
= +
𝐸(𝑠) 𝑅1 𝑅1 𝐶2 𝑠
𝑈 𝑠 𝑅 1
= 𝑅2 1 + 𝑅 ---(2.81)
𝐸(𝑠) 1 2 𝐶2 𝑠
67
Fig.2.24 Equivalent circuit of Differentiator and sign changer
𝑒 𝑡 𝑑
𝑖1 = + 𝐶1 𝑑𝑡 𝑒 𝑡 ---(2.82)
𝑅1
On taking Laplace transform of equation with zero initial conditions above we get,
1
𝐼1 𝑠 = 𝐸 𝑠 + 𝐶1 𝑠 𝐸 𝑠 ---(2.83)
𝑅1
1
𝐼1 𝑠 = + 𝐶1 𝑠 𝐸 𝑠 ---(2.84)
𝑅1
On taking Laplace transform of equation ( 2.85 ) with zero initial conditions we get,
𝐼1 𝑠 𝑅2 = − 𝑈1 𝑠 ---(2.86)
𝑅2
∴− 𝑅1
+𝑅2 𝐶1 𝑠 𝐸 𝑠 = 𝑈1 𝑠 ---(2.87)
𝑢1 𝑡 = 𝑖2 𝑅 ---(2.89)
68
Substitute for U1(s) from equation (2.91 ) in equation ( 2.87)
𝑅2
− +𝑅2 𝐶1 𝑠 𝐸 𝑠 = −𝑈 𝑠
𝑅1
𝑅2
+𝑅2 𝐶1 𝑠 𝐸 𝑠 = 𝑈 𝑠
𝑅1
𝑈 𝑠 𝑅2
= +𝑅2 𝐶1 𝑠
𝐸(𝑠) 𝑅1
𝑈 𝑠 𝑅
= 𝑅2 1 +𝑅1 𝐶1 𝑠 ---(2.92)
𝐸(𝑠) 1
By varying the values of R1 and R2 and the values of Kp and Td are adjusted.
By deriving the transfer function of the controller shown above and comparing with
the transfer function of PID-controller defined by equation (2.69) it can be proved
that the circuit shown in above figure works as PID-controller.
69
Based on the above assumptions the equivalent circuit of op-amp amplifier and sign
changer are shown in figure below
On taking Laplace transform of equation with zero initial conditions above we get,
1
𝐼1 𝑠 = 𝐸 𝑠 + 𝐶1 𝑠 𝐸 𝑠 ---(2.94)
𝑅1
1
𝐼1 𝑠 = + 𝐶1 𝑠 𝐸 𝑠 ---(2.95)
𝑅1
1
𝐹𝑟𝑜𝑚 𝑡ℎ𝑒 𝑠𝑒𝑐𝑜𝑛𝑑 𝑙𝑜𝑜𝑝 𝑜𝑓 𝑡ℎ𝑒 𝐴𝑚𝑝𝑙𝑖𝑓𝑖𝑒𝑟 𝑖1 𝑅2 + 𝑖 1 𝑑𝑡 = −𝑢1 𝑡 ---(2.96)
𝐶2
On taking Laplace transform of equation (2.96) with zero initial conditions we get,
1 𝐼1 𝑠
𝐼1 𝑠 𝑅2 + = − 𝑈1 𝑠 ---(2.97)
𝐶2 𝑠
1
∴ 𝐼1 𝑠 𝑅2 + = − 𝑈1 𝑠 ---(2.98)
𝐶2 𝑠
𝑢1 𝑡 = 𝑖2 𝑅 ---(2.101)
Substitute for i2 from equation (2.100) in equation (2.101)
𝑢 𝑡
∴ 𝑢1 = − 𝑅
𝑅 = −𝑢 𝑡 ---(2.102)
70
On taking Laplace transform of the equation (2.102) we get,
𝑈1 (𝑠) = −𝑈(𝑠) ---(2.103)
Substitute for U1(s) from equation (2.99) in equation (2.103)
𝑅2 𝐶1 1
− + + +𝑅2 𝐶1 𝑠 𝐸 𝑠 = −𝑈 𝑠
𝑅1 𝑐2 𝑅1 𝐶2 𝑠
𝑅2 𝐶1 1
+ + +𝑅2 𝐶1 𝑠 𝐸 𝑠 = 𝑈 𝑠
𝑅1 𝑐2 𝑅1 𝐶2 𝑠
𝑈 𝑠 𝑅2 𝐶1 1
= + + +𝑅2 𝐶1 𝑠
𝐸(𝑠) 𝑅1 𝑐2 𝑅1 𝐶2 𝑠
𝑈 𝑠 𝑅2 𝐶1 1
= + + +𝑅2 𝐶1 𝑠
𝐸(𝑠) 𝑅1 𝑐2 𝑅1 𝐶2 𝑠
𝑈 𝑠 𝑅 𝑅1 𝐶2 +𝑅2 𝐶1 1
= 𝑅2 +𝑅 +𝑅1 𝐶1 𝑠 ---(2.104)
𝐸(𝑠) 1 𝑅1 𝐶2 2 𝐶2 𝑠
71
The term Kp in the transfer function of proportional controller is called the
gain of the controller. Hence the proportional controller amplifies the error signal and
increases the loop gain of the system. The following aspects of system behavior are
improved by increasing loop gain.
(iii)Relative stability
1
𝑇𝑟𝑎𝑛𝑠𝑓𝑒𝑟 𝑓𝑢𝑛𝑐𝑡𝑖𝑜𝑛 𝑜𝑓 𝑃𝐼 − 𝑐𝑜𝑛𝑡𝑟𝑜𝑙𝑙𝑒𝑟, 𝐺𝑐 𝑠 = 𝐾𝑝 1 + ---(2.106)
𝑇𝑖 𝑠
𝑊ℎ𝑒𝑟𝑒 𝐾𝑝 𝑖𝑠 𝑡ℎ𝑒 𝑝𝑟𝑜𝑝𝑜𝑡𝑖𝑜𝑛𝑎𝑙 𝑔𝑎𝑖𝑛 𝑎𝑛𝑑 𝑇𝑖 𝑖𝑠 𝑖𝑛𝑡𝑒𝑔𝑟𝑎𝑙 𝑡𝑖𝑚𝑒
The block diagram of unity feedback system with PI- controller is shown below.
Let the open loop transfer function G(s) be a second order system with transfer
function, as shown below
𝜔𝑛2
𝐺 𝑠 =
𝑠(𝑠 + 2𝛿𝜔𝑛 )
Now, loop transfer function = Gc(s) G(s) H(s)
2 2 (1+𝑇 𝑠)
𝐾𝑝 𝜔𝑛
1 𝜔𝑛
= 𝐺𝑐 𝑠 𝐺 𝑠 . 1 = 𝐾𝑝 1 + 𝑇 𝑠 = 𝑖
---(2.107)
𝑖 𝑠(𝑠+2𝛿𝜔𝑛 ) 𝑠2 𝑇𝑖 (𝑠+ 2𝛿𝜔𝑛 )
72
Now the closed loop transfer function is given by,
𝐶(𝑠) 𝐺𝑐 𝑠 𝐺(𝑠)
=
𝑅(𝑠) 1 + 𝐺𝑐 𝑠 𝐺(𝑠)
𝐾𝑝 𝜔𝑛2 (1 + 𝑇𝑖 𝑠)
𝐶(𝑠) 𝑠 2 𝑇𝑖 (𝑠 + 2𝛿𝜔𝑛 )
=
𝑅(𝑠) 𝐾𝑝 𝜔𝑛2 (1 + 𝑇𝑖 𝑠)
1+ 2
𝑠 𝑇𝑖 (𝑠 + 2𝛿𝜔𝑛 )
𝐶(𝑠) 𝐾𝑝 𝜔𝑛2 (1 + 𝑇𝑖 𝑠)
= 2
𝑅(𝑠) 𝑠 𝑇𝑖 𝑠 + 2𝛿𝜔𝑛 + 𝐾𝑝 𝜔𝑛2 (1 + 𝑇𝑖 𝑠)
𝐶(𝑠) 𝐾𝑝 𝜔𝑛2 (1 + 𝑇𝑖 𝑠)
=
𝑅(𝑠) 𝑇𝑖 𝑠 3 + 2𝛿𝜔𝑛 𝑇𝑖 𝑠 2 + 𝐾𝑝 𝜔𝑛2 𝑇𝑖 𝑠 + 𝐾𝑝 𝜔𝑛2 )
𝐶(𝑠) 𝐾𝑝 𝜔𝑛2 (1 + 𝑇𝑖 𝑠)
=
𝑅(𝑠) 𝐾𝑝
𝑇𝑖 (𝑠 3 + 2𝛿𝜔𝑛 𝑠 2 + 𝐾𝑝 𝜔𝑛2 𝑠 + 𝑇 𝜔𝑛2 )
𝑖
𝐾𝑝 2
𝐶(𝑠) 𝑇𝑖 𝜔𝑛 (1 + 𝑇𝑖 𝑠)
=
𝑅(𝑠) 𝐾𝑝
(𝑠 3 +2𝛿𝜔𝑛 𝑠 2 + 𝐾𝑝 𝜔𝑛2 𝑠 + 𝑇 𝜔𝑛2 )
𝑖
𝐶(𝑠) 2 (1+𝑇 𝑠)
𝐾𝑖 𝜔𝑛 𝐾𝑝
= 3 2
𝑖
2 𝑠+ 𝐾 𝜔2 ) ∴ 𝐾𝑖 = ---(2.108)
𝑅(𝑠) (𝑠 +2𝛿𝜔𝑛 𝑠 + 𝐾𝑝 𝜔𝑛 𝑖 𝑛 𝑇𝑖
From the closed loop transfer function(2.108) it is observed that the PI-
controller introduces a zero in the system and increases the order by one. The
increase in the order of the system results in a less stable system than the original
one because higher order systems are less stable than lower order systems.
From the loop transfer function (2.107)it is observed that the PI-controller
increases the type number by one. The increase in type number results in reducing
the steady state error. For example if the steady state error of the original system is
constant, the integral controller will reduce the error to zero.
2.17.3 EFFECT OF PD-CONTROLLER
The proportional plus derivative controller (PD-controller) produces an output signal
consisting of two terms: one proportional to error signal and the other proportional
to the derivative of error signal.
𝑇𝑟𝑎𝑛𝑠𝑓𝑒𝑟 𝑓𝑢𝑛𝑐𝑡𝑖𝑜𝑛 𝑜𝑓 𝑃𝐷 − 𝑐𝑜𝑛𝑡𝑟𝑜𝑙𝑙𝑒𝑟, 𝐺𝑐 𝑠 = 𝐾𝑝 1 + 𝑇𝑑 𝑠 ---(2.109)
𝑊ℎ𝑒𝑟𝑒 𝐾𝑝 𝑖𝑠 𝑡ℎ𝑒 𝑝𝑟𝑜𝑝𝑜𝑡𝑖𝑜𝑛𝑎𝑙 𝑔𝑎𝑖𝑛 𝑎𝑛𝑑 𝑇𝑑 𝑖𝑠 𝑑𝑒𝑟𝑖𝑣𝑎𝑡𝑖𝑣𝑒 𝑡𝑖𝑚𝑒
The block diagram of unity feedback system with PD- controller is shown below
𝐾𝑝 𝜔𝑛2 1 + 𝑇𝑑 𝑠
𝐶(𝑠) 𝑠(𝑠 + 2𝛿𝜔𝑛 )
=
𝑅(𝑠) 𝐾𝑝 𝜔𝑛2 1 + 𝑇𝑑 𝑠
1+
𝑠(𝑠 + 2𝛿𝜔𝑛 )
𝐶(𝑠) 𝐾𝑝 𝜔𝑛2 1 + 𝑇𝑑 𝑠
=
𝑅(𝑠) 𝑠(𝑠 + 2𝛿𝜔𝑛 ) + 𝐾𝑝 𝜔𝑛2 1 + 𝑇𝑑 𝑠
𝐶(𝑠) 𝐾𝑝 𝜔𝑛2 (1 + 𝑇𝑑 𝑠)
= 2
𝑅(𝑠) 𝑠 + 2𝛿𝜔𝑛 𝑠 + 𝐾𝑝 𝜔𝑛2 𝑇𝑑 𝑠 + 𝐾𝑝 𝜔𝑛2 )
𝐶(𝑠) 𝐾𝑝 𝜔𝑛2 (1 + 𝑇𝑑 𝑠)
= 2
𝑅(𝑠) 𝑠 + (2𝛿𝜔𝑛 + 𝐾𝑝 𝜔𝑛2 𝑇𝑑 )𝑠 + 𝐾𝑝 𝜔𝑛2 )
2 (𝐾 +𝐾 𝑠)
𝜔𝑛
𝐶(𝑠)
∴ 𝐾𝑑 = 𝐾𝑝 𝑇𝑑 ---(2.111)
𝑝 𝑑
= 2 )𝑠+ 𝐾 𝜔 2 )
𝑅(𝑠) 𝑠2 +(2𝛿𝜔𝑛 +𝐾𝑑 𝜔𝑛 𝑝 𝑛
From the closed loop transfer function (2.111) it is observed that the PD-
controller introduces a zero in the system and increases the damping ratio. The
addition of the zero may increase the peak overshoot and reduce the rise time. But
the effect of increased damping ultimately reduces the peak overshoot.
From the loop transfer function(2.110) it is observed that the PD-controller
does not modify the type number of the system. Hence PD-controller will not act
modify steady state error.
74
Problems on Controller
1.The following diagram shown unity feedback with derivative control. By using
derivative control the damping ratio is to be made 0.5. Determine the value of Td
[May/June-2014]
Solution:
𝑇𝑟𝑎𝑛𝑠𝑓𝑒𝑟 𝑓𝑢𝑛𝑐𝑡𝑖𝑜𝑛 𝑜𝑓 𝑃𝐷 − 𝑐𝑜𝑛𝑡𝑟𝑜𝑙𝑙𝑒𝑟, 𝐺𝑐 𝑠 = 1 + 𝑇𝑑 𝑠
Open loop transfer function G(s) be a second order system with transfer function, as
shown below
16
𝐺 𝑠 =
(𝑠 2 +1.6𝑠)
Now, Gc(s) G(s)
16 𝑇𝑑 𝑠 16 + 16
𝐺𝑐 𝑠 𝐺 𝑠 = 1 + 𝑇𝑑 𝑠 =
(𝑠 2 +1.6𝑠) (𝑠 2 +1.6𝑠)
Now the closed loop transfer function is given by,
𝐶(𝑠) 𝐺𝑐 𝑠 𝐺(𝑠)
=
𝑅(𝑠) 1 + 𝐺𝑐 𝑠 𝐺(𝑠)
𝑇𝑑 𝑠 16 + 16
𝐶(𝑠) (𝑠 2 +1.6𝑠)
=
𝑅(𝑠) 𝑇 𝑠 16 + 16
1+ 𝑑 2
(𝑠 +1.6𝑠)
𝐶(𝑠) 𝑇𝑑 𝑠 16 + 16
= 2
𝑅(𝑠) (𝑠 +1.6𝑠) + 𝑇𝑑 𝑠 16 + 16
𝐶(𝑠) 𝑇𝑑 𝑠 16 + 16
= 2
𝑅(𝑠) 𝑠 + 1.6𝑠 + 𝑇𝑑 𝑠 16 + 16
𝐶(𝑠) 𝑇𝑑 𝑠 16 + 16
= 2
𝑅(𝑠) 𝑠 + (1.6 + 16𝑇𝑑 )𝑠 + 16
The standard form of closed loop transfer function for second order system is
𝐶(𝑠) 𝜔𝑛2
= 2
𝑅(𝑠) 𝑠 + 2𝛿𝜔𝑛 𝑠 + 𝜔𝑛2
75
Comparing with the standard form
2𝛿𝜔𝑛 = 16 𝑇𝑑 + 1.6 and 𝜔𝑛2 = 16 , Given damping ratio = 0.5
2𝛿𝜔𝑛 − 1.6 = 16 𝑇𝑑
2𝛿𝜔𝑛 − 1.6
𝑇𝑑 =
16
2𝑥0.5𝑥4 − 1.6
𝑇𝑑 =
16
2.4
𝑇𝑑 =
16
𝑇𝑑 = 0.15 𝑆𝑒𝑐
2.A closed loop control system with unity feedback is shown in figure. By using
derivative control the damping ratio is to made 0.75. Determine the value Td. Also
determine rise time, peak time and peak overshoot without derivative control and
with derivative control. The input to the system is unit step input.
Solution:
Without Controller Transfer function of the system
4
𝐶(𝑠) 2
= 𝑠 +𝑠
𝑅(𝑠) 4
1+ 2
𝑠 +𝑠
𝐶(𝑠) 4
= 2
𝑅(𝑠) 𝑠 +𝑠+4
On comparing with the standard form
𝜔𝑛2 = 4 and 𝜔𝑛 = 2 rad/sec
1
2𝛿𝜔𝑛 = 1 and 𝛿 =
2𝑥2
𝛿 = 0.25
76
Rise time:
1 − 𝛿2
𝜋−𝜃 𝜋 − 𝑡𝑎𝑛−1
𝛿
𝑡𝑟 = =
𝜔𝑑 𝜔𝑛 1 − 𝛿 2
𝜋 − 1.318
𝑡𝑟 =
2 1 − 0.252
𝑡𝑟 = 0.942 Sec
Peak time:
𝜋 𝜋
𝑡𝑝 = =
𝜔𝑑 𝜔𝑛 1 − 𝛿 2
𝜋
𝑡𝑝 =
2 1 − 0.252
𝑡𝑝 = 1.62 Sec
Peak overshoot:
𝛿𝜋
−
2
% 𝑀𝑝 = 𝑒 1−𝛿 𝑥 100
0.25 𝑥 2
−
% 𝑀𝑝 = 𝑒 1−0.252 𝑥 100
% 𝑀𝑝 = 44.4 %
4 (1 + 𝑇𝑑 𝑠)
𝑠2 + 𝑠
4 (1 + 𝑇𝑑 𝑠)
1+
𝑠2 + 𝑠
𝐶(𝑠) 4 (1 + 𝑇𝑑 𝑠)
= 2
𝑅(𝑠) 𝑠 + 𝑠 + 4 (1 + 𝑇𝑑 𝑠)
𝐶(𝑠) 4 (1 + 𝑇𝑑 𝑠)
= 2
𝑅(𝑠) 𝑠 + (1 + 4𝑇𝑑 )𝑠 + 4
On comparing with the standard form
𝜔𝑛2 = 4 and 𝜔𝑛 = 2 rad/sec
2𝛿𝜔𝑛 = 1 + 4𝑇𝑑
77
2𝛿𝜔𝑛 −1
𝑇𝑑 = And Substitute given damping ratio 0.75 for PD controller System
4
2𝑥0.75𝑥2 − 1
𝑇𝑑 =
4
𝑇𝑑 = 0.5
Rise time:
1 − 𝛿2
𝜋−𝜃 𝜋 − 𝑡𝑎𝑛−1
𝛿
𝑡𝑟 = =
𝜔𝑑 𝜔𝑛 1 − 𝛿 2
1 − 0.752
𝜋 − 𝑡𝑎𝑛−1
0.75
𝑡𝑟 =
2 1 − 0.752
𝑡𝑟 = 0.942 Sec
Peak time:
𝜋 𝜋
𝑡𝑝 = =
𝜔𝑑 𝜔𝑛 1 − 𝛿 2
𝜋
𝑡𝑝 =
2 1 − 0.752
𝑡𝑝 = 2.37 Sec
Peak overshoot:
𝛿𝜋
−
% 𝑀𝑝 = 𝑒 1−𝛿 2 𝑥 100
0.75 𝑥 2
−
% 𝑀𝑝 = 𝑒 1−0.752 𝑥 100
% 𝑀𝑝 = 2.8 %
3.For the system shown in Figure. Find the effect of PD controller with Td = 1/10 on
peak overshoot and settling time when it is excite by unit step input. [Apr/May 2015]
Solution:
First simply the given block diagram by cascading blocks
78
Now we include the PD controller with given system
𝑌(𝑠) (1 + 𝑇𝑑 𝑠 )5
=
𝑋(𝑠) 𝑠(𝑠 + 3) + (1 + 𝑇𝑑 𝑠 )5
𝑌(𝑠) (5𝑇𝑑 𝑠 + 5 )
= 2
𝑋(𝑠) 𝑠 + 3𝑠 + 5𝑇𝑑 𝑠 + 5
𝑌(𝑠) (5𝑇𝑑 𝑠 + 5 )
= 2
𝑋(𝑠) 𝑠 + (3 + 5𝑇𝑑 )𝑠 + 5
Substitute Td = 1/10 = 0.1 given in the problem
𝑌(𝑠) (0.5𝑠 + 5 )
= 2
𝑋(𝑠) 𝑠 + 3.5𝑠 + 5
The standard form of closed loop transfer function for second order system is
𝐶(𝑠) 𝜔𝑛2
= 2
𝑅(𝑠) 𝑠 + 2𝛿𝜔𝑛 𝑠 + 𝜔𝑛2
On comparing with the standard form
𝜔𝑛2 = 5 and 𝜔𝑛 = 2.23 rad/sec
3.5
2𝛿𝜔𝑛 = 3.5 and 𝛿 = 2𝑥2.23
𝛿 = 0.754
79
Peak overshoot:
𝛿𝜋
−
% 𝑀𝑝 = 𝑒 1−𝛿 2 𝑥 100
0.754 𝑥 3.14
−
% 𝑀𝑝 = 𝑒 1−0.754 2
𝑥 100
% 𝑀𝑝 = 1.99 ≅ 2
Settling Time:
4
For 2% error 𝑡𝑠 =
𝛿𝜔𝑛
4
𝑡𝑠 =
0.754 𝑥 2.23
𝑡𝑠 = 2.285 𝑆𝑒𝑐
3
For 5% error 𝑡𝑠 =
𝛿𝜔𝑛
3
𝑡𝑠 =
0.754 𝑥 2.23
𝑡𝑠 = 1.714 𝑆𝑒𝑐
80
LINKS TO VIDEOS
UNIT II
https://www.youtube.com/watch?v=ziu1OTwUrbw
https://www.youtube.com/watch?v=YuZ3iwA-47I
https://www.youtube.com/watch?v=ONkuhKtbvYs
https://www.youtube.com/watch?v=bUYzLCwAoCQ
https://drive.google.com/drive/folders/1UrctnMzYLF9KjPf6VbWCMQ
pASWj0_uFm
81
E-book References
82
9.Assignments UNIT II
Slow Learner
2. Derive the unit step response and unit ramp response for the first order
system shown in fig.
83
9.Assignments UNIT II
Medium Learner
100
T ( s) =
s 2 + 10s + 100
Determine the damping ratio, natural frequency of oscillations, rise
time, settling time and peak overshoot.
3. Determine the unit Step response of the control system shown in figure.
84
9.Assignments UNIT II
In the system, x(t) is the input displacement and θ(t) is the output
angular displacement. Assume that the masses involved are negligibly
small and that all motions are restricted to be small; therefore, the system
can be considered linear. The initial conditions for x and θ are zeros, or x(0-
) = 0 and θ(0-) = 0. Show that this system is a differentiating element .
Then obtain the response θ(t) when x(t) is a unit-step input.
Explain why the proportional control of a plant that does not possess an
integrating property (which means that the plant transfer function does not
include the factor 1/s) suffers offset in response to step inputs
The block diagram of Figure. shows a speed control system in which the
output member of the system is subject to a torque disturbance. In the
diagram, Ω(s), Ω(s) ,T(s) and D(s) are the Laplace transforms of the
reference speed, output speed, driving torque, and disturbance torque,
respectively. In the absence of a disturbance torque, the output speed is
equal to the reference speed.
85
10.TWO MARKS QUESTIONS AND ANSWERS-UNIT II
1.Define rise time with reference to time response. (K1 , CO2)
The time taken for response to rise from 0% to 100% for the very first time is
rise time.
2.Give the steady state errors to a various standard inputs for type 2
system. (K1, CO2)
Steady state error=0 for unit step and ramp input
Steady state error=1/Ka for unit parabolic input
86
9.Define Rise time. (K1 , CO2)
The time taken for response to raise from 0% to100% for very first time is Rise
time
87
17.How the system is classified depending on the value of damping?
(K1, CO2)
Depending on the value of damping, the system can be classified into the
following four cases
Case 1 : Undamped system, δ = 0
Case 2 : Under damped system, 0 < δ< 1
Case 3 : Critically damped system, δ= 1
Case 4 : Over damped system, δ> 1.
88
23.What is Proportional controller and what are its advantages?
(K1 , CO2)
The Proportional controller is a device that produces a control signal which is
proportional to the input error signal. The advantages in the proportional
controller are improvement in steady-state tracking accuracy, disturbance signal
rejection and the relative stability. It also makes a system less sensitive to
parameter variations.
89
11. PART B UNIT II
1.Derive the time response of first order system for unit step input and
unit ramp input signal. (K1 , CO2)
2.Derive the unit step response and unit ramp response for the first order
system shown in fig. (K3 ,CO2)
3.Derive the unit step response for the critical damped Second order
system. (K1,CO2)
4.Derive the unit step response of undamped and under damped second
order system.(K1 ,CO2)
5.Derive the time response of first order system for unit impulse input and
Parabolic input signal . (K1,CO2)
6.Determine the unit Step response of the control system shown in figure.
(K3,CO2)
7.Derive the unit step response for over damped second order system.
(K1 , CO2 )
90
8.Measurements conducted on a servo mechanism show that the system
response as
9.Determine the time response specification and expression for output for
unit step input to a system having the system equation.
d2y dy
2
+ 5 + 16 y = 9 x
dt dt
Assume zero initial conditions. (K3, CO2)
100
T ( s) =
s + 10s + 100
2
K
G( s) =
s ( s + 10)
Determine the gain K, so that the system will have the damping ratio
of 0.5. For this value of K, Determine the settling time, peak overshoot,
and time to peak overshoot for a unit step input. (K3, CO2)
91
13.The OLTF of a system with unity feedback is
10
G( s) =
s (0.1s + 1)
Evaluate the static error constant of the system.
Obtain steady state error when subjected to the input given by the
polynomial . (K5, CO2)
a2 2
r (t ) = a0 + a1t + t
2
14.The following diagram shows unity feedback with derivative control.
By using this derivative control the damping ratio is to be made 0.5.
Determine the value of Td . (K3 , CO2)
18.For the system shown, find the dynamic error coefficient method for
input r(t)=5 . (K3,CO2)
92
19.For the system shown find the effect of PID controller with Td=1/10 on
peak overshoot and settling time when it is excited by unit step
input. (K3 , CO2)
20.A closed loop control system with unity feedback is shown in figure.
By using derivative control that damping ratio is to made 0.75.
Determine the value Td. Also determine the rise time, peak time and
peak overshoot without derivative control and with derivative control.
The input to the system is unit step. (K3, CO2)
21.Find the overall transfer functions for the given system and also find
the value of β to make damping ratio of the given system is equal to
0.5. (K3, CO2)
93
22.A second order system has unity feedback and an open loop transfer
function is
500
G( s) =
s ( s + 15)
i)Draw a block diagram for the closed loop system.
ii)What is the characteristic equation of the closed loop system?
iii)What is the numerical value of natural frequency and damping
ratio?
iv)What is the settling time of the system? (K2, CO2)
G ( s ) = K / s ( sT + 1)
, where K and T are positive constant. By what factor should the
amplifier gain K be reduced, So that the peak overshoot of unit step
response of the system is reduce from 75% to 25%. (K4 , CO2)
24.Explain in detail about steady state error and systems . (K2 , CO2)
25. For servomechanism with open loop transfer function given below
explain what type of input signal give rise to constant steady state error
and calculate their values. (K3, CO2)
a.) G(s) = (20(s + 2))/(s(s + 1)(s + 3))
b.) G(s) = (10/((s + 2)(s + 3))
c.) G(s) = (10/(s^2(s + 1)(s + 2))
94
12.Supportive Online Certification courses (NPTEL, Swayam,
Coursera, Udemy, etc.,)
95
13.Real time Applications in day to day life and to industry
UNIT II
❖ Vacuum Control Systems which control the vacuum of a specific industrial
chamber or vessel using different control strategies like PD, PID controllers, etc.,
❖ Machine vision guided robotics( where an embedded or overhead camera is used
to position a manipulator rather than position encoders and inverse kinematics or
use both)
Industry Applications
Control systems are mainly used for controlling the equipments of machines in
industry. In recent years control systems have proliferative applications in in
modern industry and technology. Control systems are found in abundance in all
sectors of industry such as:
❖ Quality control of manufactured products
❖ Automatic assembly line
❖ Machine tool control
❖ Space technology and weapon systems
❖ Computer control
❖ Power Systems
❖ Robotics
❖ Micro Electro Mechanical Systems(MEMS)
❖ Smart transportation systems
❖ Ship stabilization systems
❖ Temperature control systems
❖ Steering control of automobiles
❖ Missile launching system
❖ Sun tracking control of solar collectors
96
14.Contents beyond Syllabus ( COE related value
added courses)
97
(ii)Obtain impulse response of a unity feedback system having forward
path transfer function of G(s) = 1/𝑠+9
MATLAB Code :
num = [1];
den = [1 9]
g = tf (num,den)
t = feedback(g,1)
impulse(t,'r')
Output:
98
15. ASSESSMENT SCHEDULE
Unit 2 Assignment
08.02.2024
Assessment
Unit 3 Assignment
24.02.2024
Assessment
Unit 5 Assignment
12.04.2024
Assessment
TEXT BOOK:
❖ Nagarath, I.J. and Gopal, M., “Control Systems Engineering”, New Age
International Publishers, 2017.
❖ Richard C.Dorf and Bishop, R.H., “Modern Control Systems”, Pearson Education,
14th edition, 2016.
❖ John J.D., Azzo Constantine, H. and Houpis Sttuart, N Sheldon, “Linear Control
System Analysis and Design with MATLAB”, CRC Taylor& Francis 2013.
❖ M.Gopal, “Control System: Principle and design”, McGraw Hill Education, 2018.
❖ NPTEL Video Lecture Notes on “Control Engineering “by Prof. S. D. Agashe, IIT
Bombay.
100
17.Mini Project suggestions
Slow Learners
❖ Auditorium Control System Using IR
❖ Appliances Security Controller Using Power Line
Medium Learners
❖ Access Control System
Using Microcontroller/Microprocessor
❖ Automatic Sprinkler Control System
To p p e r s
❖ A u t o m a t i c S p e e d C o n t r o l l e r f o r Fa n s a n d C o o l e r s U s i n g
Current Sensor
❖ Bomb Detection Robotics Using Embedded Controller
❖ Bi-Directional Visitors Counter
101
AUTOMATIC CONTROL
To automate temperature control with a PID controller, the following are required:
Install an electronic temperature measurement device
Automate the valve by adding an actuator (and perhaps a positioner) so it can be
driven electronically
Install a controller and connect it to the temperature measurement device and
automated control valve
The operator sets the PID controller’s set point (SP) to the desired temperature, and
the controller’s output (CO) sets the position of the control valve. The temperature
measurement, called the process variable (PV), is then transmitted to the PID
controller, which compares it to the set point and calculates the difference, or error
(E), between the two signals. Based on the error and the controller’s tuning
constants, the controller calculates the appropriate controller output to set the
control valve at the correct position to keep the temperature at the set point (Figure
2). If the temperature rises above its set point, the controller will reduce the valve
position and vice versa.
Each of the controller’s three modes reacts differently to the error. The amount of
response produced by each control mode is adjustable by changing the controller’s
tuning settings.
These tuning rules work well on processes with very long time constants relative to
their dead times and on level control loops, which contain an integrating process.
They do not work well on control loops that contain self-regulating processes, such
as flow, temperature, pressure, speed, and composition.
A self-regulating process always stabilizes at some point of equilibrium, which
depends on the process design and controller output; if the controller output is set
to a different value, the process will respond and stabilize at a new point of
equilibrium.
102
Thank you
Disclaimer:
This document is confidential and intended solely for the educational purpose of RMK Group of
Educational Institutions. If you have received this document through email in error, please notify the
system manager. This document contains proprietary information and is intended only to the
respective group / learning community as intended. If you are not the addressee you should not
disseminate, distribute or copy through e-mail. Please notify the sender immediately by e-mail if you
have received this document by mistake and delete this document from your system. If you are not
the intended recipient you are notified that disclosing, copying, distributing or taking any action in
reliance on the contents of this information is strictly prohibited.
103