0% found this document useful (0 votes)
34 views18 pages

14 Miniature and Residual Circuit Breakers

The document details various miniature and residual circuit breakers, including UL 1077 and UL 489 certified versions with a wide current range of 1...125A and multiple trip characteristic curves (B, C, D). It outlines the specifications, features, and applications of these circuit breakers, which are used for circuit protection, isolation, and load operation controls in various settings. Additionally, it includes information on switch disconnectors, residual blocks, and accessories available for these devices.

Uploaded by

Kaos
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
34 views18 pages

14 Miniature and Residual Circuit Breakers

The document details various miniature and residual circuit breakers, including UL 1077 and UL 489 certified versions with a wide current range of 1...125A and multiple trip characteristic curves (B, C, D). It outlines the specifications, features, and applications of these circuit breakers, which are used for circuit protection, isolation, and load operation controls in various settings. Additionally, it includes information on switch disconnectors, residual blocks, and accessories available for these devices.

Uploaded by

Kaos
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 18

Circuit protection andd isolation

14 Miniature and residual circuit breakers

UL 1077 and UL 489 certified


versions
High breaking capacity
Various trip characteristic curves:
Type B, C or D
Wide 1...125A current range
Residuals with trip characteristic
curves type A, AC and B
Switch disconnectors
Accessories available.

SEC. - PAGE
Miniature circuit breakers 1...63A, UL 1077
1P - 10kA, 1 module, curve types B, C and D ........................................................................................................... 14 - 2
1P+N - 6kA, 1 module, curve type C ......................................................................................................................... 14 - 3
1P+N - 6kA, 2 modules, curve type C ....................................................................................................................... 14 - 3
2P - 10kA, 2 modules, curve types B, C and D ......................................................................................................... 14 - 4
3P - 10kA, 3 modules, curve types B, C and D ......................................................................................................... 14 - 5
4P - 10kA, 4 modules, curve types B, C and D ......................................................................................................... 14 - 6
Miniature circuit breakers 1...63A, UL 489
1P - 10kA, 1 module ........................................................................................................................................................... 14 - 7
2P - 10kA, 2 modules ......................................................................................................................................................... 14 - 8
3P - 10kA, 3 modules ......................................................................................................................................................... 14 - 9
Miniature circuit breakers 80...125A, UL 1077
1P, 2P, 3P and 4P - 10kA, curve type C ............................................................................................................................. 14 - 10
3P and 4P - 10kA, curve type D ......................................................................................................................................... 14 - 10
Add-on blocks and accessories ............................................................................................................................. 14 - 11
Modular switch disconnectors .............................................................................................................................. 14 - 13
Residual blocks ........................................................................................................................................................ 14 - 13
Residual current operated circuit breakers ........................................................................................................ 14 - 14
Residual current operated circuit breakers with overcurrent protection ..................................................... 14 - 15

Dimensions ............................................................................................................ 14 - 16
Wiring diagrams ...................................................................................................... 14 - 16
Technical characteristics ............................................................................................ 14 - 17
14

Page 14-2 Page 14-10 Page 14-11

MINIATURE CIRCUIT BREAKERS UP TO 63A MINIATURE CIRCUIT BREAKERS 80...125A ADD-ON BLOCKS AND ACCESSORIES
• 1P, 1P+N, 2P, 3P and 4P versions • 1P, 2P, 3P and 4P versions • Auxiliary and indicator contacts
• IEC rated current In: 1...63A • IEC rated current In: 80...125A • Undervoltage trip releases
• IEC short-circuit breaking capacity Icn: • IEC short-circuit breaking capacity Icn: • Shunt trip releases
10kA (6kA for 1P+N) 10kA • Connection accessories.
• Trip characteristic curve: Type B, C, D • Trip characteristic curve: Type C, D
• UL 1077 or UL 489 certified versions. • UL 1077 certified versions.

Page 14-13

SWITCH DISCONNECTORS
• 1P, 2P, 3P and 4P versions
• IEC rated current In: 32...125A
• Clear OFF contact status indication
• Auxiliary contact block available.

Page 14-13 Page 14-14 Page 14-15

RESIDUAL BLOCKS FOR CIRCUIT BREAKERS RESIDUAL CURRENT OPERATED CIRCUIT RESIDUAL CURRENT OPERATED CIRCUIT
UP TO 63A BREAKERS 25...63A BREAKERS WITH OVERCURRENT
• 2P, 3P and 4P versions • 2P and 4P versions PROTECTION UP TO 40A
• IEC rated current In: 40 and 63A • IEC rated current In: 25, 40 and 63A • 1P+N versions
• Residual current: 30 and 300mA • IEC rated residual operating current IΔn: • IEC rated current In: 6...40A
• Residual current operating characteristic: 30mA and 300mA • IEC rated short-circuit capacity Icn: 10kA
Type A. • Residual current operating characteristic: • Trip characteristic curve: Type C
Type A, B and AC • Residual current: 30 and 300mA
• Auxiliary contact and signalling contact • Residual current operating characteristic:
blocks available. Type AC and A
• Auxiliary contact and signalling contact
blocks available.
14 Miniature and residual circuit breakers
Miniature circuit breakers 1...63A, UL 1077
,1'EX

1P - 10kA (IEC/EN/BS) Order code Curve IEC IEC N° of Qty Wt General characteristics
In Icn DIN per These devices are used to protect against short circuits and
1 module module pkg overloads of wiring installations and loads in panel boards,
office buildings, stores and similar applications.
[A] [kA] n° n° [kg] Their purpose is circuit protection, circuit isolation and load
Single pole, thermal and magnetic trip type, B-curve operation controls. They have instantaneous trip
characteristic. characteristics defined as follows:
P1MB1PB01 B 1 10 1 12 0.115 – B-curve: instantaneous trip 3...5 times In
for non-inductive or low inductive loads (heating resistors,
P1MB1PB02 B 2 10 1 12 0.115 generators, very long wire lines)
P1MB1PB03 B 3 10 1 12 0.115 – C-curve: instantaneous trip 5...10 times In
P1MB1PB04 B 4 10 1 12 0.115 for inductive loads (mixed and inductive resistive loads
with low inrush current)
P1MB1PB06 B 6 10 1 12 0.115 – D-curve: instantaneous trip 10...14 times In
P1MB1PB08 B 8 10 1 12 0.115 for highly inductive loads (loads with high inrush and
P1MB1PB10 B 10 10 1 12 0.115 current such as motors).
Main features include:
P1MB1PB13 B 13 10 1 12 0.115 – IEC rated current In: 1...63A
P1MB1P... P1MB1PB16 B 16 10 1 12 0.115 – Pole width: 17.5mm / 0.69”
P1MB1PB20 B 20 10 1 12 0.115 – Contact status with flag indicator
– Trip characteristic: curve type B, C and D
P1MB1PB25 B 25 10 1 12 0.115 – Auxiliary contacts and trip releases mounted on MCB left
P1MB1PB32 B 32 10 1 12 0.115 side
P1MB1PB40 B 40 10 1 12 0.115 – Fixing on 35mm DIN rail (IEC/EN/BS 60715).
P1MB1PB50 B 50 10 1 12 0.115 Operational characteristics
P1MB1PB63 B 63 10 1 12 0.115 – Dissipation per pole: 3...13W
Single pole, thermal and magnetic trip type, C-curve – IEC rated insulation voltage Ui: 440V
characteristic. – IEC rated impulse voltage Uimp: 4kV
– IEC rated operational voltage Ue: 230/400VAC
P1MB1PC01 C 1 10 1 12 0.115 – UL 1077 rated operational voltage: 277VAC
P1MB1PC01V6 C 1.6 10 1 12 0.115 – Short circuit breaking capacity:
P1MB1PC02 C 2 10 1 12 0.115 IEC/EN/BS 10kA - UL 7.5kA 240V - 5kA 277V.
P1MB1PC03 C 3 10 1 12 0.115 Certifications and compliance
P1MB1PC04 C 4 10 1 12 0.115 Certifications obtained: cURus (E369585); EAC;
P1MB1PC06 C 6 10 1 12 0.115 TÜV-Rheinland.
Compliant with standards: IEC/EN/BS 60898-1,
P1MB1PC08 C 8 10 1 12 0.115 IEC/EN/BS 60947-2, UL 1077, CSA C22.2 n°235.
P1MB1PC10 C 10 10 1 12 0.115
P1MB1PC13 C 13 10 1 12 0.115
P1MB1PC16 C 16 10 1 12 0.115
P1MB1PC20 C 20 10 1 12 0.115
P1MB1PC25 C 25 10 1 12 0.115
P1MB1PC32 C 32 10 1 12 0.115
P1MB1PC40 C 40 10 1 12 0.115
P1MB1PC50 C 50 10 1 12 0.115
P1MB1PC63 C 63 10 1 12 0.115
Single pole, thermal and magnetic trip type, D-curve
characteristic.
P1MB1PD01 D 1 10 1 12 0.115
P1MB1PD01V6 D 1.6 10 1 12 0.115
P1MB1PD02 D 2 10 1 12 0.115
P1MB1PD03 D 3 10 1 12 0.115
P1MB1PD04 D 4 10 1 12 0.115
P1MB1PD06 D 6 10 1 12 0.115
P1MB1PD08 D 8 10 1 12 0.115
P1MB1PD10 D 10 10 1 12 0.115
P1MB1PD13 D 13 10 1 12 0.115
P1MB1PD16 D 16 10 1 12 0.115
P1MB1PD20 D 20 10 1 12 0.115
P1MB1PD25 D 25 10 1 12 0.115
P1MB1PD32 D 32 10 1 12 0.115
P1MB1PD40 D 40 10 1 12 0.115
P1MB1PD50 D 50 10 1 12 0.115
P1MB1PD63 D 63 10 1 12 0.115

Accessories Dimensions Technical characteristics


14-2 page 14-12 page 14-16 page 14-17
14 Miniature and residual circuit breakers
Miniature circuit breakers 1...63A
,1'EX

1P+N - 6kA Order code Curve IEC IEC N° of Qty Wt General characteristics
In Icn DIN per These devices are used to protect against short circuits and
1 module module pkg overloads of wiring installations and loads in panel boards,
office buildings, stores and similar applications.
[A] [kA] n° n° [kg] Their purpose is circuit protection, circuit isolation and
Single pole + neutral, thermal and magnetic trip type, load operation controls. They have characteristics
B-curve characteristic. of instantaneous trip defined as follows:
P1MB1MB06 B 6 6 1 12 0.115 – B-curve: instantaneous trip 3...5 times In
for non-inductive or low inductive loads (heating resistors,
P1MB1MB10 B 10 6 1 12 0.115 generators, very long wire lines)
P1MB1MB16 B 16 6 1 12 0.115 – C-curve: instantaneous trip 5...10 times In
P1MB1MB20 B 20 6 1 12 0.115 for inductive loads (mixed loads, resistive and inductive
with low inrush current)
P1MB1MB25 B 25 6 1 12 0.115 – D-curve: instantaneous trip 10...14 times In
P1MB1MB32 B 32 6 1 12 0.115 for highly inductive loads (loads with high inrush and
Single pole + neutral, thermal and magnetic trip type, current such as motors).
C-curve characteristic. Main features include:
– IEC rated current In: 2...40A
P1MB1MC02 C 2 6 1 12 0.115 – Pole width: 9mm/0.35” (0.5 module)
P1MB1M...
P1MB1MC04 C 4 6 1 12 0.115 – Contact status with flag indicator
P1MB1MC06 C 6 6 1 12 0.115 – Trip characteristic: curve type B and C
– Auxiliary contacts and trip releases mounted on left side
P1MB1MC10 C 10 6 1 12 0.115 – Fixing on 35mm DIN rail (IEC/EN/BS 60715).
P1MB1MC13 C 13 6 1 12 0.115
P1MB1MC16 C 16 6 1 12 0.115 Operational characteristics
– Dissipation per pole: 3...7.5W
P1MB1MC20 C 20 6 1 12 0.115 – IEC rated insulation voltage Ui: 440V
P1MB1MC25 C 25 6 1 12 0.115 – IEC rated impulse voltage Uimp: 4kV
P1MB1MC32 C 32 6 1 12 0.115 – IEC rated operational voltage Ue: 230VAC.
P1MB1MC40 C 40 6 1 12 0.115 Certifications and compliance
Certifications obtained: EAC, TÜV-SUD.
Compliant with standards: IEC/EN/BS 60898-1,
IEC/EN/BS 60947-2.

1P+N - 6kA Order code Curve IEC IEC N° of Qty Wt General characteristics
14
In Icn DIN per – IEC rated current In: 1...63A
2 modules module pkg – Pole width: 17.5mm / 0.69”
– Contact status with flag indicator
[A] [kA] no. n° [kg] – Trip characteristic: curve type C
Single pole + neutral, thermal and magnetic trip type, – Auxiliary contacts and trip releases mounted on left side
C-curve characteristic. – Fixing on 35mm DIN rail (IEC/EN/BS 60715).
P1MB1NC01 C 1 6 2 6 0.190
Operational characteristics
P1MB1NC02 C 2 6 2 6 0.190 – Dissipation per pole: 3...13W
P1MB1NC04 C 4 6 2 6 0.190 – IEC rated insulation voltage Ui: 440V
P1MB1NC06 C 6 6 2 6 0.190 – IEC rated impulse voltage Uimp: 4kV
– IEC rated operational voltage Ue: 230/400VAC.
P1MB1NC10 C 10 6 2 6 0.190
P1MB1NC16 C 16 6 2 6 0.190 Certifications and compliance
P1MB1NC20 C 20 6 2 6 0.190 Certifications obtained: EAC.
Compliant with standards: IEC/EN/BS 60898-1,
P1MB1NC25 C 25 6 2 6 0.190 IEC/EN/BS 60947-2.
P1MB1NC32 C 32 6 2 6 0.190
P1MB1N...
P1MB1NC40 C 40 6 2 6 0.190
P1MB1NC50 C 50 6 2 6 0.190
P1MB1NC63 C 63 6 2 6 0.190

Accessories Dimensions Technical characteristics


page 14-12 page 14-16 page 14-17 14-3
14 Miniature and residual circuit breakers
Miniature circuit breakers 1...63A, UL 1077
,1'EX

2P - 10kA (IEC/EN/BS) Order code Curve IEC IEC N° of Qty Wt General characteristics
In Icn DIN per These devices are used to protect against short circuits and
2 modules module pkg overloads of wiring installations and loads in panel boards,
office buildings, stores and similar applications.
[A] [kA] n° n° [kg] Their purpose is circuit protection, circuit isolation and
Two pole, thermal and magnetic trip type, B-curve load operation controls. They have characteristics
characteristic. of instantaneous trip defined as follows:
P1MB2PB01 B 1 10 2 6 0.230 – B-curve: instantaneous trip 3...5 times In
for non-inductive or low inductive loads (heating resistors,
P1MB2PB02 B 2 10 2 6 0.230 generators, very long wire lines)
P1MB2PB04 B 4 10 2 6 0.230 – C-curve: instantaneous trip 5...10 times In
P1MB2PB06 B 6 10 2 6 0.230 for inductive loads (mixed loads, resistive and inductive
with low inrush current)
P1MB2PB10 B 10 10 2 6 0.230 – D-curve: instantaneous trip 10...14 times In
P1MB2PB13 B 13 10 2 6 0.230 for highly inductive loads (loads with high inrush and
P1MB2PB16 B 16 10 2 6 0.230 current such as motors).
Main features include:
P1MB2PB20 B 20 10 2 6 0.230 – IEC rated current In: 1...63A
P1MB2PB25 B 25 10 2 6 0.230 – Pole width: 17.5mm / 0.69”
P1MB2P... – Contact status with flag indicator
P1MB2PB32 B 32 10 2 6 0.230
– Trip characteristic: curve type B, C and D
3 P1MB2PB40 B 40 10 2 6 0.230 – Auxiliary contacts and trip releases mounted on left side
P1MB2PB50 B 50 10 2 6 0.230 – Fixing on 35mm DIN rail (IEC/EN/BS 60715).
P1MB2PB63 B 63 10 2 6 0.230
Operational characteristics
Two pole, thermal and magnetic trip type, C-curve – Dissipation per pole: 3...13W
4 characteristic. – IEC rated insulation voltage Ui: 440V
P1MB2PC01 C 1 10 2 6 0.230 – IEC rated impulse voltage Uimp: 4kV
P1MB2PC01V6 C 1.6 10 2 6 0.230 – IEC rated operational voltage Ue: 230/400VAC
– UL 1077 rated operational voltage: 480VAC
P1MB2PC02 C 2 10 2 6 0.230 – Short circuit breaking capacity:
P1MB2PC03 C 3 10 2 6 0.230 IEC/EN/BS 10kA - UL 7.5kA 480V.
P1MB2PC04 C 4 10 2 6 0.230
Certifications and compliance
P1MB2PC06 C 6 10 2 6 0.230 Certifications obtained: cURus (E369585); EAC;
P1MB2PC08 C 8 10 2 6 0.230 TÜV-Rheinland.
P1MB2PC10 C 10 10 2 6 0.230 Compliant with standards: IEC/EN/BS 60898-1,
IEC/EN/BS 60947-2, UL 1077, CSA C22.2 n°235.
P1MB2PC13 C 13 10 2 6 0.230
P1MB2PC16 C 16 10 2 6 0.230
P1MB2PC20 C 20 10 2 6 0.230
P1MB2PC25 C 25 10 2 6 0.230
P1MB2PC32 C 32 10 2 6 0.230
P1MB2PC40 C 40 10 2 6 0.230
P1MB2PC50 C 50 10 2 6 0.230
P1MB2PC63 C 63 10 2 6 0.230
Two pole, thermal and magnetic trip type, D-curve
characteristic.
P1MB2PD01 D 1 10 2 6 0.230
P1MB2PD01V6 D 1.6 10 2 6 0.230
P1MB2PD02 D 2 10 2 6 0.230
P1MB2PD03 D 3 10 2 6 0.230
P1MB2PD04 D 4 10 2 6 0.230
P1MB2PD06 D 6 10 2 6 0.230
P1MB2PD08 D 8 10 2 6 0.230
P1MB2PD10 D 10 10 2 6 0.230
P1MB2PD13 D 13 10 2 6 0.230
P1MB2PD16 D 16 10 2 6 0.230
P1MB2PD20 D 20 10 2 6 0.230
P1MB2PD25 D 25 10 2 6 0.230
P1MB2PD32 D 32 10 2 6 0.230
P1MB2PD40 D 40 10 2 6 0.230
P1MB2PD50 D 50 10 2 6 0.230
P1MB2PD63 D 63 10 2 6 0.230

Accessories Dimensions Technical characteristics


14-4 page 14-12 page 14-16 page 14-17
14 Miniature and residual circuit breakers
Miniature circuit breakers 1...63A, UL 1077
,1'EX

3P - 10kA (IEC/EN/BS) Order code Curve IEC IEC N° of Qty Wt General characteristics
In Icn DIN per These devices are used to protect against short circuits and
3 modules module pkg overloads of wiring installations and loads in panel boards,
office buildings, stores and similar applications.
[A] [kA] n° n° [kg] Their purpose is circuit protection, circuit isolation and
Three pole, thermal and magnetic trip type, B-curve load operation controls. They have characteristics
characteristic. of instantaneous trip defined as follows:
P1MB3PB01 B 1 10 3 4 0.345 – B-curve: instantaneous trip 3...5 times In
for non-inductive or low inductive loads (heating resistors,
P1MB3PB02 B 2 10 3 4 0.345 generators, very long wire lines)
P1MB3PB04 B 4 10 3 4 0.345 – C-curve: instantaneous trip 5...10 times In
P1MB3PB06 B 6 10 3 4 0.345 for inductive loads (mixed loads, resistive and inductive
with low inrush current)
P1MB3PB10 B 10 10 3 4 0.345 – D-curve: instantaneous trip 10...14 times In
P1MB3PB13 B 13 10 3 4 0.345 for highly inductive loads (loads with high inrush and
P1MB3PB16 B 16 10 3 4 0.345 current such as motors).
Main features include:
P1MB3P... P1MB3PB20 B 20 10 3 4 0.345 – IEC rated current In: 1...63A
P1MB3PB25 B 25 10 3 4 0.345 – Pole width: 17.5mm / 0.69”
3 5 P1MB3PB32 B 32 10 3 4 0.345 – Contact status with flag indicator
– Trip characteristic: curve type B, C and D
P1MB3PB40 B 40 10 3 4 0.345 – Auxiliary contacts and trip releases mounted on left side
P1MB3PB50 B 50 10 3 4 0.345 – Fixing on 35mm DIN rail (IEC/EN/BS 60715).
P1MB3PB63 B 63 10 3 4 0.345
4 6 Operational characteristics
Three pole, thermal and magnetic trip type, C-curve – Dissipation per pole: 3...13W
characteristic. – IEC rated insulation voltage Ui: 440V
P1MB3PC01 C 1 10 3 4 0.345 – IEC rated impulse voltage Uimp: 4kV
P1MB3PC01V6 C 1.6 10 3 4 0.345 – IEC rated operational voltage Ue: 230/400VAC
– UL 1077 rated operational voltage: 480VAC
P1MB3PC02 C 2 10 3 4 0.345 – Short circuit breaking capacity:
P1MB3PC03 C 3 10 4 4 0.345 IEC/EN/BS 10kA - UL 7.5kA 480V.
P1MB3PC04 C 4 10 3 4 0.345
Certifications and compliance
P1MB3PC06 C 6 10 3 4 0.345 Certifications obtained: cURus (E369585); EAC;
P1MB3PC08 C 8 10 3 4 0.345 TÜV-Rheinland.
P1MB3PC10 C 10 10 3 4 0.345 Compliant with standards: IEC/EN/BS 60898-1,
P1MB3PC13 C 13 10 3 4 0.345
IEC/EN/BS 60947-2, UL 1077, CSA C22.2 n°235. 14
P1MB3PC16 C 16 10 3 4 0.345
P1MB3PC20 C 20 10 3 4 0.345
P1MB3PC25 C 25 10 3 4 0.345
P1MB3PC32 C 32 10 3 4 0.345
P1MB3PC40 C 40 10 3 4 0.345
P1MB3PC50 C 50 10 3 4 0.345
P1MB3PC63 C 63 10 3 4 0.345
Three pole, thermal and magnetic trip type, D-curve
characteristic.
P1MB3PD01 D 1 10 3 4 0.345
P1MB3PD01V6 D 1.6 10 3 4 0.345
P1MB3PD02 D 2 10 3 4 0.345
P1MB3PD03 D 3 10 4 4 0.345
P1MB3PD04 D 4 10 3 4 0.345
P1MB3PD06 D 6 10 3 4 0.345
P1MB3PD08 D 8 10 3 4 0.345
P1MB3PD10 D 10 10 3 4 0.345
P1MB3PD13 D 13 10 3 4 0.345
P1MB3PD16 D 16 10 3 4 0.345
P1MB3PD20 D 20 10 3 4 0.345
P1MB3PD25 D 25 10 3 4 0.345
P1MB3PD32 D 32 10 3 4 0.345
P1MB3PD40 D 40 10 3 4 0.345
P1MB3PD50 D 50 10 3 4 0.345
P1MB3PD63 D 63 10 3 4 0.345

Accessories Dimensions Technical characteristics


page 14-12 page 14-16 page 14-17 14-5
14 Miniature and residual circuit breakers
Miniature circuit breakers 1...63A, UL 1077
,1'EX

4P - 10kA (IEC/EN/BS) Order code Curve IEC IEC N° of Qty Wt General characteristics
In Icn DIN per These devices are used to protect against short circuits and
4 modules module pkg overloads of wiring installations and loads in panel boards,
office buildings, stores and similar applications.
[A] [kA] n° n° [kg] Their purpose is circuit protection, circuit isolation and
Four pole, thermal and magnetic trip type, B-curve load operation controls. They have characteristics of
characteristic. instantaneous trip defined as follows:
P1MB4PB01 B 1 10 4 3 0.460 – B-curve: instantaneous trip 3...5 times In
for non-inductive or low inductive loads (heating resistors,
P1MB4PB02 B 2 10 4 3 0.460 generators, very long wire lines)
P1MB4PB04 B 4 10 4 3 0.460 – C-curve: instantaneous trip 5...10 times In
P1MB4PB06 B 6 10 4 3 0.460 for inductive loads (mixed loads, resistive and inductive
with low inrush current)
P1MB4PB10 B 10 10 4 3 0.460 – D-curve: instantaneous trip 10...14 times In
P1MB4PB13 B 13 10 4 3 0.460 for highly inductive loads (loads with high inrush and
P1MB4P... P1MB4PB16 B 16 10 4 3 0.460 current such as motors).
Main features include:
P1MB4PB20 B 20 10 4 3 0.460 – IEC rated current In: 1...63A
3 5 7 P1MB4PB25 B 25 10 4 3 0.460 – Pole width: 17.5mm / 0.69”
P1MB4PB32 B 32 10 4 3 0.460 – Contact status with flag indicator
– Trip characteristic: curve type B, C and D
P1MB4PB40 B 40 10 4 3 0.460 – Auxiliary contacts and trip releases mounted on left side
P1MB4PB50 B 50 10 4 3 0.460 – Fixing on 35mm DIN rail (IEC/EN/BS 60715).
4 6 8 P1MB4PB63 B 63 10 4 3 0.460
Operational characteristics
Four pole, thermal and magnetic trip type, C-curve – Dissipation per pole: 3...13W
characteristic. – IEC rated insulation voltage Ui: 440V
P1MB4PC01 C 1 10 4 3 0.460 – IEC rated impulse voltage Uimp: 4kV
P1MB4PC02 C 2 10 4 3 0.460 – IEC rated operational voltage Ue: 230/400VAC
– UL 1077 rated operational voltage: 480VAC
P1MB4PC04 C 4 10 4 3 0.460 – Short circuit breaking capacity:
P1MB4PC06 C 6 10 4 3 0.460 IEC/EN/BS 10kA - UL 7.5kA 480V.
P1MB4PC10 C 10 10 4 3 0.460
Certifications and compliance
P1MB4PC13 C 13 10 4 3 0.460 Certifications obtained: cURus (E369585); EAC;
P1MB4PC16 C 16 10 4 3 0.460 TÜV-Rheinland.
P1MB4PC20 C 20 10 4 3 0.460 Compliant with standards: IEC/EN/BS 60898-1,
IEC/EN/BS 60947-2, UL 1077, CSA C22.2 n°235.
P1MB4PC25 C 25 10 4 3 0.460
P1MB4PC32 C 32 10 4 3 0.460
P1MB4PC40 C 40 10 4 3 0.460
P1MB4PC50 C 50 10 4 3 0.460
P1MB4PC63 C 63 10 4 3 0.460
Four pole, thermal and magnetic trip type, D-curve
characteristic.
P1MB4PD01 D 1 10 4 3 0.460
P1MB4PD02 D 2 10 4 3 0.460
P1MB4PD04 D 4 10 4 3 0.460
P1MB4PD06 D 6 10 4 3 0.460
P1MB4PD10 D 10 10 4 3 0.460
P1MB4PD13 D 13 10 4 3 0.460
P1MB4PD16 D 16 10 4 3 0.460
P1MB4PD20 D 20 10 4 3 0.460
P1MB4PD25 D 25 10 4 3 0.460
P1MB4PD32 D 32 10 4 3 0.460
P1MB4PD40 D 40 10 4 3 0.460
P1MB4PD50 D 50 10 4 3 0.460
P1MB4PD63 D 63 10 4 3 0.460

Accessories Dimensions Technical characteristics


14-6 page 14-12 page 14-16 page 14-17
14 Miniature and residual circuit breakers
Miniature circuit breakers 1...63A, UL 489
,1'EX

1P - 10kA (IEC/EN/BS) Order code Curve IEC Rat. N° of Qty Wt General characteristics
In volt. DIN per These devices comply with the UL 489 standard, mostly used
1 module mod. pkg in the North American markets. They are designed to protect
feeder circuits, the part of the system from the network
[A] [V] n° n° [kg] supply point to the protection device for a branch circuit.
One pole, thermal and magnetic trip type, C-curve They can also be used on the international market thanks to
characteristic. compliance with the IEC/EN/BS 60947-2 standard.
P1MBUH1PC01 C 1 277 1 12 0.133 They have characteristics of tripping instantaneously defined
as follows:
P1MBUH1PC01V6 C 1.6 277 1 12 0.133 – C-curve: instantaneous trip 5...10 times In
P1MBUH1PC02 C 2 277 1 12 0.133 for inductive loads (mixed loads, resistive and inductive
P1MBUH1PC03 C 3 277 1 12 0.133 with low inrush current)
– D-curve: instantaneous trip 10...14 times In
P1MBUH1PC04 C 4 277 1 12 0.133 for highly inductive loads (loads with high inrush and
P1MBUH1PC05 C 5 277 1 12 0.133 current such as motors).
P1MBUH1PC06 C 6 277 1 12 0.133
Operational characteristics
P1MBUH1PC07 C 7 277 1 12 0.133 – Dissipation per pole: 3...13W
P1MBUH1PC08 C 8 277 1 12 0.133 – Rated voltage 1...32A: 277V (UL 489)
P1MB...1P... P1MBUH1PC10 C 10 277 1 12 0.133 – Rated voltage 35...63A: 120V (UL 489)
– Rated insulation voltage Ui: 440V (IEC/EN/BS 60947-2)
P1MBUH1PC12 C 12 277 1 12 0.133 – Rated impulse voltage Uimp: 4kV (IEC/EN/BS 60947-2)
P1MBUH1PC13 C 13 277 1 12 0.133 – Rated operational voltage Ue: 230/400VAC
P1MBUH1PC15 C 15 277 1 12 0.133 (IEC/EN/BS 60947-2)
– Short circuit breaking capacity:
P1MBUH1PC16 C 16 277 1 12 0.133 IEC/EN/BS 10kA - UL 10kA.
P1MBUH1PC20 C 20 277 1 12 0.133
P1MBUH1PC25 C 25 277 1 12 0.133 Certifications and compliance
Certifications obtained: cULus (E481234); EAC.
P1MBUH1PC30 C 30 277 1 12 0.133 Compliant with standards: UL 489, IEC/EN/BS 60947-2.
P1MBUH1PC32 C 32 277 1 12 0.133
P1MBUL1PC35 C 35 120 1 12 0.133
P1MBUL1PC40 C 40 120 1 12 0.133
P1MBUL1PC50 C 50 120 1 12 0.133
P1MBUL1PC60 C 60 120 1 12 0.133
P1MBUL1PC63 C 63 120 1 12 0.133
One pole, thermal and magnetic trip type, D-curve
14
characteristic.
P1MBUH1PD01 D 1 277 1 12 0.133
P1MBUH1PD01V6 D 1.6 277 1 12 0.133
P1MBUH1PD02 D 2 277 1 12 0.133
P1MBUH1PD03 D 3 277 1 12 0.133
P1MBUH1PD04 D 4 277 1 12 0.133
P1MBUH1PD05 D 5 277 1 12 0.133
P1MBUH1PD06 D 6 277 1 12 0.133
P1MBUH1PD07 D 7 277 1 12 0.133
P1MBUH1PD08 D 8 277 1 12 0.133
P1MBUH1PD10 D 10 277 1 12 0.133
P1MBUH1PD12 D 12 277 1 12 0.133
P1MBUH1PD13 D 13 277 1 12 0.133
P1MBUH1PD15 D 15 277 1 12 0.133
P1MBUH1PD16 D 16 277 1 12 0.133
P1MBUH1PD20 D 20 277 1 12 0.133
P1MBUH1PD25 D 25 277 1 12 0.133
P1MBUH1PD30 D 30 277 1 12 0.133
P1MBUH1PD32 D 32 277 1 12 0.133
P1MBUL1PD35 D 35 120 1 12 0.133
P1MBUL1PD40 D 40 120 1 12 0.133
P1MBUL1PD50 D 50 120 1 12 0.133
P1MBUL1PD60 D 60 120 1 12 0.133
P1MBUL1PD63 D 63 120 1 12 0.133

Accessories Dimensions Technical characteristics


page 14-12 page 14-16 page 14-17 14-7
14 Miniature and residual circuit breakers
Miniature circuit breakers 1...63A, UL 489
,1'EX

2P - 10kA (IEC/EN/BS) Order code Cur- IEC Rated N° of Qty Wt General characteristics
ve In voltage DIN per These devices comply with the UL 489 standard, mostly used
2 modules mod. pkg in the North American markets. They are designed to protect
feeder circuits, the part of the system from the network
[A] [V] n° n° [kg] supply point to the protection device for a branch circuit.
Two pole, thermal and magnetic trip type, C-curve They can in any case be used on the international market
characteristic. thanks to compliance with the IEC/EN/BS 60947-2 standard
P1MBUH2PC01 C 1 480Y/277 2 6 0.255 as well.
They have characteristics of tripping instantaneously defined
P1MBUH2PC01V6 C 1.6 480Y/277 2 6 0.255 as follows:
P1MBUH2PC02 C 2 480Y/277 2 6 0.255 – C-curve: instantaneous trip 5...10 times In
P1MBUH2PC03 C 3 480Y/277 2 6 0.255 for inductive loads (mixed loads, resistive and inductive
with low inrush current)
P1MBUH2PC04 C 4 480Y/277 2 6 0.255 – D-curve: instantaneous trip 10...14 times In
P1MBUH2PC05 C 5 480Y/277 2 6 0.255 for highly inductive loads (loads with high inrush and
P1MBUH2PC06 C 6 480Y/277 2 6 0.255 current such as motors).
P1MBUH2PC07 C 7 480Y/277 2 6 0.255 Operational characteristics
P1MBUH2PC08 C 8 480Y/277 2 6 0.255 – Rated voltage 1...32A: 480Y/277V (UL 489)
P1MB...2P... P1MBUH2PC10 C 10 480Y/277 2 6 0.255 – Rated voltage 35...63A: 240V (UL 489)
– Rated insulation voltage Ui: 440V (IEC/EN/BS 60947-2)
P1MBUH2PC12 C 12 480Y/277 2 6 0.255 – Rated impulse voltage Uimp: 4kV (IEC/EN/BS 60947-2)
3 P1MBUH2PC13 C 13 480Y/277 2 6 0.255 – Rated operational voltage Ue: 230/400VAC
P1MBUH2PC15 C 15 480Y/277 2 6 0.255 (IEC/EN/BS 60947-2)
– Short circuit breaking capacity:
P1MBUH2PC16 C 16 480Y/277 2 6 0.255 IEC/EN/BS 10kA - UL 10kA.
P1MBUH2PC20 C 20 480Y/277 2 6 0.255
4 Certifications and compliance
P1MBUH2PC25 C 25 480Y/277 2 6 0.255
Certifications obtained: cULus (E481234); EAC.
P1MBUH2PC30 C 30 480Y/277 2 6 0.255 Compliant with standards: UL 489, IEC/EN/BS 60947-2.
P1MBUH2PC32 C 32 480Y/277 2 6 0.255
P1MBUL2PC35 C 35 240 2 6 0.255
P1MBUL2PC40 C 40 240 2 6 0.255
P1MBUL2PC50 C 50 240 2 6 0.255
P1MBUL2PC60 C 60 240 2 6 0.255
P1MBUL2PC63 C 63 240 2 6 0.255
Two pole, thermal and magnetic trip type, D-curve
characteristic.
P1MBUH2PD01 D 1 480Y/277 2 6 0.255
P1MBUH2PD01V6 D 1,6 480Y/277 2 6 0.255
P1MBUH2PD02 D 2 480Y/277 2 6 0.255
P1MBUH2PD03 D 3 480Y/277 2 6 0.255
P1MBUH2PD04 D 4 480Y/277 2 6 0.255
P1MBUH2PD05 D 5 480Y/277 2 6 0.255
P1MBUH2PD06 D 6 480Y/277 2 6 0.255
P1MBUH2PD07 D 7 480Y/277 2 6 0.255
P1MBUH2PD08 D 8 480Y/277 2 6 0.255
P1MBUH2PD10 D 10 480Y/277 2 6 0.255
P1MBUH2PD12 D 12 480Y/277 2 6 0.255
P1MBUH2PD13 D 13 480Y/277 2 6 0.255
P1MBUH2PD15 D 15 480Y/277 2 6 0.255
P1MBUH2PD16 D 16 480Y/277 2 6 0.255
P1MBUH2PD20 D 20 480Y/277 2 6 0.255
P1MBUH2PD25 D 25 480Y/277 2 6 0.255
P1MBUH2PD30 D 30 480Y/277 2 6 0.255
P1MBUH2PD32 D 32 480Y/277 2 6 0.255
P1MBUL2PD35 D 35 240 2 6 0.255
P1MBUL2PD40 D 40 240 2 6 0.255
P1MBUL2PD50 D 50 240 2 6 0.255
P1MBUL2PD60 D 60 240 2 6 0.255
P1MBUL2PD63 D 63 240 2 6 0.255

Accessories Dimensions Technical characteristics


14-8 page 14-12 page 14-16 page 14-17
14 Miniature and residual circuit breakers
Miniature circuit breakers 1...63A, UL 489
,1'EX

3P - 10kA (IEC/EN/BS) Order code Cur- IEC Rated N° of Qty Wt General characteristics
ve In voltage DIN per These devices comply with the UL 489 standard, mostly used
3 modules mod. pkg in the North American markets. They are designed to protect
feeder circuits, the part of the system from the network
[A] [V] n° n° [kg] supply point to the protection device for a branch circuit.
Three pole, thermal and magnetic trip type, C-curve They can also be used on the international market thanks to
characteristic. compliance with the IEC/EN/BS 60947-2 standard.
P1MBUH3PC01 C 1 480Y/277 3 4 0.388 They have characteristics of tripping instantaneously defined
as follows:
P1MBUH3PC01V6 C 1.6 480Y/277 3 4 0.388 – C-curve: instantaneous trip 5...10 times In
P1MBUH3PC02 C 2 480Y/277 3 4 0.388 for inductive loads (mixed loads, resistive and inductive
P1MBUH3PC03 C 3 480Y/277 3 4 0.388 with low inrush current)
– D-curve: instantaneous trip 10...14 times In
P1MBUH3PC04 C 4 480Y/277 3 4 0.388 for highly inductive loads (loads with high inrush and
P1MBUH3PC05 C 5 480Y/277 3 4 0.388 current such as motors).
P1MBUH3PC06 C 6 480Y/277 3 4 0.388
Operational characteristics
P1MBUH3PC07 C 7 480Y/277 3 4 0.388 – Rated voltage 1...32A: 480Y/277V (UL 489)
P1MBUH3PC08 C 8 480Y/277 3 4 0.388 – Rated voltage 35...63A: 240V (UL 489)
P1MB...3P... P1MBUH3PC10 C 10 480Y/277 3 4 0.388 – Rated insulation voltage Ui: 440V (IEC/EN/BS 60947-2)
– Rated impulse voltage Uimp: 4kV (IEC/EN/BS 60947-2)
P1MBUH3PC12 C 12 480Y/277 3 4 0.388 – Rated operational voltage Ue: 230/400VAC
3 5 P1MBUH3PC13 C 13 480Y/277 3 4 0.388 (IEC/EN/BS 60947-2)
P1MBUH3PC15 C 15 480Y/277 3 4 0.388 – Short circuit breaking capacity:
IEC/EN/BS 10kA - UL 10kA.
P1MBUH3PC16 C 16 480Y/277 3 4 0.388
P1MBUH3PC20 C 20 480Y/277 3 4 0.388 Certifications and compliance
4 6 P1MBUH3PC25 C 25 480Y/277 3 4 0.388 Certifications obtained: cULus (E481234); EAC.
Compliant with standards: UL 489, IEC/EN/BS 60947-2.
P1MBUH3PC30 C 30 480Y/277 3 4 0.388
P1MBUH3PC32 C 32 480Y/277 3 4 0.388
P1MBUL3PC35 C 35 240 3 4 0.388
P1MBUL3PC40 C 40 240 3 4 0.388
P1MBUL3PC50 C 50 240 3 4 0.388
P1MBUL3PC60 C 60 240 3 4 0.388
P1MBUL3PC63 C 63 240 3 4 0.388
Three pole, thermal and magnetic trip type, D-curve
14
characteristic.
P1MBUH3PD01 D 1 480Y/277 3 4 0.388
P1MBUH3PD01V6 D 1,6 480Y/277 3 4 0.388
P1MBUH3PD02 D 2 480Y/277 3 4 0.388
P1MBUH3PD03 D 3 480Y/277 3 4 0.388
P1MBUH3PD04 D 4 480Y/277 3 4 0.388
P1MBUH3PD05 D 5 480Y/277 3 4 0.388
P1MBUH3PD06 D 6 480Y/277 3 4 0.388
P1MBUH3PD07 D 7 480Y/277 3 4 0.388
P1MBUH3PD08 D 8 480Y/277 3 4 0.388
P1MBUH3PD10 D 10 480Y/277 3 4 0.388
P1MBUH3PD12 D 12 480Y/277 3 4 0.388
P1MBUH3PD13 D 13 480Y/277 3 4 0.388
P1MBUH3PD15 D 15 480Y/277 3 4 0.388
P1MBUH3PD16 D 16 480Y/277 3 4 0.388
P1MBUH3PD20 D 20 480Y/277 3 4 0.388
P1MBUH3PD25 D 25 480Y/277 3 4 0.388
P1MBUH3PD30 D 30 480Y/277 3 4 0.388
P1MBUH3PD32 D 32 480Y/277 3 4 0.388
P1MBUL3PD35 D 35 240 3 4 0.388
P1MBUL3PD40 D 40 240 3 4 0.388
P1MBUL3PD50 D 50 240 3 4 0.388
P1MBUL3PD60 D 60 240 3 4 0.388
P1MBUL3PD63 D 63 240 3 4 0.388

Accessories Dimensions Technical characteristics


page 14-12 page 14-16 page 14-17 14-9
14 Miniature and residual circuit breakers
Miniature circuit breakers 80...125A, UL 1077
,1'EX

1P, 2P, 3P and 4P - 10kA Order code Curve IEC IEC N° of Qty Wt General characteristics
In Icn DIN per These devices are used to protect against short circuits and
(IEC/EN/BS) module pkg overloads of wiring installations and loads in panel boards,
office buildings, stores and similar applications.
[A] [kA] no. no. [kg] Their purpose is circuit protection, circuit isolation and
One pole, thermal and magnetic trip type, C-curve load operation controls. They have characteristics
characteristic. of instantaneous trip defined as follows:
P2MB1PC080 C 80 10 1.5 9 0.166 – C-curve: instantaneous trip 5...10 times In
for inductive loads (mixed loads, resistive and inductive
P2MB1PC100 C 100 10 1.5 9 0.166 with low inrush current)
P2MB1PC125 C 125 10 1.5 9 0.166 – D-curve: instantaneous trip 10...14 times In
Two pole, thermal and magnetic trip type, C-curve for highly inductive loads (loads with high inrush and
characteristic. current such as motors).
Main features include:
P2MB1P... P2MB2PC080 C 80 10 3 4 0.340 – IEC rated current In: 80...125A
P2MB2PC100 C 100 10 3 4 0.340 – Pole width: 27mm / 1.06”
P2MB2PC125 C 125 10 3 4 0.340 – Contact status with flag indicator
– Trip characteristic: curve type C and D
Three pole, thermal and magnetic trip type, C-curve – Fixing on 35mm DIN rail (IEC/EN/BS 60715).
characteristic.
P2MB3PC080 C 80 10 4.5 3 0.510 Operational characteristics
P2MB3PC100 C 100 10 4.5 3 0.510 – Dissipation per pole: 15...20W
– IEC rated insulation voltage Ui: 400V
P2MB3PC125 C 125 10 4.5 3 0.510 – IEC rated impulse voltage Uimp: 4kV
Four pole, thermal and magnetic trip type, C-curve – IEC rated operational voltage Ue: 230/400VAC (230VAC
characteristic. 1P version)
P2MB4PC080 C 80 10 6 2 0.680 – Short circuit breaking capacity:
IEC/EN/BS 10kA - UL 5kA 240V (1P) - 5kA 480V (2-3-4P).
P2MB4PC100 C 100 10 6 2 0.680
P2MB4PC125 C 125 10 6 2 0.680 Certifications and compliance
Three pole, thermal and magnetic trip type, D-curve Certifications obtained: cURus (E369585); EAC;
characteristic. TÜV-Rheinland.
Compliant with standards: IEC/EN/BS 60898-1,
P2MB3PD080 D 80 10 4.5 3 0.510 IEC/EN/BS 60947-2, UL 1077, CSA C22.2 n°235.
P2MB2P... P2MB3PD100 D 100 10 4.5 3 0.510
P2MB3PD125 D 125 10 4.5 3 0.510
3 Four pole, thermal and magnetic trip type, D-curve
characteristic.
P2MB4PD080 D 80 10 6 2 0.510
P2MB4PD100 D 100 10 6 2 0.510
4 P2MB4PD125 D 125 10 6 2 0.510
 Icn at 230V.

P2MB3P...

3 5

4 6

P2MB4P...

3 5 7

4 6 8

Accessories Dimensions Technical characteristics


14-10 page 14-12 page 14-16 page 14-17
14 Miniature and residual circuit breakers
Add-on blocks and accessories
,1'EX

Add-on blocks for miniature Order code Description Qty per Qty Wt General characteristics
MCB per – Auxiliary and indicator contact width: 9mm/0.35”
circuit breakers 1...63A pkg (0.5 module)
– Undervoltage and shunt trip release width: 18mm/0.71”
n° n° [kg] (1 module)
Auxiliary contact. – Maximum combination: 3 add-on blocks on MCB left side
P1X1011 1 changeover contact 1 12 0.040 only of which 1 undervoltage or shunt release directly on
for P1MB... MCB side and then 2 contacts of which 1 auxiliary and
1 indicator.
P1X1011UH 1 changeover contact 1 12 0.040
for P1MBU... Operational characteristics
– IEC rated impulse voltage Uimp: 4kV
Indicator contact for thermal-magnetic trip.
– IEC rated operational current in AC: 6A 230V; 3A 400V
P1X1311 1 changeover contact 1 12 0.040 (auxiliary contacts).
Undervoltage trip release. Certifications and compliance
P1X14230 230V 50/60Hz 1 8 0.070 Certifications obtained: EAC, cULus (excluding P1X14230
P1X1011 P1X16... and P1X16024).
Shunt trip release.
Compliant with standards: IEC/EN/BS 60947-5-1,
P1X16230 110...415V 50/60Hz 1 8 0.070 CSA C22.2 n° 5.
P1X16024 12...24VDC 50/60Hz 1 8 0.070
 Not suitable for P1MBU...

Add-on blocks for Order code Description Qty per Qty Wt General characteristics
MCB per – Auxiliary and indicator contact width: 9mm/0.35”
miniature circuit breakers pkg (0.5 module)
80...125A n° n° [kg]
– Shunt trip release width: 17.5mm/0.69” (1 module)
– Maximum combination: 3 add-on blocks on MCB sides of
Auxiliary contact. which 1 undervoltage or shunt release on MCB right side
P2X1011 1 changeover contact 1 10 0.040 and 2 contacts on the left of which 1 auxiliary and
1 indicator.
Indicator contact for thermal-magnetic trip.
P2X1311 1 changeover contact 1 10 0.040 Operational characteristics
Shunt trip release. – IEC rated insulation voltage Ui: 500V
– Rated impulse voltage Uimp: 4kV
P2X16230 110...415V 50/60Hz 1 8 0.070 – Rated operational current in AC: 6A 230V; 3A 400V
(auxiliary contacts).
14
Certifications and compliance
P2X1311 P2X16230
Certifications obtained: EAC.
Compliant with standards: IEC/EN/BS 60947-5-1.

Dimensions Wiring diagrams Technical characteristics


page 14-16 page 14-16 page 14-17 14-11
14 Miniature and residual circuit breakers
Accessories
,1'EX

Accessories for miniature Order code Description Qty Wt General and operational characteristics
per SINGLE-POLE SUPPLY BUSBAR
circuit breakers pkg – Rated operational voltage Ue: 1000V
– Central point of power supply: 100A max.
n° [kg] – Side point of power supply: 63A max.
P1X9031 Single-pole supply busbar 10 0.160 – Spacing: 17.8mm/0.70”
P1X9032 Two-pole supply busbar 10 0.320 – Busbar section: 10mm²
P1X9033 – For paralleling connection
P1X9033 Three-pole supply busbar 10 0.474 – For 57 modules, 1000mm/39.37” long (57 1P breakers).
P1X9034 Four-pole supply busbar 10 0.600
P1X9130 Kit of 5 isolating covers 10 0.030 TWO-POLE, THREE-POLE AND FOUR-POLE
for unused busbar terminals SUPPLY BUSBARS
– Rated operational voltage Ue: 690V
P1X9133 P1X9131 End cap for P1X9031 50 0.001 – Central point of power supply: 100A max.
P1X9132 End cap for P1X9032 50 0.001 – Side point of power supply: 63A max.
P1X9133 End cap for P1X9033 50 0.001 – Spacing: 17.8mm/0.70”
– Busbar section: 10mm²
P1X9134 End cap for P1X9034 50 0.001 – For paralleling connection
P1X9201 Single-pole terminal for 25 0.010 – Two-pole: for 56 modules, 1000mm/39.37” long
busbar supply; conductor (28 2P breakers)
P1X9201 P1X9210 P1X9202 cross section 25mm² max. – Three-pole: for 57 modules, 1012mm/39.84” long
P1X9210 1-pole terminal for supplying 25 0.010 (19 3P breakers)
busbar; conductor cross section – Four-pole: for 56 modules, 1000mm/39.37” long
25mm² max.; left entry (14 4P breakers).
P1X9202 Single-pole terminal for 25 0.022 PADLOCKABLE ATTACHMENT
busbar supply; conductor – Max. padlock diameter 5mm/0.20”
cross section 50mm² max. – Padlockable in ON and OFF
P1X1810 P2X1810
P1X1810 Padlockable attachment for 10 0.001 – One can be fitted for each pole of the breaker.
breaker control lever P1MB...
 Suitable for P1MB... P2X1810 Padlockable attachment for 10 0.002
Not suitable for P1MBU... breaker control lever P2MB...

UL approved supply busbar Order code Description Qty Wt Main features


per UL approved power bars are divided into two groups:
pkg – Bars for UL 1077 approved thermal-magnetic circuit
breakers;
n° [kg] – Bars for UL 489 approved thermal-magnetic circuit
Power bars for UL 1077 thermal-magnetic circuit breakers, breaker bars.
type P1MB... Both models are supplied 1000mm/39.37” long and can be
1P18K57S0U50 Single-pole supply busbar 10 0.160 cut to the desired length. This feature makes it easy to adapt
to any combination of installed thermal-magnetic circuit
2P18L56S0U50 Two-pole supply busbar 10 0.320 breakers. Special end caps must be applied at the points
3P18L57S0U50
3P18L57S0U50 Three-pole supply busbar 10 0.474 where the bars are cut, to ensure IP20 protection and to
BRB5W Kit of 5 insulating caps for 10 0.030 comply with UL standards.
unused bar terminals
A69 End cap for 50 0.001 Operational characteristics
1P18K57S0U50 POWER BARS FOR UL APPROVED THERMAL-MAGNETIC
A7 End cap for 50 0.001 CIRCUIT BREAKERS
802150S 2P18L56S0U50 and – Maximum rated AC voltage: 600V
3P18L57S0U50 – Central power point: 160A max
802150S Single-pole terminal block 25 0.030 – Side point for power supply: 80A max
to supply busbar – Spacing: 17.8mm/0.70”
1P18K57S0U50; conductor – Bar section: 18mm²
section 10 to 1 AWG – For parallel connection
– Single pole: for 57 modules, 1000mm/39.37” long
802180 Single-pole terminal block 10 0.030 (57 1P switches)
to supply busbar – Two pole: for 56 modules, 1000mm/39.37” long
2P18L56S0U50 and (28 2P switches)
802180 3P18L57S0U50; conductor – Three pole: for 57 modules, 1012mm/39.84” long
section 10 to 1 AWG (19 3P switches).
Power bars for UL 489 thermal-magnetic circuit breakers,
type P1MBU... Certifications
ULC157A18A Single pole power bar 10 0.160 UL 508 for P18K57... bars (for use with UL 1077 approved
thermal-magnetic circuit breakers).
ULC256A18A Two pole power bar 10 0.320 UL 489 for UL... bars (for use with UL 489 approved thermal-
ULC...
ULC357A18A Three pole power bar 10 0.474 magnetic circuit breakers).
BRU3V Kit of 3 insulating caps 10 0.022
for unused bar terminals
A68 End cap for all ULC... type 50 0.001
BRU3V bars
802307 Single-pole terminal block 10 0.030
to power bars; conductor
section 14 to 2 AWG

802307

Dimensions Wiring diagrams Technical characteristics


14-12 page 14-16 page 14-16 page 14-17
14 Miniature and residual circuit breakers
Switch disconnectors.
,1'EX Residual blocks

Switch disconnectors Order code Ie N° of DIN Qty per Wt General characteristics


module pkg These devices are mainly used for disconnection and
insulation of power lines and systems. They can also be used
[A] n° n° [kg] to switch various types of resistive and inductive loads.
Modular switch disconnectors - 1P. Main features include:
P1MS1P032 32 1 12 0.083 – IEC rated current In: 32...125A
– Pole width: 17.5mm / 0.69”
P1MS1P040 40 1 12 0.083 – Clear contact status indication
P1MS1P063 63 1 12 0.083 – Wide terminals for easy wiring
P1MS1P100 100 1 12 0.083 – Auxiliary contacts can be mounted on left side and
padlockable attachment
P1MS1P... P1MS1P125 125 1 12 0.083 – Fixing on 35mm DIN rail (IEC/EN/BS 60715).
Modular switch disconnectors - 2P.
P1MS2P032 32 2 6 0.170 Operational characteristics
– Utilisation category: AC-22A
P1MS2P040 40 2 6 0.170 – IEC rated insulation voltage Ui: 1000V
P1MS2P063 63 2 6 0.170 – IEC rated impulse voltage Uimp: 4kV
– IEC rated operational voltage Ue: 1P 230...240V; 2P, 3P,
new P1MS2P100
P1MS2P125
100
125
2
2
6
6
0.170
0.170
4P 400...440V
– IEC rated short-time withstand current Icw: 12xIe (for
Modular switch disconnectors - 3P. 1 second).
P1MS2P... P1MS3P032 32 3 4 0.250
Certifications and compliance
P1MS3P040 40 3 4 0.250 Certifications obtained: TÜV-Rheinland, EAC.
P1MS3P063 63 3 4 0.250 Compliant with standards: IEC/EN/BS 60947-3.
P1MS3P100 100 3 4 0.250
P1MS3P125 125 3 4 0.250
Modular switch disconnectors - 4P.
P1MS4P032 32 4 3 0.330
P1MS4P040 40 4 3 0.330
P1MS4P063 63 4 3 0.330
P1MS3P...
P1MS4P100 100 4 3 0.330
P1MS4P125 125 4 3 0.330

14

P1MS4P...

Add-on blocks for switch Order code Description Qty per Qty per Wt Operational characteristics (auxiliary contact)
breaker pkg – Utilisation category AC-12: 6A 230V; 3A 400V
disconnectors P1MS... – Utilisation category DC-12: 0.4A 250V; 6A 24V.
n° n° [kg]
P1X1011S Auxiliary contact, 1 1 0.040
1 changeover contact
P1X1810 Padlockable 1 10 0.001
attachment for
breaker control lever
P1MS...

P1X1011S P1X1810

Residual blocks Order code Type IEC IEC N° of Qty Wt General characteristics
In IΔn DIN per These devices are intended for the protection of people
module pkg against indirect contact (electric shock) and of installations
against fire hazards due to a persistent earth/ground fault
[A] [mA] n° n° [kg] current.
Residual blocks – 2P – type A. They snap onto the P1MB... series thermal-magnetic circuit
P1RA2P40A030 A 40 30 2 1 0.160 breakers; this combination forms a single device to protect
people, protect against fire and protect lines.
P1RA2P40A300 A 40 300 2 1 0.160
P1RA2P63A030 A 63 30 2 1 0.160 Operational characteristics
P1RA2P63A300 A 63 300 2 1 0.160 – IEC rated insulation voltage Ui: 400V
– IEC rated impulse voltage Uimp: 4kV
Residual blocks – 3P – type A. – IEC rated frequency: 50/60Hz
P1RA2P...
P1RA3P40A030 A 40 30 3.5 1 0.205 – IEC rated operational voltage Ue: 230/400V
P1RA3P40A300 A 40 300 3.5 1 0.205 – IEC rated residual current for tripping IΔn: 30mA; 300mA
– Dissipation per pole: 1.6W (40A), 2.7W (63A).
P1RA3P63A030 A 63 30 3.5 1 0.205
P1RA3P63A300 A 63 300 3.5 1 0.205 Certifications and compliance
Residual blocks – 4P – type A. Compliance with standards: IEC/EN/BS 61009-1.
Certifications obtained: TÜV-SUD, EAC.
P1RA4P40A030 A 40 30 3.5 1 0.230
P1RA4P40A300 A 40 300 3.5 1 0.230
P1RA4P63A030 A 63 30 3.5 1 0.230
P1RA4P63A300 A 63 300 3.5 1 0.230
P1RA3P...

Dimensions Wiring diagrams Technical characteristics


page 14-16 page 14-16 page 14-17 14-13
14 Miniature and residual circuit breakers
Residual current operated circuit breakers
,1'EX

2P - 2 modules Order code Type IEC IEC N° of Qty Wt General characteristics


These RCCBs are intended for the protection of people
4P - 4 modules In IΔn DIN per
module pkg against indirect contact (electric shock) and of installations
against fire hazards due to a persistent earth/ground fault
[A] [mA] n° n° [kg] current. Specifically to prevent electric shock, RCCBs must
Two pole RCCB type AC. be rated with a rated residual current (IΔn) not exceeding
30mA so that these devices trip in the case of earth/ground
P1RD2P25AC030 AC 25 30 2 1 0.185 fault only. They usually are connected in series with thermal-
P1RD2P25AC300 AC 25 300 2 1 0.185 magnetic breakers which assure short circuit and overcurrent
protection too. P1RC types have a IΔn of either 30mA or
P1RD2P40AC030 AC 40 30 2 1 0.185
300mA and are available with three different versions of
P1RD2P40AC300 AC 40 300 2 1 0.185 residual current tripping, as follows:
P1RD2P63AC030 AC 63 30 2 1 0.185 Type AC – Tripping for earth/ground fault is ensured “for
P1RD2P63AC300 AC 63 300 2 1 0.185 residual sinusoidal alternating currents, suddenly applied or
Two pole RCCB type A. slowly rising”. The symbol identifying Type AC is the
following:
P1RD2P... P1RD2P25A030 A 25 30 2 1 0.185
Type A – Tripping for earth/ground fault is ensured “for
P1RD2P25A300 A 25 300 2 1 0.185
residual sinusoidal alternating currents and pulsating direct
P1RD2P40A030 A 40 30 2 1 0.185 currents, suddenly applied or slowly rising”. In addition to
P1RD2P40A300 A 40 300 2 1 0.185 the protection given by Type AC, this version protects against
residual current with pulsating waveform. This can be caused
P1RD2P63A030 A 63 30 2 1 0.185 by circuits connected with electronic equipment. The symbol
P1RD2P63A300 A 63 300 2 1 0.185 identifying Type A is the following:
new Four pole RCCB type AC.
Type B – tripping is ensured for all conditions already
P1RD4P25AC030 AC 25 30 4 1 0.326 covered by types AC and A. They also ensure tripping for
P1RD4P25AC300 AC 25 300 4 1 0.326 high-frequency leakage currents up to 1000Hz and direct
currents. They are particularly suitable for applications with
P1RD4P40AC030 AC 40 30 4 1 0.326 inverters, UPSs and electric vehicle charging stations.
P1RD4P40AC300 AC 40 300 4 1 0.326 The symbol identifying Type B is the following:
P1RD4P63AC030 AC 63 30 4 1 0.326
P1RD4P63AC300 AC 63 300 4 1 0.326 Main features include:
Four pole RCCB type A. – IEC rated current In: 25A, 40A and 63A
– Versions: 2P and 4P
P1RD4P25A030 A 25 30 4 1 0.326
– Type of operation: AC, A and B
P1RD4P25A300 A 25 300 4 1 0.326 – Pole width: 17.5mm / 0.69”
P1RD4P... P1RD4P40A030 A 40 30 4 1 0.326 – Contact status with flag indicator
– Fixing on 35mm DIN rail (IEC/EN/BS 60715).
P1RD4P40A300 A 40 300 4 1 0.326
Operational characteristics
P1RD4P63A030 A 63 30 4 1 0.326
– Dissipation per pole:
P1RD4P63A300 A 63 300 4 1 0.326 • 1.1W for P1RC2/4P25... type AC or A
Four pole RCCB type B. • 2.9W for P1RC2/4P40... type AC, A or B
• 7.2W for P1RC2/4P63... type AC, A or B
P1RC4P40B030 B 40 30 4 1 0.335
• 9.7W for P1RC/4P80... type B
P1RC4P40B300 B 40 300 4 1 0.335 – IEC rated insulation voltage Ui: 400V
P1RC4P63B030 B 63 30 4 1 0.335 – IEC rated impulse voltage Uimp: 4kV
– IEC rated frequency: 50/60Hz
P1RC4P63B300 B 63 300 4 1 0.335
– IEC rated operational voltage Uc: 230VAC for 2P;
P1RC4P80B030 B 80 30 4 1 0.335 230/400VAC for 4P
P1RC4P80B300 B 80 300 4 1 0.335 – IEC rated residual operating voltage Ue: IΔn: 30mA; 300mA
– IEC short-circuit breaking capacity Icn: 10kA
Certifications and compliance
Certifications obtained: TÜV-Rheinland (types AC and A), EAC.
Compliant with standards: IEC/EN/BS 61008-1,
IEC/EN/BS 61008-2-1 (all types); IEC/EN/BS 62423 (type B).

P1RC4PB...

Add-on blocks for P1RD... Order code Description Qty per Qty Wt General characteristics
MCB per – Auxiliary and indicator contact width: 9mm/0.35”
pkg (0.5 module)
– Undervoltage and shunt trip release width: 18mm/0.71”
n° n° [kg] (1 module)
Auxiliary contact. – Maximum combination: 3 add-on blocks on MCB left side
P1X1011 1 changeover contact 1 12 0.040 only of which 1 undervoltage or shunt release directly on
MCB side and then 2 contacts of which 1 auxiliary and
Indicator contact for trip. 1 indicator.
P1X1311 1 changeover contact 1 12 0.040
Operational characteristics
Undervoltage trip release. – IEC rated impulse voltage Uimp: 4kV
P1X14230 230V 50/60Hz 1 8 0.070 – IEC rated operational current in AC: 6A 230V; 3A 400V
(auxiliary contacts).
Shunt trip release.
P1X16230 110...415V 50/60Hz 1 8 0.070 Certifications and compliance
Certifications obtained: EAC, cULus (excluding P1X14230
P1X1011 P1X16... P1X16024 12...24VDC 50/60Hz 1 8 0.070 and P1X16024).
Padlockable attachment Compliant with standards: IEC/EN/BS 60947-5-1,
P1X1810 Padlockable 1 10 0.001 CSA C22.2 n° 5.
attachment for
breaker control lever

Dimensions Technical characteristics


14-14 page 14-16 page 14-17
14 Miniature and residual circuit breakers
Residual current operated circuit breakers with overcurrent protection
,1'EX

1P+N - 10kA Order code Curve IEC IEC IEC Mod. Qty Wt General characteristics
In Icn IΔn DIN per These devices both detect and trip in the event of residual
2 modules pkg current and protect circuits in the case of short circuits and
overcurrent. From a practical point of view, they integrate
[A] [kA] [mA] n° n° [kg] both functions of MCB and RCCB.
Single pole + neutral RCBO type AC. They have a C-type trip characteristic (instantaneous trip
P1RE1NC06AC030 C 6 10 30 2 1 0.205 5-10 times In) and are used for inductive loads (mixed loads,
resistive and inductive with low inrush current).
P1RE1NC06AC300 C 6 10 300 2 1 0.205 In addition, they have a rated residual current (IΔn) of either
P1RE1NC10AC030 C 10 10 30 2 1 0.205 30mA or 300mA and are available with two different versions
P1RE1NC10AC300 C 10 10 300 2 1 0.205 of residual current tripping type AC or A as described on
page 14-14.
P1RE1NC16AC030 C 16 10 30 2 1 0.205 Its main features are:
P1RE1NC16AC300 C 16 10 300 2 1 0.205 – IEC rated current In: 6...40A
P1RE1NC20AC030 C 20 10 30 2 1 0.205 – Version: 1P+N
– Contact status with flag indicator
P1RE1NC20AC300 C 20 10 300 2 1 0.205 – Double control lever to distinguish the residual current
P1RE1N...
P1RE1NC25AC030 C 25 10 30 2 1 0.205 tripping from short circuit or overcurrent tripping
P1RE1NC25AC300 C 25 10 300 2 1 0.205 – Trip characteristic: curve type C
– Fixing on 35mm DIN rail (IEC/EN/BS 60715).
P1RE1NC32AC030 C 32 10 30 2 1 0.205
P1RE1NC32AC300 C 32 10 300 2 1 0.205 Operational characteristics
P1RE1NC40AC030 C 40 10 30 2 1 0.205 – Dissipation per pole: 3...13W
– Rated insulation voltage Ui: 400V
P1RE1NC40AC300 C 40 10 300 2 1 0.205
new Single pole + neutral RCBO type A.
– Rated impulse voltage Uimp: 4kV
– Operating frequency: 50/60Hz
P1RE1NC06A030 C 6 10 30 2 1 0.205 – Rated operational voltage Ue: 230VAC
– Rated residual operating voltage IΔn: 30mA; 300mA
P1RE1NC06A300 C 6 10 300 2 1 0.205 – IEC short-circuit breaking capacity Icn: 10kA
P1RE1NC10A030 C 10 10 30 2 1 0.205
P1RE1NC10A300 C 10 10 300 2 1 0.205 Certifications and compliance
Certifications obtained: TÜV Rheinland, EAC.
P1RE1NC13A030 C 13 10 30 2 1 0.205 Compliant with standards: IEC/EN/BS 61009-1,
P1RE1NC16A030 C 16 10 30 2 1 0.205 IEC/EN/BS 61009-2-1.
P1RE1NC16A300 C 16 10 300 2 1 0.205
P1RE1NC20A030 C 20 10 30 2 1 0.205
P1RE1NC20A300 C 20 10 300 2 1 0.205 14
P1RE1NC25A030 C 25 10 30 2 1 0.205
P1RE1NC25A300 C 25 10 300 2 1 0.205
P1RE1NC32A030 C 32 10 30 2 1 0.205
P1RE1NC32A300 C 32 10 300 2 1 0.205
P1RE1NC40A030 C 40 10 30 2 1 0.205
P1RE1NC40A300 C 40 10 300 2 1 0.205

Add-on blocks for P1RE... Order code Description Qty per Qty Wt General characteristics
MCB per – Auxiliary and indicator contact width: 9mm/0.35”
pkg (0.5 module)
– Undervoltage and shunt trip release width: 18mm/0.71”
n° n° [kg] (1 module)
Auxiliary contact. – Maximum combination: 3 add-on blocks on MCB left side
P1X1011 1 changeover contact 1 12 0.040 only of which 1 undervoltage or shunt release directly on
MCB side and then 2 contacts of which 1 auxiliary and
Indicator contact for trip. 1 indicator.
P1X1311 1 changeover contact 1 12 0.040
Operational characteristics
Undervoltage trip release. – IEC rated impulse voltage Uimp: 4kV
P1X14230 230V 50/60Hz 1 8 0.070 – IEC rated operational current in AC: 6A 230V; 3A 400V
(auxiliary contacts).
Shunt trip release.
P1X16230 110...415V 50/60Hz 1 8 0.070 Certifications and compliance
Certifications obtained: EAC, cULus (excluding P1X14230
P1X1011 P1X16... P1X16024 12...24VDC 50/60Hz 1 8 0.070 and P1X16024).
Padlockable attachment Compliant with standards: IEC/EN/BS 60947-5-1,
P1X1810 Padlockable 1 10 0.001 CSA C22.2 n° 5.
attachment for
breaker control lever

Dimensions Technical characteristics


page 14-16 page 14-17 14-15
14 Miniature and residual circuit breakers
Dimensions [mm (in)]
,1'EX

MINIATURE CIRCUIT BREAKERS ACCESSORIES


P1MB... Add-on contacts Undervoltage and shunt releases
18 max 36 max 60 (2.36”)
P1X1011 - P1X0111S - P1X14230 - P1X16...
54 max 72 max
(0.71” max) (1.42” max) (2.12” max) (2.83” max) 45 (1.77”) P1X1011UH - P1X1311
9 max 18 max
(0.35” max) 66 (2.60”) 66 (2.60”)
(0.71” max)
60 (2.36”) 60 (2.36”)

(1.77” max)
(3.40” max)
86.5 max

45 max
(1.38”)
35

86 (3.38”)

45 (1.77”)
81 (3.19”)

83 (3.27”)

45 (1.77”)
81 (3.19”)
5.5 (0.22”)
5.5 (0.22”)

5.52 (0.22”)
74 max
(2.91” max)
P1MBUH... - P1MBUL....
36 max SWITCH DISCONNECTORS
18 max 54 max
(0.71” max)
(1.42” max)
(2.12” max)
60 (2.36”) P1MS....
47 (1.85”)
18 (0.71”) 36 (1.42”) 60 (2.36”)
max max 54 (2.12”) max 72 (2.83”) max 42 (1.65”)
116 (4.57”)

(1.77” max)

45 (1.77”) max
77 (3,03”) max
(1.38”)

45 max

35 (1.38”)
35

5.52 (0.22”)
5.52 (0.22”) 74 (2.91”) max
70 max(2.75” max)

MINIATURE CIRCUIT BREAKERS ACCESSORIES


P2MB... Add-on contacts Shunt release
P2X1011 - P2X1311 P2X16230
67 max 74 (2.91”)
(2.64” max) 74 (2.91”)
27 max 54 max 81 max 108 max 43 (1.69”)
(1.06” max) (4.25” max) 49.5 max 43 (1.69”)
(2.12” max) (3.19” max) (1.95” max) 32
32
5.5 (0.22”) (1.26”) (1.26”)
9 max 5.4 18 max 5.4
(0.35” max) (0.21”) (0.71” max) (0.21”)
85 max (3.35” max)

45 (1.77”)
80 (3.15”)

79 (3.11”)
45 (1.77”)
79 (3.11”)

44 (1.73”)
60 (2.36”)
74.5 (2.93”)

RESIDUAL BLOCKS
P1RA
35.3 63 (2.48”) 63 (2.48”) 69.2 (2.72”)
(1.39”)
(1.38”)
92 (3.62”)

92 (3.62”)
92 (3.62”)

35

115 (4.53”) 133 (5.24”)


71.3 (2.81”) 69.7 (2.74”)

RESIDUAL CURRENT OPERATED CIRCUIT BREAKERS RESIDUAL CURRENT OPERATED CIRCUIT


P1RD... BREAKERS WITH OVERCURRENT PROTECTION
P1RE...
36max 71-72max 5.5 68 (2.68”) 36max 5.5 68 (2.68”)
(1.42”max) (2.79”-2.83”max) (0.22”) 44 (1.73”) (1.42”max) (0.22”) 44 (1.73”)
81 (3.19”)

81 (3.19”)
45 (1.77”)

45 (1.77”)

Wiring diagrams

P1X1011 - P1X1011S - P1X1011UH - P2X1011 P1X1311 - P2X1311 P1X14230 P1X16... - P2X16230

14-16
14 Miniature and residual circuit breakers
Technical characteristics
,1'EX

TYPE P1MB1M... P1MB1N... P1MB...P... P2MB P1MS... P1RA P1RD... P1RE...


Description Miniature Miniature Miniature Miniature Switch Residual blocks Residual current Residual current
circuit breakers circuit breakers circuit breakers circuit breakers disconnectors operated circuit operated circuit
breakers breakers w/
overcurrent prot.
Standards IEC/EN/BS 60898, IEC/EN/BS 60898, IEC/EN/BS 60898, IEC/EN/BS 60947-2 IEC/EN/BS 60947-3 IEC/EN/BS 61008-1 IEC/EN/BS 61008-1 IEC/EN/BS
IEC/EN/BS 60947-2 IEC/EN/BS 60947-2 IEC/EN/BS 60947-2 UL 1077 IEC/EN/BS IEC/EN/BS 61009-2-1
UL 1077 - UL 489 61008-2-1 61008-2-1
IEC rated insulation V 500 230 1000 400 1000 400 400 400
voltage Ui
IEC rated impulse withstand kV 4 4 4 6 4 4 4 4
voltage Uimp
IEC rated operational in AC V 230 230 230 (1P, 1P+N) 230 (1P) 230...240 (1P) 230 (2P) 230 (2P) 230
voltage Ue 230/400 230/400 400...440V 230/400 (3P, 4P) 230/400(4P)
(2P, 3P, 4P) (2P, 3P, 4P) (2P, 3P, 4P)
in DC V — — 80 (1P, 2P) 80(1P) /125(2P) –– –– — —
Rated frequency Hz 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60
Maximum rated current A 40 63 63 125 125 63 63 40
Available rated current for A 2, 4, 6, 10, 13, 16, 1, 2, 4, 6, 10, 1, 1.6, 3, 4, 6, 8, 80, 100, 125 30, 40, 63, 40, 63 25, 40, 63 6, 10, 16, 20,
types 20, 25, 32, 40 16, 20, 25, 32, 10, 13, 16, 20, 25, 100, 125 (80A B type only) 25, 32, 40
40, 50, 63 32, 40, 50, 63
Versions 1P+N 1P+N 1P, 2P, 3P, 4P 1P, 2P, 3P, 4P 1P, 2P, 3P, 4P 2P, 3P, 4P 2P, 4P 1P+N
Tripping characteristic curve B-C C B-C-D C-D –– –– — C
Instantaneous tripping Curve B: 3...5In Curve B: 3...5In Curve B: 3...5In
Curve C: 5...10In Curve C: 5...10In Curve C: 5...10In Curve C: 5...10In –– — –– Curve C: 5...10In
Curve D: 10...14In Curve D: 10...14In
Residual operation characteristic type — — — — –– A AC, A, B AC, A
Rated residual current IΔn mA — — — — –– 30, 300 30, 300 30, 300
Short circuit capacity (IEC/EN/BS) kA 6 (Icn/Icu) 6 (Icn/Icu) 10 (Icn/Icu) 10 (Icu) –– –– 10 (Inc) 10 (Icn)
Short circuit capacity kA –– –– 7.5 (1P 240V) 5 –– –– –– ––
(UL 1077)  5 (1P 277V)
7.5 (2,3,4P 480V)
Mechanical life cycle 20,000 20,000 20,000 10,000 7,000 20,000 20,000 20,000
14
Electrical life cycle 10,000 10,000 10,000 10,000 1,000 10,000 10,000 10,000
Tightening torque of Nm 1.1...1.2 1.8...2 1.8...2 3.2...3.5 3.2...3.5 1.8...2 1.8...2 1.8...2
terminals lb.in 9.7...10.6 16...17.7 16...17.7 28.8...31 28.8...31 16...17.7 16...17.7 16...17.7
Tool PZ2 PzZ2 PZ2 PZ2 PZ2 PZ2 PZ2 PZ2
Conductor section min...max. mm2 1...16 1...35 1...35 2.5...50 1...50 1...25 2.5...35 1...16
AWG 14...6 14...2 14...2 14...1/0 16...1 14...6 14...2 16...3
AMBIENT CONDITIONS
Temperature Operating °C -40...+70 -40...+70 -40...+70 -40...+70 -25...+70 -25...+60 -25...+60 -25...+60
Storage °C -40...+80 -40...+80 -40...+80 -40...+80 -25...+70 -40...+80 -40...+80 -40...+80
Max. altitude m 2,000 2,000 2,000 2,000 2,000 2,000 2,000 2,000
Pollution degree 2 2 2 3 3 2 2 2
Mounting 35mm DIN rail (IEC/EN/BS 60715)
TRIP CHARACTERISTICS
Curve B Curve C Curve D
Tripping time [s] Tripping time [s] Tripping time [s]
10000 10000 10000

1000 1000 1000

100 100 100

10 10 10

1 1 1

0,1 0,1 0,1

0,01 0,01 0,01


1 1,45 3 5 7 9 20 40 60 100 1 1,45 3 5 7 9 20 40 60 100 1 1,45 3 5 7 9 20 40 60 100
1,13 2 4 6 8 10 30 50 70 1,13 2 4 6 8 10 30 50 70 1,13 2 4 6 8 10 30 50 70
Multiple of In [A] Multiple of In [A] Multiple of In [A]

 UL489 only P1MBU... version; for the operational voltages for these devices refer to the pages for the  For the UL 489, P1MBU... versions to 32A: 1P 277V; 2P and 3P 480Y/277V. From 35 to 63A: 1P 120V;
chosen product. 2P and 3P 240V.
 For the UL 489, P1MBU... versions, the following rated current currents are also available: 5, 7, 12, 15,  UL 1077 standard: 60VDC (1P) / 125VDC (2P), short circuit capacity 7.5kA.
30, 35, 60A. For the UL 489, P1MBU... versions: 60VDC (1P, 2P) / 125VDC (2P), short circuit capacity 10kA
 UL 1077 standard: 60VDC (1P, 2P), short circuit capacity 10kA.
 For the UL 489, P1MBU..., short circuit capacity 10kA.

14-17

You might also like