Installation Manual SD110 r2

The EAE KNX 1-10V Dimmer Actuator features 10 independent switching and dimming outputs, with a maximum switching voltage of 250V and current of 16A per channel. It can be programmed via ETS4 or higher and includes functions such as staircase lighting and forced operation. Installation must be performed by trained electricians, adhering to relevant standards and ensuring the device is protected from moisture and damage.

Uploaded by

Hamza Marga
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views1 page

Installation Manual SD110 r2

The EAE KNX 1-10V Dimmer Actuator features 10 independent switching and dimming outputs, with a maximum switching voltage of 250V and current of 16A per channel. It can be programmed via ETS4 or higher and includes functions such as staircase lighting and forced operation. Installation must be performed by trained electricians, adhering to relevant standards and ensuring the device is protected from moisture and damage.

Uploaded by

Hamza Marga
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Installation Manual SD110

EAE KNX 1-10V DIMMER SD110 R2.0

Operation and Display


-Programming Led (3)
RED Led will be light up after the programming button is pressed.

Connection Example

Connection
1. Relay outputs 2. Indicator LEDs 3. KNX prog. 4. KNX
button Connection
5. KNX prog. LED 6. 0-10V Outputs 7. Man. Ctrl. 8. Physical
Buttons Address Label

Description Scale Drawings


EAE KNX 1-10V Dimmer Actuator has 10 independent switching and dimming
outputs. Maximum switching voltage is 250V and maximum current is 16A for each
channel. Dimming functions can be used by 1-10V controlled ballasts only. The
device can be operated manually via push button on it. Each channel can be
programmed via ETS4 or above.
Channel features of switch & dim actuator;

• Staircase lighting
• Forced Operation
• Channel Disabling
• Operating Hour Counter

All features can be used separately or together. Please consider that those features
will be processed depending on priority. Bus Voltage Fail & Return behavior can be
set via ETS configuration.

Technical Data

Type of protection IP 20 EN 60 529


Safety class II EN 61 140
Power Supply 21V… 30V DC, SELV KNX Bus
Current consumption < 10mA
Connections - Screw terminals
0,5…3,31 mm² solid and stranded wire
0,5…3,31 mm² stranded wire with ferrule

- Max. tightening torque 0.5Nm


- KNX Bus connection terminal
Output - Switching 10 output, passive Commissioning
- Dimming 10 output, 0-10V Determination of the physical address and setting of parameters are actualized
- Cable length max. 200m. with Engineering Tool Software (ETS4 or higher). “.knxprod” file must be imported
-Max. switching power 4000VA to the ETS. Please check website for latest “.knxprod” file.
- Mechanical life > 1 x 106 www.eaetechnology.com
Type of contact - potential-free, bistable
Operating elements LED (red) and programming button to assign A detailed information about parameter configuration can be found in
physical address Product Manual of device.
Temperature range Ambient -5° C + 45° C
Storage -25° C + 55° C Installation and commissioning of device may only be implemented by trained
Transport -25° C + 70° C electricians. The relevant standards, directives, regulations and instructions must
Dimensions 66 x W x 90mm be observed when planning and implementing the electrical installation.
Width W in mm 18mm -When connecting the device make sure that the device is isolated!
Width W in units 10 modules -Protect the device against moisture, dirt and damage during transport, storage and
Weight 0,45 Kg operation!
Humidity Maximum air humidity -Do not operate the device out of the specified technical data which is stated.
95 % no moisture condensation
-The device may only be operated in closed enclosures (Distribution boards etc.)
Box Plastic, polycarbonate, white colour
Cleaning
CE In accordance with the EMC guideline and low
voltage If device becomes dirty, only a dry cloth can be used for cleaning. It is not suitable
Application program Communication objects 151 to use wet cloths, caustics and solvents.
Number of addresses(max) 255

© EAE Technology www.eaetechnology.com