03 Reg615
03 Reg615
– Introduction
– Application examples
– Hardware and options
– Functionality highlights
September 29,
Slide 2
2022
—
REG615 – Generator Protection and Control
Introduction
—
REG615 – Generator Protection and Control
Introduction
September 29,
Slide 4
2022
—
REG615 – Generator Protection and Control
Introduction
Standard configuration
Standard configuration A – Interconnection protection for distributed power generation
– Main features are low-voltage ride-through protection, directional reactive power undervoltage protection (QU) and the voltage
vector shift protection.
– 4CT + 5VT, and up to 16 BI/10 BO
Standard configuration D – Generator protection with generator differential and directional overcurrent protection and synchro-check
– Other main features are reverse power and directional overpower, out-of-step, overexcitation and underexcitation protection
– 7CT + 5VT, and up to 12 BI/10 BO
September 29,
Slide 5
2022
—
REG615 – Generator Protection and Control
Function Availability
Standard configuration IEC 61850 A C D
Protection
Three-phase non-directional overcurrent protection, low
PHLPTOC - 1 1
stage
Three-phase non-directional overcurrent protection, high
PHHPTOC - 1 1
stage
Three-phase non-directional overcurrent protection,
PHIPTOC 1 1 1
instantaneous stage
Three-phase directional overcurrent protection, low stage DPHLPDOC 2 - 1TR)
September 29,
Slide 6
2022
—
REG615 – Generator Protection and Control
Function Availability
Standard configuration IEC 61850 A C D
Protection
Three-phase undervoltage protection PHPTUV 2 2 2
Three-phase overvoltage protection PHPTOV 2 2 2
Positive-sequence undervoltage protection PSPTUV 2 2 2
Negative-sequence overvoltage protection NSPTOV 2 2 2
Frequency protection FRPFRQ 6 6 4
Overexcitation protection OEPVPH - 1 1
Three-phase thermal protection for feeders, cables and
T1PTTR 1 - -
distribution transformers
Three-phase thermal overload protection, two time constants T2PTTR - 1 1
Circuit breaker failure protection CCBRBRF 1 1 1
Three-phase inrush detector INRPHAR 1 1 1
Master trip TRPPTRC 2 3 3
Arc protection ARCSARC 3 3 3
Multipurpose protection MAPGAPC 18 18 18
Stablized and instantaneous differential protection for machines MPDIF - - 1
Third harmonic-based stator earth-fault protection H3EFPSEF - 1 -
Underpower protection DUPPDPR - 2 2
September 29,
Slide 7
2022
—
REG615 – Generator Protection and Control
Function Availability
Standard configuration IEC 61850 A C D
Protection
Three-phase undervoltage protection PHPTUV 2 2 2
Three-phase overvoltage protection PHPTOV 2 2 2
Positive-sequence undervoltage protection PSPTUV 2 2 2
Negative-sequence overvoltage protection NSPTOV 2 2 2
Frequency protection FRPFRQ 6 6 4
Overexcitation protection OEPVPH - 1 1
Three-phase thermal protection for feeders, cables and
T1PTTR 1 - -
distribution transformers
Three-phase thermal overload protection, two time constants T2PTTR - 1 1
Circuit breaker failure protection CCBRBRF 1 1 1
Three-phase inrush detector INRPHAR 1 1 1
Master trip TRPPTRC 2 3 3
Arc protection ARCSARC 3 3 3
Multipurpose protection MAPGAPC 18 18 18
Stablized and instantaneous differential protection for machines MPDIF - - 1
Third harmonic-based stator earth-fault protection H3EFPSEF - 1 -
Underpower protection DUPPDPR - 2 2
September 29,
Slide 8
2022
—
REG615 – Generator Protection and Control
Function Availability
Standard configuration IEC 61850 A C D
Protection
Reverse power/directional overpower protection DOPPDPR 2 3 2
Three-phase underexcitation protection UEXPDIS - 1 1
Three-phase underimpedance protection UZPDIS - 1 -
Out-of-step protection OOSRPSB - 1 1
Interconnection functions
Directional reactive power undervoltage protection DQPTUV 1 - -
Low-voltage ride-through protection LVRTPTUV 3 - -
Voltage vector shift protection VVSPPAM 1 - -
Power Quality
Current total demand distortion CMHAI 1 1 1
Voltage total harmonic distortion VMHAI 1 1 1
Voltage variation PHQVVR 1 1 1
Voltage unbalance VSQVUB 1 1 1
Control
Circuit-breaker control CBXCBR 1 1 1
Disconnector control DCXSWI 2 2 2
September 29,
Slide 9
2022
—
REG615 – Generator Protection and Control
Function Availability
Standard configuration IEC 61850 A C D
Control
Earthing switch control ESXSWI 1 1 1
Disconnector position indication DCSXSWI 3 3 3
Earthing switch indication ESSXSWI 2 2 2
Synchronism and energizing check SECRSYN 1 - 1
Condition monitoring and supervision
Circuit-breaker condition monitoring SSCBR 1 1 1
Trip circuit supervision TCSSCBR 2 2 2
Current circuit supervision CCSPVC 1 - -
Fuse failure supervision SEQSPVC 1 1 1
Runtime counter for machines and devices MDSOPT 1 1 1
Measurement
Disturbance recorder RDRE 1 1 1
Load profile record LDPRLRC 1 1 1
Fault record FLTRFRC 1 1 1
Three-phase current measurement CMMXU 1 1 2
Sequence current measurement CSMSQI 1 1 1
Residual current measurement RESCMMXU 1 1 1
September 29,
Slide 10
2022
—
REG615 – Generator Protection and Control
Function Availability
Standard configuration IEC 61850 A C D
Measurement
Three-phase voltage measurement VMMXU 2 1 2
Residual voltage measurement RESVMMXU 1 2 1
Sequence voltage measurement VSMSQI 1 1 1
Three-phase power and energy measurement PEMMXU 1 1 1
RTD/mA measurement XRGGIO130 (1) (1) (1)
Frequency measurement FMMXU 1 1 1
5) 6)
IEC 61850-9-2 LE sampled value sending SMVSENDER (1) (1) (1)
IEC 61850-9-2 LE sampled value receiving (voltage
SMVRCV (1) (1) (1)
sharing) 5) 6)
Other
Minimum pulse timer (2 pcs) TPGAPC 4 4 4
Minimum pulse timer (2 pcs, second resolution) TPSGAPC 1 1 1
Minimum pulse timer (2 pcs, minute resolution) TPMGAPC 1 1 1
Pulse timer (8 pcs) PTGAPC 2 2 2
Time delay off (8 pcs) TOFGAPC 4 4 4
Time delay on (8 pcs) TONGAPC 4 4 4
Set-reset (8 pcs) SRGAPC 4 4 4
September 29,
Slide 11
2022
—
REG615 – Generator Protection and Control
Application Examples
—
REG615
Generator Protection and Control
September 29,
Slide 13
2022
—
REG615
Generator Protection and Control
September 29,
Slide 14
2022
—
REG615
Generator Protection and Control
September 29,
Slide 15
2022
—
REG615
Generator Protection and Control
September 29,
Slide 16
2022
—
REG615
Generator Protection and Control
Application Examples (5
Generator in block connection with a transformer using
standard configuration C and RET615 transformer
differential protection relay
– One single-phase voltage transformer connected to the
generator neutral for residual overvoltage protection
– Phase-to-earth voltages connected to the generator
protection relay on the terminal side
Standard configuration C includes overcurrent (including
voltage-dependent), underimpedance and frequency,
voltage and power-based protection, as well as residual
overvoltage-based earth-fault protection for the
generator. In addition, under- and overexcitation
protection are used.
September 29,
Slide 17
2022
—
REG615 – Generator Protection and Control
Hardware and options
—
REG615 – Generator Protection and Control
Hardware and Options
September 29,
Slide 19
2022
—
REG615 – Generator Protection and Control
Hardware and Options
September 29,
Slide 20
2022
—
REG615 – Generator Protection and Control
Functionality Highlights
—
REG615 - Generator Protection and Control
Functionality Highlights
September 29,
Slide 22
2022
—
REG615 - Generator Protection and Control
Functionality Highlights
September 29,
Slide 23
2022
—
REG615 - Generator Protection and Control
Functionality Highlights
Underpower Protection
– Protects the generator from very low power output
conditions
– Steam turbines become easily overheated if the steam
flow becomes too low or ceases to flow through the
turbine.
– Hydro turbines of Kaplan type may be damaged due to
the turbine blade surfing on the water and setting up
axial pressure on the bearing.
– Diesel engines may be damaged due to insufficient
lubrication.
– With parallel-connected generators, disconnecting the
low-load generator and allowing the remaining
generators to feed the network is more economical.
—
REG615 - Generator Protection and Control
Functionality Highlights
Frequency Protection
– Overfrequency
– Underfrequency
– Frequency rate-of-change
– Four to six frequency protection stages are available
– The operation mode can be selected individually for
each stage
– The operation mode can also based on a combination of
frequency limit and frequency rate-of-change
September 29,
Slide 30
2022
—
REG615 - Generator Protection and Control
Functionality Highlights
September 29,
Slide 31
2022
—
REG615 - Generator Protection and Control
Functionality Highlights
September 29,
Slide 32
2022
—
REG615 - Generator Protection and Control
Functionality Highlights
Control functions
– REG615 features in addition to the circuit-breaker control.
– Two control blocks for the control of motor-operated disconnectors or circuit-breaker trucks and their position
indications
– A control block for the control of motor-operated earthing switch and its position indication.
– Devices can be controlled via the protection relay’s local HMI or a remote control system.
– Dedicated push buttons for opening and closing of the primary devices.
– Generator circuit breaker closing is not connected in the standard configurations C and D as the closing is expected from
the external synchronizer.
– The single-line diagram indicates the position of the primary devices.
– Forcing of local/remote switch to local position via a binary input (prohibiting remote control during for example
maintenance).
– Interlocking schemes are configured using PCM600.
– Synchronism and energizing check (std. conf. A and D)