DI-M9305 Digital Single Riser Output Module
DI-M9305 Digital Single Riser Output Module
Features
Fire Alarm
During normal standby, Output port (O1, O2) is Equipment
provided with Class B pathway supervision 47AU
Fig. 1
(Z1, Z2) IN & OUT: Connecting with loop of FACP,
polarity-insensitive.
(I1, I2) IN & OUT: Power input terminals. For
connecting with 24VDC power from Listed FACP or
power supply.
O1, O2: Output terminals to 24VDC powered devices
CODE: connecting with P-9910B programmer.
Recommended Wiring
17 AWG or above fire cable for all terminals, and Fig. 2
subject to local codes.
FACP
Z2
Z1
Z1 Z2
DI-M9305 Module
in out
I1 I2 I1 I2 O1 O2
Controlled Device 1
24VDC power line to next device
Controlled Device N
Fig. 4
47kΩ/1W End-of-line
Resistor
Fig. 6
Fig. 5
This Data Sheet is subject to change without notice. Please contact GST for more information or questions.