Siimo User Manual - 4.0 1
Siimo User Manual - 4.0 1
First-time Use
For the users who use this product for the first time, read the manual carefully. If
in doubt concerning some functions or performances, contact the technical sup-
port personnel of Our company to ensure correct use.
ATTENTIONS
Ø Please power off when wiring.
Ø Electronic components inside AC drive are especially sensitive to static
electricity, do not put anything into internal of AC drive.And do not touch main
circuit board.
Ø After power cut, if indicator is still lamp, it still have high voltage in AC drive.
It is very dangerous, please do not touch internal circuit and components.
Ø Please ensure the grounding terminals of AC drive is grounded correctly.
Ø Never connect input power supply with output terminal U,V,W of AC drive.
-1-
1. Safety and Attentions
————————————————————————————————
1.1 Safety Matters...................................................................................6
1.2 Use Considerations...........................................................................9
-2-
Chapter 1 Safety and Attentions
-3-
Chapter 1 Safety and Attentions
-4-
Chapter 1 Safety and Attentions
Chapter 1
being kept, or when periodical inspection is performed, insulation inspection shall
be conducted with motor so as to avoid damaging the inverter because of the
insulation failure of the motor windings. The motor wires must be disconnected
from the inverter during the insulation inspection. It is recommended to use the
500V mega meter, and the insulating resistance measured shall be 5MΩ at least.
Mechanical Vibrations
Inverter may encounter mechanical resonance point of the load device at
certain output frequencies which can be avoided by setting the skip frequency
paramet- ers of the inverter.
-6-
Chapter 1 Safety and Attentions
Lightning Protection
The product has integrated lightning over-current protection device which
has certain self-protection capacity against the lightning. Additional protection
devices have to be installed between inverter and power supply in the area where
lightning occurs frequently.
Altitude De-rating
In places where the altitude is above 1000 m and the cooling effect reduces
-7-
Chapter 1 Safety and Attentions
due to thin air, it is necessary to de-rate the AC drive. Contact Our company for
technical support.
Adaptable Motor
Standard adaptive motor is quadrupole squirrel- cage asynchronous
induction motor. If it is not above- mentioned motor, please select AC drive upon
rated current of moter. If you need to drive permanent magnet synchronous
motor, please consult our company;
The cooling fan of non variable frequency motor and rotor spindle are
coaxially connected. While despinning, the fan cooling effect also declines at the
same time.Hence, for overheated occasion of moter, you shall install strong
exhaust fan or change variable frequency motor;
AC drives have built- in adaptive motor standard parameters. It is necessary
to make motor parameter identification or amend default values to accord with
actual values, or it will influence operation effects and protective values;
As short circuit existing inside cable or motor will cause inverter alarming,
enen explosion. Therefore, please make insulation short- circuit test of initial
installed motor and cable first. And the test also is necessary in routine
maintenance.
-8-
2. Product Brief Introduction
————————————————————————————————
2.1 Position and content of nameplate.....................................................10
2.2 Nameplate model description and rated parameters...........................10
2.3 Specifications and models of AC drives...............................................11
2.4 Technical Features...........................................................................17
2.5 All components schematic diagram of AC drive...................................20
2.6 Appearance and installation dimensions............................................21
2.7 External keyboard with tray installation dimension drawing................25
2.8 Optional accessories.......................................................................26
-9-
Chapter 2 Product Brief Introduction
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑩
① Product Line
② For synchronous machines
③ Design Version:A/B/C
Voltage Rating:Single-phase 110V/220V
④ Three-phase 220V/380V/690V
Adapted motor power mark: R75 1R5
011 015
⑤ Motor power(kW): 0.75 1.5
11 15
Applicable motors: G-General Purpose;p-Fan and
⑥
pump type
⑦ B:Built-in brake unit
Adapted motor power mark: R75 1R5
011 015
⑧ Motor power(kW): 0.75 1.5
11 15
Applicable motors: G-General Purpose;p-Fan and
⑨ pump type
⑩ B:Built-in brake unit
- 10 -
Chapter 2 Product Brief Introduction
- 11 -
Chapter 2 Product Brief Introduction
CA600-7T030GB 42 38 30
CA600-7T037GB 49.5 47 37
CA600-7T045GB 58 55 45
CA600-7T055GB 70 65 55
CA600-7T075G 90 86 75
- 12 -
Chapter 2 Product Brief Introduction
- 13 -
Chapter 2 Product Brief Introduction
- 14 -
Chapter 2 Product Brief Introduction
CA600S-7T030GB 42 38 30
CA600S-7T037GB 49.5 47 37
CA600S-7T045GB 58 55 45
CA600S-7T055GB 70 65 55
CA600S-7T075G 90 86 75
- 15 -
Chapter 2 Product Brief Introduction
- 16 -
Chapter 2 Product Brief Introduction
- 17 -
Chapter 2 Product Brief Introduction
- 18 -
Chapter 2 Product Brief Introduction
Display parameters
LED Display
- 19 -
Chapter 2 Product Brief Introduction
5
1
6
2
7
3 8
- 20 -
Chapter 2 Product Brief Introduction
Schematic diagram of overall dimensions and installation dimensions of 30~132KW sheet metal
chassis
- 21 -
Chapter 2 Product Brief Introduction
Model Description: Product model number followed by "B" indicates that the
brake unit is standard, "(B)" indicates that the brake unit is optional, if there is
demand, please specify when ordering.
Lower inlet and lower outlet model opening size and installation hole size
Installation(mm) Dimensions(mm) Aperture(
Model
A B H W D mm)
CA600-3SR40G
64 138 148 74 130 φ4.5
CA600-3SR75G
CA600-3S1R5G
76 156 165 86 140 φ5
CA600-3S2R2GB
CA600-3S4R0GB \ \ 234 123 176 \
CA600-3S5R5GB \ \ 275 160 186 \
CA600-4TR75GB
CA600-4T1R5GB/2R2PB 76 156 165 86 140 φ5
CA600-4T2R2GB/4R0PB
CA600-4T4R0GB/5R5PB
98 182 192 110 165 φ5
CA600-4T5R5GB/7R5PB
CA600-4T7R5GB/9R0PB
111 223 234 123 176 φ6
CA600-4T9R0GB/011PB
CA600-4T011GB/015PB
147 264 275 160 186 φ6
CA600-4T015GB/018PB
CA600-4T018GB/022PB
174 319 330 189 186 φ6
CA600-4T022GB/030PB
- 22 -
Chapter 2 Product Brief Introduction
- 23 -
Chapter 2 Product Brief Introduction
Upper inlet and lower outlet model opening size and installation hole size
CA600-4TR75GB
CA600-4T1R5GB/2R2PB 144 127 167 88 φ5
CA600-4T2R2GB/4R00PB
CA600-4T4R0GB/5R5PB
129 144 194 112 φ5
CA600-4T5R5GB/7R5PB
CA600-4T7R5GB/9R0PB
142 196 236 125 φ6
CA600-4T9R0GB/011PB
CA600-4T011GB/015PB
180 227 277 162 φ6
CA600-4T015GB/018PB
CA600-4T018GB/022PB
209 283 333 191 φ6
CA600-4T022GB/030PB
CA600-4T030G(B)/037P(B) 275 358 408 257 φ7
- 24 -
Chapter 2 Product Brief Introduction
CA600-4T037G(B)/045P(B)
CA600-4T045G(B)/055P(B)
330 477 527 312 φ9
CA600-4T055G(B)/075P(B)
CA600-4T075G(B)/093P(B)
370 503 553 352 φ9
CA600-4T093G/110P
- 25 -
Chapter 2 Product Brief Introduction
For the detailed functions and usage instructions of the optional accessories,
see the related optional accessories description.
If you need the above options, please specify when ordering.
Name Model Function Remarks
"B" after the product Built-in braking unit
For dynamic braking
Built-in braking model number is standard
unit "(B)" after the product Built-in braking unit
For dynamic braking
model number is optional
External LED External LED display and CA series general
operation CA600-LED
operation keyboard RJ45 interface
panel
External LCD External LCD display and CA series general
operation CA600E-LCD
operating keyboard RJ45 interface
panel
External LED2 External LED display and CA series general
operation CA600-LED2
pure key keyboard RJ45 interface
panel When running without a
keyboard or when the
keyboard is externally
Keyboard
CA600KB drawn, using this Optional
gusset
keyboard gusset will have
a good protective and
aesthetic effect.
Standard 8-core network
Available in 4 sizes:
cable, can be connected
Extension cable CA-CAB 1m, 3m, 5m and
with CA600-LED,
10m
CA600-LCD, CA600-LED2
If other function modules are needed to expand functions (such as: I/O card, PG card, EPS card,
etc.), please choose CA600 series expansion board, and specify the function module card when
ordering.
- 26 -
3. Installation
————————————————————————————————
3.1 Mechanical Installation........................................................................................... 28
3.2 Electrical Installation................................................................................................ 31
3.3 Basic wiring diagram............................................................................................... 35
3.4 Control terminals and wiring.................................................................................38
3.5 Main circuit terminals and connection............................................................... 40
3.6 Control circuit terminal and wiring......................................................................43
3.7 Treatment of EMC problem.................................................................................... 48
- 27 -
Chapter 3 Installation
3.1Mechanical Installation
3.1.1Installation Environment
● Environment temperature: Surrounding environment temperature has a great
impact on lifetime of AC drive, and the operation environment temperature of
AC drive shall not exceed allowable temperature range (- 10℃~40℃).
● While AC drive is installed on the surface of inflaming retardants, and
enough space around is necessary for heat dissipation. When AC drive works, it
will produce plenty of heats. And make vertical installation onto supporting
holder with screw.
Chapter 3
● Please install it in some places that are not easy to vibrate. And the vibration
shall not be larger than 0. 6G. Especially pay attention to keep away from
punching machine and other equipments.
● Avoid to be installed where there are direct sunlights, moist surroundings and
water drops.
● Avoid to be installed where there are corrosivity, inflammability and explosive
gas.
● Avoid to be installed where there are oil contamination, dirts and metal
dusts.
- 28 -
Chapter 3 Installation
3.1.3 The installation of the model needs to pay attention to the problem of heat
dissipation. So please note the following:
● Please install the inverter vertically so that the heat can be dissipated
upwards.
But not upside down. If there are many inverters in the cabinet, it is better
to install them side by side. In the occasions that need to be installed up and
down, please refer to Figure 3-1 to install the heat insulation deflector.
● The installation space is as shown in Figure 3-1 to ensure the cooling space
of the inverter. However, please consider the heat dissipation of other
components in the cabinet when arranging.
● The mounting bracket must be made of flame retardant material.
● For applications with metal dust, it is recommended to install the radiator
outside the cabinet. At this time, the space in the fully sealed cabinet should be
as large as possible.
installation
Installation Notes instructions
structure
● Remove the bottom plate of the inverter;
Plastic structure ● Insert the box into the cabinet with holes in
through wall the installation size, and fix it with M4x12 Figure 3-2
screws and M4 nuts;
installation
● Put the bottom plate back into the inverter;
● Install the flange type hanging angle to the
Sheet metal upper and lower parts of the inverter body;
structure through ● Put the inverter into the cabinet with the Figure 3-3
installation holes opened according to the size,
wall installation
and fix it with M6 screws and nuts;
- 29 -
Chapter 3 Installation
Cabine
t Bottom plate
Inverter
M*4 Screw
Flange hook
M*6 Screw
Cabinet
M*6 Screw
Flange hook
CA600 series inverters use plastic casing. For the removal of the terminal cover
of the plastic casing, see Figure 3-4. Use a tool to push the hook of the terminal
cover to the inside and forcefully push it out.
- 30 -
C
Chapter 3 Installation
Cable of
Cable of Control
Output Groundi
MCCB Contactor Input circuit
Models Side Main ng wire
(A) (A) Side Main wire(mm
Circuit (mm²)
Circuit(mm²) ²)
(mm²)
CA600-3SR4GB 10 9 2.5 2.5 1.5 2.5
CA600-3SR75GB 16 12 2.5 2.5 1.5 2.5
CA600-3S1R5GB 25 18 2.5 2.5 1.5 2.5
CA600-3S2R2GB 32 25 2.5 2.5 1.5 2.5
CA600-3S4R0GB 50 40 4 4 1.5 4
CA600-3S5R5GB 80 63 4 4 1.5 4
CA600-4TR75GB 6 9 2.5 2.5 1.5 2.5
CA600-4T1R5GB 10 9 2.5 2.5 1.5 2.5
CA600-4T2R2GB 10 12 2.5 2.5 1.5 2.5
CA600-4T4R0GB 16 16 2.5 2.5 1.5 2.5
CA600-4T5R5GB 20 18 2.5 2.5 1.5 2.5
CA600-4T7R5GB 32 25 4.0 4.0 1.5 4
CA600-4T9R0GB 40 32 4.0 4.0 1.5 6
CA600-4T011GB 40 32 4.0 4.0 1.5 6
CA600-4T015GB 50 40 6.0 6.0 1.5 6
CA600-4T018GB 63 40 10 10 1.5 10
- 31 -
Chapter 3 Installation
Cable of
Cable of Control
Output Groundi
MCCB Contactor Input circuit
Models Side Main ng wire
(A) (A) Side Main wire(mm
Circuit (mm²)
Circuit(mm²) ²)
(mm²)
CA600-4T022GB 80 50 10 10 1.5 16
CA600-4T030G(B) 100 65 16 16 1.5 16
CA600-4T037G(B) 100 80 25 25 1.5 25
CA600-4T045G(B) 125 115 35 35 1.5 25
CA600-4T055G(B) 160 150 50 50 1.5 25
CA600-4T075G(B) 225 170 70 70 1.5 25
CA600-4T093G(B) 250 205 95 95 1.5 25
CA600-4T110G 315 245 120 120 1.5 25
CA600-4T132G 350 300 120 120 1.5 25
CA600-4T160G 400 400 150 150 1.5 25
CA600-4T185G 500 410 185 185 1.5 25
CA600-4T200G 500 410 185 185 1.5 25
CA600-4T220G 630 475 240 240 1.5 25
CA600-4T250G 630 475 2×120 2×120 1.5 25
CA600-4T280G 700 620 2×120 2×120 1.5 25
CA600-4T315G 800 620 2×150 2×150 1.5 35
CA600-4T355G 1000 800 2×185 2×185 1.5 35
CA600-4T400G 1250 800 2×240 2×240 1.5 35
CA600-4T450G 1250 1000 2×240 2×240 1.5 35
CA600-4T500G 1720 1500 3×183 3×183 1.5 35
CA600-4T550G 1900 1500 3×240 3×240 1.5 35
CA600-4T630G 2200 1650 3×240 3×240 1.5 35
CA600-4T710G 2500 1650 3×240 4×185 1.5 35
CA600-4T800G 2800 1800 3×240 4×185 1.5 35
CA600-7T011GB 32 25 4.0 4.0 1.5 6
CA600-7T015GB 40 32 4.0 4.0 1.5 6
CA600-7T018GB 50 40 6.0 6.0 1.5 6
CA600-7T022GB 63 40 10 10 1.5 10
CA600-7T030G(B) 80 50 10 10 1.5 16
CA600-7T037G(B) 100 65 16 16 1.5 16
CA600-7T045G(B) 100 80 25 25 1.5 25
CA600-7T055G(B) 125 115 35 35 1.5 25
- 32 -
Chapter 3 Installation
Cable of
Cable of Control
Output Groundi
MCCB Contactor Input circuit
Models Side Main ng wire
(A) (A) Side Main wire(mm
Circuit (mm²)
Circuit(mm²) ²)
(mm²)
CA600-7T075G(B) 160 150 50 50 1.5 25
CA600-7T093G(B) 225 170 70 70 1.5 25
CA600-7T110G 250 205 95 95 1.5 25
CA600-7T132G 315 245 120 120 1.5 25
CA600-7T160G 350 300 120 120 1.5 25
CA600-7T185G 400 400 150 150 1.5 25
CA600-7T200G 400 400 150 150 1.5 25
CA600-7T220G 500 410 185 185 1.5 25
CA600-7T250G 500 410 185 185 1.5 25
CA600-7T280G 630 475 240 240 1.5 25
CA600-7T315G 630 475 2×120 2×120 1.5 35
CA600-7T355G 700 620 2×120 2×120 1.5 35
CA600-7T400G 800 620 2×150 2×150 1.5 35
CA600-7T450G 800 620 2×150 2×150 1.5 35
CA600-7T500G 1000 800 2×185 2×185 1.5 35
CA600-7T550G 1000 800 2×185 2×185 1.5 35
CA600-7T630G 1250 800 2×240 2×240 1.5 35
CA600-7T710G 1250 800 2×240 2×240 1.5 35
- 33 -
Chapter 3 Installation
- 34 -
Chapter 3 Installation
- 35 -
Chapter 3 Installation
- 36 -
Chapter 3 Installation
- 37 -
Chapter 3 Installation
Note:
The parts above 4KW of the CA600 series are optional functions. If you need it,
please specify when ordering.
Note:
The parts above 4KW of CA600 series are optional functions. If you need it, please
specify when ordering.
- 38 -
Chapter 3 Installation
AO2
+10V AI1 AI2 485+ CME COM Y1 COM TA TB TC
FM
AO2
GND GND AO1 485+ 485- CME COM Y1 COM +24V
FM
GND TEMP AI3 AO2 DI9 DI10 Y2 DI6 DI7 COM GND
- 39 -
Chapter 3 Installation
- 40 -
Chapter 3 Installation
P(+)、(-) DC bus positive and negative terminals Common DC bus input point
- 41 -
Chapter 3 Installation
P(+)、(-) DC bus positive and negative terminals Common DC bus input point
● Confirm power switch stays in the state of OFF and then start wiring
operation or it will give rise to electric shock hazard!
● Wiring personnel must be those professional trainees or it will cause
equipment damages and personal injuries!
● Reliable ground connection is necessary or it will give rise to electric
shock or fire alarm!
● Confirm the input power is in accordance with the rated value of AC
drive, or it will cause damages to AC drive!
● Confirm motor is adaptive with AC drive or it will cause damages to
motor or cause AC drive protection!
● Power supply shall not be connected to the terminals of U, V and W,
or it will cause damages to AC drive!
● Brake resistance shall not be connected directly to DC bus + 2 , - or it
will cause damages to AC drive!
- 42 -
Chapter 3 Installation
At the moment of power failure,DC bus○ + 2,○- terminals still have residual
volta- ge, you just can touch it after internal“charge”power light is off confirming
the voltage is less than 36V, it may cause electric shock.
When you select external brake unit for AC drive ≥30KW, the polarity of○ + 2
fire hazard.
The wiring length of brake unit shall not be more than 10m, and only twisted
pair or tight double-line is available in parallel.
Brake resistance cannot be connected onto DC bus directly, or it may cause
damag- es to AC drive, or even fire hazard.
C.Brake resistance connection terminal (+) and PB:
AC drive ≤22KW and built- in brake unit.
The recommended value of brake resistance model selection reference and
wiring distance shall be less than 5m, or it may cause damages to AC drive.
D.AC drive output side U, V and W:
AC drive output side shall not be connected to capacitor or surge absorber, or
it will frequent protection of AC drive, or even damages.
When the cable of motor is overlong, the effects of distributed capacitance
will generate electric resonance easily, and give rise to dielectric breakdown of
motor.
The generated large leakage current makes AC drive suffer overcurrent
protection. If cable length is more than 100m,alternating current output reactor
shall be installed.
E.Grounding terminal :
Terminals must have been reliable ground connection,and resistance value
ofground wire shall be less than 4Ω ,or it will cause abnormal work of
equipment,and even damages.
Grounding terminal and null line N terminal of power supply cannot be
shared.
- 43 -
Chapter 3 Installation
AO2
+10V AI1 AI2 485+ CME COM Y1 COM TA TB TC
FM
+10V AI1 AI2 DI1 DI2 DI3 DI4 HDI T/A T/B T/C
AO2
GND GND AO1 485+ 485- CME COM Y1 COM +24V
FM
- 44 -
Chapter 3 Installation
- 45 -
Chapter 3 Installation
Normally
TA-TB
closed terminal
Relay Contact drive capability:
output 1 AC250V, 3A, COSφ=0.4. DC30V, 1A
Normally open
TA-TC
terminal
Normally
RA-RB
closed terminal
Relay Contact drive capability:
output 2 AC250V, 3A, COSφ=0.4. DC30V, 1A
Normally open
RA-RC
terminal
Keyboard Control
External
extension board External keyboard interface, can use standard
keyboard
cable RJ45 network cable for external extension.
interface
interface interface
- 46 -
Chapter 3 Installation
- 47 -
Chapter 3 Installation
Figure 3-13 Wiring diagram of digital input terminals in four different modes
- 48 -
Chapter 3 Installation
- 49 -
Chapter 3 Installation
- 50 -
Chapter 3 Installation
- 51 -
4.Operation and Display
————————————————————————————————
4.1 Keypad description................................................................................................... 52
4.2 Organization of Inverter Function Codes...........................................................54
4.3 Function code viewing and modification method description.................. 55
- 52 -
Chapter 4 Operation and Display
Figure 4-1 Operation panel diagram Figure 4-2 Operation panel diagram
(standard configuration LED keyboard ) (standard configuration LCD keyboard )
4.1.2 Function indicator description
Indicator
Name meaning Color
sign
Tuning/Torque
On - torque control
TUNE/TC Control/Fault Red
Flashing - Tuning\Fault status
Indicator
- 53 -
Chapter 4 Operation and Display
5-digit LED display can display the set frequency, output frequency, various
monitoring data and alarm codes. The function code is usually displayed as a
decimal number. For example, the value of the P0-11 function code is displayed
as "50.00", which means the decimal number "50.00". When the function code
value is displayed in hexadecimal, the highest digit of the nixie tube displays "H.",
indicating that the current function code value is displayed in hexadecimal. For
example, the value of the P7-29 function code is displayed as "H. At this time, the
value of P7-29 is the hexadecimal number "0x3f".
The user can freely set the monitoring data of stop and running status
according to function code P7-29/P7-30, see function code P7-29/P7-30 for
details.
4.1.4 Description of keyboard buttons
Program /
Enter or exit the first-level menu, return to the upper-level menu
Escape key
Enter Enter the menu screen step by step, set parameters to confirm
Increment key
Increment of data or function code
(+)
Decrement key
Decrement of data or function code
(-)
In the stop display interface and the running display interface,
the display parameters can be selected cyclically. For the
Shift key specific display meaning, please refer to P7-29 and P7-30;
when modifying the parameters, you can select the
modification bit of the parameter
In the running state, pressing this key can be used to stop the
running operation; in the fault alarm state, it can be used to
Stop/Reset key
reset the operation. The characteristics of this key are restricted
by the function code P7-27.
Jog When P7-28 is set to 0, it is the jog running button, and when
run/Direction P7-28 is set to 1, it is the direction button. Press this button to
keys reverse the direction.
- 54 -
Chapter 4 Operation and Display
Program /
Enter or exit the first-level menu, return to the upper-level menu
Escape key
Enter Enter the menu screen step by step, set parameters to confirm
Increment key
Increment of data or function code
(+)
Decrement key
Decrement of data or function code
(-)
In the running state, pressing this key can be used to stop the
running operation; in the fault alarm state, it can be used to
Stop/Reset key
reset the operation. The characteristics of this key are restricted
by the function code P7-27.
Jog When P7-28 is set to 0, it is the jog running button, and when
run/Direction P7-28 is set to 1, it is the direction button. Press this button to
keys reverse the direction.
Function
Function description Illustrate
code group
Basic function
P0~PF Compatible with KD600 series function codes
parameter group
The second motor parameters, acceleration and
Second motor
A0~A3 deceleration time, control mode, etc. can be set
parameter group independently
System parameter setting, user function code
Enhanced function customization, optimization control, AI/AO correction,
B0~B6
parameter group master-slave control, brake function and sleep
function;
Special plane
Choose to use different professional inverter
C0~CF function selection
group functions;
- 55 -
Chapter 4 Operation and Display
Function
Function description Illustrate
code group
Monitoring U0 is the fault record parameter group, and U1 is the
U0~U1 parameter group user monitoring parameter, which is convenient to
check the relevant output status;
AC drives adopts three-level menu structure for parameter setting and other
operations. The three-level menus respectively are: functional parameter
group( firstlevel menu) → function code ( second- level menu)-function code
setting value (third-level menu). Operational process is shown in Figure 4-2:
Level II menu
(Function code serial Level III menu
(function code value
setting)
number selection)
Note:
When operating in the third-level menu, you can press PRG key or ENTER key
to return to the second-level menu. But pressing the ENTER key will save the
currentparameter modification value and transfer to the next function code; while
pressi- ng the PRG key will abandon the current parameter modification.
Example: Change function code P1-04 from 0.00Hz to 5.00Hz.
- 56 -
Chapter 4 Operation and Display
In the third-level menu state, if the parameter has no flashing bit, it means
that the parameter value of the function code cannot be modified. For the specific
reason, please refer to the description of the function code attribute.
- 57 -
5.Synchronous Motor Open Loop Vector (SVC) Commissioning Instructions
————————————————————————————————
5.1 Set the synchronization type, control method and motor parameters............ 58
5.2 Parameter identification......................................................................................... 58
5.3 No-load test run.........................................................................................................58
5.4 Quick start test run, set it when quick start and stop are required, otherwise skip this step .....59
5.5 Load and run...............................................................................................................59
- 58 -
Chapter 5 Synchronous Motor Open Loop Vector (SVC) Commissioning Instructions
5.1 Set the synchronization type, control method and motor parameters
The motor type is set to synchronous motor and the control mode is SVC, that
is, P0-03=11.
Note:
The ten digit of P0-03 is the motor type selection, and the one digit is the
control
mode;
Tens place: 1: synchronous motor, 0: asynchronous motor;
Ones place: 1: SVC, 2: VF, 3: Closed loop vector (reserved)
Set P4-01~P4-06 according to the actual motor parameters.
Connect the motor, if there is a load, set P4-00 to 1; if it is an empty shaft, set
P4-00 to 2, the digital tube will display TUNE, in order to ensure the control effect,
the motor is best to be no-load and set P4 -00 is 2.
Press the RUN key to perform parameter identification, and wait for TUNE to
disappear, then the parameter identification ends.
The identification process lasts for about 1 minute, and you can press the STOP
button in the middle to exit. During this period, current will be sent, run the motor
at the set acceleration and deceleration time to 60% of the rated frequency of the
motor to observe whether the motor runs smoothly, if not, press STOP to exit,
reach 60% of the rated frequency of the motor, and decelerate to stop after a
period of time.
After parameter identification, check whether the parameters of P4-17~ P4-20
are normal.
- 59 -
Chapter 5 Synchronous Motor Open Loop Vector (SVC) Commissioning Instructions
5.4 Quick start test run, set it when quick start and stop are
required,otherwise skip this step
Reduce the motor acceleration time (for example, set it to 1 second), change
the speed loop and current loop PI parameter settings, and press the run key to
check whether the motor can quickly accelerate to the set frequency.
After the above 5 steps, you can run the motor with load and use the inverter
normally.
Note:
Loading or changing the moment of inertia of the system, if the system
response cannot achieve the expected effect, it is necessary to adjust the two
parameters P3-04 and P3-06 appropriately. If you replace it with another motor,
you generally need to set the rated frequency and rated current of the motor, and
then perform parameter identification.
- 60 -
6.Troubleshooting and Countermeasures
————————————————————————————————
6.1 Fault alarm and countermeasures...................................................................... 61
6.2 Common faults and their solutions..................................................................... 66
6.3 Common faults of synchronous motors and their solutions.......................68
- 61 -
Chapter 6 Troubleshooting and Countermeasures
If a fault occurs during the system operation, the inverter will immediately
protect the motor to stop the output, and the corresponding inverter fault relay
contact will act. The inverter panel displays the fault code. The fault type and
common solution corresponding to the fault code are shown in the following
table. The list in the table is for reference only, please do not repair or modify it
without authorization. If the fault cannot be eliminated, please seek technical
support from our company or the product agent.
Table 9-1 Fault alarm and countermeasures
- 62 -
Chapter 6 Troubleshooting and Countermeasures
- 63 -
Chapter 6 Troubleshooting and Countermeasures
Overvol
t age
during ◆The input voltage is too high ◆Adjust the voltage to the
consta ◆There is an external force normal range
Err10
nt driving the motor to run during ◆Cancel external power or
speed the acceleration process install braking resistor
operati
on
- 64 -
Chapter 6 Troubleshooting and Countermeasures
Short to
ground Err20 ◆Motor short circuit to ground ◆Replace the cable or motor
fault
read and
◆Replace the main control
write Err25 ◆EEPROM chip damaged
board
failure
- 65 -
Chapter 6 Troubleshooting and Countermeasures
PID
feedback ◆PID feedback value is less than ◆Check the feedback signal
Err32
lost at the set value of PA-13 or reset the PA-13
runtime
◆The load is too large or the stall ◆Reduce the load or replace
Fast
occurs the inverter with a higher power
current Err33
◆The set acceleration time is too ◆Properly extend the
limiting
short acceleration time
The
◆The current running time of
running
Err39 the inverter > the set value of ◆Reset
time has
P7-38
arrived
Accumulat
◆Use parameter
ed
◆The accumulated running time initialization function 2 to clear
running Err40
reaches the set value P7-20 the recording time or reset the
time
accumulated running time
reached
Switching
motors ◆Switch the motor through the
Err42 ◆Motor switch after shutdown
during terminals during operation
operation
- 66 -
Chapter 6 Troubleshooting and Countermeasures
Master-sla ◆The master is not set but the ◆Set the host and reset the
ve control slave is set fault
communic Err46 ◆The communication line is ◆Check the communication line
ation abnormal or the communication and communication parameter
dropped parameters are incorrect P8 group
The following fault conditions may be encountered during the use of the
inverter,please refer to the following methods for simple fault analysis.
Table 9-2 Common faults and their solutions
Serial Fault
Possible reason Solution
number phenomenon
- 67 -
Chapter 6 Troubleshooting and Countermeasures
Serial Fault
Possible reason Solution
number phenomenon
- 68 -
Chapter 6 Troubleshooting and Countermeasures
If the motor does not start normally with load, you can try the following
operations:
6.3.2 Adjust the speed loop PI parameters (under normal circumstances do not
need to adjust)
Note:
The inertia of the drive system is equal to the motor inertia plus the load
inertia.
The inertia of the motor is proportional to the mass of the motor and the
square of the diameter of the motor; the inertia of the transmission load is
proportional to the mass of the load and the square of the diameter of the
transmission wheel; if there is a deceleration or speed-up device, the inertia is
proportional to the speed-up ratio and inversely proportional to the deceleration
ratio .
For loads with large inertia, if fast speed response is required, the integration
time needs to be reduced, but it is easy to cause speed overshoot, resulting in
overvoltage of the inverter, and a discharge device is required to discharge. If
there is no discharge device, the integration time can be increased.
6.3.3 Adjust the PI parameters of the current loop (under normal circumstances,
do not need to adjust)
- 70 -
Chapter 6 Troubleshooting and Countermeasures
- 71 -
Chapter 7 Modbus communication protocol
7.1 Agreement
The inverter is connected to the "single master and multiple slave" PC/PLC
control network with RS232/RS485 bus.
- 72 -
Chapter 7 Modbus communication protocol
- 73 -
Chapter 7 Modbus communication protocol
CRC CHK high bits method, please refer to the description of CRC check in this
section.
END 3.5 character time
Function Number of
Frame Slave Read code read CRC check
address command address function Finish
header code 0×03 codes (h) L...H
H...L
H...L
- 74 -
Chapter 7 Modbus communication protocol
- 75 -
Chapter 7 Modbus communication protocol
Note: If the write command is unsuccessful, the failure reason will be returned.
CRC (Cyclical Redundancy Check) uses the RTU frame format, and the
message includes an error detection field based on the CRC method. The CRC field
detects the content of the entire message. The CRC field is two bytes containing a
16-bit binary value. It is calculated by the transmitting device and added to the
message. The receiving device recalculates the CRC of the received message and
compares it with the value in the received CRC field. If the two CRC values a re not
equal, it means that there is an error in the transmission.
The CRC is stored in 0xPFPF first, and then a process is called to process the
consecutive 8-bit bytes in the message with the value in the current register. Only
the 8Bit data in each character is valid for CRC, and the start and stop bits and
parity bits are invalid.In the process of CRC generation, each 8-bit character is
XORed with the contents of the register independently, and the result is moved to
the direction of the least significant bit,and the most significant bit is filled with 0.
The LSB is extracted and detected. If the LSB is 1, the register is individually ORed
with the preset value. If the LSB is 0, it is not performed.The whole process is
repeated 8 times. After the last bit (8th bit) is completed, the next 8-bit byte is
XORed with the current value of the register independently. The value in the final
register is the CRC value after all bytes in the message are executed.When the CRC
is added to the message, the low byte is added first, then the high byte. The CRC
simple function is as follows:
unsigned int crc_chk_value(unsigned char *data_value,unsigned char length){
unsigned int crc_value=0xPFPF;
int I;
while(length--) {
crc_value^=*data_value++;
for(i=0;i<8;i++) {
if(crc_value&0x0001) {
crc_value=(crc_value>>1)^0xa001;
}
else
{
crc_value=crc_value>>1;
}
}
}
return(crc_value);
}
- 76 -
Chapter 7 Modbus communication protocol
U0、U1 0x70xx、0x71xx
Note that, because the EEPROM is frequently stored, the service life of the
EEPROM will be reduced. Therefore, some function codes do not need to be stored
in the communication mode, just change the value in the RAM.
If it is a parameter of group P, to realize this function, it can be realized only
by changing the high-order F of the function code address to 0.
If it is a group A parameter, to realize this function, just change the
high-order A of the function code address to 4 to realize it.
The corresponding function code addresses are expressed as follows: high
- 77 -
Chapter 7 Modbus communication protocol
- 78 -
Chapter 7 Modbus communication protocol
Example 1: Read the operating frequency of the first device: 0x01 0x03 0x10 0x02
0x00 0x01 0x21 0x0A
0x10 0x02 (1002) operating frequency address, 0x00 0x01 (0001) a data
0x21 0x0A (210A) CRC check value
Example 2: Read the bus voltage, output voltage and output current of the first
device at the same time: 0x01 0x03 0x10 0x03 0x00 0x03 CRC check value, the
meaning of the data is similar to that of example 1.
Note: The communication setting value is a percentage of the relative value,
10000 corresponds to 100.00%, -10000 corresponds to -100.00%.
For frequency dimension data, the percentage is relative to the maximum
frequency (P0-14); for torque dimension data, the percentage is P3-21, P3-23,
A3-21, A3-23.
Note: D0 output terminal needs to select 16 (communication control) function.
AO output needs to select 7 (communication control output) function.
- 79 -
Chapter 7 Modbus communication protocol
Command
Type Command content
address
Digital output terminal BIT0: RELAY1 output control BIT1: DO1 output
0x2001
control (write only) control BIT2: RELAY2 output control
0000: No fault
0001: Reserved
0002: Reserved
0003: Reserved
0004: Acceleration overcurrent
0005: Deceleration overcurrent 0006:
Constant speed overcurrent 0007: Stop
overcurrent
0008: Acceleration overvoltage
0009: Deceleration overvoltage 000A:
Inverter fault address 0x8000
Constant speed overvoltage 000B: Stop
overvoltage
000C: Undervoltage fault 000D: Inverter
overload 000E: Motor overload 000F: Module
overheat 0010: Reserved
0011: Current detection fault 0012: Reserved
0013: Reserved
0014: Motor short circuit fault to ground 0015:
Motor tuning fault
0016: Reserved
- 80 -
Chapter 7 Modbus communication protocol
The return address when communication fails: read fault 83XX, write fault 86X. Chapter 10
- 81 -
8. Function & Parameter Table
————————————————————————————————
8.1 Functional group....................................................................................................... 82
- 82 -
Chapter 8 Function & Parameter Table
Indicates that the inverter parameters can be modified during stop and
☆
running (0)
★ Indicates that the inverter is in a running state and cannot be modified (1)
- 83 -
Chapter 8 Function & Parameter Table
0: Up/Down modification
frequency, no memory after
shutdown
1: Up/Down modification
frequency power-off
memory
2: AI1
Main
3: AI2
frequency
P0-06 4: Multi-speed 1 ★ F006
source X
5: Simple PLC
selection
6: PID
7: Communication given 8:
PULSE pulse setting
9: Up/Down modifies the
frequency, and the memory
is stopped when the power is
turned off.
0: Up/Down modification
frequency, no memory after
shutdown
1: Up/Down modification
frequency power-off
memory
2: AI1
Auxiliary
3: AI2
frequency
P0-07 4: Multi-speed 0 ★ F007
source Y
5: Simple PLC
selection
6: PID
7: Communication given 8:
PULSE pulse setting
9: Up/Down modifies the
frequency, and the memory
is stopped when the power is
turned off.
- 84 -
Chapter 8 Function & Parameter Table
- 85 -
Chapter 8 Function & Parameter Table
Communic
Function Factory
Name Description (setting range) Change ation
code Default
Address
Upper limit Lower limit frequency P0-18~
P0-16 50.00Hz ☆ F010
frequency maximum frequency P0-14
Upper limit
0.00~Maximum frequency
P0-17 frequency 0.00Hz ☆ F011
P0-14
offset
Lower 0.00Hz~upper limit frequency
P0-18 0.00Hz ☆ F012
frequency P0-16
Frequency
1: 1 decimal point
P0-20 Decimal 2 ★ F014
2: 2 decimal places
Selection
Acceleration
0: 1 second
and
P0-21 1: 0.1 seconds 1 ★ F015
deceleration
2: 0.01 seconds
time unit
Acceleration
0: Maximum frequency
and
(P0-14) 1: Preset frequency
deceleration
P0-22 (P0-11) 0 ★ F016
time
2: Motor rated frequency
reference
(P4-05 or A1- 05)
frequency
0s~30000s(P0-21=0)
Acceleration
P0-23 0.0s~3000.0s(P0-21=1) 10.0s ☆ F017
time 1
0.00s~300.00s(P0-21=2)
0s~30000s(P0-21=0)
P0-24 Deceleration 0.0s~3000.0s(P0-21=1) 10.0s ☆ F018
time 1 0.00s~300.00s(P0-21=2)
- 86 -
Chapter 8 Function & Parameter Table
Communica
Function Description (setting Factory Chang
Name tion
code range) Default e
Address
Overmodulatio
P0-25 n voltage boost 0%~10% 3% ★ F019
value
Carrier Model is
P0-26 0.5kHz~16.0kHz determine ☆ F01A
frequency
d
The carrier
frequency is 0: Invalid;
P0-27 1 ☆ F01B
adjusted with 1: Valid;
temperature
0: No operation
1: Restore factory
parameters, excluding
motor parameters,
record information
and frequency decimal
Parameter
P0-28 point P0-20 0 ★ F01C
initialization
2: Clear record
information
3: Backup current user
parameters
4: Restore user backup
parameters
0: direct start
1: Speed Tracking
P1-00 Start method 2: Asynchronous 0 ☆ F100
motor pre- excitation
start
0: start from stop
frequency
Speed tracking 1: Start with target
P1-01 0 ★ F101
method frequency
2: start from maximum
frequency
Maximum
P1-02 speed tracking 30%~150% 100% ★ F102
current
Speed tracking
P1-03 1~100 20 ☆ F103
speed
P1-04 Start frequency 0.00Hz~10.00Hz 0.00Hz ☆ F104
Start frequency
P1-05 0.0s~100.0s 0.0s ★ F105
hold time
Start DC braking
P1-06 0%~100% 0% ★ F106
current
- 87 -
Chapter 8 Function & Parameter Table
- 88 -
Chapter 8 Function & Parameter Table
Communi
Functio Description (setting Factory Chang
Name cation
n code range) Default e
Address
Instantaneous stop
and non- stop
P1-29 automatic 1~100 20 ☆ F110D
adjustment
of integral
Group P2: V/F control parameters
0: Straight line VF
curve
1: Multi-point VF
curve
2: Square VF curve
3: 1.7th power
P2-00 V/F curve setting curve 0 ★ F200
4: 1.5 power curve
5: 1.3 power curve
6: VF full
separation mode
7: V/F half
separation mode
P2-01 Torque boost 0.0%~30.0% 0.0% ☆ F201
Torque boost 0.00Hz~Maximum
P2-02 25.00Hz ★ F202
cut-off frequency frequency
V/F frequency
P2-03 0.00Hz~P2-05 1.30Hz ★ F203
point P1
V/F voltage point
P2-04 0.0%~100.0% 5.2% ★ F204
V1
V/F frequency
P2-05 P2-03~P2-07 2.50Hz ★ F205
point P2
V/F voltage point
P2-06 0.0%~100.0% 8.8% ★ F206
V2
V/F frequency P2-05~Motor rated
P2-07 15.00Hz ★ F207
point P3 frequency
V/F voltage point
P2-08 0.0%~100.0% 35.0% ★ F208
V3
Slip Compensation
P2-09 0.0%~200.0% 50.0% ☆ F209
Coefficient
P2-10 Flux Brake Gain 0~200 100 ☆ F20A
Oscillation Model is
P2-11 0~100 determine ☆ F20B
suppression gain
d
VF slip
P2-13 compensation time 0.02s~1.00s 0.30s ☆ F20D
constant
0: Digital setting
(P2-14)
Output voltage 1: AI1
source selection 2: AI2
P2-15 3: Multi-segment 0 ☆ F20F
when VF is
separated instruction
4: Simple PLC
5: PID
- 89 -
Chapter 8 Function & Parameter Table
Factor Communic
Functio Description (setting Chang
Name y ation
n code range) e
Default Address
6: Communication
given
Output voltage 7: PULSE pulse
P2-15 source selection setting (Di5) 100.0% 0 ☆ F20F
when VF is separated corresponds to the
rated voltage of the
motor
V/F separation
0V~Motor rated
P2-16 output voltage digital 0V ☆ F210
voltage
setting
V/F separation
P2-17 output voltage 0.0~3000.0s 1.0s ☆ F211
acceleration time
V/F separation
P2-18 output voltage 0.0~3000.0s 1.0s ☆ F212
deceleration time
0: Frequency and
output voltage
deceleration time are
V/F separation and independent
P2-19 0 ☆ F213
stop mode selection 1: After the voltage is
reduced to 0, the
frequency is reduced
again
Group P3: Vector control parameters
Switching frequency
P3-00 0.00~P3-02 5.00 Hz ☆ F300
P1
Switching frequency 10.00
P3-02 P3-00~P0-14 ☆ F302
P2 Hz
Low frequency speed
P3-04 0.1~10.0 4.0 ☆ F304
proportional gain
Low frequency speed
P3-05 0.01s~10.00s 0.50s ☆ F305
integration time
High frequency speed
P3-06 0.1~10.0 2.0 ☆ F306
proportional gain
High frequency speed
P3-07 0.01~10.00s 1.00s ☆ F307
integration time
Speed loop integral 0: Points take effect
P3-08 0 ★ F308
attribute selection 1: Integral separation
Torque current
P3-11 0~30000 2200 ☆ F30B
regulator Kp
Torque current
P3-12 0~30000 1500 ☆ F30C
regulator Ki
Excitation current
P3-13 0~30000 2200 ☆ F30D
regulator Kp
Excitation current
P3-14 0~30000 1500 ☆ F30E
regulator Ki
P3-15 Flux Brake Gain 0~200 0 ☆ F30F
- 90 -
Chapter 8 Function & Parameter Table
Factor Communica
Functio Description (setting Chang
Name y tion
n code range) e
Default Address
Field weakening
P3-16 torque correction 50%~200% 100% ☆ F310
factor
P3-17 Slip compensation 50%~200% 100% ☆
gain F311
Speed loop feedback
P3-18 0.000~1.000s 0.015s ☆ F312
filter time constant
Speed loop output
P3-19 0.000~1.000s 0.000s ☆ F313
filter time constant
0: P3-21
1: AI1
2: AI2
3: Communication
Electric torque upper
P3-20 given 0 ☆ F314
limit source
4: PLUSE given (The
analog range
corresponds to
P3-21)
Electric torque upper
P3-21 0.0%~200.0% 150.0% ☆ F315
limit
0: P3-23
1: AI1
2: AI2
3: Communication
Braking torque upper
P3-22 given 0 ☆ F316
limit source
4: PLUSE given (The
analog range
corresponds to
P3-23)
Braking torque upper
P3-23 0.0~200.0% 150.0% ☆ F317
limit
Low-speed
P3-24 magnetizing current 0.0%~50.0% 25.0% ★ F318
of synchronous motor
Magnetizing cut-off
P3-25 frequency of 0%~100% 10% ★ F319
synchronous motor
P3-26 Pre-excitation time 0s~5s 0.1s ★ F31A
0: Disable
Synchronous motor
1: Identification
initial position
P3-27 method one 1 ★ F31B
identification enable
2: Identification
selection
method 2
Initial position
P3-28 identification voltage 30%~130% 80% ★ F31C
given percentage
Group P4: First motor parameter
0: no function
Motor parameter
P4-00 1: Static tuning 0 ★ F400
tuning
2: Rotary tuning
- 91 -
Chapter 8 Function & Parameter Table
Model is
P4-01 Motor 1 rated power 0.1kw~1000.0kw ★ F401
determined
Motor 1 rated
P4-02 1V~1500V 380V ★ F402
voltage
Motor 1 Number of Model is
P4-03 2 to 64 ○ F403
motor poles determined
0.01A~
600.00A(Motor
rated
Motor 1 rated power<=30.0KW)
P4-04 P4-01 OK ★ F404
current 0.1A~
6000.0A(Motor
rated
power>30.0KW)
P4-05 Motor 1 rated 0.01Hz~P0-14 50.00 Hz ★
frequency F405
P4-06 Motor 1 rated speed 0rpm~60000rpm P4-01 OK ★ F406
0.01A~P4-04
(Motor rated
Motor 1 no-load power<=30.0KW) Model is
P4-07 ★ F407
current 0.1A~P4-04 determined
(Motor rated
power>30.0KW)
Motor 1 stator Model is
P4-08 0.001Ω~65.535Ω ★ F408
resistance determined
Motor 1 rotor Model is
P4-09 0.001Ω~65.535Ω ★ F409
resistance determined
Motor 1 mutual Model is
P4-10 0.1Mh~6553.5Mh ★ F40A
inductance determined
Motor 1 leakage Model is
P4-11 0.01Mh~655.35Mh ★ F40B
inductance determined
Acceleration at
P4-12 1.0s~6000.0s 10.0s ☆ F40C
Dynamic Full Tuning
Deceleration at
P4-13 1.0s~6000.0s 10.0s ☆ F40D
dynamic full tuning
Synchronous motor Model is
P4-17 0.001Ω~65.535Ω ★ F411
stator resistance determined
Synchronous motor Model is
P4-18 0.01Mh~655.35Mh ★ F412
D-axis inductance determined
Synchronous motor Model is
P4-19 0.01Mh~655.35Mh ★ F413
Q-axis inductance determined
Synchronous motor Model is
P4-20 1V~65535V ★ F414
back EMF determined
No-load current of
P4-21 0.0%~50.0% 10.0% ★ F415
synchronous motor
- 92 -
Chapter 8 Function & Parameter Table
Factor Communic
Functio Chang
Name Description (setting range) y ation
n code e
Default Address
Group P5: Input terminal
DI1
termina
P5-00 1 ★ F500
l
function
0: No function
1: Forward rotation (FWD) 2:
Reverse operation (REV)
3: Three-wire running control 4:
DI2
Forward jog (FJOG)
termina
P5-01 5: Reverse Jog (RJOG) 6: Terminal 2 ★ F501
l
UP
function
7: Terminal DOWN
8: Free parking
9: Fault reset (RESET) 10: run pause
11: External fault normally open
DI3 input 12: Multi-segment command
termina terminal 1
P5-02 13: Multi-segment command 9 ★ F502
l
function terminal 2
14: Multi-segment command
terminal 3
15: Multi-segment command
terminal 4
DI4 16: Acceleration and deceleration
termina selection terminal 1
P5-03 12 ★ F503
l 17: Acceleration and deceleration
function selection terminal 2
18: Frequency source switching
19: UP/DOWN setting clear
(terminal, keyboard) 20: Running
command switching terminal
DI5 21: Acceleration and deceleration
termina prohibition 22: PID invalid
P5-04 13 ★ F504
l (pause)
function 23: PLC status reset
24: Swing frequency pause 25:
Timing trigger input
26: Immediate DC braking
DI6 27: External fault normally closed
termina input 28: Counter input
P5-05 29: Counter reset F505
l
function 30: Length count input 31: Length
count reset
32: Torque control prohibited
33: PULSE (pulse) frequency input
34: Frequency modification 0 ★
prohibited
35: PID action direction is reversed
DI7 36: External parking terminal 1
termina
P5-06 F506
l
function
- 93 -
Chapter 8 Function & Parameter Table
Communic
Function Factory Chang
Name Description (setting range) ation
code Default e
Address
DI
P5-10 terminal 0.000~1.000s 0.010s ☆ F50A
filter time
0: Two-wire type 1
Terminal
1: Two-wire type 2
P5-11 command 0 ★ F50B
2: Three-wire type 1
method
3: Three-wire type 2
Terminal
UP/
1.00Hz/
P5-12 DOWN 0.01Hz/s~100.00Hz/s ☆ F50C
s
change
rate
0: High level
1: low level
Terminal Ones place: DI1;
P5-13 valid logic Tens place: DI2; 00000 ★ F50D
1 Hundreds: DI3;
Thousands: DI4;
Ten thousand: DI5
- 94 -
Chapter 8 Function & Parameter Table
- 95 -
Chapter 8 Function & Parameter Table
Factor Communic
Functio Chang
Name Description (setting range) y ation
n code e
Default Address
DI3 turn-on
P5-39 0.0s~3600.0s 0.0s ☆ F527
delay time
DI3 off delay
P5-40 0.0s~3600.0s 0.0s ☆ F528
time
AI1 is
selected as 0~53, the function is the same as
P5-41 0 ★ F529
DI terminal the common DI terminal
function
AI2 is
selected as 0~53, the function is the same as
P5-42 0 ★ F52A
the common DI terminal
DI terminal
function
Valid mode
Ones place, AI1: 0: Active high,
selection
1: Active low Ten, AI2:
P5-44 when AI is 0x00 ☆ F52C
0: Active high,
used as DI
1: Active low Hundreds: reserved
terminal
Factor Communica
Function Description (setting Chang
Name y tion
code range) e
Default Address
0: Running frequency
1: set frequency
2: Output current (100%
corresponds to twice
AO1 output the rated current of the
P6-09 motor) 0 ☆ F609
selection
3: Output power (100%
corresponds to twice
the rated power of the
motor)
4: Output voltage
(100% corresponds to
1.2 times the rated
voltage of the inverter)
5: Analog AI1 input
value
6: Analog AI2 input
value 7:
AO2 output
P6-10 Communication 0 ☆ F60A
selection
settings
8: Output torque
9: length
10: count value
11: Motor speed
12: Bus voltage (0 to 3
times the rated voltage
of the inverter)
13: Pulse input
14: Output current
(100% corresponds to
1000.0A) 15: Output
FMP output voltage (100.0%
P6-11 0 ☆ F60B
selection corresponds to
1000.0V) 16: Output
torque (actual
torque value - 2 times
rated to 2 times rated)
FMP output
P6-12 maximum 0.01KHz~100.00KHz 50.00 ☆ F60C
frequency
AO1 output lower
P6-13 -100.0%~P6-15 0.0% ☆ F60D
limit
The lower limit
P6-14 corresponds to AO1 0.00V~10.00V 0.00V ☆ F60E
output
AO1 output upper
P6-15 P6-13~100.0% 100.0% ☆ F60F
limit
- 97 -
Chapter 8 Function & Parameter Table
Communica
Functio Description (setting Factory
Name Change tion
n code range) Default
Address
The upper limit
P6-16 corresponds to AO1 0.00~10.00V 10.00V ☆ F610
output
P6-17 AO2 output lower -100.0%~P6-19 0.0% ☆
limit F611
The lower limit
P6-18 corresponds to the 0.00V~10.00V 0.00V ☆ F612
AO2 output
P6-19 Ao2 output upper P6-17~100.0% 100.0% ☆
limit F613
The upper limit
P6-20 corresponds to AO2 0.00~10.00V 10.00V ☆ F614
output
Main relay T pick-up
P6-21 0.0s~3600.0s 0.0s ☆ F615
delay
Main relay R pick-up
P6-22 0.0s~3600.0s 0.0s ☆ F616
delay
Y1 high level output
P6-23 0.0s~3600.0s 0.0s ☆ F617
delay
P6-26 Main relay T off delay 0.0s~3600.0s 0.0s ☆ F61A
Main relay R off
P6-27 0.0s~3600.0s 0.0s ☆ F61B
delay
Y1 low level output
P6-28 0.0s~3600.0s 0.0s ☆ F61C
delay
Y2 low level output
P6-29 0.0~3600.0S 0.0s ☆ F61D
delay
Group P7: Accessibility and keyboard display
Jog running 0.00Hz~Maximum
P7-00 6.00Hz ☆ F700
frequency frequency
P7-01 Jog acceleration time 0.0s~3000.0s 10.0s ☆ F701
P7-02 Jog deceleration time 0.0s~3000.0s 10.0s ☆ F702
P7-03 Acceleration time 2 0.0s~3000.0s 10.0s ☆ F703
P7-04 Deceleration time 2 0.0s~3000.0s 10.0s ☆ F704
P7-05 Acceleration time 3 0.0s~3000.0s 10.0s ☆ F705
P7-06 Deceleration time 3 0.0s~3000.0s 10.0s ☆ F706
P7-07 Acceleration time 4 0.0s~3000.0s 10.0s ☆ F707
P7-08 Deceleration time 4 0.0s~3000.0s 10.0s ☆ F708
P7-09 Hop Frequency 1 0.00Hz~Maximum 0.00Hz ☆
frequency F709
P7-10 Hop Frequency 1 0.00Hz~Maximum 0.00Hz ☆
Amplitude frequency F70A
0.00Hz~Maximum
P7-11 Hop Frequency 2 0.00Hz ☆ F70B
frequency
Hop Frequency 2 0.00Hz~Maximum
P7-12 0.00Hz ☆ F70C
Amplitude frequency
Forward and reverse
P7-15 0.0s~3000.0s 0.0s ☆ F70F
dead time
- 98 -
Chapter 8 Function & Parameter Table
Communica
Function Description (setting Factory
Name Change tion
code range) Default
Address
0: default mode
1: 0.1Hz
2: 0.5Hz
3: 1Hz
4: 2Hz
Keyboard Knob
P7-16 5: 4Hz 2 ☆ F710
Accuracy
6: 5Hz
7: 8Hz
8: 10Hz
9:0.01Hz
10:0.05Hz
Set cumulative
P7-20 0h~65000h 0h ☆ F714
operating time
0: invalid
1: Jog priority mode
1
2: Jog priority mode
2
P7-21 Jog priority 1 ☆ F715
When the user fails
or the PID is lost, the
jog is still valid
Stop mode and DC
braking can be set
Frequency detection 0.00Hz~Maximum
P7-22 50.00Hz ☆ F716
value (PDT1 level) frequency
Frequency check
P7-23 hysteresis value 0.0%~100.0% 5.0% ☆ F717
(PDT1 hysteresis)
Frequency arrival
P7-24 0.0%~100.0% 0.0% ☆ F718
detection width
- 99 -
Chapter 8 Function & Parameter Table
Factor Communica
Function Chang
Name Description (setting range) y tion
code e
Default Address
0: Forward jog
1: Forward and reverse
Quick /JOG
switching
P7-28 key function 0 ★ F71C
2: Reverse jog
selection
3: Switch between panel and
remote control
0000~0xPFPF (hexadecimal
number) 0000 to 0xPFPF
Bit00: Running frequency 0001
Bit01: Set frequency 0002
Bit02: Bus voltage 0004
Bit03: Output voltage 0008
Bit04: Output current 0010
Bit05: Output power 0020
LED running Bit06: DI input status 0040
P7-29 H.441F ☆ F71D
display Bit07: DO output status 0080
Bit08: AI1 voltage 0100
Bit09: AI2 voltage 0200
Bit10: PID setting value 0400
Bit11: PID feedback value 0800
Bit12: Count value 1000
Bit13: Length value 2000
Bit14: Load speed display 4000
Bit15: PLC stage 8000
1~0x1PPF (hexadecimal
number) Bit00: Set frequency
0001
Bit01: Bus voltage 0002
Bit02: DI input status 0004
Bit03: DO output status 0008
Bit04: AI1 voltage 0010
LED stop Bit05: AI2 voltage 0020
P7-30 H.0043 ☆ F71E
display Bit06: PID setting value 0040
Bit07: PID feedback value 0080
Bit08: Count value 0100
Bit09: Length value 0200
Bit10: Load speed display 0400
Bit11: PLC stage 0800
Bit12: Input pulse frequency
1000 Bit13~Bit15: Reserved
- 100 -
Chapter 8 Function & Parameter Table
Communica
Function Description (setting Factory Chang
Name tion
code range) Default e
Address
Load speed
0.001~655.00 1.000 ☆ F71F
P7-31 display factor
Radiator Measure
P7-32 12℃~100℃ ● F720
temperature d value
Cumulative Measure
P7-33 0h~65535h ● F721
power-on time d value
Cumulative Measure
P7-34 0h~65535h ● F722
running time d value
0: Disable
Current 1: Enable, When the time
running timing is up, a fault is reported
P7-36 0 ★ F724
enable 2: Enable, When the time
selection is up, a fault is not
reported
Selection of 0: Digital setting P7-38
timing source 1: AI1
P7-37 0 ★ F725
for the current 2: AI2 (AI takes P7-38 as
run 100%)
Current
P7-38 running time 0.0min~6500.0min 0.0min ☆ F726
set value
High level
P7-39 0.0s~6000.0s 2.0s ☆ F727
timing
low level
P7-40 0.0s~6000.0s 2.0s ☆ F728
timing
0: Invalid (start terminal
Activate the
command is valid and
P7-41 protection 1 ☆ F729
start directly)
function
1: Valid
Frequency
reaches
P7-43 0.00Hz~P0-14 50.00Hz ☆ F72B
detection
value 1
Frequency
detection
P7-44 0.0%~100.0% 0.0% ☆ F72C
value 1 arrival
width
Current
reaches
P7-45 0.0%~300.0% 100.0% ☆ F72D
detection
value 1
Current
detection
P7-46 0.0%~300.0% 0.0% ☆ F72E
value 1 arrival
width
- 101 -
Chapter 8 Function & Parameter Table
Communic
Function Description (setting Factory Chang
Name ation
code range) Default e
Address
Whether the
jump frequency
0: invalid
P7-50 is valid during 0 ☆ F732
1: Valid
acceleration and
deceleration
Set the power-on
P7-51 0h~65530h 0h ☆ F733
arrival time
Acceleration time
0.00Hz~Maximum
P7-53 1/2 switching 0.00Hz ☆ F735
frequency (P0-14)
frequency point
Deceleration time
0.00Hz~Maximum
P7-54 1/2 switching 0.00Hz ☆ F736
frequency (P0-14)
frequency point
Frequency
0.00Hz~Maximum 50.00H
P7-55 detection value ☆ F737
frequency (P0-14) z
(PDT2 level)
Frequency
P7-56 detection PDT2 0.0%~100.0% 5.0% ☆ F738
hysteresis value
Frequency
0.00Hz~Maximum 50.00H
P7-57 reaches ☆ F739
frequency (P0-14) z
detection value 2
Frequency arrival
P7-58 detection 2 0.0%~100.0% 0.0% ☆ F73A
amplitude
Zero current
P7-59 0.0%~300.0% 10.0% ☆ F73B
detection value
Zero current
P7-60 detection delay 0.01s~300.00s 1.00s ☆ F73C
time
Output current
P7-61 amplitude 20.0%~400.0% 200.0% ☆ F73D
detection
Software
P7-62 overcurrent 0s~6500.0s 0s ☆ F73E
maximum
allowable time
Current reaches
P7-63 20.0%~300.0% 100.0% ☆ F73F
detection value 2
Current arrival
P7-64 detection 2 0.0%~300.0% 0.0% ☆ F740
amplitude
0x0~0x1PF
Bit00: Target torque%
0001 Bit01: Output
torque% 0002 Bit02:
LED running Pulse input pulse
P7-65 display frequency (KHz) 0004 H.010 ☆ F741
parameter 2 Bit03: DI5 high-speed
pulse sampling linear
speed (m/min) 0008
Bit04: Motor speed (rmp)
0010
- 102 -
Chapter 8 Function & Parameter Table
0: 300BPS
1: 600BPS
P8-00 Baud rate setting 2 ☆ F800
2: 1200BPS
3: 2400BPS
- 103 -
Chapter 8 Function & Parameter Table
Factor Communic
Functio Name Description (setting range) y Change ation
n code Default Address
4: 4800BPS
Baud rate 5: 9600BPS
P8-00 2 ☆ F800
setting 6: 19200BPS
7: 38400BPS
0: No parity <8,N,2>
1: Even parity <8,E,1>
P8-01 Data Format 0 ☆ F801
2: odd parity <8,O,1>
3: No parity 1<8,N,1>
- 104 -
Chapter 8 Function & Parameter Table
Overvoltage
suppression
P9-20 1.0%~150.0% 10.00% ★ F914
mode 2 limit
value
- 105 -
Chapter 8 Function & Parameter Table
Communic
Function Factory
Name Description (setting range) Change ation
code Default
Address
0~22202;
Units place: Motor overload -
Err14 0: Free parking
1: stop according to the stop
Fault mode 2: keep running
P9-22 protectio Ten: reserved 00000 ☆ F916
n action 1 Hundreds place: input phase
loss-Err23 Thousands place:
output phase loss-Err24 Ten
thousand: parameter read and
write exception - Err25
0~22222;
Ones place: Communication
failure - Err27 0: Free parking
1: stop according to the stop
mode 2: keep running
Fault
Tens place: External fault -
P9-23 protectio 00000 ☆ F917
Err28
n action 2
Hundreds place: excessive speed
deviation fault - Err29
Thousands: User-defined fault
1-Err30 Ten thousand:
user-defined fault 2-Err31
0~22222;
Ones place: PID feedback lost
during runtime - Err32
0: Free parking
1: stop according to the stop
mode 2: keep running
Fault
Tens place: load loss fault - Err34
P9-24 protectio 00000 ☆ F918
Hundreds place: software
n action 3
overcurrent - Err16
Thousands place: The current
continuous running time reaches
-Err39
Ten thousand: the running time
reaches - Err40
- 106 -
Chapter 8 Function & Parameter Table
Factor Communica
Function Description (setting
Name y Change tion
code range)
Default Address
Abnormal standby
P9-27 0.0%~100.0% 100% ☆ F91B
frequency set value
Drop load 0: invalid
P9-28 0 ☆ F91C
protection option 1: Valid
0:No temperature
Temperature
sensor
P9-38 sensor type 0 ☆ F926
1:PT100
selection
2:PT1000
0: Keypad (F10.01)
1: Analog AI1
2: Analog AI2
3: Analog AI3
PA-00 PID setting source 4: Pulse setting (HDI) 0 ☆ FA00
5: Rs485
communication setting
6: Multi-speed
command
- 107 -
Chapter 8 Function & Parameter Table
0: AI1
1: AI2
2: AI1-AI2
3: Communication
PID feedback
PA-03 given 0 ☆ FA03
source
4: PULSE given
5: AI1+AI2
6: MAX(|AI1|, |AI2|)
7: MIN(|AI1|, |AI2|)
0: Forward action
PA-04 PID action direction 0 ☆ FA04
1: Reverse action
- 108 -
Chapter 8 Function & Parameter Table
PID parameter
PA-23 switching deviation PA-22~100.0% 80.0% ☆ FA17
2
PA-24 PID initial value 0.0%~100.0% 0.0% ☆ FA18
PA-25 PID initial value 0.00s~650.00s 0.00s ☆
hold time FA19
Twice output
PA-26 deviation positive 0.00%~100.00% 1.00% ☆ FA1A
maximum value
Twice output
PA-27 deviation reverse 0.00%~100.00% 1.00% ☆ FA1B
maximum value
Units: Integral
PID integral
PA-28 separation 0: invalid; 00 ☆ FA1C
properties
1: Valid
0: Relative to the
central frequency
Pb-00 Swing setting method 0 ☆ FB00
1: Relative to the
maximum frequency
Swing frequency
Pb-01 0.0%~100.0% 0.0% ☆ FB01
amplitude
Jump frequency
Pb-02 0.0%~50.0% 0.0% ☆ FB02
amplitude
Pb-03 Swing frequency cycle 0.1s~3000.0s 10.0s ☆ FB03
Triangular wave
Pb-04 0.1%~100.0% 50.0% ☆ FB04
rising time coefficient
- 109 -
Chapter 8 Function & Parameter Table
Communica
Function Description Factory
Name Change tion
code (setting range) Default
Address
PC-08 Multi-speed 8 -100.0%~100.0% 0.0% ☆ FC08
- 110 -
Chapter 8 Function & Parameter Table
Acceleration/deceleration
PC-19 time of simple PLC multi- 0~3 0 ☆ FC13
speed 0
Acceleration/deceleration
PC-21 time of simple PLC multi- 0~3 0 ☆ FC15
speed 1
Acceleration/deceleration
PC-25 time of simple PLC multi- 0~3 FC19
0 ☆
speed 3
Acceleration/deceleration
PC-27 time of simple PLC multi- 0~3 0 ☆ FC1B
speed 4
Acceleration/deceleration
PC-29 time of simple PLC multi- 0~3 0 ☆ FC1D
speed 5
Acceleration/deceleration
PC-31 time of simple PLC multi- 0~3 0 ☆ FC1F
speed 6
- 111 -
Chapter 8 Function & Parameter Table
Acceleration/deceleration
PC-33 time of simple PLC multi- 0~3 0 ☆ FC21
speed 7
Acceleration/deceleration
PC-35 time of simple PLC multi- 0~3 0 ☆ FC23
speed 8
Acceleration/deceleration
PC-39 time of simple PLC multi- 0~3 0 ☆ FC27
speed 10
Acceleration/deceleration
PC-41 time of simple PLC multi- 0~3 0 ☆ FC29
speed 11
Acceleration/deceleration
PC-43 time of simple PLC multi- 0~3 0 ☆ FC2B
speed 12
Acceleration/deceleration
PC-44 time of simple PLC multi- 0~3 0 ☆ FC2C
speed 13
- 112 -
Chapter 8 Function & Parameter Table
Acceleration/deceleration
PC-46 time of simple PLC multi- 0~3 0 ☆ FC2E
speed 14
Acceleration/deceleration
PC-48 time of simple PLC multi- 0~3 0 ☆ FC30
speed 15
0: s (second) 1:h
PC-50 Time unit of multi-speed 0 ☆ FC32
(hour)
0: Acceleration and
deceleration time 1
Multi-speed priority 1: Acceleration and
acceleration and deceleration time 2
PC-52 0 ☆ FC34
deceleration time 2: Acceleration and
selection deceleration time 3
3: Acceleration and
deceleration time 4
Multi-speed PC-00~ 0: %
PC-53 0 ☆ FC35
PC-15 unit selection 1: Hz
0: Function code
PC-00 given
1: AI1
2: AI2
Multi-segment
3: PULSE pulse FC37
PC-55 instruction 0 given 0 ☆
4: PID
mode
5: Preset frequency
given (P0-11),
UP/DOWN can be
modified
- 113 -
Chapter 8 Function & Parameter Table
0: Digital setting
(PD-01) 1: AI1
2: AI2
3: Communication
given
Torque command 4: PULSE pulse
PD-00 0 ★ FD00
source selection frequency setting
5: MIN (AI1, AI2)
6: MAX (AI1, AI2)
(1-6 option full scale
corresponds to
PD-01)
- 114 -
Chapter 8 Function & Parameter Table
Curve 1 maximum
PE-07 input corresponding -100.0%~100.0% 100.0% ☆ FE07
setting
PE-08 Curve 2 minimum -10.00~PE-10 0.00V ☆
input FE08
Curve 2 minimum
PE-09 input corresponding -100.0%~100.0% 0.0% ☆ FE09
setting
PE-10 Curve 2 Knee 1 Input PE-08~PE-12 3.00V ☆ FE0A
Curve 2 inflection
PE-11 point 1 input -100.0%~100.0% 30.0% ☆ FE0B
corresponding setting
PE-12 Curve 2 Knee 2 Input PE-10~PE-14 6.00V ☆ FE0C
Curve 2 inflection
PE-13 point 2 input -100.0%~100.0% 60.0% ☆ FE0D
corresponding setting
PE-14 Curve 2 maximum PE-12~10.00V 10.00V ☆
input FE0E
Curve 2 maximum
PE-15 input corresponding -100.0%~100.0% 100.0% ☆ FE0F
setting
PE-24 AI1 set jump point -100.0%~100.0% 0.0% ☆ FE18
PE-25 AI1 sets the jump 0.0%~100.0% 0.5% ☆
range FE19
Communic
Function Description (setting Factory
Name Change ation
code range) Default
Address
AI2 set jump
PE-26 -100.0%~100.0% 0.0% ☆ FE1A
point
AI2 set jump
PE-27 0.0%~100.0% 0.5% ☆ FE1B
range
Group PF: Manufacturer parameters
1: Motor No. 1
A0-00 Motor selection 1 ★ A000
2: Motor No. 2
1: Open loop vector
The second
control (speed
A0-01 motor control A001
sensorless vector) 2: VF 2 ★
mode
Control
- 115 -
Chapter 8 Function & Parameter Table
Motor 0: no function
A1-00 parameter 1: Static tuning 0 ★ A100
tuning 2: Dynamic full tuning
0.01A~600.00A(Motor
Motor 2 rated rated power<=30.0KW)
A1-04 A1-01 OK ★ A104
current 0.1A~6000.0A(Motor
rated power>30.0KW)
Communica
Functio Description (setting Factory
Name Change tion
n code range) Default
Address
0.01A~A1-04
(Motor rated
Motor 2 no-load power<=30.0KW)
A1-07 A1-01 OK ★ A107
current 0.1A~A1-04
(Motor rated
power>30.0KW)
Motor 2 stator 0.001ohm~ Model is
A1-08 determine ★ A108
resistance 65.535ohm
d
Motor 2 rotor 0.001ohm~ Model is
A1-09 determine ★ A109
resistance 65.535ohm
d
Motor 2 mutual Model is
A1-10 0.1mH~6553.5mH determine ★ A10A
inductance
d
Motor 2 leakage 0.01mH~ Model is
A1-11 determine ★ A10B
inductance 655.35mH
d
Acceleration at
A1-12 Dynamic Full 1.0s~6000.0s 10.0s ☆ A10C
Tuning
Deceleration at
A1-13 1.0s~6000.0s 10.0s ☆ A10D
dynamic full tuning
- 116 -
Chapter 8 Function & Parameter Table
Commu
Function Description (setting Factory
Name Change nication
code range) Default
Address
Excitation current
A3-13 0~30000 2000 ☆ A30D
regulator Kp
Excitation current
A3-14 0~30000 1300 ☆ A30E
regulator Ki
0: P3-21
2: AI2
1: AI1 (analog range
Electric torque
A3-20 corresponds to P3-21) 0 ☆ A314
upper limit source
3: Communication
given
4: PLUSE given
- 117 -
Chapter 8 Function & Parameter Table
0: P3-23
2: AI2
1: AI1 (analog range
Braking torque
A3-22 corresponds to P3-23) 0 ☆ A316
upper limit source
3: Communication
given
4: PLUSE given
0: output current
LCD top menu 1: Motor speed
display/LED 2: Load speed
B0-01 0 ☆ B001
second line 3: Output voltage
display 4: PID given
5: PID feedback
Factor
Function Description (setting Communicati
Name y Change
code range) on Address
Default
LCD language 0: Chinese
B0-02 0 ☆ B002
selection 1: English
LED menu toggle 0: Disable
B0-03 0 ☆ B003
selection 1: enable
Vector operating
0: real-time frequency
B0-04 frequency display 0 ☆ B004
1: set frequency
selection
- 118 -
Chapter 8 Function & Parameter Table
Factor Communic
Functio Description (setting Chang
Name y ation
n code range) e
Default Address
B1-19 Custom function code uP0-00~uU1-xx uP0-00 ☆
19 B113
B1-20 Custom function code uP0-00~uU1-xx uP0-00 ☆
20 B114
B1-21 Custom function code uP0-00~uU1-xx uP0-00 ☆
21 B115
B1-22 Custom function code uP0-00~uU1-xx uP0-00 ☆
22 B116
B1-23 Custom function code uP0-00~uU1-xx uP0-00 ☆
23 B117
B1-24 Custom function code uP0-00~uU1-xx uP0-00 ☆
24 B118
B1-25 Custom function code uP0-00~uU1-xx uP0-00 ☆
25 B119
B1-26 Custom function code uP0-00~uU1-xx uP0-00 ☆
26 B11A
B1-27 Custom function code uP0-00~uU1-xx uP0-00 ☆
27 B11B
B1-28 Custom function code uP0-00~uU1-xx uP0-00 ☆
28 B11C
B1-29 Custom function code uP0-00~uU1-xx uP0-00 ☆
29 B11D
B1-30 Custom function code uP0-00~uU1-xx uP0-00 ☆
30 B11E
B1-31 Custom function code uP0-00~uU1-xx uP0-00 ☆
31 B11F
Group B2: Optimize control parameters
- 119 -
Chapter 8 Function & Parameter Table
Dead Time
0: no compensation
B2-00 Compensation 1 ☆ B200
1: Compensation
Enable Selection
0: Asynchronous
B2-01 PWM method modulation 0 ☆ B201
1: Synchronous
modulation
0: 7 segments in the
whole process
PWM
1:
B2-02 seven-segment/five- 0 ☆ B202
Seven-segment/five-
segment selection
segment automatic
switching
360.0V
B2-04 Braking point 330.0V~1200.0V ☆ B204
690.0V
200.0V
B2-05 Undervoltage point 150.0V~820.0V ☆ B205
350.0V
0: limit mode 0
1: Restricted Mode 1
Low frequency carrier
2: Unlimited (the
B2-08 limitation mode 0 ☆ B208
carrier of all
selection
frequency bands is
the same)
- 120 -
Chapter 8 Function & Parameter Table
Communic
Functio Description (setting Factory
Name Change ation
n code range) Default
Address
Host sending 0: Running
B4-02 frequency 0 ★ B402
frequency selection:
1: Target frequency
Slave follow master 0: Do not follow 1:
B4-03 command source 0 ★ B403
Follow
selection
Slave receive 100.00
B4-04 0.00%~600.00% ☆ B404
frequency coefficient %
Slave receives torque
B4-05 -10.00~10.00 1.00 ☆ B405
coefficient
- 121 -
Chapter 8 Function & Parameter Table
Brake release
B5-02 frequency 0.0s~20.0s 1.0s ★ B502
maintenance time
Current limit value
B5-03 50.0%~200.0% 120.0% ★ B503
during holding brake
Brake pull-in
B5-04 0.00Hz~20.00Hz 1.50Hz ★ B504
frequency
Brake pull-in delay
B5-05 0.0s~20.0s 0.0s ★ B505
time
Holding time of
B5-06 brake pull-in 0.0s~20.0s 1.0s ★ B506
frequency
Group B6: Sleep wakeup function parameters
Factor Communica
Function Description (setting Chang
Name y tion
code range) e
Default Address
B6-01 Sleep frequency 0.00Hz~P0-14 0.00Hz ☆ B601
B6-02 Sleep delay 0.0s~3600.0s 20.0s ☆ B602
0.0%~100.0% When
Wake-up
B6-03 B6-00=3, the unit 10.0% ☆ B603
difference
becomes Hz
B6-04 Wake up delay 0.0s~3600.0s 0.5s ☆ B604
Sleep delay 0: PID automatic
B6-05 frequency output adjustment 1: Sleep 0 ☆ B605
selection frequency B6-01
Communica
Functio Smallest Chang
Name Description (setting range) tion
n code unit e
Address
Group U0: Fault logging parameters
- 122 -
Chapter 8 Function & Parameter Table
00: No fault
Err01: Inverter module protection
Err04: Overcurrent during
Last acceleration Err05: Overcurrent
U0-00 failure during deceleration Err06: 1 ●
Overcurrent during constant 7000
type
speed operation
Err08: Overvoltage during
acceleration Err09: Overvoltage
during deceleration Err10:
Overvoltage during constant
speed operation
Err12: Undervoltage fault Err13:
Drive overload fault Err14: Motor
overload fault Err15: Drive
Last overheated
U0-01 failure Err17: Current detection failure 1 ●
Err20: Short circuit fault to ground 7001
type
Err23: Input phase loss fault
Err24: output phase loss fault
Err25: Eeprom operation failure
Err27: Communication failure
Err28: External fault
Err29: The speed deviation is too
large Err30: User-defined fault 1
Err31: User-defined fault 2
Err33: Fast current limiting Err34:
load drop fault
Err32: PID feedback lost during
Types of runtime Err35: Input power failure
first and Err37: parameter storage
U0-02 1 ● 7002
second exception Err39: The running time
faults has arrived Err40: Cumulative
running time reached Err42:
Switch the motor during
operation
Err46: Master-slave control
communication dropped
- 123 -
Chapter 8 Function & Parameter Table
- 124 -
Chapter 8 Function & Parameter Table
- 125 -
Chapter 8 Function & Parameter Table
- 126 -
Address:Ruko Taman Meruya Plaza II Blok B no. 1 Jakarta Barat 11620 Indonesia