0% found this document useful (0 votes)
28 views96 pages

Guardlink Ethernet/Ip Interface: User Manual

The GuardLink EtherNet/IP Interface User Manual provides essential information for the installation, configuration, and operation of the product, emphasizing the need for trained personnel to follow safety guidelines and applicable codes. It includes sections on system design, mechanical installation, electrical connections, and network interface setup. Users are advised to read the manual thoroughly to ensure proper use and avoid potential hazards.

Uploaded by

mohammedopel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views96 pages

Guardlink Ethernet/Ip Interface: User Manual

The GuardLink EtherNet/IP Interface User Manual provides essential information for the installation, configuration, and operation of the product, emphasizing the need for trained personnel to follow safety guidelines and applicable codes. It includes sections on system design, mechanical installation, electrical connections, and network interface setup. Users are advised to read the manual thoroughly to ensure proper use and avoid potential hazards.

Uploaded by

mohammedopel
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 96

GuardLink EtherNet/IP

Interface
Catalog Number 432ES-IG3

User Manual Original Instructions


GuardLink EtherNet/IP Interface User Manual

Important User Information


Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before
you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to
requirements of all applicable codes, laws, and standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably
trained personnel in accordance with applicable code of practice.

If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this
equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with
any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

These labels may also be on or inside the equipment to provide specific precautions.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.

ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).

The following icon may appear in the text of this document.

Identifies information that is useful and can help to make a process easier to do or easier to understand.

2 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Table of Contents
About This Publication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Who Should Use this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Summary of Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Chapter 1
Introduction Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Automatic Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Physical Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Modes of Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
System Design. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
GuardLink Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Taps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Tap Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Tap Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Tap Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Channel Order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Terminator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Commissioning Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Guard Locking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

Chapter 2
Mechanical Installation Approximate Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
High Vibration Areas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Cable Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Chapter 3
Electrical Connections Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Power Supply. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Multiple Power Supplies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Chapter 4
Add the Network Interface Set the IP Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Module Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Alternative Methods to Set the IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Update Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Before You Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Update Firmware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Install the Profile. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Add the Network Interface Module to a Controller Project . . . . . . . . . . . . . . . . . . . . . . . 32
View Module Profile Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
General Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Connection Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Safety Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 3


Table of Contents

Module Info Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39


Channels Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Internet Protocol Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Port Configuration Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Network Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Time Sync Page. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Append GuardLink Nodes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Append GuardLink Nodes to the Network Interface Module . . . . . . . . . . . . . . . . . . 44
Manual Method. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Discover Modules Method. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Chapter 5
Modify GuardLink Topology Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Online Node Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Controller Online . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Safety Locked or Unlocked . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Node Tags Used in Routines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Insert a Node. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Change a Node . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Append a Node . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Delete a Node . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Remove the Last Node . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

Chapter 6
Controller Tags Interface Input Tags. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Interface Output Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Tap Input Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Guard Locking Input Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Tap and Guard Locking Output Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

Chapter 7
Troubleshooting Diagnostic Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Controller Organizer Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Channel Faults. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Node Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Fault Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
All Nodes Faulted. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Verify Module Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Verify Device on the Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Cannot Disable DHCP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76

Appendix A
Specifications Catalog Number Explanation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Environmental. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78

4 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Table of Contents

Appendix B
Certifications and Directives Agency and Directive Marks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
CE Conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
UKCA Conformity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
SIL Rating. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Performance Level/Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

Appendix C
Safety Statements CIP Safety Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

Appendix D
Uninstall the Logix Designer Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Application Module Profile
Appendix E
Configure Automatic Automatic Diagnostics on PanelView 5000 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Diagnostics
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 5


Table of Contents

Notes:

6 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Preface

About This Publication This manual is a reference guide for the 432ES-IG3 EtherNet/IP™ Communications Module for
the 432ES-IG3 GuardLink® Network Interface Module.

This publication describes the procedures to install, wire, configure, and troubleshoot the
432ES-IG3 GuardLink network interface module. You must be familiar with the following:
• Use of a safety controller in a Logix 5000® control system.
• Use of safety systems.
• Use of the Studio 5000® Logix and View Designer application environment.
• Knowledge of applicable regulatory standards.

ATTENTION: Personnel who are responsible for the design, application, and
maintenance of safety-related programmable electronic systems (PES) must
be aware of the safety requirements in the application of the system.
Personnel must also be trained in the use of the system.

Who Should Use this Manual Use this manual to design, install, program, or troubleshoot systems that use the 432ES-IG3
GuardLink EtherNet/IP network interface module.

You are required to have a basic understanding of electrical circuitry and familiarity with
safety-related control systems. If you do not, obtain the proper training before using this
product.

IMPORTANT Read and thoroughly understand the manual before installing or


operating a system that contains this device.

Summary of Changes This publication contains the following new or updated information. This list includes
substantive updates only and is not intended to reflect all changes.
Topic Page
Updated Guard Locking section. 18

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 7


Preface

Definitions The Industrial Automation Glossary (publication AG-7.1) contains terms and abbreviations that
Rockwell Automation uses to describe industrial automation systems. The following table lists
specific terms and abbreviations that are used in this manual.
Table 1 - Terms and Abbreviations
Term Description
Add-on Profile - A Logix Designer application file that facilitates the implementation of
AOP the 432ES. This term is also known as the module profile.
Common Industrial Protocol - An industrial communication protocol that Logix 5000-
CIP based automation systems use on Ethernet, ControlNet®, and DeviceNet®
communication networks.
CIP Safety™ Safety certified version of CIP™.
CIP Security™ Helps CIP connected device protect itself from malicious CIP communications.
CIP Sync™ Synchronizes the timing of events.
The client is a GuardLink-enabled device that connects into one of the GuardLink
Client circuit channels of the 432ES-IG3 network interface module. Each client is a node.
Dynamic Host Configuration Protocol - A network management protocol that Internet
DHCP Protocol networks use to assign an IP address and other network configuration
parameters to each device on a network dynamically.
FW Firmware revision level.
Includes all hardware that connects to one channel of the 432ES. This hardware
GuardLink circuit includes the cables, taps, safety devices, and the terminator.
The on-state of the output of a logic block, or the state of an input to a logic block, or a
HI voltage level that is above the turn-on threshold. HI is equal to a Boolean value of 1.
HMI Human Machine Interface - A Rockwell Automation® product in the PanelView™ family.
Host The host is the 432ES-IG3 network interface module.
HW Hardware revision level.
Logic off-state or a voltage level below the turn-off threshold. LO is equivalent to a
LO Boolean value of 0.
Media Access Control Identification Number - An Ethernet device on a network is
MAC ID assigned a unique physical (hardware) number. This number must associate with the
IP address that is assigned to the device for proper communication.
NC No connection.
A GuardLink-enabled device that is installed in a GuardLink circuit. Up to 32 nodes can
Node connect to a circuit. The nodes are numbered from 0 to 31.
All nodes on the GuardLink channel are safety valid, and the safety Status tag for the
Operational state channel is set to a value of 1.
Output Signal Switching Device - Typically, OSSD is a pair of solid-state signals that are
connected to a DC source supply. The signals are tested for short circuits to the DC
power supply, to the DC common, and between the two signals.
OSSD The 432ES-IG3 network interface module does not have OSSD outputs because the
safety status is transmitted over the Ethernet network. In the controller input tags, the
SIL 3 rated signal for the safety output on each channel is called Status.
The probability of failure to danger per hour. When IEC 61508 is applied, the acronym
PFHd (PFH) PFH implies the probability of failure to danger.
PLC (PAC) A programmable logic controller or a programmable automation controller.
The input reaction time is the time from when the signal changes on an input terminal
Reaction time to when safety data is sent to the GuardLogix® controller.
Describes the time between the initial demand that is placed on a safety device/
Response time system, to the time when its output changes to a safe state.
One or more nodes on the GuardLink channel are not safety valid, and the safety Status
Safe state tag for the channel is set to a value of 0.
The safety circuit receives input signals that satisfy its requirements to allow
Safety valid transition to an operational state.
A tap connects a safety device to the GuardLink circuit. GuardLink-enabled taps are
nodes on the GuardLink circuit. Passive taps are not GuardLink-enabled and therefore
Tap must connect to a GuardLink-enabled device to be considered as a node on the
GuardLink circuit. A tap is not considered as a node when the tap is a passive or
passive power tap with a shorting plug.

8 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Preface

Additional Resources These documents contain additional information concerning related products from Rockwell
Automation.
Resource Description
ControlLogix System Selection Guide, publication 1756-SG001 Provides information to help you select a ControlLogix® system.
ControlLogix 5580 and GuardLogix 5580 Controllers User Manual, Provides information to help you design a system, operate a ControlLogix or GuardLogix-
publication 1756-UM543 based controller system, and develop applications.
Guardmaster DG Safety Relay and GuardLink System User Manual, Provides a detailed description of the GuardLink system when connected to the
publication 440R-UM015 Guardmaster® DG safety relay.
GuardLink EtherNet/IP Network Interface Installation Instructions, Describes how to install a 432ES-IG3 network interface module.
publication 432ES-IN001
ControlFLASH Plus Quick Start Guide, publication CFP-QS001 Describes how to use the ControlFLASH Plus™ software to upgrade device firmware.
Describes how to configure and use EtherNet/IP devices to communicate on the EtherNet/IP
EtherNet/IP Network Devices User Manual, publication ENET-UM006 network.
Ethernet Reference Manual, publication ENET-RM002 Describes basic Ethernet concepts, infrastructure components, and infrastructure features.
Ethernet Media Specifications Technical Data, publication 1585-TD001 Provides technical specifications for Ethernet media cables and accessories.
Provides guidance on how to conduct security assessments, implement Rockwell
System Security Design Guidelines Reference Manual, Automation products in a secure system, harden the control system, manage user access,
publication SECURE-RM001 and dispose of equipment.
Industrial Components Preventive Maintenance, Enclosures, and Contact Provides a quick reference tool for Allen-Bradley® industrial automation controls and
Ratings Specifications, publication IC-TD002 assemblies.
Designed to harmonize with NEMA Standards Publication No. ICS 1.1-1987 and provides
Safety Guidelines for the Application, Installation, and Maintenance of general guidelines for the application, installation, and maintenance of solid-state control in
Solid-state Control, publication SGI-1.1 the form of individual devices or packaged assemblies incorporating solid-state
components.
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Provides general guidelines for installing a Rockwell Automation industrial system.
Product Certifications website, rok.auto/certifications. Provides declarations of conformity, certificates, and other certification details.

You can view or download publications at rok.auto/literature.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 9


Preface

Notes:

10 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 1
Introduction
Overview A GuardLink® system is a collection of components to simplify a series connection of safety
devices while achieving the highest industrial safety rating. The system has these important
features:
• Simplifies the connection of series connected safety devices.
• Facilitates the scalability of the safety series connections.
• Provides diagnostic information about each device in the system without having to run
a separate status wire back to the machine control system.
• Allows the simultaneous or individual lock/unlock of guard locking interlocks in the
series-connected system. No need for an additional wire from the machine control
system to lock/unlock the safety gate.
• Helps ease communication to the machine control system over EtherNet/IP™.
Communication includes the sending of non-safety commands to devices and the
receiving of status information back from the safety devices.

The following image shows a typical safety system that uses the 432ES-IG3 network interface
module. A typical system consists of an HMI, a GuardLogix® controller, the 432ES-IG3
GuardLink EtherNet/IP network interface module, and a series connection of safety devices,
which connect to the interface through taps in a trunk and drop network configuration.

The GuardLogix controller and PanelView™ reside in an environmentally protected control


cabinet. The 432ES network interface module and associated taps and devices are at various
points on the machine.
Figure 1 - Typical 432ES-IG3 Network Interface Module Safety System
InInCabinet
Cabinet OnOnthe
Machine
Machine
PanelView 5000
Tap
INPUT INPUT INPUT INPUT

Zone 3
GuardLogix
SIL2 CPU OUTPUT OUTPUT
Zone 2 432ES-IG3
432ES-IG3 Drop
5069-L3100ERMS2 5069-IB8S 5069-IB8S 5069-OBV8S 5069-OBV8S

Zone 1
Esc Sel
INPUT INPUT INPUT INPUT INPUT
MOD Power

V34.01
Trunk
SA Power

Compact GuardLogix

Terminator

24V DC Power
CIP Safety™ Supplies
INPUT INPUT INPUT INPUT
PWR INPUT

over EtherNet/IP Class 2 (4 A) Passive Power Tap

The 432ES-IG3 network interface module can control up to three safety zones, one zone for
each GuardLink channel. With logic, the channels can combine to control only one or two
zones.

Requirements
A GuardLogix controller must control the 432ES-IG3 network interface module. See the
ControlLogix System Selection Guide, publication 1756-SG001. As of the time of release, you can
use the following controllers:
• 1756 GuardLogix 5580 controllers
• 5069 Compact GuardLogix 5380 controllers

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 11


Chapter 1 Introduction

The controller must run Studio 5000® version 34.01 or later. You must use FactoryTalk® Linx
6.30 or later for communications. A PanelView 5000 HMI is required for automatic diagnostic
reporting. PanelView Performance Plus can be used with FactoryTalk SE; setup is not
automatic.

The 432ES-IG3 network interface module provides additional status information and the ability
to upgrade the firmware in GuardLink-enabled devices. To achieve this functionality, the
firmware in the taps and guard locking switch is upgraded to 2.00x. The 432ES-IG3 network
interface module can operate with firmware 1.00x, but 2.00x is the preferred level. When
multiple levels of protocol connect on a channel, the channel operates at the lowest level.

IMPORTANT • Channels 0 and 1 can operate with GuardLink 1.0 or 2.0. If nodes are
mixed, the channel operates at 1.0.
• Channel 2 can only operate with GuardLink 2.0 devices.

Automatic Diagnostics
Automatic diagnostics is a system-level feature in devices that provides device diagnostics to
HMIs and other clients, with zero programming. GuardLink 2.0 products come with the
automatic diagnostics feature enabled by default, so diagnostics - including device
description conditions and state events - are sent to an HMI device.

You can deactivate and activate the whole feature while online or offline from the Controller
Properties dialog box. You can also deactivate automatic diagnostics for a specific device in
the module properties. See Configure Automatic Diagnostics on page 87 for more information.

Physical Features The following image identifies the key physical features of the 432ES-IG3 network interface
module. Connections for the GuardLink channels, the Ethernet ports, and the power
connections are all M12 quick disconnect cables to reduce installation and troubleshooting
costs. Status indicators use color and blink rates to provide status and diagnostic information.
Figure 2 - 432ES Network Interface Module Key Features
EtherNet/IP
EtherNet/IPLink
Link 11 EtherNet/IP Link
EtherNet/IP Link2 2
D-code
D-codeM12
M12 Connector
connector D-code M12connector
D-code M12 Connector

Link1 Status
Link 1 statusIndicator
indicator Link 22status
Link Statusindicator
Indicator
ModuleStatus
Module statusIndicator
indicator Network status
Network Statusindicator
Indicator
Ch0
Node Addressswitches
Node address Switches
Label Pockets
Label Pockets
GuardLinkChannel
GuardLink Channel 00

Ch1
GuardLink connectors
GuardLink Connectors
GuardLink
GuardLinkChannel
Channel 11 M12 A-Code
M12 A-Code Micro Style
Micro Style
ChannelStatus
Channel status Indicators
indicators Ch2
GuardLink
GuardLinkChannel
Channel 22

Module Power
Module Power PWR
status Indicator
Status indicator
Power In
Power In Power Out
Power Out
4-PinMicro
4-Pin M12 A-code M12 A-code
Style 4-Pin M12
4-Pin M12A-code
A-code Micro Style
Micro Style Micro Style

12 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 1 Introduction

Modes of Operation
The GuardLink system has four modes of operation for each channel:
• Start Up - Initializes the system when power is initially applied. The 432ES network
interface module determines the number of channels in use, and the number and type
of nodes on each channel.
• Operational - All safety devices on the GuardLink channel are safety-valid.
• Safe State - One or more of the devices on the GuardLink channel are not safety-valid.
• Firmware Update - The 432ES network interface module or one of its client devices is
undergoing a firmware update. Updates can only occur when the system is in the safe
state.

The 432ES network interface module has three independent channels. Any channel can be in
the operational state, while the others can be in a safe state. The 432ES-IG3 network interface
module has one safety-rated controller Status tag for each channel.

In the operational state, the 432ES network interface module transmits the channel Status = 1
to the safety controller, which indicates the channel is in an operating state. The machine
must use the Status tag as part of the safety function to allow the machine to enter Run mode.

In the safe state, the 432ES network interface module transmits the channel Status = 0 to the
safety controller, which indicates the channel is operating in a safe state; one or more safety
devices are actuated (not valid).

System Design GuardLink Components


Each GuardLink circuit accommodates up to 32 taps.

A typical GuardLink system consists of:


• One GuardLink interface
• One tap for each safety device
• One terminator for each GuardLink circuit
• Patchcords and cordsets

Taps Taps create nodes in the GuardLink circuit. A safety device connects to each tap. The following
types of taps are available:
• GuardLink-enabled taps that interface with devices that have voltage-free safety
contacts
• GuardLink-enabled taps that interface with devices that have OSSD signals
• GuardLink-enabled 8-pin taps can be either Power to Release or Power to Lock
• Passive taps that interface with devices that are GuardLink-enabled
• Passive power taps that interface with devices that are GuardLink-enabled and add
power to the link

GuardLink-enabled taps are available in an 8-pin and 5-pin device connection version. Passive
style taps are only available in a 5-pin device connection version.

The taps are intended to mount on the machine, near the location of the device the tap
monitors. You can mix and connect the different tap types and versions in any order.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 13


Chapter 1 Introduction

Tap Type Description


The OSSD tap is designed to specifically interface with safety products that generate OSSD
outputs. The OSSD tap does not perform testing on the OSSD signals as the input device must
perform the test.
The OSSD tap verifies if the outputs of the connected device are energized or de-energized. If the
outputs are de-energized, then the tap goes to a safe state, and the input status indicator is red. If
OSSD Tap the outputs of the device are energized, then the tap shows a solid or flashing green input status
indicator.
If the OSSD tap inputs are not the same state for 3 or more seconds, then the tap enters a
recoverable fault state. Both inputs must go to LO and then back to HI to recover.
The 8-pin OSSD taps are available in Power to Release and Power to Lock versions for guard
locking switches.
The EMSS tap is designed to interface with two voltage-free contacts. The tap applies 24V to one
side of the contact on both channels and looks for the 24V on the monitoring input. The tap pulse
tests these contacts.
The tap verifies if both contacts are closed or open. When the contacts open, the tap goes to a
safe state, and the input status indicator is red. When the contacts close, the tap goes to an
EMSS Tap operational state, which turns the input status indicator either solid or flashing green.
The EMSS tap has a 10 second simultaneity window. If one contact opens, the second contact must
open within 10 seconds. Similarly, if one contact closes, the second contact must close within 10
seconds. If the simultaneity window requirement is not met, the tap goes to a recoverable fault
state. To recover, both contacts must cycle open and then closed again within 10 seconds.
The 8-pin EMSS taps are available in Power to Release and Power to Lock versions for guard
locking switches.
The passive tap is designed to interface with safety-rated devices that have built-in GuardLink
Passive Tap technology. The passive tap simply passes the GuardLink signals to and from the device. The
passive tap does not operate with safety devices that have OSSD or EMSS outputs.
The passive power tap has two significant features:
• The passive power tap acts as a passive tap by passing the GuardLink signals directly to
Passive Power devices with built-in GuardLink technology
Tap • The passive power tap allows additional power to be introduced into the GuardLink circuit to
compensate for voltage drops resulting from long cable lengths and numerous devices in the
circuit.

Tap Connections
The following image identifies the tap connections. Follow the instructions to modify the
GuardLink circuit. The Link In (J1) connection supplies power to the tap.
Figure 3 - Tap Connections
GuardLink-enabled and Passive Passive Power
J3 Device J4 Power In J3 Device
INPUT PWR INPUT

J1 Link In J2 Link Out J1 Link In J2 Link Out

Tap Cabling
The GuardLink system is designed to minimize wiring with quick-disconnect patchcords, while
also allowing some manual wiring to terminals, when pinout incompatibilities exist.

The preferred cables are the Bulletin 889D hardware (red jacket, PVC, unshielded, with epoxy
coat). Use any jacket color, however, the red is the preferred color to indicate a safety circuit.
To minimize the voltage drop due to wire resistance, the preferred wiring gauge for the link
cable is 18 AWG (0.823 mm²).

Visit rockwellautomation.com/en-us/products/hardware/allen-bradley/connection-devices/
cables-and-cordsets/dc-micro--m12-/dc-micro-cordsets-and-patchcords.html for other
options, such as right-angle connectors, stainless-steel couplings, and shielded cables.
To maintain the integrity of the GuardLink signal, the wiring distance between GuardLink-
enabled devices is important. There are two application cases:
• Case 1: Includes Guard Locking Devices on page 15
• Case 2: No Guard Locking Devices on page 15

14 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 1 Introduction

For both cases, the wiring distance between the taps and the safety device is limited to 10 m
(32.8 ft). Proper wiring requires at least 22 AWG (0.33 mm²) wire size for 5-conductor cables
and for 8-conductor cables.
Case 1: Includes Guard Locking Devices

When the GuardLink circuit includes one or more guard locking devices, the maximum
distance between GuardLink-enabled devices is 30 m (98.4 ft). If the distance between devices
is greater than 30 m (98.4 ft), you must insert a GuardLink-enabled tap at a maximum of every
30 m (98.4 ft). If a device is not needed at a particular location, use a shorting plug for the
device connection.
The following image shows an example GuardLink circuit that includes at least one guard
locking device.

Tap 1 is a GuardLink-enabled tap that can be connected to a guard locking or a non-guard


locking device.
Tap 2 is a passive tap, which is connected to a GuardLink-enabled device.

The following image also shows tap 3 as a safety device with terminal block connections. In
this case, a cordset is used to connect the safety device to the tap. The safety device can be a
guard locking or non-guard locking device.

Because the GuardLink circuit has at least one guard locking switch, the maximum distance
between GuardLink-enabled devices is 30 m (98.4 ft). When a passive tap is used, the cable
length includes both the length of the link cable and the length of the device cable.
Figure 4 - Example Guard Locking Circuit
GuardLink-
Guard Locking or enabled Guard
Non-guard Locking Locking Safety
Safety Device Device

Guard Locking or
889D-M5NC-x Non-guard
889D-F5NCDM-x Locking Safety
5­wire Patchcord or 5­wire Cordset or
889D-F5NCDM-x 889D-M8NB-x Device
889D-F8NBDM-x
8­wire Patchcord 5­wire Patchcord 8­wire Cordset
10 m (32.8 ft) length, max 10 m (32.8 ft) length, max 10 m (32.8 ft) length, max

INPUT INPUT INPUT

White Black Brown Blue GuardLink-enabled Tap Passive Tap GuardLink-enabled Tap
++ - - 898D-418U-DM2
DG 24V Terminator
Safety Power 889D-F4NE-30
Wire Cordset 30 m (98.4 ft) length, max
Relay Supply between GuardLink-enabled Devices All lengths, 30 m (98.4 ft) length, max
30 m (98.4 ft) length, max
(includes link and device cables)

Case 2: No Guard Locking Devices

The following image shows an example of a GuardLink circuit with no guard locking devices.
When the GuardLink circuit excludes any guard locking devices, the maximum distance
between 2…32 GuardLink-enabled devices is 100 m (328.1 ft). The distance from the DG safety
relay or the 432ES-IG3 network interface to the first tap is limited to 30 m (98.4 ft). If a passive
power tap is used with a shorting plug, the total length between the two neighboring
GuardLink-enabled taps is 100 m (328.1 ft).

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 15


Chapter 1 Introduction

Figure 5 - Example of a Non-guard Locking Circuit


Non-guard Locking
Safety Device
889D-F5NCDM-x
5­wire Patchcord
10 m (32.8 ft) length, max

889D-F5NCDM-x 889D-M5NC-x Non-guard


5­wire Patchcord or 5­wire Cordset or Locking Safety
889D-F8NBDM-x 889D-M8NB-x Device
8­wire Patchcord 8­wire Cordset
10 m (32.8 ft) length, max 898D-41KU-DM2 10 m (32.8 ft) length, max
Shorting Plug

INPUT PWR INPUT INPUT

White Black Brown Blue GuardLink-enabled Tap Passive Power Tap GuardLink-enabled Tap
++ - - 898D-418U-DM2
DG 24V Terminator
889D-F4NE-30 Two 889D-F4MEDM-x
Safety Power Wire Cordset 4-wire Patchcord
Relay Supply 30 m (98.4 ft) length, max 100 m (328 ft) length, max Link 1: 30 m (98.4 ft) length, max
Links 2…32: 100 m (328 ft) length, max

Tap Replacement
You can replace a GuardLink tap with the same type of tap while the link is powered. When the
connections are remade, the GuardLink circuit recovers automatically.
When a GuardLink tap is replaced with another type of tap that is removed or added to the
circuit, cycle the power to the DG safety relay to relearn the number and types of connected
taps. If you use the 440R-ENETR interface, cycle its power and update the Add-on Profile (AOP)
of the interface.

For applications with the 432ES network interface, momentarily remove a link cable to cycle
the power to the channel, or cycle the power to the 432ES network interface. The 432ES
network interface AOP must also be updated.

Channel Order
Each channel acts independently. You can add the nodes to any channel in any order. For
example, it is not necessary to add nodes to Channel 0 first. You can add to Channel 1 or
Channel 2 first.

Each channel can accommodate up to 32 nodes, numbered 0...31. The nodes must be
sequential with no skipping over numbers.

You can either add the hardware, then add the nodes into the Controller Organizer (software),
or vice versa. We recommend that you add the hardware before you change the controller
tree. This order allows the Discover Modules feature to add the nodes to the Controller
Organizer quickly, in the correct order, with the correct part number, and compatible
electronic keying.
• Channels 0 and 1 can accommodate protocols 2.0 and 1.0.
• When multiple levels of protocol connect on a channel, the channel operates at the
lowest level. Protocol 1.0 provides basic on/off information, with limited diagnostics.
Protocol 2.0 provides on/off, additional diagnostic information, and firmware updates.
• Channel 2 only operates with GuardLink 2.0 devices. If a GuardLink 1.0 device (Series A
tap or Series A 440G-MZ) is installed on Channel 2, all nodes on Channel 2 show a fault
condition with the message, “(Code 16#0312) Connection Request Error: Invalid link
address.”

16 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 1 Introduction

Terminator The terminator plays a key role in the GuardLink system. To understand the role of the
terminator helps you to understand the modifications you can apply to the GuardLink circuit,
such as how to change tap types, insert nodes, delete nodes, and append nodes.

The terminator must be installed on the J2 connector of the last tap to complete the link
connection. The terminator contains internal electrical components specifically for a
GuardLink system; other terminators cannot be used as substitutes.
Figure 6 - Terminator (Catalog Number 898D-418U-DM2)

The following image shows an example GuardLink circuit. When power is applied to the
GuardLink circuit, components in the terminator set a specific reference voltage. The device,
which connects to the terminator, reads this voltage and determines that it is the last device.
The last device is the safety source, as it initiates the GuardLink safety signal. Upon initiation,
the GuardLink safety signal determines the number of devices and the identity of the devices
in the circuit. After initiation, the GuardLink signal monitors all devices for their safety status.
Figure 7 - Terminator Determines the Source of the GuardLink Safety Signal

432ES-IG3

INPUT INPUT INPUT INPUT INPUT INPUT INPUT

Node 0 1 2 3 4 5 6

GuardLink Safety Signal


Terminator
Upon power-up, the Terminator establishes the
source of the GuardLink safety signal as node 6.

The terminator affects the closest GuardLink-enabled device. As of the date of this
publication, the device can be a Smart Tap or a 440G-MZ guard locking switch. Additional
GuardLink-enabled devices will be available in the future.
After the initial power-up and establishment of the GuardLink circuit, the terminator plays no
role. You can remove the GuardLink circuit with no effect on the system, though this action
causes the next power cycle to result in a faulted state.

A new GuardLink configuration does not generate if you move the terminator without a power
cycle. Modifications to the GuardLink circuit are only realized upon power-up with the
terminator in place. For a simple power-up, break the link signal at any point in the circuit
before the device that last had the terminator.

The terminator is also an important tool when you commission a new system, troubleshoot an
existing system, or make topology changes.
To help troubleshoot a GuardLink system, reduce the number of taps in the
GuardLink circuit by relocating the terminator. After relocation, cycle power to the
DG safety relay to allow it to relearn how many taps are connected. If a
440R-ENETR interface is used, then you must cycle the power to it and update the
AOP of the interface.
For applications with the 432ES network interface, momentarily remove a link
cable to cycle the power to the channel, or cycle the power to the 432ES network
interface. The 432ES network interface AOP must also be updated.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 17


Chapter 1 Introduction

Commissioning Example
For example, the system requires 15 nodes. During commissioning, connect five nodes at a
time, rather than connecting all 15 at once. After moving the terminator, cycle power to the tap
or switch from where the terminator is removed. Reapply power to the channel after you
install the terminator in its new location.

Guard Locking The international standard ISO 14119, most recently updated in 2013, provides requirements for
the application of interlock safety devices.

When guard locking devices are applied, the opening of the guards must be prevented until all
hazards have reached a safe state. This configuration requires proper design of the Unlock
function, which consists of two different types:
• Unconditional Unlocking - The Unlock command can be issued at any time, regardless
of the state of the machine. In this scenario, the guard locking switch unlocks the
safety gate and generates a stop command. The safety distance calculation timing
begins immediately when the switch unlocks. The machine must be designed such that
the operator cannot reach the hazard until it is in a safe state.
• Conditional Unlocking - The unlock command can only be issued after the hazard has
reached a safe state. The conditions for unlocking can be based on the time when the
stopping performance of the hazard is known and consistent, or other conditions may
exist, like required tolerances of pressure, temperature, atmospheric conditions, speed,
or other criteria. If there is variability in the hazard stopping performance, then
monitoring for a safe state may be required before the unlock command can be issued.

In some applications, the risk assessment may determine that the safety rating of the guard
unlocking function is lower than the safety rating of the guard monitoring function. For
example, the guard monitoring function may require a SIL3/PLe rating, whereas the unlocking
function may only require a SIL2/PLd rating. This is justified when the existing guards limit the
operator's exposure to the hazard or increase the probability of avoiding the hazard.

Firmware 3.001 adds a safety-rated Lock/Unlock Enable controller tag. This tag is labeled
LockUnlockEn. You can use logic to confirm safe conditions before enabling the lock and
unlock commands to be sent to client devices. The conditions must be tested in the safety
task.

The following image shows two (redundant) input conditions in the Safety Task are required to
enable unlock and lock commands to be sent to clients on Channel 0. If either condition is not
satisfied, lock and unlock commands cannot be sent to the client devices. Each channel has
an enable output tag.
Figure 8 - Conditional Unlocking Example

When conditional locking/unlocking is required, the lock/unlock event requires two tags to be
set:
• The LockUnlockEn in the safety task
• The Lock or Unlock tag for the client in the main task.
The sequence of setting the tags is interchangeable. You can first set the unlock or lock tags
to the individual clients and then set the LockUnlockEn tag to execute the unlock or lock
commands or vice versa. From a functional safety perspective, all guard locking devices
connected to one of the three GuardLink channels must be considered as unlocked if one
guard locking device is commanded to unlock. No individual guard locking/unlocking is
achievable within one GuardLink channel from a functional safety perspective.

18 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 1 Introduction

IMPORTANT When the LockUnlockEn tag is set to 1, the channel immediately


transitions to a safe state.

If only unconditional locking/unlocking is needed, then the safety rated Lock/UnlockEn tags
can be hidden (not used) by setting the Output Data selection in the Module Definition to None.
When None is selected, firmware 3.001 is backward compatible with firmware 2.001 and 1.001
regarding the locking function.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 19


Chapter 1 Introduction

Notes:

20 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 2
Mechanical Installation
Approximate Dimensions The following image shows the body and mounting dimension of the 432ES network interface
module. Two sets of mounting holes allow you to mount the module directly to a panel, or to
the front or side of the machine.

Mounting holes accommodate M3 (#4) pan head screws. Torque to 0.68 N•m (6 lb•in).
Figure 9 - Approximate Dimensions [mm (in.)]
M3 (#4) 37 (1.46) 19.8
16.2 (0.64) (0.78)

M3 (#4)

166.5 (6.56)
179 (7.05) 168.6 (6.64)

M3 (#4)

M3 (#4)
27
(1.06)

43.3
(1.70)

32 18
(1.26) (0.71)

High Vibration Areas


The following image shows the recommended mounting if the module is in an area that is
subject to shock or vibration.

Use a flat and lock washer; mount the flat washer underneath the lock washer. Torque the
mounting screws to 0.68 N•m (6 lb•in).
Figure 10 - High Vibration Mounting [mm (in.)]

Lock Washer

Flat Washer
6.5 (0.25) max outside diameter

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 21


Chapter 2 Mechanical Installation

Cable Clearance The 432ES-IG3 network interface module can accommodate both straight and right-angle
connectors. The following image shows the typical vertical cable clearance for the straight
and right-angle connectors.
Figure 11 - Cable Clearance [mm (in.)]

100 (3.93)

68 (2.7)

The following image shows an example of the 432ES-IG3 network interface module that is
mounted against a side wall with all cables using right-angle quick-disconnect connectors.
Figure 12 - Side Mounting with Right-angle Connectors
EtherNet/IP™ Link 1
EtherNet/IP Link 2

432ES-IG3

GuardLink® Channels
Power Connections

22 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 3
Electrical Connections
Wiring
ATTENTION: Before you install and wire any device, disconnect power to the
system. Calculate the maximum current in each power and common wire.
Observe all electrical codes that dictate the maximum current allowable for
each wire size. Current above the maximum ratings can cause wiring to
overheat, which can cause damage.

Do not run signal or communications wiring and power wiring in the same conduit. Route wires
with different signal characteristics by separate paths.

Separate wiring with signal type. Bundle wiring with similar electrical characteristics together.
Label wiring to all devices in the system. Use tape, shrink-tubing, or other means to label
wires. Also use colored insulation to identify wires based on signal characteristics. For
example, you can use blue for DC wiring and red for AC wiring.

IMPORTANT Fault exclusions for conductors and wiring must follow the
requirements of EN ISO 13849-2, table D.3 and D.4. A fault exclusion can
reduce the overall safety rating of the related safety function to a
maximum of PLd per EN ISO 13849-1.

The following image identifies the connectors and the following tables list the connections for
the pins.
Figure 13 - Pin Assignments
Table 2 on page 23 Table 4 on page 24

Table 5 on
page 24

Table 3 on page 24

Table 2 - Power In
4-pin A-code Micro (M12) Convex Pin Description
1 Output power +24V DC
2 2 Module power +24V DC
3 1
4 3 Module power 0V
4 Output power 0V
Recommended cordset catalog numbers:
• 889D-F4AE-x (1) - Straight concave, no connector
• 889D-R4AE-x (1) - Right-angle concave, no connector
(1) x = 2 [2 m (6.6 ft)], 5 [5 m (16.4 ft)], 10 [10 m (32.8 ft)], 15 [15 m (49.21 ft)], 20 [20 m (65.62 ft)], or 30 [30 m (98.42 ft)] for
standard cable lengths. For other cable lengths, contact your local Allen-Bradley distributor or Rockwell Automation sales
office.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 23


Chapter 3 Electrical Connections

Table 3 - Power Out


4-pin A-code Micro (M12) Concave Pin Description
1 Output power +24V DC
2 2 Module power +24V DC
1 3
4 3 Module power 0V
4 Output power 0V
Recommended patchcords catalog numbers:
• 889D-F4AEDM-x (1) - Straight concave, straight convex connector
• 889D-R4AEDE-x (1) - Right-angle concave, right-angle convex connector
(1) x = 0M3, 0M6, 1 [1 m (3.28 ft)], 2 [2 m (6.6 ft)], 5 [5 m (16.4 ft)], 10 [10 m (32.8 ft)], 15 [15 m (49.21 ft)], 20 [20 m (65.62 ft)], or
30 [30 m (98.42 ft)] for standard cable lengths. For other cable lengths, contact your local Allen-Bradley distributor or
Rockwell Automation sales office.

Table 4 - GuardLink Channels


4-pin A-code Micro (M12) Concave Pin Description
1 24V DC
2 2 GuardLink® safety signal
1 3
4 3 0V
4 CLU (control lock unlock)
Recommended patchcords catalog numbers:
• 889D-F4NEDM-x (1) - Straight concave, straight convex connector
• 889D-R4AEDE-x (1) - Right-angle concave, right-angle convex connector
(1) x = 0M3, 0M6, 1 [1 m (3.28 ft)], 2 [2 m (6.6 ft)], 5 [5 m (16.4 ft)], 10 [10 m (32.8 ft)], 15 [15 m (49.21 ft)], 20 [20 m (65.62 ft)], or
30 [30 m (98.42 ft)] for standard cable lengths. For other cable lengths, contact your local Allen-Bradley distributor or
Rockwell Automation sales office.

Table 5 - EtherNet/IP Ports


4-pin D-code Micro Concave Pin Description
1 Tx Data+
2 3 2 Rx Data+
1 4 3 Tx-
4 Rx-
Recommended Ethernet cables catalog numbers:
• 1585D-M4UBJM-x (1) - Straight convex, RJ45 straight convex connector
• 1585D-E4UBJM-x (1) - Right-angle convex, RJ45 straight convex connector
• 1585D-E4UBDE-x (1) - Right-angle convex, M12 right-angle convex connector
• 1585D-M4UBDM-x (1) - Straight convex, M12, straight convex connector
(1) x = OM15, 0M2, 0M3, OM6, 1 [1 m (3.28 ft)], 2 [2 m (6.6 ft)], 2M5, 3 [3 m (9.84 ft)], 4 [4 m (13.12 ft)], 5 [5 m (16.4 ft)],
10 [10 m (32.8 ft)], 15 [15 m (49.21 ft)], 20 [20 m (65.62 ft)], 30 [30 m (98.42 ft)], or 40 [40 m (131.23 ft)] for standard cable
lengths. For other cable lengths, contact your local Allen-Bradley distributor or Rockwell Automation sales office.

Power Supply An external 24V DC power supply source provides power for the 432ES-IG3 network interface
module block. To comply with the European Low Voltage Directive (LVD), power must come
from a protected extra low voltage (PELV) DC source.

To comply with UL restrictions, power must come from DC sources that has double insulation
or reinforced insulation to isolate the secondary circuits from the primary circuit. The DC
power supply must satisfy the requirements for the National Electric Code (NEC) Class 2 and
ground to protective earth.

Many of our Bulletin 1606 power supplies are both PELV and NEC Class 2 compliant. The
following is a list of compliant power supplies:
• Power supply 1606-XLP30E
• Power supply 1606-XLP50E
• Power supply 1606-XLP50EZ
• Power supply 1606-XLP72E
• Power supply 1606-XLP95E
• 1694 modular electronic circuit protector
• On-machine power supply 1607-XT100D1B
24 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024
Chapter 3 Electrical Connections

The 432ES-IG3 network interface module has isolated module and output power connections.
Both power connections are daisy chained to similar blocks (for example, 56RF and 1732E).
This feature allows you to turn output power off, while maintaining module/input power. You
can turn output power off to commission and troubleshoot to help prevent inadvertent
actuation of output devices.

The 432ES-IG3 network interface module does not use output power. The output power solely
passes from the power-in to the power-out connector. The following image shows an example
of how the connections work.
Figure 14 - Module/Output Power Daisy Chain
EtherNet/
EtherNet/IP™

56RF/1732E 56RF/1732E
432ES-IG3 (a) EtherNet/IP

(b)

White Module/Input Power


Blue
Black Output Power
Brown
+ +
DC ok
24…28V
PLC (c)
(a) (b) (c)
1606-XLP95E
N L

Class 2 (4 amp)
Power Supply
Three GuardLink Standard I/O Standard I/O
Channels Channels Channels
(a) Does not use output power.
(b) Typical Bulletin 889D DC micro cordset wire colors
(c) PLC can turn off output power while still being able to monitor input devices.

Multiple Power Supplies Depending on the number of devices and the cable lengths, the GuardLink circuit can require
additional power to maintain the voltage at an appropriate value. Add power to a GuardLink
channel with the 440S-PF5D4 passive power tap (seven taps max per channel).
When you use multiple power supplies, you can turn on the power supplies simultaneously, or
turn on the power supplies sequentially. To turn on power supplies in sequential, begin with
the 432ES-IG3 network interface module and end with the terminator.

The 24V common of all power supplies must connect together. In addition, the 24V common
must connect to protective earth (PE) ground to be PELV-compliant. The 24V common
connections must be at one joint location to avoid ground loop circuits.

You can use the 1607-XT100D1B on-machine power supply in GuardLink applications. The
power supply has a 96…264 AC input and supplies a 24V DC supply, which meets NEC Class 2
with an earth grounded 0V terminal.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 25


Chapter 3 Electrical Connections

Figure 15 - Multiple Power Supplies


440S-PF5D4
Passive Power Tap

PWR INPUT
INPUT

+ + + +
DC ok DC ok
24… 24…
28V 28V
1606-XLP95E 1606-XLP95E
N L N L
PS1 PS2

PE

26 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 4
Add the Network Interface Module
To add the 432ES-IG3 network interface module in your GuardLink® system, follow the steps
that are explained in this chapter.
1. Set the IP Address.
2. Download and install the firmware from rok.auto/pcdc.
3. Update Firmware on page 28.
4. Install the Profile on page 31.
5. Add the Network Interface Module to a Controller Project on page 32.
6. Append GuardLink Nodes on page 44.

Download the network interface module firmware and profile (AOP) files from rok.auto/pcdc.
Search 432 and select Downloads to access the network interface module profile.

Set the IP Address Before you can connect to the controller through the Ethernet or USB port, configure the
EtherNet/IP™ in Linx-based software on your workstation.

For more information on how to install communication drivers, see the EtherNet/IP Network
Devices User Manual, publication ENET-UM006.

When the network interface module is in the out-of-the-box state, the following apply
regarding IP addresses:
• The network interface module ships without an IP address.
• The network interface module is DHCP-enabled. That is, the network interface module
is configured to obtain an IP address via a DHCP server.

If there is no DHCP server or the DHCP server is not configured to set the IP address, you must
set the IP address with the three IP address switches marked X1, X10, and X100. The IP address
becomes 192.168.1.X1 X10 X100.

Requirements
To set the IP address, obtain the following:
• EtherNet/IP driver installed on the programming workstation
• MAC ID from the device, which is on the label on the side of the device
• Recommended IP address for the device

Alternative Methods to Set the IP Address


The network interface module supports the following methods to change the IP address:
• EtherNet/IP Address Commissioning Tool
• BOOTP/DHCP utility
• FactoryTalk® Linx 6.30 or later software
• Studio 5000 Logix Designer® application

For more information on how to use these methods, see the EtherNet/IP Network Devices User
Manual, publication ENET-UM006.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 27


Chapter 4 Add the Network Interface Module

Update Firmware Use ControlFLASH Plus™ software to update the firmware. For information on how to download,
install, and use ControlFLASH Plus software, see the ControlFLASH Plus Quick Start Guide,
publication CFP-QS001.

The network interface and GuardLink-enabled devices contain the latest firmware when
shipped from the factory. Subsequent firmware revisions to address anomalies are released
during the life of a product.
Verify that you have downloaded the firmware to your computer. Check rok.auto/pcdc to
determine if later revisions of the controller firmware are available.

Before You Update


You can only upgrade the firmware of devices with GuardLink firmware 2.0 or later. In addition,
all devices on the channel must have firmware 2.0 or later.
Firmware updates are occasional processes and must be planned according to
when time is available. Updating a device at node 0 takes a few minutes. Updating
the firmware on many devices on a large GuardLink system can be time
consuming. Updating a device in node position 20 can take upwards of
20 minutes; node position 31 can take upwards of 45 minutes.
A helpful technique is to have a spare 4-conductor link cable to connect temporarily from one
of the channels of the 432ES-IG3 network interface module directly to the device that requires
updating. This technique places the device at node 0 for a quick update. After the update,
reconnect the cables and move to the next device.

In the following example, the 440G-MZ safety switch is updated at node 0 on CH2.

To update the firmware:


• The tap or 440G-MZ safety switch must have a network connection to the controller.
• The controller must be online (Rem Run, Rem Prog, or Rem Test).
• The controller must be Safety Unlocked.
1. Open the Module Properties for the 432ES-IG3 network interface module and navigate to
the Connection page.
2. Check the Inhibit Module checkbox.
Notice that the 432ES network interface module Status is now Inhibited. All devices
have a Status of Waiting.
3. Select Apply, and then select Yes to confirm in the follow-up window.

28 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 4 Add the Network Interface Module

4. Select the 440G-MZ safety switch on CH2 and navigate to the Connection page.
5. Check the Inhibit Module checkbox.
Notice that the 440G-MZ safety switch Status is now Inhibited. All other devices remain
with a Status of Waiting.
6. Select Apply, and then select Yes to confirm in the follow-up window.

IMPORTANT When your update completes, return to the Connection page and clear
the inhibit checkboxes for all devices.

Update Firmware
1. From the Start menu, select Flash Programming Tools > ControlFLASH Plus.
2. To choose a device to update, select the network icon to open the network browser.
- For the 432ES module, navigate to the device.
- For a safety switch, first navigate to the channel on the 432ES device, then to the
safety switch.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 29


Chapter 4 Add the Network Interface Module

The window populates with all devices on the selected channel, along with the address and
firmware in each device. In the following example, there is only one device on channel 0.
3. To navigate to the firmware on your computer, select Settings and select the Firmware
Locations tab.

4. After you locate the firmware, select OK.


5. Check the box of the device that you want to update.

6. Select Next.
7. Select Flash.

30 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 4 Add the Network Interface Module

8. When the update is complete, select Close.


9. Select Done.

8
9

Install the Profile To install the network interface module profile:


1. Run the MPSetup file.
2. Follow the dialog prompts and select the group of GuardLink EtherNet/IP Module
Profiles.
This action installs module profiles for the 432ES-IG3 network interface module and the
other GuardLink-enabled devices.

The default location of the installed module profile is:


C:\Program Files (x86)\Rockwell Software\RSLogix 5000\Module Profiles\RA 432ES GL-EIP.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 31


Chapter 4 Add the Network Interface Module

Add the Network Interface Use the Studio 5000 Logix Designer application to open or create a controller project.
Module to a Controller 1. Right-click the Ethernet module of the controller with which you want to communicate
and select New Module.
Project

2. In the Select Module Type window, type 432 in the filter field.
The list of available catalog numbers reduces to the 432ES-IG3 network interface
module catalog number.

3. Choose 432ES-IG3 and select Create.


The module window opens.
The navigator column lists the pages that apply to the module (see General Page on
page 33). An asterisk next to the page name indicates that a change is made.
You must select OK (or Apply) to accept the change. Be sure to apply any changes
made on each page.

32 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 4 Add the Network Interface Module

View Module Profile Properties


To view information about the module profile, right-click the New Module title bar (or Module
Properties after installation), and then select About Module Profile.

The following screenshot shows 1.00.20.0 as the specific software version of the profile.

Right-click the title bar

General Page

On the General page, these fields are available:


Field Description
Name Enter the name of the module (required). It is used to identify the controller tags.
Description Enter more information about the module (optional).
Ethernet Address Enter the IP address of the module.
View the details of the module.
Module Definition on page 34 Select Change to open the Module Definition window.
Safety Network Number (SNN) View the SNN for the 432ES-IG3 network interface module.
on page 34 Select the Ellipsis button (…) to modify the SNN.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 33


Chapter 4 Add the Network Interface Module

Module Definition

From the Module Definition window, you can change the series letter, the major and minor
revisions, the electronic keying, and the Output Data (revision 3.001 only). The Module
Definition can only be changed when the host computer is Offline with the controller and the
controller is not safety locked.

On the Module Definition window, these fields are available:


Field Description
Series Select the series letter of the device.
Select the firmware revision level of the device:
• Revision 1.001 was the initial release.
Revision
• Revision 2.001 added CIP Security.
• Revision 3.001 added Lock/Unlock safety rating.
Select the desired electronic keying for the device:
• Compatible Module - The Vendor ID, Product Type, Product Code, and the major
revision of the interface firmware must be correct. The minor revision level is
Electronic Keying ignored.
• Exact Match - The Vendor ID, Product Type, Product Code, Major revision of the
interface firmware and the minor revision of the interface firmware must be
current.
With firmware revision 1.001 and 2.001, the only choice is Safety.
Input Data With firmware revision 3.001, the only choice is Safety Data.
With firmware revision 1.001 and 2.001, output data is not visible (not used).
With firmware revision 3.001, output data can be either:
• Safety Data - the Lock/Unlock Enable is available for conditional locking/
Output Data unlocking safety rating.
• None - the output assembly is not available; only unconditional locking/
unlocking is available. Use this option for backward compatibility with firmware
1.001 and 2.001.

Safety Network Number (SNN)

You can use the following methods to change the SNN:


• In Time-based format, select the Generate button to create an SNN.
• Check the Manual format and edit the number.
• Paste the number from your cache (for example, the SNN copied from the controller).
This option automatically changes the format to Time-based.

34 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 4 Add the Network Interface Module

Original Time-based Manual Pasted from Controller

After you download the SNN and enter Remote Run, you can get this module status and fault
message:
Status IO Faulted
Module Fault (Code 16#080e) safety network number mismatch.

This fault occurs because the SNN that resides in the 432ES-IG3 network interface module is
not the same as the SNN that resides in the controller. To download the SNN to the 432ES-IG3
network interface module, inhibit the module on the Connection page, and then reset
ownership of the interface on the Safety page.

Connection Page
The following screenshot shows an example of the Connection page in an offline controller
project.
Figure 16 - Connection Page

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 35


Chapter 4 Add the Network Interface Module

On the Connection page, these fields are available:


Field Description
Requested Packet Interval View the input RPI.
(RPI) To change the RPI, see Safety Page on page 37.
Connection over EtherNet/IP The only choice is Unicast; Multicast is not supported. Connection is only to the
host controller.
Leave this box unchecked to allow a connection to the module. Check this box to
Inhibit Module inhibit connection to this module. You cannot change this box when the controller
is Safety Locked or in Run mode.
Major Fault if Connection Fails Check this box to allow the controller to show a major fault when a safety input or
While in Run Mode output connection is lost while the controller is in Run mode.
This box is checked by default. When checked, certain diagnostics automatically
Enable Automatic Diagnostics publish to FactoryTalk Alarms and Events. If unchecked, the messages do not
automatically publish. You can only change this box while the controller is offline.
See Appendix E on page 87.
Module Fault This box shows the description of a module fault.
Reports the current condition of the module. Examples include Offline, Creating,
Status Connecting, Faulted, Running, and Waiting.

Inhibit Module

You can only inhibit the module if the controller is Safety Unlocked. When the 432ES-IG3
network interface module is inhibited, the status shows Inhibited, and the nodes have a status
of Waiting.

The module ConnectionFaulted tag is set to 1, and all three channels revert to a safe state. All
other module tags are set to 0. The node tags retain the values at the time that the inhibit is
applied. The node tag values remain unchanged until the inhibit is removed.

The following screenshot shows an example with the inhibited 432ES-IG3 network interface
module. On the node devices (taps and switches), the Link indicators on all three channels are
steady red, and all Device indicators on all three channels flash green.
Figure 17 - Module Inhibited

36 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 4 Add the Network Interface Module

Safety Page
The following screenshot shows an example of the Safety page with an online controller
project.
Figure 18 - Safety Page

On the Safety page, these fields are available:


Field Description
Connection Type This field is read-only and always shows Safety Input.
The RPI can be adjusted directly between 2…500 ms. Alternatively, select
Safety Input Advanced (see Advanced Connection Reaction Time Limit Configuration on
page 38).
The RPI is the interval in which the controller inquires the status of the module
inputs and outputs.
A small RPI selection consumes network bandwidth and can cause spurious
Requested Packet Interval (RPI) trips because other devices cannot gain access to the network. Applications
(ms) that use safety light curtains to guard a hazard require the fastest response
possible. The system maintains maximum performance when you select an
appropriate RPI. Changes to the RPI momentarily cause a connection fault and
all three channels to revert to a safe state.
This field shows the maximum network delay in milliseconds when the
Max Observed Network Delay (ms) controller is online and the module is connected. Select Reset to clear the
values and restart the observations.
The Configuration Ownership field has two possible statuses (also see Reset
Ownership on page 38):
• Local - This status is the desired status. The controller in the project owns
Configuration Ownership the 432ES-IG3 network interface module and is the only controller that can
send message instructions to the module.
• Not Owned - The controller cannot send messages to or receive messages
from the 432ES-IG3 network interface module.
The configuration signature defines the configuration of the module. The
configuration signature is used to identify the unique configuration of the
Configuration Signature module. It is not necessary to monitor this signature as the GuardLogix®
controller automatically monitors the signature.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 37


Chapter 4 Add the Network Interface Module

Advanced Connection Reaction Time Limit Configuration

The following screenshot shows the Advanced Connection Reaction Time Limit Configuration
window, which allows you to make additional adjustments to the reaction time. The RPI,
timeout multiplier, and network delay multiplier can be changed to modify the reaction time.
• Connection Reaction Time Limit (ms) - This field automatically calculates according to
the RPI time.

ATTENTION: Add the connection reaction time limit for the safety inputs to
the total response time in the GuardLink circuit and safety devices to
calculate the safety distance.
Figure 19 - Advanced Connection Reaction Time Limit Configuration

IMPORTANT To determine what is appropriate, analyze each safety channel. The


default Timeout Multiplier (2) and Network Delay Multiplier (200) creates
a worst-case input connection-reaction time limit of 4 times the RPI. A
safety administrator must approve changes to these parameters only
after a thorough review.

If the RPI and connection reaction time limit for the network have the appropriate settings,
then the Connected tag must remain low. Monitor the connection status bit to verify that it is
not spiking intermittently due to timeouts.
Reset Ownership

When you reset ownership, the SNN passes to the device, which allows the controller to own
the 432ES-IG3 network interface module. The controller can be in Program, Run, or Test mode.

To reset ownership:
1. Confirm that your host computer is online with the controller.
2. Confirm that the controller is in Safety Unlocked mode.
3. From the Connection page, check the Inhibit Module box and select Apply.

38 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 4 Add the Network Interface Module

4. From the Safety page, select the Reset Ownership button. The Reset Ownership window
appears.
- The Reset Ownership button only works if the connection to the module is inhibited
and the controller is online. If you do not complete step 3, an error message displays
(Failed to perform the required operation).
- If previous edits are not applied, an error message displays (Ownership cannot be
reset until pending edits are applied). Select the Apply button in the lower right
corner.

5. You are prompted to continue. Select Yes.

6. After a short while, a message box appears (Requested message timed out). Select OK.
7. From the Connection page, uncheck the Inhibit Module box and select Apply.
8. The SNN passes to the device. On the Safety page, Configuration Ownership shows
Local. Now the controller and 432ES-IG3 network interface module SNN match.

Module Info Page


The Module Info page only populates when the controller project is online. The controller can
be in Program, Run, or Test mode. The information displays as read-only.

The following screenshot shows an example of the Module Info page with Studio 5000® online.
The 432ES-IG3 network interface module is in a running state with no major or minor faults.
The module is configured and owned, and the module identity is a match for electronic keying.
Figure 20 - Module Info Page

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 39


Chapter 4 Add the Network Interface Module

On the Module Info page, these fields are available:


Field Description
Identification View the product identity and attributes.
Major and Minor Faults can have three states:
• None - The 432ES-IG3 network interface module is functioning properly.
Major Fault/ • Recoverable - You can clear the fault without needing to cycle power to the 432ES-IG3
Minor Fault network interface module.
• Nonrecoverable - Send a DeviceReset command to the 432ES-IG3 network interface module
or cycle power by momentarily removing the connection.
Internal State can have two states:
• Run mode - The RunMode tag is set to 1 and the ConnectionFault tag is set to 0. The 432ES
Internal State network interface module is operating properly.
• Unconnected - The Inhibited module or other cause sets the ConnectionFault tag to 1. Loss of
the physical Ethernet connection prevents the Module Info page from being populated.
Indicates whether the 432ES-IG3 network interface module is configured:
• Configured - The 432ES-IG3 network interface module is properly configured. Configuration
Configured selects Used on the Channel page to allow a channel to go to an operational state.
• No - The 432ES-IG3 network interface module is not properly configured.
Indicates whether a controller owns the 432ES-IG3 network interface module:
• Owned - There is an exclusive owner connection that is open to the device. Owned means
Owned that there is a safety connection to the 432ES-IG3 network interface module.
• No - There is no safety connection. See Reset Ownership on page 38 to reset ownership.
Indicates whether the series letter and revision in the controller match the values in the
432ES-IG3 network interface module:
Module Identity • Match - The 432ES-IG3 network interface module matches the identity in the controller.
• No - The 432ES-IG3 network interface module does not match the identity in the controller.
The IP address switches set the Protection mode during power-up.
• Implicit - The device cannot accept any configuration or parameter changes due to the
internal state. This issue can be due to conditions like an active safety connection, active
firmware update, device in a nonrecoverable fault.
Protection Mode • Explicit - Set by the IP switches and prevents all configuration or parameter changes
(regardless of device state). To make such changes, use the IP switches to disable explicit
protection. Explicit messages that affect the operation of the device are blocked. Explicit
messages can fetch diagnostic information, such as changes to the IP address, reset of the
module, and update of the firmware.

On the Module Info page, you can:


• Refresh - Updates the fields while maintaining the connection to the 432ES-IG3 network
interface module.
• Reset Module - The Reset Module button only works when the connection is inhibited,
which results in the ConnectionFaulted tag being set to 1. The 432ES network interface
module performs the equivalent of a power cycle. Upon completion, the Module Info
page updates with any changes.
If the module is not inhibited, an error message displays (Failed to perform the
required operation).
Channels Page
The following screenshot shows the Channels page that lets you select the mode for each
channel. By default, each channel is set to Not Used. Set the desired channels to Used and
select Apply. Changes to any channel mode cause the Status bit of all three channels to turn
off (0) and then back on (1) momentarily if the Status bit was initially on because the safety
connection turns off momentarily to apply the new configuration.

When a channel is not used, the channel Fault bit sets to 1 and the channel SIL 3 Status tag sets
to 0. On the 432ES network interface module, the channel indicator flashes red.

40 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 4 Add the Network Interface Module

Figure 21 - Channels Page

Internet Protocol Page


The following screenshot shows an example of the Internet Protocol page. This page is only
populated and editable when the controller is online.

To change information in the fields, select Manually configure the IP settings. After you make
changes, select the Set button, which enables as you make changes.
Figure 22 - Internet Protocol Page

The ideal basic settings are:


• Manually configure IP settings
• Physical Module IP Address - Shows an assigned address
• Subnet mask - 255.255.255.0

Advanced applications:
• Gateway Address - Set to 0.0.0.0 unless you require controllers outside the local
network read status data.
• Set button - Applies the changes that are made to the Internet Protocol settings.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 41


Chapter 4 Add the Network Interface Module

Port Configuration Page

On the Port Configuration page, these fields are available:


Field Description
Port Ports available.
Enable Check the boxes to enable ports. For security purposes, disable the unused port.
Shows whether the port is active or inactive. If the port is not enabled, the link status is
Link Status blank.
Typically, this option is checked. If unchecked, you must specify the speed of the port. If
Auto-Negotiate the port is not enabled, the speed cannot be set.
If this option is unchecked, you must select either 10 Mbps or 100 Mbps (preferred). The
Speed Selected 432ES-IG3 network interface module does not communicate at 1 Gbps. If Auto-Negotiate is
checked, this field is blank.
If Auto-Negotiate is checked, this field shows the current speed, either 10 Mbps or
Speed Current 100 Mbps. If Auto-Negotiate is unchecked, the field is read-only.
If Auto-Negotiate is unchecked, you must select either half-duplex (communications in one
Duplex Selected direction at a time) or full-duplex (communications in both directions simultaneously). Full-
duplex is the preferred selection
If Auto-Negotiate is checked, this field shows the current duplex. If Auto-Negotiate is
Duplex Current unchecked, the field is read-only.
Port Diagnostics Select the ellipsis (…). Figure 23 shows an example of the port diagnostics.
When Auto-Negotiate is checked, the Set button is disabled. When Auto-Negotiate is
Set unchecked, the Set button is enabled. After you adjust the configuration, select the Set
button to download the changes to the 432ES-IG3 network interface module.

Figure 23 - Port Diagnostics Example

42 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 4 Add the Network Interface Module

Network Page
The information in the Network page (shown in the following screenshot) is read-only. The
fields populate when the controller is online.
Figure 24 - Network Page

The 432ES-IG3 network interface module supports the following topologies:


• Linear topology - A collection of devices that are daisy chained together.
• Device Level Ring (DLR) - Supports a ring topology. As defined by the Open DeviceNet®
Vendor Association (ODVA), Device Level Ring is an EtherNet/IP™ protocol. DLR provides
a means to detect, manage, and recover from single faults in a ring-based network.
• Star topology - Consists of a number of modules that connect to a central switch.
Modules can be added or removed without affecting the rest of the network.

For more information on the supported EtherNet/IP network topologies and other EtherNet/IP
features, see the EtherNet/IP Network Devices User Manual, publication ENET-UM006.

Time Sync Page


The Time Sync page (shown in the following screenshot) displays and status information about
the module when the project is online:
• CIP Sync™ Time Synchronization
• UTC System Time
• Grandmaster Clock - Shows the controller on the subnet checks the option (Enable Time
Synchronization), and marks the role of the controller (Is the System Time Master).
• Local Clock information

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 43


Chapter 4 Add the Network Interface Module

Figure 25 - Time Sync Page

Append GuardLink Nodes Each node is a GuardLink-enabled tap or a GuardLink-enabled safety switch. Each node must
correspond to the controller organizer in the order in which the nodes connect to the host
interface.
The order in which the channels populate is not critical; the three channels are independent.

Append GuardLink Nodes to the Network Interface Module


Append nodes to the controller tree in one of two ways:
• Manual method - Select each device individually.
• Discover modules method - Installed nodes can be discovered and loaded onto the
controller tree.

In either method, the controller can be in Rem Run, Rem Prog, or Rem Test mode, and the
controller can be either Safety Unlocked or Safety Locked.
If the controller is offline, you can only add nodes manually.

Manual Method
With the 432ES-IG3 network interface module present in the controller tree, add nodes to the
controller tree into the GuardLink® channels.
1. Right-click the desired GuardLink channel and select New Module.
2. Navigate to the node that you want to add.

44 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 4 Add the Network Interface Module

3. Follow the same process as you did to add the network interface module to the
controller tree.

Discover Modules Method


To discover the modules, first install and power the nodes. The host computer must also be
online with the controller. In this example, the host computer is in Rem Run mode with the
controller Safety Locked. The controller owns the 432ES-IG3 network interface module and is
in the Running status.

In the example shown in step 1, Ch0 already has two nodes. Additional nodes are added to the
GuardLink circuit, then added to the controller tree with the Discover Modules feature.
1. Right-click the desired channel and select Discover Modules.

The Select Module Type window opens (see step 2) with the Module Discovery tab. After a short
while, the table automatically populates with the list of modules (client devices) that connect
to the channel, in the order in which they connect. The table also shows the firmware revision
of the device and additional information.
2. Select the Create button for a node to add the node to the controller tree.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 45


Chapter 4 Add the Network Interface Module

The New Module window opens and shows the General Page (see General Page on page 33).

3. The node position automatically populates; no action is needed.


The configuration pages and fields can vary for different nodes. See the online
help or user manuals for those nodes for more details about configuration options.
4. Enter a unique node name (required).
Create names that are easy to locate in your controller tree. For example, start
with the letter N for node. The first digit is the channel, the next two digits are the
position on the channel; node 0…31. Then continue with your own text for
additional description.
Example naming scheme:
• N000_freetext
• N001_freetext
• N100_freetext
• N101_freetext
• N200_freetext
• N201_freetext
5. Once you complete all other configuration settings, select OK to add the node to the
controller tree.
6. Navigate to the Connection Page (see Connection Page on page 35).

46 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 4 Add the Network Interface Module

7. Make necessary changes to the Requested Packet Interval (RPI).


Select the desired RPI value, within the range of 20…500 ms (default 100 ms).
We recommend that you change the RPI with the controller offline, as those
changes apply to all nodes on all channels. Change the RPI of the lowest node (for
example, Node 0 on Channel 0), select Apply, and then download the change to the
controller.
8. If desired, check the Inhibit Module box.
When you inhibit a node, the 432ES-IG3 network interface module immediately sets its
respective channel UnverifiedDevice tag to 1, which sets its Fault tag to 1, which sets its
Tripped tag to 1, which finally sets its channel Status tag to 0 (a safe state).
9. Once you complete all necessary changes, select OK.
The Online Module creation message appears (see step 10). This window allows you to inhibit
the module during creation.
When you check the Inhibit module connections box, the Inhibit Module checkbox
on the Connection page also checks and the module is inhibited from use.
10. Review the message and select Yes to accept changes.

The Module Info page (shown in the following screenshot) populates after the module is
created and the module is online.
Figure 26 - Example Module Info Page for a Node

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 47


Chapter 4 Add the Network Interface Module

Notes:

48 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 5
Modify GuardLink Topology
Overview Add, change, and/or remove nodes from any of the channels on the 432ES-IG3 network
interface module to modify GuardLink® topology.

IMPORTANT Verify and validate the performance of the safety function for all
modifications to the GuardLink topology before you put the machine
into a Production mode setting.

Consider the following situations:


• The controller is online with the host computer.
• The controller is Safety Locked or Unlocked.
• The node tags are used in a program routine.

Online Node Changes


The physical nodes on the GuardLink circuit can be changed with power to the 432ES-IG3
network interface module. Understand the role of the terminator.

You can implement some node changes while online with the controller in a remote setting (for
example, Rem Run), then switched back to Run mode without stopping production. Changes
that allow the system to run:
• Changes to the catalog number of a similar node (cannot change from a tap to a guard
locking switch).
• Node tags not used in a program routine.

Other node changes require you to place the host offline, make the change, and then download
the change to the controller. The controller stops Production mode to institute the change.
Cases that require offline changes:
• Renumbering a node value.
• Node tags used in a program routine.

Controller Online
You can modify some node attributes while the GuardLink circuit is powered and with the
controller online in Rem Run, Rem Prog, or Rem Test mode.
You cannot modify nodes if the controller is set to Run mode.

Safety Locked or Unlocked


You can make a limited number of changes to the nodes while the controller is in the Safety
Locked mode. If you must download the configuration to the controller, first change the
controller mode Safety Unlock.

Node Tags Used in Routines


If a node tag is used in a program routine, you cannot modify or delete the node while the
controller is online. Take the controller offline, make the changes, and then download the
changes to the controller.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 49


Chapter 5 Modify GuardLink Topology

Insert a Node You can only insert nodes while the host computer is offline. Node insertion requires you to
reassign the upper node positions, which cannot be accomplished while the controller is
online. The following example shows the controller in Rem Run mode and Safety Unlocked.

The following steps demonstrate how the 432ES-IG3 network interface module responds when
a node is added. In this example, six nodes connect to CH0; the nodes are named as colors.
The safety status of channel 0 is 1 (operational).
Figure 27 - Initial State of GuardLink Circuit

A simple program is created to monitor each node. If a safety demand is placed on a node, the
node trips and its Pt.Data tag sets to 1. The following screenshot of the MainProgram tab
shows that a safety demand is placed on the Black node (Node 0), while all other nodes have
no safety demand.
Figure 28 - Simple Program to Identify Safety Demands on Nodes

50 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 5 Modify GuardLink Topology

The following screenshot shows an example of inserting a node.


1. Without removing the power to the 432ES-IG3 network interface module, remove the
link cable at connector J1 of node 4. The safety system transitions from an operational
to a safe state.
- Ch0.Tripped: 0 to 1
- Ch0.Fault: 0 to 1
- Ch0.Status: 1 to 0
- Ch0.UnverifiedDevice: 0 to 1
- Ch0.DeviceCount: 6 to 6 to 0
When the link is broken, the DeviceCount remains at 6. The transition to 0 occurs
when the new tap is added to J1 (Link In) and J2 (Link Out) of the new tap is left open.
- Ch0.DeviceTripAddress: Shows -2 because the trip is due to an external event.
- Ch0.TripTimestamp: Updated to the date and time when the event occurred.
- The Controller Organizer shows status errors on nodes 4 and 5 (IO Faulted), an Invalid
link address.
- On the 432ES network interface module, the CH0 indicator flashes red.
- On the taps, the Link status indicators are steady red, and the Device status
indicators flash green.
Figure 29 - Break Link Cable

2. Connect the new node to the Yellow node. Then connect the J1 of the new node to J2 of
the Orange node.
This connection completes the GuardLink circuit. The device count gets incremented
and there are no additional changes. The safety system remains in a safe state
The following screenshot shows the results after completing the GuardLink
connections.
- Ch0.DeviceCount: 6 to 7
- The channel is still tripped with a fault and unverified device.
- Node 4 correctly reports an Electronic Keying Mismatch because the inserted node is
a different tap catalog number.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 51


Chapter 5 Modify GuardLink Topology

Figure 30 - Node Added to Complete the GuardLink Circuit

Before you insert the node at position 4 in the Controller Organizer, you must reassign the
current nodes Yellow (4) and Green (5) to positions 5 and 6. This change preserves any logic or
automatic diagnostic reporting that is associated with nodes 4 and 5 because the logic is
associated with the node name, not the node number.
3. Take the controller offline.
4. Change the node position from 5 to 6.
5. Select OK.
6. To change node position 4 to position 5, repeat step 3…step 5.

52 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 5 Modify GuardLink Topology

7. The Controller Organizer shows the updated nodes, with node 4 missing. Right-click the
CH0, GuardLink branch and select New Module.

8. In the Select Module Type window, type 440S in the filter field.
9. Highlight the tap that you want to add and select Create.

10. The New Module window automatically populates with the first available node position
(4). Type in a unique name (Blue in this example) for the node and select OK.
- By default, the electronic keying is set to Compatible.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 53


Chapter 5 Modify GuardLink Topology

11. The Blue node appears in position 4. You can now add code to the Main Routine to
capture the event when the Blue node trips.

12. The changes download to the controller.

13. Read the download messages, and select Download.

54 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 5 Modify GuardLink Topology

14. In the follow-up message, select Yes to change the mode back to Remote Run.
15. Set the mode back to Safety Locked.

The 432ES-IG3 network interface module system is Running.

Change a Node In this example, the 440S-SF8D in node position 4 changes to a 440S-SF5D. This change can
take place while the 432ES-IG3 network interface module is powered. There are two cases:
• Case1 - If the Logix Designer application does not use any of the node 4 tags in a
program routine, then the node can change with the controller in Rem Run and Safety
Locked modes.
• Case2 - If the Logix Designer application uses a node 4 tag in a program routine, the
controller must be offline and Safety Unlocked. Delete the existing node, create a node,
and give the node the same name. The program routine for node 4 is retained after you
return the controller online, as long as the name of the node remains the same.

This example demonstrates Case1. The Blue Safety Demand ladder logic from the Insert a Node
section is removed from the main routine. In addition, the safety demand on the Black node is
removed.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 55


Chapter 5 Modify GuardLink Topology

While you replace the tap, the Link cables are disconnected. The channel is in a safe state with
the following CH0 channel tags:
• Ch0.Tripped: 1
• Ch0.Fault: 1
• Ch0.Status: 0
• Cho.UnverifiedDevice: 1

When you install the new tap with the link cables connected and the new switch operational,
the Logix Designer application reports an electronic keying error at node 4. The CH0 channel
tags remain unchanged.
Figure 31 - Node 4 Has a Keying Error

To correct this error, first delete the node, and add the correct catalog number.
1. Right-click the node and then select Delete.

56 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 5 Modify GuardLink Topology

2. The Logix Designer application presents a danger warning. Select Yes if no danger
exists.

3. Right-click the CH0, GuardLink channel and then select Discover Modules.
4. Select Create to add the new modules to the Controller Organizer.

The node number automatically assigns to the first open position, which is position 4.
5. In this example, none of the tags for node 4 are used in a program routine. Therefore,
you can assign a unique name to the node or assign the same name as the node it
replaced.
6. To apply the name, select OK, then close the window.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 57


Chapter 5 Modify GuardLink Topology

7. The online module creation message appears. This window allows you to inhibit module
connection. In this example, leave the box unchecked and select Yes.

8. Close the Module Discovery window.

The new 440S-SF5D tap replaces the 440S-SF8D tap at node position 4, and CH0 transitions to
an operational state with Status at a value of 1.

Append a Node In this example, an additional node is added after the last node. Node topology can change
while power is applied to the 432ES-IG3 network interface module.

When you increase the number of nodes in a GuardLink circuit, you must first understand the
role of the terminator, see Terminator on page 17. When appending additional nodes, remove
power from the last node by removing the Link In connection.

ATTENTION: When you append nodes to a GuardLink circuit, remove the Link
In cable from the last node. After you add the additional nodes with the
terminator at the last node, reconnect the Link In cable.
Failure to break the link signal does not allow the appended node to activate.
Subsequent operation of the appended safety device does not affect the
safety function and can lead to personnel injury.
Conclude changes to the safety system configuration with a risk assessment
verification test.

With the terminator that is connected to the last node, connect the link cables, and the
GuardLink system automatically determines the correct number and type of nodes.

58 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 5 Modify GuardLink Topology

In this example, the node is added in the Logix Designer application first, and then the
hardware is added afterwards. Node 7 is manually added to CH0 in the Logix Designer
application first. The node shows a fault message (Invalid link address). Although a new node
is appended, the CH0 Status remains at 1 (in an operational state) since the hardware has not
changed.

The following recommended steps show how to add nodes to a channel. You can perform
these steps with power applied to the 432ES-IG3 network interface module.
1. Remove the Link In connection to node 6. This action removes node 6 as the GuardLink
Safety Source. Observe these tag changes:
- Ch0.Tripped: 0 to 1
- Ch0.Fault: 0 to 1
- Ch0.Status: 1 to 0
- Ch0.UnverifiedDevice: 0 to 1
- Device Count remains unchanged.
- Node 6 shows a fault (Invalid link address).

432ES-IG3

INPUT INPUT INPUT INPUT INPUT INPUT INPUT

Node 0 1 2 3 4 5 6

2. Remove the terminator from node 6.

432ES-IG3

INPUT INPUT INPUT INPUT INPUT INPUT INPUT

Node 0 1 2 3 4 5 6

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 59


Chapter 5 Modify GuardLink Topology

3. Connect the new tap, with the terminator and safety device to node 6.

432ES-IG3

INPUT INPUT INPUT INPUT INPUT INPUT INPUT INPUT

Node 0 1 2 3 4 5 6 7

4. Reconnect the Link In connection to node 6. Node 7 is the new GuardLink Safety Source.
Observe these tag changes:
- Ch0.Tripped: 1 to 0
- Ch0.Fault: 1 to 0
- Ch0.Status: 0 to 1
- Ch0.UnverifiedDevice: 1 to 0
- Device Count: 7 to 8

432ES-IG3

INPUT INPUT INPUT INPUT INPUT INPUT INPUT INPUT

Node 0 1 2 3 4 5 6 7

Delete a Node You must remove the inner nodes with the controller offline. While offline, the nodes can be
renumbered to maintain a consecutive sequence.

ATTENTION: If you delete nodes while the controller is online, unexpected


behavior, including a nonrecoverable fault that requires a power cycle of the
controller, can occur.

If you remove the last node, you can delete the node with the controller while the host is
online. The controller can be Safety Locked or Unlocked.
• If the tags of any node are used in a program routine, perform the change offline and
download to the controller. Remove both the node and its associated program lines.
• If no node tags are used in a program routine, consider the position of the node.

60 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 5 Modify GuardLink Topology

Remove the Last Node


In this example, the program routines do not use any tags from the last node. The controller is
online, and Safety Locked. The CH0 Status tag is 1 (in an operational state).
1. Right-click the node and select Delete.

2. Select Yes to confirm the deletion.

With the node removed, the 432ES-IG3 network interface module detects an unverified device
(tag = 1). This change causes the Fault tag to be a value of 1, which causes the Tripped tag to
be a value of 1. As a result, CH0 transitions to a safe state; the Status tag shows 0.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 61


Chapter 5 Modify GuardLink Topology

3. Remove the node 7 hardware.


a. Remove the Link In cable to node 6.
b. Remove the Link Out cable from node 6.
c. Add the terminator to node 6.
d. Reconnect the Link In cable to node 6.

Node 6 is now the GuardLink Safety Source. The CH0 Status bit returns to a value of 1
(operational state).

62 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 6
Controller Tags
This chapter contains the controller tags for the GuardLink® system. There are three different
AOPs:
• 432ES-IG3 network interface module
• 440S taps
• 440G guard locking switches

Every tap has the same AOP and every guard locking switch has the same AOP.

Interface Input Tags The following table shows the descriptions of the input tags for the 432ES-IG3 network
interface module.
Table 6 - Interface Input Tags
Automatic
Tag Name Diagnostic Data Type Description
Indicates whether the 432ES-IG3 network interface module is in Run mode or a faulted state.
BOOL • 0channel
= Not in Run mode, or in a fault state (includes recoverable and nonrecoverable faults). When 0, all three SIL 3
RunMode No status bits report as in the safe state.
• 1 = Run mode
Indicates whether the 432ES-IG3 network interface module has a connection to a controller. The controller sets
this bit.
ConnectionFaulted No BOOL • 0 = Connection OK
• 1 = No connection
Indicates whether the 432ES-IG3 network interface module has one or more diagnostics bits set.
DiagnosticActive No BOOL • 0 = No diagnostics active
• 1 = One or more diagnostics codes are present
Indicates whether the 432ES-IG3 network interface module is synchronized with a 1588 Grandmaster clock.
CIPSyncValid No BOOL • 0 = Not synchronized
• 1 = Synchronized
Indicates whether the 432ES-IG3 network interface module was once synchronized with a 1588 Grandmaster clock
but is not now synchronized.
CIPSyncTimeout No BOOL • 0 = No timeout
• 1 = Timeout has occurred
Increments for each time a distinct diagnostic condition is detected and each time a distinct diagnostic condition
transitions from detected to not detected. Set to zero by a power cycle. Wraps from 255…1, skipping zero.
DiagnosticSequenceCount No SINT For example, if the 24V supply drops momentarily to 16V and returns to 24V. The diagnostic sequence count
increments by 2 (by 1 for the transition to 16V and again by 1 for the transition back to 24V).
Voltage Too Low: Indicates whether the module power voltage supply is too low, below 20.3V. Increase the voltage
Yes, to at least 20.4V to clear the warning.
LSystemPowerWarning BOOL • 0 = Voltage not too low
M-LOPWR
• 1 = Voltage too low
Indicates that the supply voltage level to the interface is too high. The trip point occurs between 27V to 28.3V. The
Yes, voltage must be reduced to a level between the specified ranged of 20.4V to 26.4V.
HSystemPowerWarning BOOL
M-HIPWR • 0 = Voltage not too high
• 1 = Voltage too high
Yes, • 0 = No internal fault present
InternalFault BOOL
M-IFLT • 1 = An internal fault is present
Indicates whether the device or port pair is in DLR mode.
DLREnabled BOOL • 0 = Device is not in DLR mode
• 1 = Device is in DLR mode
CHANNEL_
Ch0 - GL:I:0 -
• 0 = No devices have demand on safety function
Ch0.Tripped No BOOL
• 1 = At least one device has demand on safety function

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 63


Chapter 6 Controller Tags

Table 6 - Interface Input Tags (Continued)


Automatic
Tag Name Diagnostic Data Type Description
Indicates whether the GuardLink channel detects a fault. If the channel is disabled, the fault bit sets to 1.
• 0 = Channel fault is not detected; channel has normal data
Yes,
Ch0.Fault BOOL • 1 = Channel fault detected
CH-FLT
This tag is a roll-up of all diagnostic conditions for this channel. This Fault member triggers both the
DiagnosticActive member and increments/decrements the Diagnostic Sequence Count.
Indicates whether the data on the channel is uncertain.
Ch0.Uncertain No BOOL • 0 = Data is valid
• 1 = Data validity is questionable
Indicates whether the GuardLink channel is operational. This tag is the SIL3/PLe safety bit.
Ch0.Status No BOOL • 0 = The channel is in a safe state
• 1 = The channel is in an operational state; the safety conditions for each node on the channel are valid.
Indicates whether a faulted terminator is detected at the end of the GuardLink circuit. This fault does not indicate
Yes, a missing terminator.
Ch0.TerminatorFault BOOL
CH-TFLT • 0 = The terminator is present and functions properly
• 1 = The terminator does not function properly
Indicates whether more than 32 devices are detected on the channel. A missing terminator sets this tag to 1. A
Yes, break anywhere in the channel Link (trunk) cable sets this tag to 1.
Ch0.TooManyDevices BOOL • 0 = Number of devices is no more than 32
CH-DEVCNT
• 1 = Too many devices found on the channel (greater than 32).
Indicates that there are client devices that keying did not verify. A missing terminator sets this tag to 1. In FW 2.001
running with 1.0 taps, an open trunk cable generates an unverified device value of 1. This fault can require you to
Yes, cycle power to the channel to clear the fault.
Ch0.UnverifiedDevice BOOL
CH-DEVUNV • 0 = All devices have been verified
• 1 = Unverified devices present
Ch0.DeviceCount No SINT Indicates the number of client devices (hardware) detected on the channel.
Indicates the client device or event that caused the last transition from the operational to the safe state.
• -1 = After power up.
• -2 = Shows if the device that caused the trip is not known or if the channel is running protocol 1.0. Examples
include an open link cable and a node that cannot respond due to a fault.
• -3 = Shows that you sent an unlock command to one or multiple devices while the channel is in operational
Ch0.DeviceTripAddress No SINT mode. FW 3.001 (with Output Data set to Safety Data in the Module Definition) shows that you set the
LockUnlockEn channel output tag to 1.
• -4 = The channel is set to Not Used on the Channels page of the module properties (see Channels Page on
page 40).
• 0…31 = The non-locking client device that caused the transition. If Node 0 caused the transition, the value is 0. If
Node 17 caused the transition, the value is 17. After the first node causes the trip, subsequent device trips do not
change the DeviceTripAddress, because the subsequent trips did not cause the Status to transition from 1 to 0.
Indicates the time stamp of the last transition from an operational to a safe state. The time stamp is updated for
all causes, whether the cause was due to a device, an inhibit command, a connection fault, or other cause. In the
Ch0.TripTimestamp No LINT list of Controller Tags, change the Style to Date/Time to show the value as a date and time.
A decimal value of 0, shown as a Date/Time, is DT#1969-12-31-19:00:00.000 (UTC-5:00) - adjusted for your time
zone.
CHANNEL_
Ch1 - GL:I:0 See descriptions in Ch0.
CHANNEL_ See descriptions in Ch0.
Ch2 - GL:I:0
AB:Etherne
Port1 - t_Port_Cha —
nnel:S:1
Yes, • 0 = No fault
Port1.Fault BOOL
PORT-FLT • 1 = Fault present on port, or the port is used but not connected.
Indicates whether the data on the port is uncertain.
Port1.Uncertain No BOOL • 0 = Data is valid
• 1 = Data validity is questionable
• 0 = The port is not connected
Port1.Connected No BOOL
• 1 = The port is connected to a network.
• 0 = Half-duplex
Port1.FullDuplex No BOOL
• 1 = Full-duplex

64 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 6 Controller Tags

Table 6 - Interface Input Tags (Continued)


Automatic
Tag Name Diagnostic Data Type Description
Indicates the status of link auto-negotiation.
• 0 = Auto-negotiation in progress.
• 1 = Auto-negotiation and speed detection failed. Using default values for speed and duplex. Default values are
product-dependent; recommended defaults are 10 Mbps and half-duplex.
Port1.AutonegotiationStatus No SINT
• 2 = Auto negotiation has failed but detected speed. Duplex was defaulted. Default value is product-dependent;
recommended default is half-duplex.
• 3 = Successfully negotiated speed and duplex
• 4 = Auto-negotiation not attempted. Forced speed and duplex.
Network speed.
• 10 = 10 Mbps
Port1.Speed No INT
• 100 = 100 Mbps
• 1000 = 1000 Mbps (not supported by the 432ES-IG3 network interface module)
AB:Etherne
Port2 - t_Port_Cha See descriptions in Port1.
nnel:S:1
The number of TCP/IP connections currently open to the adapter. This number will change over time, as
TCPConnections No INT connections are opened and then closed automatically.
The number of CIP™ connections currently open to and through the adapter. This tag consists of 1 safety
CIPConnections No INT connection plus one connection for each used channel. In addition, a channel with over 24 devices use an
additional connection. The max number of expected CIP connections is 7.
A running sum of the number of Sequenced Address Item Sequence Numbers that are skipped in Class 0 and Class
CIPLostPackets No DINT 1 connections that the adapter and its children consume.
A running count of the number of connections that time out, both originated and targeted, both to and through the
CIPTimeouts No DINT adapter.
The number of Class 3 packets and unconnected packets that the device sends and receives in the previous
HMIPacketRate No DINT second.
IOPacketRate No DINT The number of class 0 and class 1 packets that the adapter transmits and receives in the previous second.
The sum over all ports of the following Ethernet Link object values: In Discards, In Errors, In Unknown Protos, Out
Discards, Out Errors, Alignment Errors, FCS Errors, Single Collisions, Multiple Collisions, SQE Test Errors, Deferred
EthernetErrors No DINT Transmissions, Late Collisions, Excessive Collisions, MAC Transmit Errors, Carrier Sense Errors, Frame Too Long,
and MAC Receive Errors.
The percentage of the capacity of the compute engine of the product (whether that is a CPU, a core of a CPU, or a
CPUUtilization No INT thread) most important to the performance of communication of packets by the product. Due to the variations in
communication architectures of various products, each product must define this value that is based on its design.
The current value of the Network Status instance attribute of the DLR object for devices with multiple Ethernet
ports that support DLR. Values:
• 0 = Normal
DLRNetworkState No SINT • 1 = Ring Fault
• 2 = Unexpected Loop Detected
• 3 = Partial Network Fault
• 4 = Rapid Fault/Restore Cycle
Reports as a DLS supervisor.
DLRSupervisorState No SINT • 0 = Not a supervisor
• 1 = Supervisor
The offset in nanoseconds from the local clock to the system time. This value is useful for the detection of steps in
LocalClockOffset No LINT time. This value updates when a PTP update is received.
The time when the Local Clock Offset was most recently sampled. This value is zero and the first-time stamp
LocalClockOffsetTimestamp No LINT occurs when the module synchronizes with the Grandmaster clock.
GrandMasterClockID No SINT[8] The EUI-64 Identity of the CIP Sync™ Grandmaster clock to which the module is synced.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 65


Chapter 6 Controller Tags

Interface Output Tags The following table shows the descriptions of the output tags for the 432ES-IG3 network
interface module. Each channel has a Lock/UnlockEn tag. The Lock/UnlockEn is a safety-rated
signal and should be used in a safety task to allow or prevent locking and unlocking
commands to be processed by the client devices.
The LockUnlockEn tag is only visible and used when firmware 3.001 is selected and the Output
Data is set to Safety Data in the Module Definition.
Table 7 - Interface Output Tags
Automatic
Tag Name Diagnostic Data Type Description
• 0 = Prevents the execution of the lock and unlock commands to the client devices. The channel can transition to
an operating state if all the clients are safety satisfied.
LockUnlockEn No BOOL
• 1 = Immediately sets the channel to a safe state and allows the lock and unlock commands to be sent to the
client devices.

Tap Input Tags The following table lists the controller tags of Bulletin 440S GuardLink-enabled taps. The tags
that Automatic Diagnostics reports update when the tap is in a safe state.
Table 8 - Tap Input Tags
Automatic
Tag Name Diagnostic Data Type Description
• 0 = Not Run mode
RunMode No BOOL
• 1 = Run mode
The device always reports the value as 0. The controller modifies the value. If the connection is faulted, the device
cannot report a fault value, therefore the controller sets the value to 1.
ConnectionFaulted No BOOL • 0 = Connection not faulted
• 1 = Connection faulted
• 0 = No diagnostics active
DiagnosticActive No BOOL
• 1 = One or more diagnostic or prognostics thresholds reached
Increments for each time a distinct diagnostic condition is detected and each time a distinct diagnostic condition
transitions from detected to not detected. Set to zero by product reset or power cycle. Upon power-up, the
DiagnosticSequenceCount No SINT channels are in a fault state until a safety connection is made. Therefore, at least 1 fault always exists after the
reset. Wraps from 255 (-1) to 1, zero is skipped.
CHANNEL_
Pt - DI:I:0 -
• 0 = No demand on safety function
Pt.Data No BOOL
• 1 = Device has demand on safety function
Indicates whether a fault has occurred within the GuardLink-enabled tap. This tag is a roll-up of all diagnostic
conditions for this tap. This fault member triggers both the DiagnosticActive member and increments/decrements
Pt.Fault No BOOL the diagnostic sequence count.
• 0 = No fault
• 1 = Fault present
• 0 = Normal data
Pt.Uncertain No BOOL
• 1= Uncertain status
Status of the aux pin, reported by FW 2.00x or later. DataAux applies only to 8-pin OSSD taps.
DataAux No BOOL • 0 = Aux pin off
• 1 = Aux pin on
Reported only with FW 2 or later. Reports the status of the Node Channel A.
DataA No BOOL • 0 = Channel A off
• 1 = Channel A on
Reported only with FW 2 or later. Reports the status of the Node Channel B.
DataB No BOOL • 0 = Channel B off
• 1 = Channel B on
Device requires a reset. To clear the fault condition, send a DeviceReset command. To clear the fault, cycle power
Yes, to the tap, the channel, or the 432ES-IG3 network interface module.
InternalFault BOOL • 0 = No internal fault
M-IFLT
• 1 = Internal fault
Indicates whether a short circuit between connector pins is present. To clear the fault, cycle power to the tap, the
Yes, channel, or the 432ES-IG3 network interface module.
ShortCircuit BOOL • 0 = No short circuit
M-SHCI
• 1 = Short circuit present

66 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 6 Controller Tags

Table 8 - Tap Input Tags (Continued)


Automatic
Tag Name Diagnostic Data Type Description
Indicates whether the GuardLink safety signal is corrupt, which can be due to electromagnetic interference (EMC).
Possible sources include closely coupled cabling, transients on the ground conductor, internal fault on a
Yes, downstream (higher node number) tap, or other possible causes. To clear the fault, a power system to the
GuardLinkSignalFault BOOL 432ES-IG3 network interface module can be required.
M-SIGFLT
• 0 = Valid safety signal
• 1 = Invalid safety signal
Input voltage is below the minimum specification. The device can continue to operate. For devices operating at
firmware 1, the LSystemPowerWarning is set to 1 if the voltage supply is out of range (high or low). Increase the
Yes,
LSystemPowerWarning BOOL supply voltage to at least 20.4V and cycle power to the 432ES network interface module to clear the warning.
M-LOPWR • 0 = No warning
• 1 = Voltage supply is below minimum specification
Indicates that the supply voltage level at the tap is too high. The trip point typically occurs between 27…28.3V. The
voltage must reduce to a level between the specified ranged of 20.4…26.4V. For devices operating at firmware 1,
Yes, the LSystemPowerWarning is set to 1 if the voltage supply is out of range (high or low).
HSystemPowerWarning BOOL
M-HIPWR • 0 = No warning
• 1 = Voltage supply is above specification
A signal discrepancy between the tap input channels A and B is detected. Check the device wiring and operation.
Perform a functional test of the device and confirm consistent performance of the device outputs. This fault
Yes, typically occurs with mechanically operated contacts and can be cleared by cycling the device.
DiscrepancyFault BOOL
M-DSCFLT • 0 = No discrepancy warning
• 1 = Discrepancy warning

Guard Locking Input Tags The following table shows unique tags of guard locking switches. The tags that Automatic
Diagnostics reports update when the tap is in a safe state.
Table 9 - Guard Locking Input Tags
Automatic
Tag Name Diagnostic Data Type Description
• 0 = Not Run mode
RunMode No BOOL
• 1 = Run mode
The device always reports the value as 0. The controller modifies the value. If the connection is faulted, the device
cannot report a fault value, therefore the controller sets the value to 1.
ConnectionFaulted No BOOL • 0 = Connection not faulted
• 1 = Connection faulted
• 0 = No diagnostics active
DiagnosticActive No BOOL
• 1 = One or more diagnostic or prognostics thresholds reached
Increments for each time a distinct diagnostic condition is detected and each time a distinct diagnostic condition
DiagnosticSequenceCount No SINT transitions from detected to not detected. Set to zero by product reset or power cycle. Wraps from 255 (-1) to 1,
zero is skipped.
CHANNEL_ —
Pt - DI:I:1
• 0 = No demand on safety function
Pt.Data No BOOL
• 1 = Device has demand on safety function
Indicates whether a fault has occurred within the GuardLink-enabled switch. This tag is a roll-up of all diagnostic
conditions for this switch. This fault member triggers both the DiagnosticActive member and increments/
Pt.Fault No BOOL decrements the diagnostic sequence count.
• 0 = No fault
• 1 = Fault present
• 0 = Normal data
Pt.Uncertain No BOOL
• 1= Uncertain status
Status of the door position. For firmware 1, this tag indicates that the door is both closed and locked. For firmware,
2, this tag indicates that the door is closed and ready to lock.
DoorClosed No BOOL • 0 = Door open
• 1 = Door closed
Status of the lock. For firmware 1, this tag is not used. For firmware, 2, this tag indicates that the door is both
closed and locked.
DoorLocked No BOOL • 0 = Can be closed, but is not locked
• 1 = Closed and locked
Device requires a reset; send a DeviceReset command to clear the fault condition or cycle power to the GuardLink
Yes, device.
InternalFault BOOL • 0 = No internal fault
M-IFLT
• 1 = Internal fault

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 67


Chapter 6 Controller Tags

Table 9 - Guard Locking Input Tags (Continued)


Automatic
Tag Name Diagnostic Data Type Description
This tag name applies to unique coded locking switches. Verify that the actuator is a unique (not standard) coded
actuator that has not been previously taught to this switch. A switch that requires a unique coded actuator cannot
Yes,
InvalidActuatorFault BOOL validate standard actuators.
M-ACTFLT • 0 = No fault
• 1 = Invalid actuator fault
This tag name applies to unique coded locking switches. No more learns are allowed. The teach process was
locked after the last actuator was taught or the switch has already learned 8 actuators. The eighth actuator
Yes, remains functional.
TeachLimitExceeded BOOL
M-ACTLIM • 0 = No fault
• 1 = Teach limit fault
This tag name applies to unique coded locking switches. Actuator moved out of range during teach process. Cycle
Yes, power to switch and restart the teach process.
TeachProcessError BOOL • 0 = No fault
M-ACTTCH
• 1 = Fault
During the operational state, the device failed to detect the movement of the internal solenoid-driven locking bolt
to the lock position. If installed, check to see if the escape release button has been pressed. We only detect the
Yes, bolt extended, not retracted.
LockDetectionFault BOOL The DiagnosticActive bit is set to 1, and the DiagnosticSequenceCount increments by 1.
M-LCKDET
• 0 = No fault
• 1 = Fault
In the safe state, the device attempted to lock or unlock for a specified attempt length, but status input did not
indicate the device locked/unlocked. Device failed to lock or unlock. Check for excessive sideload and
Yes,
LockingFault BOOL misalignment. The DiagnosticActive bit is set to 1, and the DiagnosticSequenceCount increments by 1.
M-LCKFLT • 0 = No fault
• 1 = Fault
During the operational state, the device failed to detect the actuator.
Yes, The DiagnosticActive bit is set to 1, and the DiagnosticSequenceCount increments by 1.
ActuatorDetectionFault BOOL • 0 = No fault
M-ACTDET
• 1 = Fault
The actuator present is not the actuator that is paired with the switch.
Yes, The DiagnosticActive bit is set to 1, and the DiagnosticSequenceCount increments by 1.
ActuatorNotPairedFault BOOL
M-ACTNPR • 0 = No fault
• 1 = Fault
Reports whether a guard locking switch has reached its limit of 8 for learning a new actuator, or additional teaches
are prevented during configuration. The eighth or the last taught actuator remains functional.
TeachDisabled No BOOL • 0 = Additional learns remain
• 1 = No more learns allowed
Device has reached 100% of its rated mechanical life.
EndOfLifeWarning No BOOL • 0 = End of Life not reached
• 1 = End of Life reached
Yes, • 0 = Temperature does not exceed rated specification
OverTemperature BOOL
M-OTMP • 1 = Temperature exceeds rated specification
Yes, • 0 = Temperature not lower than rated specification
UnderTemperature BOOL
M-UTMP • 1 = Temperature lower than rated specification
Indicates whether the GuardLink safety signal is corrupt, which can be due to electromagnetic interference (EMC).
Yes, Possible sources include closely coupled cabling, transients on the ground conductor.
GuardLinkSignalFault BOOL
M-SIGFLT • 0 = Valid safety signal
• 1 = Invalid safety signal
Input voltage is below the minimum specification. The device can continue to operate. For devices operating at
firmware 1, the LSystemPowerWarning is set to 1 if the voltage supply is out of range (high or low). Increase the
Yes, supply voltage to at least 20.4V to clear the warning.
LSystemPowerWarning BOOL
M-LOPWR • 0 = No warning
• 1 = Voltage supply is below minimum specification
Indicates that the supply voltage level at the tap is too high. The trip point typically occurs between 27…28.3V. The
voltage must reduce to a level between the specified ranged of 20.4…26.4V. For devices operating at firmware 1,
Yes,
HSystemPowerWarning BOOL the LSystemPowerWarning is set to 1 if the voltage supply is out of range (high or low).
M-HIPWR • 0 = No warning
• 1 = Voltage supply is above specification

68 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 6 Controller Tags

Tap and Guard Locking The following table shows the node output tags. These tags apply to Bulletin 440S GuardLink-
enabled taps and Bulletin 440G GuardLink-enabled switches. When a non-guard locking device
Output Tags connects to a tap, the connected device ignores the lock and unlock commands. All devices
can execute the ResetDevice.
Table 10 - Node Output Tags
Automatic
Tag Name Diagnostic Data Type Description
• 0 = Cancels the previous lock command for the client device (does not unlock the device)
Lock No BOOL
• 1 = On the transition from 0 to 1, sends a lock command to the client device
• 0 = Cancels the previous unlock command for the client device (does not lock the device)
Unlock No BOOL
• 1 = On the transition from 0 to 1, sends an unlock command to the client device
• 0 = Cancels the previous ResetDevice command for the client device
ResetDevice No BOOL • 1 = On the transition from 0 to 1, sends a power cycle reset command to the client device. Use this command to
clear a fault in the client device.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 69


Chapter 6 Controller Tags

Notes:

70 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 7
Troubleshooting
Diagnostic Status The following image and table define the diagnostic status indicators on the 432ES-IG3
network interface module.
Indicators
Figure 32 - Diagnostic Status Indicators

Link 1 Link 2
Module Status (MOD) Network Status (NFT)
Ch0
GuardLink Channel 0
Ch1
GuardLink Channel 1

Ch2
GuardLink Channel 2

PWR
Module Power

Table 11 - Diagnostic Status Indicators


Indicator Status Description
Off Module is not powered.
Flashing red/ Module is not configured with an IP address, or module is in self-test.
green
Flashing green
Module is idle. Waiting for connection from controller.
Steady greenModule is powered, configured, and operating correctly (Running mode).
Update in progress (Configuration mode).
Module status IP/ Target Unique Network Identifier (TUNID) mismatch - reset ownership with
(MOD) controller.
Recoverable fault - cycle power to reset.
Flashing red Special modes:
000 - Disable explicit protection
888 - Restore factory default
900 - Set explicit protection
Unrecoverable fault detected (Critical Fault mode). Cycle the power and verify
Steady red that the network is working properly.
The module does not have an IP address and is operating in DHCP mode.
Special modes:
Off 000 - Disable explicit protection
888 - Restore factory default
900 - Set explicit protection
Network status Flashing green The module has an IP address, but no CIP™ connections are established. A
(NET) module connection can be inhibited.
Steady green The module has an IP address and CIP connections are established; operating
normally.
Flashing red An exclusive owner connection has timed out.
The module detected an error that prevents communication on the network,
Steady red such as a duplicate IP address.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 71


Chapter 7 Troubleshooting

Table 11 - Diagnostic Status Indicators (Continued)


Indicator Status Description
Off No link/no activity.
LINK1 or LINK2 Steady green Link established.
status
Flashing green Transmit or receive activity.
No GuardLink® communications established. The channel is set to unused and
Off has no client devices connected.
Green Channel is in an operational state. Communication OK, operating normally.
Flashing red/ The client is updating on this link. The link is in a safe state.
green
• Incorrect configuration.
• Short circuit on the link.
• Client number mismatch.
• GuardLink-enabled device mismatch.
• The terminator is not on one of the used GuardLink channels.
Ch0…Ch2 • A channel is set to unused and has at least one connected client device.
status • A channel is set to used but does not have a connected client device.
Flashing red • The GuardLink Host adapter is not getting a response from all client devices
when establishing the channel at power up.
• If the last device to respond to a broadcast message is the same device for
10 consecutive requests.
• More than 32 devices on the GuardLink Channel.
• Fault on the CLU line. Invalid pattern or short.
• The configuration of each client device on the channel does not match
expected client device configuration on Studio 5k (AOP).
• A GuardLink 1.0 client device is on the host adapter channel 2
Red Channel is in Safe mode.
Off No power is applied, or severe input power overvoltage.
Module power Steady green Normal operation (20.6…26.4V)
Steady red Input power out of specification (outside of 20.4…26.4V)

Faults Faults report at three different levels:


• Controller Organizer faults
• Channel faults
• Node faults

The Studio 5000 View Designer® and Logix Designer application aid in the identification and
remediation of faults. See Controller Tags on page 63. The descriptions of each tag can
provide insight into the possible causes of a nonoperating condition.

Controller Organizer Faults


The Controller Organizer reports faults with the architectural structure. The controller
compares the nodes that connect to each channel compared to the nodes that are listed in the
controller tree.

If multiple nodes show faults on a channel, correct the lowest-numbered node first.
Occasionally, higher-numbered nodes can show faults due to the lower-numbered faults.
Invalid Link Address

This fault can occur if:


• The node exists in the controller tree, but the hardware is not present.
• The link cable is disconnected at some point in the channel. The controller tree shows
that the link is broken between the running node and all nodes that have an
exclamation icon (!). If all nodes show an exclamation icon, check the cable between the
432ES network interface module and the first node.
• The terminator is removed from the channel and power is cycled to the channel.

72 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 7 Troubleshooting

Electronic Keying Mismatch

This fault occurs if major and/or minor revisions are invalid or incorrect. For example:
• You replace a Series A product with a Series B product without changing the Module
Definition.
• You replace a tap with another type of tap, such as an 8-pin OSSD replaces an 8-pin
EMSS.
Take the channel offline and correct the Module Definition.

Channel Faults
The channel fault bit indicates a channel fault. If the channel fault bit is set to 1, check if other
bits are set to 1.

If no other bits show a fault, check the value of the DeviceTrip Address. If the value is -1, then
no nodes caused the fault. A disconnected cable or the channel set to Unused can cause the
fault.

Node Faults Fault Status Indicators


There are status indicators on the taps, 440G-MZ safety switches, and the network interface
module.

If the device status indicators on all taps flash green and the link status indicators show
steady red, and the channel status indicator on the 432ES network interface module flashes
red, then:
• Hardware nodes are added, but not added to the controller tree.
• The Channels page of the 432ES network interface module shows Unused.

All Nodes Faulted

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 73


Chapter 7 Troubleshooting

Review the GuardLink Channel tags in the Controller tags:


• TerminatorFault: 1 (indicates a terminator fault)
• Tripped bit: 1 (set because the Fault bit is 1)
• Status bit: 0 (safe state)
• Fault bit: 1 (fault is present)
• DeviceTripAddress: -1 (none of the nodes caused the fault)
• Terminator bit: 1

Replace the terminator and cycle power to the channel or to the network interface module.
The controller recognizes all nodes and removes the fault status.

Verify Module Properties Use the FactoryTalk® Linx Network Browser to verify that devices are on the network, to
gather information about the devices, and to upload the EDS file, which gets the proper icon.
1. On the Start menu, select Rockwell Software® > FactoryTalk Linx Network Browser.
2. Expand the Ethernet node and expand the GuardLink® Interface.
3. Expand each of the GuardLink channels.
The GuardLink number is sequential and is automatically assigned, based on earlier
installations of a GuardLink interface. In the following example, the network browser
has three GuardLink channels:
- CH 0, GuardLink 13 (seven nodes connected)
- CH 1, GuardLink 14 (zero nodes connected)
- CH 2 GuardLink 15 (three nodes connected)

74 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Chapter 7 Troubleshooting

4. Highlight a device, right-click, and select Device Property.

The general properties show a GuardLink-enabled tap with firmware revision 2.001. Additional
properties will be added in future firmware updates.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 75


Chapter 7 Troubleshooting

Verify Device on the Use the FactoryTalk Linx Network Browser to verify that devices are on the network. This
feature is only available when the channel is in a safe state, a demand is placed on the safety
Network system, or a node is inhibited.

This feature only applies to nodes with firmware revision 2 or higher. All devices on the
channel must be 2 or higher. If the channel includes a device with firmware 1, the device
locator function cannot be used.
To determine the revision level of all devices on a channel, use the Discover
Modules feature in the Logix Designer application. Establish the host computer
online with the controller, double-click the desired channel, and select Discover
Modules. All nodes are listed with their firmware revision.
When a channel is in safe state, the Link status indicator is steady red on all nodes (devices).
When the Device Locator function is used, the Link status indicator alternates flashing red
0.5 second and green 0.5 second for the specified duration.
The following example shows where the blink duration is adjusted from the default of 9
seconds to 30 seconds. Select Blink to initiate 30 seconds to find the device.

Cannot Disable DHCP If the 432ES-IG3 network interface module is connected to a Logix controller during
configuration, DHCP cannot be disabled. In the EtherNet/IP™ Commissioner window, the
communication error is, “Failed to complete the requested operation.” [Set_Attribute_Sinlge]
(16).

Fix this error in one of two ways:


• Connect the 432ES-IG3 directly to the EtherNet/IP Commissioner (or BOOTP/DHCP tool)
or
• Remove the controller from the network.

Then, take the following steps:


1. Reset the 432ES-IG3 with IP address 888 and cycle the power.
2. Return the IP address switches back to 999 and cycle power.
The EtherNet/IP Commissioner can now be used to set the IP address and disable DHCP.
During this process, the Module Status indicator flashes red/green.
3. Connect the Ethernet cables to restore the network.
After the controller makes the connection, the Module Status indicator changes to
steady green.

76 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Appendix A
Specifications
Catalog Number Table 12 - 432ES-IG3 GuardLink Network Interface Module
Explanation
432 E S - I G 3
a b c d e f

a b c
Code Description Code Description Code Description
432 Bulletin number (1) E EtherNet/IP S Safety
(1) Safety on-machine module.

d e f
Code Description Code Description Code Description
I Inputs G GuardLink input Number of input
3 channels

General
Value
Attribute
Temp/Voltage 20.4V 24V 26.4V
Power supply 24V DC +10/-15%, NEC Class 2, PELV (SELV when alternative ground fault detection is used)
Power supply cable length, max 30 m (98.42 ft)
-20 °C (-4 °F) 84 mA 74 mA 68 mA
Operating current (typical) (1) 25 °C (77 °F) 86 mA 75 mA 70 mA
60 °C (140 °F) 87 mA 76 mA 71 mA
Safety response time 30 ms
Communication rate EtherNet/IP™ 10/100 Mbps
Internet Protocol IPv4 addressing
CIP Sync CIP Sync™/IEEE 1588 end-to-end transparent clock supported
IEC 61784-3-2: Functional safety fieldbus
Additional specifications for CPF 2 according to:
• IEC 61158-1: Overview and guidance for the IEC 61158 and IEC 61784 series
CIP Safety™ standards • IEC 61158-3-2: Datalink layer service definition - Type 2 elements
• IEC 61158-4-2: Datalink layer protocol specification - Type 2 elements
• IEC 61158-5-2: Application layer service definition - Type 2 elements
• IEC 61158-6-2: Application layer protocol specification - Type 2 elements
(1) Operating with two active Ethernet ports and no GuardLink® connections.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 77


Appendix A Specifications

Environmental
Attribute Value
Operating temperature -20…+60 °C (-4…+140 °F)
Storage temperature -40…+85 °C (-40…+185 °F)
Relative humidity Up to 95%, noncondensing
Pollution degree 3
Emissions CISPR 11, Group 1, Class A
IP20 with no QD connections
Enclosure type rating IP66, 67, 69K with connectors and the sealed covers installed properly
• Covers torque: 0.15 ±0.005 N•m (1.34 ±0.04 lb•in)
• 10…57 Hz, 0.762 mm (0.002 in.)
Vibration
• 57…500 Hz, 5.0 g

Shock • Powered: 30 g, 11 ms
• Unpowered: 50 g, 11 ms
In Operational mode, IEC 61000-4-2 to performance criteria A per IEC 61326-1
• 6 kV contact, 8 kV air discharge
ESD immunity
In Safe mode, IEC 61000-4-2 to performance criteria DS per IEC 61000-6-7
• 8 kV contact, 9 kV air discharge
In Operational mode, IEC 61000-4-3 to performance criteria A per IEC 61326-1
• 10V/m with 1 kHz sine wave 80% AM from 80 MHz…2.0 GHz
• 10V/m with 200 Hz 50%, pulse 100% AM at 900 MHz
• 10V/m with 200 Hz 50%, pulse 100% AM at 1890 MHz
• 3V/m with 1 kHz sine wave 80% AM 2.0...2.7 GHz
Radiated RF immunity
• 3V/m with 1 kHz sine wave 80% AM 2.7...6.0 GHz
In Safe mode, IEC 61000-4-3 to performance criteria DS per IEC 61000-6-7
• 20V/m with 1 kHz sine wave 80% AM from 80 MHz…2.0 GHz
• 20V/m with 200 Hz 50%, pulse 100% AM at 900 MHz
• 20V/m with 200 Hz 50%, pulse 100% AM at 1890 MHz
In Operational mode only, IEC 61000-4-4 to performance criteria B per IEC 61326-1
• ±3 kV at 5 kHz on power ports
EFT immunity
• ±3 kV at 5 kHz on Communication ports
• ±3 kV at 5 kHz on GuardLink Channel ports
In Operational mode, IEC 61000-4-5 to performance criteria B per IEC 61326-1
• ±500V line-to-line (Differential mode) and +/-1 kV line to Earth (Common mode) on
GuardLink ports with 42 Ω source
• ±2 kV line to Earth (Common Mode) on communication ports with 42 Ω source
Surge transient immunity In Safe mode, IEC 61000-4-5 to performance criteria DS per IEC 61000-6-7
• ±2 kV line to ground (Common mode) on power ports with 12 Ω source
• ±2 kV line to ground (Common mode) on GuardLink ports with 42 Ω source
• ±2 kV line to ground (Common mode) on communication ports with 42 Ω source
In Operational mode, IEC 61000-4-6 to performance criteria A per IEC 61326-1
Conducted RF immunity • 10V rms with 1 kHz sine wave 80% AM from 150 kHz to 80 MHz on all ports
In Safe mode, IEC 61000-4-6 to performance criteria DS per IEC 61000-6-7
• 20V rms with 1 kHz sine wave 80% AM from 150 kHz to 80 MHz on all ports
EMC emissions In Safe mode only, CISPR 11: Group 1, Class A
In Operational mode only, IEC 61000-4-29 to performance criteria DS per IEC 61326-3-1
EMC voltage dips
• Voltage dips; 40% of rated voltage for 10 ms on DC power
In Operational mode only, IEC 61000-4-8 and Volume 2: EtherNet/IP Adaptation of CIP™,
EMC magnetic field edition 1.26, table 8-9.2
• 30 AM, 50 Hz, 60 Hz, 1 min

78 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Appendix B
Certifications and Directives
Agency and Directive Marks
Region/Body Mark Description

UL Listed Industrial Control Equipment that is certified for


U.S.A./Canada US and Canada.

ODVA conformance tested to EtherNet/IP™ specifications


United States and CIP Safety™, CIP Sync™, and CIP Security™
requirements.

CE Marked for all applicable directives.

European Union
Waste Electrical and Electronic Equipment (WEEE) - At the
end of its life, this equipment must be collected separately
from any unsorted municipal waste.

RCM: Australian Radiocommunications Act compliant with


Australia/New Zealand AS/NZS CISPR 11: Industrial Emissions.

Korean Registration of Broadcasting and Communications


Korea Equipment, compliant with: Article 58-2 of the Radio Waves
Act, Clause 3.

The UK Conformity Assessed mark is used for goods being


United Kingdom placed on the market in Great Britain (England, Wales, and
Scotland).

Mandatory conformity mark for electronics and


Morocco electrotechnical products.

RoHS (Restriction of Hazardous Substances), environment-


China friendly use period of 25 years.

Declaration of Conformity CE Conformity


This product is CE marked and is approved for installation within the European Union and
EEA regions. This product is designed and tested to meet the European Council Directive
2006/42/EC on machinery and the following standards.
• IEC/EN 61508 - Functional safety of electrical/electronic/programmable electronic
safety-related systems
• IEC/EN 62061 - Safety of machinery - Functional safety of safety-related electrical,
electronic, and programmable electronic control systems
• EN ISO 13849-1 - Safety of machinery - Safety-related parts of control systems -
Part 1: General principles for design

This product is intended for use in an industrial environment. For a comprehensive CE


certificate visit rok.auto/certifications.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 79


Appendix B Certifications and Directives

UKCA Conformity
This product is UKCA marked and is approved for installation within the United Kingdom
regions. This product is designed and tested to meet the Supply of Machinery (Safety)
Regulations 2008 No. 1597 on machinery and the following standards.
• IEC/EN 61508 - Functional safety of electrical/electronic/programmable electronic
safety-related systems
• IEC/EN 62061 - Safety of machinery - Functional safety of safety-related electrical,
electronic, and programmable electronic control systems
• EN ISO 13849-1 - Safety of machinery - Safety-related parts of control systems -
Part 1: General principles for design

This product is intended for use in an industrial environment. For a comprehensive UKCA
certificate visit rok.auto/certifications.

SIL Rating This product meets the requirements of the safety integrity limit of SIL 3 per IEC/EN 61508.
The SIL 3 rating only applies to the GuardLink® safety signal. This product is suitable for use in
the IEC/EN 62061 applications up to SIL 3.
Attribute Rating
SIL (IEC/EN 61508) 3
PFDavg
Average probability of a dangerous failure on demand 1.95E-04
(IEC/EN 61508, not in IEC/EN 62061)
PFHD [/h] average frequency of a dangerous failure per 2.88E-09
hour
Mode of operation High Demand mode
Safety-related subsystems Type B (use of programmable / complex components)
Hardware fault tolerance, HFT 1
Safe failure fraction, SFF [%] 95.6

The SIL rating of the lock and unlock command with firmware 3.001 or later:
Attribute Rating
SIL (IEC/EN 61508) 2
PFDavg
Average probability of a dangerous failure on demand 2.54E-03
(IEC/EN 61508, not in IEC/EN 62061)
PFHD [/h] average frequency of a dangerous failure per 2.97E-08
hour
Mode of operation High Demand mode
Safety-related subsystems Type B (use of programmable / complex components)
Hardware fault tolerance, HFT 0
Safe failure fraction, SFF [%] 95

80 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Appendix B Certifications and Directives

Performance Level/ The Performance Level of the safety function is dependent on the structure of all devices that
comprise the safety function.
Category
This product can be used in safety systems that meet up to Category 4 and Performance Level
PLe in accordance with ISO 13849-1.
Attribute Rating
Category 4
Performance Level PLe (1)
MTTFd [years] 184
Diagnostic Coverage, DCavg [%] 91.3
Days, dop [days/year] 365
Hours, [hours/day] 24
T [years] 20
(1) Applies to GuardLink safety signal only.

The Performance Level rating of the lock and unlock command with firmware 3.001 or later:
Attribute Rating
Category 2
Performance Level PLd
MTTFd [years] 127.6
Diagnostic Coverage, DCavg [%] 90
Days, dop [days/year] 365
Hours, [hours/day] 24
T [years] 20

EMC Directive This product is designed and tested to meet the European Council Directive 2004/108/EC on
Electromagnetic Compatibility (EMC) and the following standards:
• EN 61000-6-4: Generic Standards - Emission Standard for Industrial Environments
• EN 61000-6-2: Generic Standards - Immunity for Industrial Environments

This product is intended for use in an industrial environment.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 81


Appendix B Certifications and Directives

Notes:

82 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Appendix C
Safety Statements
CIP Safety Devices When using CIP Safety™ devices, follow these guidelines:
• To replace safety devices, you must properly configure the replacement device and
verify the operation of the replacement device.
• If you choose to configure safety connections with a safety configuration ID (SCID)=0,
you are responsible for confirming that the originators and targets have the correct
configurations.
• Assign SNN numbers for each safety network or safety subnet that are unique system-
wide.
• When a safety device is configured directly from a workstation, compare the
transferred SCID and configuration data with the SCID and configuration data that is
originally viewed in the workstation.
• You must validate all downloads.
• Only after you have tested the signature is it verified (and configuration locked).
• When you configure an originator with connection data and/or target configuration,
download the data to the target so you can test and verify the data. Only after this step
is complete, confirm SCIDs from the target.
• Test the operation of a device completely before you set the Lock attribute.
• Clear any pre-existing configuration from any safety device before you install the
device onto a safety network.
• Commission all safety devices with MAC ID (and communication rate, if necessary)
before you install the device onto a safety network.
• When you implement a safety function, carefully consider the implications of mixing
different SIL level devices on the network.
• Test safety connection configurations after they are applied in an originator to confirm
that the target connection is operating as intended.

ATTENTION:
• Status indicators are not reliable indicators and cannot be guaranteed to
provide accurate information. They must only be used for general diagnostics
during commissioning or troubleshooting. Do not attempt to use status
indicators as operational indicators.
• Originators with an automatic SNN setting feature must only use that feature
when the safety system is not being relied upon.
• If a Type 1 Safety Open configures a device, verify that all
originator-configured safety devices have their ownership assignments as
part of the final verification process.
• Visually verify that all configuration data was downloaded correctly.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 83


Appendix C Safety Statements

Notes:

84 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Appendix D
Uninstall the Logix Designer Application Module
Profile
Instructions This appendix describes the steps to remove the Module Profile from Studio 5000®.
1. Go to a DoS command prompt.
2. Change the directory to the location of the module profiles. Following is the typical
location. Copy and paste this DoS command to the DoS prompt.
CD \Program Files (x86)\Rockwell Software\RSLogix 5000\Module Profiles\Install
3. Type the command (MPSetup /cu).

4. From the Setup Wizard, select Next

5. Select Next to uninstall.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 85


Appendix D Uninstall the Logix Designer Application Module Profile

6. Navigate to the GuardLink® Adaptor EIP Module Profile, check the box, and select Next.

7. Expand the GuardLink Adaptor to reveal the list of products to remove. This selection
removes the 432ES network interface module and all client devices.
8. Select Uninstall.

9. Uninstall was successful. Select Next.

10. Select Finish in the final window.

86 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Appendix E
Configure Automatic Diagnostics
On the Controller properties Advanced tab, Enable Automatic Diagnostics is a new feature that
was added with the 1756-L8x controllers and firmware revision 33. When enabled, it sends
analog I/O modules diagnostic information to the Automatic Diagnostics Event Summary
object.

If deactivated, you only see Mode changes and loss on communication with controllers in the
Automatic Diagnostics Event Summary object.

The automatic diagnostics feature is enabled by default in the Logix Designer application as
shown in the following screenshot. The deactivation of automatic diagnostics at the device
level deactivates all device-driven diagnostics. You still get device faulted/communication
loss diagnostics as the controller drives these diagnostics.
Figure 33 - 432ES Module Properties

Only device Add-on Profiles (AOP) that have been updated with additional diagnostics show the
Enable Automatic Diagnostics checkbox (shown in the previous screenshot). You can use this
checkbox to verify if the AOP of your device has been updated with additional diagnostics.

IMPORTANT Application alarms, such as analog input module high/low limit process
alarms, are not included.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 87


Appendix E Configure Automatic Diagnostics

Automatic Diagnostics on Automatic diagnostics are enabled by default on all devices. When you use a PanelView™ 5000
display with firmware revision 8 or later, the automatic diagnostic messages from the device
PanelView 5000 Display display automatically. For more information, see the Automatic Diagnostics chapter in the
Studio 5000 View Designer Getting Results Guide, publication 9324-GR001.
When specific events occur, messages automatically report because the controller links to the
PanelView 5000 display. In your View Designer project properties, set the Controller
References to the controller of the 432ES network interface module (see the following
screenshot):
• Logix project File
• HMI to controller
• Emulator to controller path
Figure 34 - Bind Controller to PanelView Project

When an event occurs, the diagnostic icon shows the number of active and unsuppressed
diagnostic events, as shown in the following screenshot. Each line entry shows:
• State: Active, inactive, or suppressed
• Event Time: Date and time when the event occurred
• Device Name: Path to the device and the device name
• Message: Preprogrammed message for the diagnostic code
• Diagnostic Code: The diagnostic code that applies to the event

IMPORTANT You can rearrange and configure additional columns. See Studio 5000
View Designer® help for more information.

88 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Appendix E Configure Automatic Diagnostics

Figure 35 - Diagnostics Page on PanelView 5510

432ES-IG3 network interface modules, Bulletin 440S taps, and 440G-MZ safety switches have
unique diagnostic codes that report automatically as shown in the following tables.
Table 13 - 432ES-IG3 Network Interface Module Diagnostics
Display Code Diagnostic Message
CH-FLT Channel x is faulted.
M-HIPWR Module has a high system power warning.
M-LOPWR Module has a low system power warning.
M-IFLT Module has an internal fault.
CH-TFLT Channel x has a terminator fault.
CH-DEVCNT Channel x exceeds the device count limit.
CH-DEVUNV Channel x has an unverified device.
PORT-FLT Ethernet port is not connected.

Table 14 - Bulletin 440S Tap and 440G-MZ Safety Switch Diagnostics


Display Code Diagnostic Message
M-HIPWR Module has a high system power warning.
M-LOPWR Module has a low system power warning.
M-IFLT Module has an internal fault.
M-SHCI Module has a short circuit or overcurrent condition.
M-ACTFLT Module has an incorrect actuator inserted.
M-ACTLIM Module has reached the actuator teach limit.
M-ACTTCH Module has not completed the teach process with the actuator.
M-LCKDET Module has a lock detection fault.
M-LCKFLT Module is unable to lock or unlock as commanded.
M-ACTNDT Module does not detect the actuator in the closed position.
M-OTMP Module has an over temperature condition.
M-UTMP Module has an under temperature condition.
M-DSCFLT Module has a discrepancy fault.
M-ACTNPR Module has an actuator not paired condition.
M-SIGFLT Module has a GuardLink® signal fault.

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 89


Appendix E Configure Automatic Diagnostics

Notes:

90 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Index

Numerics explanation 77
440G 63, 69
432E 440S 66, 69
dimensions 21 440S-SF5D 55, 58
mounting 21 440S-SF8D 55, 58
432ES-IG3 56RF 25
channels 13 889D-F4AEDM-x 24
communication speed 42 889D-F4AE-x 23
connections 25 889D-F4NEDM-x 24
connector 22 889D-R4AEDE-x 24
features 12 889D-R4AE-x 23
inhibit 36 explanation 77
nodes 49 category 81
power 24 CE conformity 79
status indicators 71 certifications 79
tags 63
change node 55
topology 43
440G channel faults 73
tags 63, 69 channels 16
440S channels page 40
tags 66, 69 commissioning
example 18
components 13
A connection page 35
additional resources 9 controller online 49
address
invalid 72
append node 58 D
append nodes 44 declaration of conformity 79
audience 7 default
automatic diagnostics 12 blink duration 76
duplex 65
electronic keying 53
B network delay multiplier 38
speed 65
before frimware update 28 timeout multiplier 38
definitions 8
C diagnostic status indicator
status indicator
cable diagnostic 71
clearance 22 dimensions 21
case 1 15 discover modules method 45
case 2 15
catalog number
1585D-E4UBDE-x 24 E
1585D-E4UBJM-x 24 electronic keying mismatch 73
1585D-M4UBDM-x 24
EMC directive 81
1585D-M4UBJM-x 24
1606-XLP30E 24 environmenta 78
1606-XLP50E 24
1606-XLP50EZ 24
1606-XLP72E 24
1606-XLP95E 24
1607-XT100D1B 24
1732E 25
432ES 21
432ES-IG3 7, 11, 12, 13, 22, 24, 25, 36, 42, 43,
49, 63, 71

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 91


Index

F M
fault 61, 72 manual method 44
ActuatorDetectionFault 68 mismatch
ActuatorNotPairedFault 68 electronic keying 73
after reset 66 mode
all nodes 73 common 78
Ch0.Fault 51, 56, 64 configuration 71
Ch0.TerminatorFault 64 critical fault 71
Ch0.UnverifiedDevice 64 DHCP 71
channel 73 differential 78
clear 69 DLR 63
ConnectionFault 40 firmware update 13
ConnectionFaulted 36, 63, 66, 67 high demand 80
controller organizer 72 no run 66, 67
DiscrepancyFault 67 operational 13, 78
GuardLinkSignalFault 67, 68 production 49
InternalFault 63, 66, 67 program 38, 39
InvalidActuatorFault 68 rem prog 44, 49
IO 51 rem run 44, 45, 49, 55
levels 72 rem test 44, 49
LockDetectionFault 68 remote run 55
LockingFault 68 run 13, 36, 38, 39, 40, 49, 63, 66, 67
major 40 running 71
message 59 safe 72, 78
minor 40 safe state 13
module fault 35 safety locked 49, 55
node 73 safety unlocked 38
partial network 65 safetylocked 36
Port1.Fault 64 special 71
Pt.Fault 66, 67 start up 13
rapid 65 test 38, 39
recoverable 40, 71 modes 13
ring 65
state 63 module definition 34
TeachLimitExceeded 68 module profile
TeachProcessError 68 view 33
TerminatorFault 74 module profiles
unrecoverable 40, 71 install 31
features 12
firmware 13
frimware update N
before 28 network page 43
node
delete 60
G remove last 61
general page 33 node faults 73
guard locking input tags 67, 69 node tags 49

H O
high vibration 21 online node changes 49
overview 11, 49
ownership
I reset 38
inhibit module 36
insert node 50
interface input tags 63 P
internet protocol page 41 performance level 81
invalid link address 72 port configuration page 42
power supplies
multiple 25
K power supply 24
keying mismatch 73

92 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


Index

R
reaction time limit 38
requirements 11
reset ownership 38

S
safety locked 49
safety network number 34
safety page 37
safety unlocked 49
SIL rating 80
SNN 34
specifications
environmental 78
general 77
status indicator
blink 76
Ch0 12
Ch1 12
Ch2 12
device 51
diagnostics 71
fault 73
link 51, 76
link 1 12, 71
link 2 12, 71
module 12, 71
network 12, 71
PWR 12, 71
system design 13

T
tag
guard locking input 67, 69
interface input 63
tap 69
tap input 66
tap connections 14
tap input tags 66
tap replacement 16
taps 13
terminator 17
time sync page 43

U
UKCA conformity 80
update firmware 28

W
wiring 23

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 93


Index

Notes:

94 Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024


GuardLink EtherNet/IP Interface User Manual

Notes:

Rockwell Automation Publication 432ES-UM001D-EN-P - November 2024 95


Rockwell Automation Support
Use these resources to access support information.
Find help with how-to videos, FAQs, chat, user forums, Knowledgebase, and product
Technical Support Center rok.auto/support
notification updates.
Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/phonesupport
Quickly access and download technical specifications, installation instructions, and user
Technical Documentation Center rok.auto/techdocs
manuals.
Literature Library Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature
Product Compatibility and Download Center Download firmware, associated files (such as AOP, EDS, and DTM), and access product rok.auto/pcdc
(PCDC) release notes.

Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the
form at rok.auto/docfeedback.

Waste Electrical and Electronic Equipment (WEEE)

At the end of life, this equipment should be collected separately from any unsorted municipal waste.

Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.

Allen-Bradley, ControlFLASH, ControlFLASH Plus, ControlLogix, expanding human possibility, FactoryTalk, GuardLink, GuardLogix, Guardmaster, Logix 5000, PanelView, Rockwell Automation,
Rockwell Software, Studio 5000, Studio 5000 Logix Designer, and Studio 5000 View Designer are trademarks of Rockwell Automation, Inc.
CIP, CIP Safety, CIP Security, CIP Sync, ControlNet, DeviceNet, and EtherNet/IP are trademarks of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur

Publication 432ES-UM001D-EN-P - November 2024


Supersedes Publication 432ES-UM001C-EN-P - October 2024 Copyright © 2024 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

You might also like