Eds Unit 2 Notes
Eds Unit 2 Notes
UNIT 2
INTRODUCTION
Distribution system is a part of power system, which is between distribution
substations the consumer. According to design considerations, the primary
distribution system is classified into three types radial, loop and network
systems.
Each radial feeder serves a definite service raea . Most radial feeder systems
are built as networks , but operated radially by opening switches at certain
points , throughout the physical network so that resulting configuration is
radial. . The planner determines the layout of the network and size of each
feeder segment in that network and decides where the open points should be
for proper operation as a set of radial feeders.
The other type of radial primary feeder with express feeder and back feed is
as shown in fig 2.4.The section of the feeder between the substation LV bus
and the load center of the service area is called express feeder. From which
no sub feeders or laterals will be allowed to be tapped off. The portion from
load center towards the substation is called back feed portion. However ,a sub
feeder is allowed to provide a back-feed towards the substation from the load
center.
Most of the utilities in developed countries are using single and two-phase
laterals to deliver power over short distances by tapping off only one or two
phases of the primary feeder minimizing the amount of wire that need be
strong for the short segment required to get the power in general vicinity
of few customers. Each service transformer in these systems feed power
into a small radial system around it.
Regardless of whether it uses single-phase laterals or not, the advantages
of the radial system, in addition to its lower cost, are the simplicity of
analysis and predictability for performance. Because there is only one path
between each customer and the substation, the direction of power flow is
absolutely certain. Equally important is that the load on any branch of the
system can be determined in the most straightforward manner by simply
adding up all the customer loads “downstream” from that piece of
equipment .Before the advent of economical and widely available computer
analysis, this was only an over helming advantage. Simple, straight
forward, ”back of the envelope” design procedures can be applied to the
distribution system with confidence that the resulting system would work
well.
The simplicity of analysis and confidence that operating behavior is strictly
predictable are major advantages.
Because load and power flow direction are easy to establish, voltage profiles
can be determined with accuracy without resorting to exotic calculation
methods; equipment capacity requirements can be ascertained at exactly
fault levels, can be predicted with a reasonable degree of accuracy; and
protective devices, breaker-relays and fuses can be coordinated in an
absolutely assured manner, without resorting to network methods of
analysis.
The major drawback of radial feeder is that it is less reliable than loop
or network system because there is only one path between the substation
and the customer. Thus, if any branch along this path fails a loss of power
delivery results. Generally, when such failure occurs, a repair crew is
dispatched to re-switch temporarily the radial pattern network, transferring
the interrupted customers onto another feeder, until the damaged branch
can be repaired. This minimizes the period of outages, but an outage still
occurred because of the failure.
DESIGN CONSIDERATIONS OF LOOP TYPE DISTRIBUTION
FEEDER
An alternative to purely radial feeder design is a loop system as shown in
fig 2.5 consisting of a distribution design with two paths between the power
sources(substations, service transformers) and every customer. Equipment
is sized and each loop is designed so that service can be maintained
regardless of where an open point might be on the loop. Because of this
requirement, whether operated radially(with one open point in each loop)
or with closed loops, the basic equipment capacity requirements of the loop
feeder design do not change.
4
The reliability and the quality of service of the network type distribution
arrangement are much higher than the radial and loop arrangements.
However, it is more difficult to design and operate than the radial or loop
type systems.
DESIGN PRACTICE OF SECONDARY DISTRIBUTION SYSTEM
The Secondary distribution system receives power from secondary side of
distribution transformer at low voltage and supplies power to various
connected loads via, service lines. The secondary distribution system is the
final sub system of the power system.
The secondary distribution systems are generally radial type expect
for specific service areas such as hospitals, business centers, and military
installations which require highly reliable service. In such areas, secondary
distribution system may be a grid or mesh type network.
(v) It should help to minimize the number of customers affected by any service
outage.
CLASSIFICATION OF SUB STATION
Substations are classified according to service mounting, function and type
of apparatus used.
According to service
a) Transformer substations: In these sub stations which transform power
from one voltage to another. These are:
(i) Transmission or primary substations: Which receive power from a local
generating station (i.e., 11 kv or 33 kv) and step up its voltage (i.e.,220KV or
400 KV) for primary transmission so that huge blocks of power can be
transmitted over a long distance to the load centers economically.
(ii) Sub-transmission or secondary substation: which receive power from
primary substations through primary transmission at voltages above 132 KV
and step down its voltage to 33 KV or 11 KV per secondary transmission
(iii) Step down or distribution substations: Which receive power from sub
transmission substations or directly from power stations and step down its
voltage i.e., 400 V for three phase or 230 V for single phase for secondary
distribution.
b) Industrial substations: These supplies to the industrial consumers.
c) Switching substations: Which meant for switching operations of power lines
without transformation of voltage.
d) Synchronous substations: At these substations, synchronous phase
modifiers are installed for the purpose of system power factor improvement.
e) Frequency change substations: At times for industrial utilization high
frequency supply is essential. Therefore, normal frequency is converted into
other frequencies at these substations.
f) Converting substations: For special purposes such as electric traction,
electric welding, battery charging DC supply is required. The substation
converting AC to DC are called converting substations.
According to design
a) Indoor substations: When the atmosphere is contaminated with
impurities such as metal corroding gases and fumes, conductive dust etc. It
is usual to install the apparatus within a building such substations known
as indoor substations are usually up to 33 KV or 11 KV only.
b) Outdoor substations: Outdoor substations are of two types namely.
i) Pole mounted substations: These are used for distribution purposes and
are usually double or four pole structures with suitable platforms.
ii) Foundation mounted substations: These are used for higher capacity of
transformers, because of rate of the transformer would be more than pole
mounted.
MERITS AND DEMERITS OF INDOOR AND OUTDOOR SUBSTATIONS
Outdoor substations have the following merits over indoor substations are:
i) All the equipment is visible and hence fault identification is easier
ii) Extension of the installation is easier
11
Where A4=Area supplied by one of four feeders emerging from load center
‘F’,km2
D=Load density, kVA/km2
For square shaped area, the equation 4.2 can be modified as
S4=L42D (kVA) (A4=L42) ( 2.2)
For uniformly distributed load, the % voltage drop in the main feeder at 2/3L4
is given by
From the equation 2.4, it can be concluded that the total is located at a point
on the main feeder at a distance of 2/3 L4 from the feed point ‘F’
A analysis of square shaped service area of distribution substation can be
extended for a hexagonal shaped service area of distribution substation
served by 6 feeders feeds from center point ‘F’ of the substation location as
shown in FIG
Consider each feeder service area is equal to 1/6 pf the hexagonal shaped
service area or
13
The load served by the feeder is assumed to be lumped, the % voltage drop in
the main feeder at 2/3L6 distance from the feeding point ‘F’ and is given by
From the equation 2.9 it can be concluded that the total load is located at a
point on the main feeder at a distance of from the feed point ‘F’
COMPARISION BETWEEN FOUR FEEDER AND SIX FEEDER
MODEL
Consider a square shaped service area of distribution substation served by
four feeders from the center of substation i..e, n=4
The area served by each one of the feeder,
The load current flowing in the feeder from the feeding point ‘F’ is given by
The load current flowing in the feeder from the feeding point “F” is given by
Compare the service area of 4 and 6 feeder model in the following two cases:
Case-I
Thermally limited feeder: for a given size of conductor and voltage drop is
Neglected
15
Hence ,six feeder circuits can carry 1.5 times as much load as of the four
feeder circuit
Case-II
Voltage drop limited feeder: For a given size of conductor and consider
voltage drop is equal
And total load supplied by one of the ‘n’ feeders can be determined as
Consider this total load is located on the feeder circuit at 2/3 Ln distances
from the feed point ‘F
Addition of the % voltage drop contributions of all such areas is given by
The feeder load is uniformly distributed as shown in fig:2 . The differential tapped off load
current ‘dI’ which corresponds to differential distance ‘dx’, y and (y+dy) is the distance
between the point 1& 2 from the feeding end of the circuit respectively.
Is and Ir are the sending end and receiving end currents of circuit, I1 and I2 are the currents
in the main feeder at points 1 and 2 respectively.
……..2
Substituting the value of ‘C’ in equation (1)
The current in the feeder at a distance “Y” away from the feeder circuit
breaker can be determined from the equation (3)
The voltage drop due to current at any point ‘Y’ from the source of the
circuit is
i.e. voltage drop in single phase 2 wire system ungrounded system is equal to
i.e. the power loss due to the load current in the conductors of the single
phase system is equal to 2 times the power loss in one of the conductors of
3phase system.
Single phase, 2 wire with uni grounded system:
A system having grounding at only one location is called uni grounded system.
There is no earth current flowing through in this system, therefore presently
it is not generally used. It can be compared with 3 phase 4 wire balanced
system maintaining the load constant.
Since the power input to 3 phase system is same as that of the single phase
uni grounded system
i.e. the current in the single phase uni grounded system is equal to the 3
times the current of 3 phase system.
Voltage drop in 3 phase system
23
i.e. the voltage drop in single phase , 2 wire unigrounded system is equal to
6 times voltage drop of 3 phase 4 wire system
Single phase , 2 wire system with multi grounded common neutral:
Single phase, 2 wire multi grounded common neutral system as shown in the
figure. In this case the neutral is connected in parallel with ground at various
places through ground electrodes in order to reduce the current in neutral
conductor.
Let current in the phase conductor in and return current in the neutral
conductor is The return current in neutral conductor =
Where varies from 0.25 to 0.33 and it is almost independent of
size of the neutral conductor.
The voltage drop and power loss in per unit are
Let assume equal load division takes place among the phase.
Since the power input to the 3 phase system is same as two phase with
neutral system.
i.e. the current in the 2 phase with neutral system is equal to 1.5 times the
current of 3 phase system.
The voltage drop analysis can be performed depending upon whether the
neutral is uni grounding or multi grounding.
If the neutral is uni grounded and neutral impedance is equal to zero
If the neutral is multi grounded and neutral impedance is greater than zero.
The power loss analysis also depends upon whether the neutral is uni
grounded or multi grounded
If the neutral is uni grounded