TGS-40.5 Technical Data 20221010

The TGS-40.5 Gas Insulated Switchgear is designed for indoor use with an operating temperature range of -5°C to +40°C and a maximum altitude of 3000m. It complies with several IEC standards for high-voltage switchgear and features various electrical parameters including a rated voltage of 40.5 kV and short-circuit breaking current options of 20 kA and 31.5 kA. The switchgear utilizes sulphur hexafluoride (SF6) as an insulating gas and has a protection degree of IP67 for gas-filled compartments.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
97 views8 pages

TGS-40.5 Technical Data 20221010

The TGS-40.5 Gas Insulated Switchgear is designed for indoor use with an operating temperature range of -5°C to +40°C and a maximum altitude of 3000m. It complies with several IEC standards for high-voltage switchgear and features various electrical parameters including a rated voltage of 40.5 kV and short-circuit breaking current options of 20 kA and 31.5 kA. The switchgear utilizes sulphur hexafluoride (SF6) as an insulating gas and has a protection degree of IP67 for gas-filled compartments.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Indoor Gas Insulated Metal-Clad Switchgear

TGS-40.5
Technical Data

TGOOD
2022-10-10
Product TGS-40.5 Gas Insulated Switchgear
Technical Data

Operating environmental conditions

Place of installation Indoor

Ambient temperature -5°C ~ +40°C

Altitude 3000m

Daily average ≯95%;


Air humidity
Monthly average ≯90% (25°C)

Type of insulating gas Sulphur hexafluoride (SF6)

This product shall be placed in a site without risk of fire hazard, explosion, chemical corrosion and
sharp vibration.

Standard compliance

High-voltage switchgear and control gear-Part 200: AC metal-enclosed switchgear


IEC 62271-200
and control gear for rated voltages above 1kV and up to and including 52kV

High-voltage switchgear and control gear-Part 100: High-voltage alternating- current


IEC 62271-100
circuit-breakers

High voltage switchgear and controlgear-Part 102: Alternating current disconnectors


IEC 62271-102
and earthing switches

High-voltage switchgear and controlgear–Part 103: Switches for rated voltages above
IEC 62271-103
1 kV up to and including 52 kV

High-voltage switchgear and controlgear - Part 206: Voltage presence indicating


IEC 62271-206
systems for rated voltages above 1 kV and up to and including 52 kV

IEC 61869-2 Current transformers

IEC 61869-3 Voltage transformers

IEC 60529 Degrees of protection provided by enclosure (IP code)

tgood.com 1 TGQDMK550411
Product TGS-40.5 Gas Insulated Switchgear
Technical Data

Electrical parameter of switchgear

Rated voltage kV 40.5

Rated frequency Hz 50
1min power frequency withstand voltage (RMS)
kV 95/118
(phase to phase, to earth/across isolating distance)
Lightning impulse withstand voltage (RMS)
kV 185/215
(phase to phase, to earth/across isolating distance)
Rated busbar current A 630, 1250

Rated short-circuit breaking current kA 20, 31.5

Load switch 20 / 4
Rated short-time withstand
kA/s
current/duration
Circuit-breaker 31.5/4

Rated peak withstand current kA 50, 80

Rated short-circuit making current (peak) kA 50, 80

Protection degree of gas-filled compartment IP 67

Protection degree of compartments IP 4X

Load switch panel ≤ 150


Circuit resistance μΩ
Circuit-breaker panel ≤ 150

SF6 gas rated pressure (gauge pressure at 20°C) MPa 0.05

SF6 gas minimum pressure (gauge pressure at 20°C) MPa 0.02

SF6 gas annual leakage rate ≤ 0.1%

Partial discharge pC ≤ 20 @1.1Ur

EMC Class 3, performance A

Radiation uSv/h ≤ 5 @40.5kV, ≤ 150 @118kV

Moisture content UL/L ≤ 150

AFLR, 20kA, 1s (Load switch panel)


Internal arc classification
AFLR, 31.5kA, 1s (CB panel)
TMY-60x6 (630A C/V);
Busbar dimension mm
TMY-80x8 (1250A V)
Panel dimension with top box (W x D x H) mm 500x1000x2250 (C/V)

Functional panel weight kg 650/700 (C/V)

Extension Top ( Lateral optional)

tgood.com 2 TGQDMK550411
Product TGS-40.5 Gas Insulated Switchgear
Technical Data

Electrical parameter of load switch and circuit-breaker

Circuit-breaker

Standard compliance IEC 62271-100

Rated voltage kV 40.5

1min power frequency withstand voltage (RMS)


kV 95/118
(phase to phase, to earth/across isolating distance)
Lightning impulse withstand voltage (RMS)
kV 185/215
(phase to phase, to earth/across isolating distance)
Rated current A 630/1250

Rated frequency Hz 50

Rated short-circuit breaking current kA 20, 31.5

Rated short-time withstand current/duration kA/s 20/4, 31.5/4

Rated peak withstand current kA 50, 80

Rated short-circuit making current (peak) kA 50, 80

Rated operation sequence O-0.3s-CO-180s-CO

Mechanical endurance Time 20,000

Electrical endurance at 100% Isc Time 30, E2


Xiamen Hongfa Electroacoustic Co., Ltd
Vacuum interrupter
HFTD-40.5/1250-31.5kA
Mechanism Spring type

Motor V/A DC110/-

Opening/closing coil V/A DC110/1.68


5-20 (CC1), C2
Rated cable charging current switching A
50 (CC2), C2
58.5/2.36 (OP1)
Out of step making and breaking kV/kA
58.5/7.9 (OP2)
Double earth fault breaking kA 27.4

DC component 51%

DC time constant ms 45

First-pole-to-clear factor 1.5

Out-of-phase voltage factor 2.5

Closing time, opening time ms 32-48; 20-43

Load switch

Standard compliance IEC 62271-103

Rated voltage kV 40.5

tgood.com 3 TGQDMK550411
Product TGS-40.5 Gas Insulated Switchgear
Technical Data

1min power frequency withstand voltage (RMS)


kV 95/118
(phase to phase, to earth/across isolating distance)
Lightning impulse withstand voltage (RMS)
kV 185/215
(phase to phase, to earth/across isolating distance)
Rated current A 630

Rated frequency Hz 50

Rated short-circuit breaking current kA 20

Rated short-time withstand current/duration kA/s 20/4

Rated peak withstand current kA 50

Rated short-circuit making current (peak) kA 50 (3 times)


5,000, M2 (Load switch)
Mechanical endurance Time
3,000 (Earthing switch)
Mechanism Spring type

Motor V/A DC110/-

Opening coil V/A DC110/1.68

4.2-8.4 (CC1)
Rated cable charging current switching A
21 (CC2)

Rated line charging current switching A 2.1

Closing, opening time ms ≤ 12000; 30-50

Disconnector Switch (If Applicable)

Applicable standard IEC 62271-102


A
Rated current 630/1250
kA
Rated short-time withstand current 31.5

Peak withstand current 80


s
Rated duration of short circuit 4

Mechanical endurance 3,000

Motorized operation availability No

Earthing Switch

Applicable standard IEC 62271-102

Rated short-time withstand current kA 20, 31.5

Peak withstand current kA 50, 80

Rated duration of short-circuit s 4

tgood.com 4 TGQDMK550411
Product TGS-40.5 Gas Insulated Switchgear
Technical Data

Short-circuit making capability Times 2 (Switch); 5 (CB)

Mechanical endurance Times 3,000

Motorized operation availability No

Mechanical parameter of load switch and circuit-breaker


Load Three-position
Circuit-breaker
switch disconnector
Rated short-time breaking current kA 20 31.5
2500± 3100±
Contact pressure N
300 300
Isolated moving
and fixed
contact ≥93;
Clearance between opening contacts mm 87±3 17±1 Grounding
moving and
fixed contact
≥90.
Overtravel mm 33±3 4±1

Speed at instant of touching m/s 2.7±0.2 0.8±0.25

Speed at instant of opening m/s 2.5±0.2 1.7±0.25

Contact closing bouncing time ms ≤3


Opening and closing insimultaneity of three pole
ms ≤3 ≤2 ≤3
contact

Electrical parameter of tangible type overvoltage protection (surge arrester)*

Type SH-YH5WZ-51/134

System nominal voltage kV RMS 35

Continuous running voltage kV RMS 40.8

DC 1mA reference voltage kV 73

2ms rectangular current discharge capacity 400

Residual voltage of steep impulse current (peak) kV 154

Residual voltage of lightning impulse current (peak) kV 134

Residual voltage of operation impulse current (peak) kV 114

Power frequency reference voltage 51

tgood.com 5 TGQDMK550411
Product TGS-40.5 Gas Insulated Switchgear
Technical Data

Electrical parameters of current transformer*

CSR1-40.5
Rated
Rated primary Accuracy class and rated Accuracy class and rated
Type secondary
current secondary output (VA) secondary output (VA)
current
0.2S 0.2 0.5 10P20 10P15 10P10

200 2.5 7.5 10 2.5 3.75 5


High-precision
Current 400 5 5 12.5 15 5 7.5 12.5
transformer
600 10 20 25 7.5 12.5 12.5

CBC1-40.5
Rated
Rated primary Accuracy class and rated Accuracy class and rated
Type secondary
current secondary output (VA) secondary output (VA)
current
0.2 0.5 1 10P15 10P10 10P5

200 7.5 2.5 5


Open-type
Current 400 5 5 12.5 7.5 10
transformer
600 10 20 10 15

Electrical parameter of voltage transformer*

Type VSSIF4-40.5/195L

Rated voltage ratio 35/√3/0.1/√3/0.1/3

Accuracy class combination 0.2/3P, 0.5/3P, 1/3P, 3/3P

Rated secondary output VA 30/100, 100/100, 150/100, 300/100

Limit VA 300

*Other type or parameter of component is optional, please consult TGOOD.

tgood.com 6 TGQDMK550411