Introduction To 4 in 1 Process Control Trainer IT-5200
Introduction To 4 in 1 Process Control Trainer IT-5200
Measurement (4 in 1)
To understand the function and placement of each component, we will refer to diagram given in Fig 4.
EE-223 Instrumentation and Introduction Process Control Trainer
Measurement (4 in 1)
The Water Storage tank (Fig 5) has 32 liters capacity and it will serve as our main storage tank.
The Delivery valve (Fig 8) will always remain open. It is used when disconnecting the main water
storage tank for servicing.
Next to delivery valve, there is a strainer to filter out water, electronic flow sensor and pump. The
readings of flow sensor are available on flow sensor interface of the control module. See Fig 26.
Flow meter gives the readings in US gallons per minute (GPM) or liters per minute (LPM). Note that
1 US Gallon is approximately equal to 3.785 liters.
The motorized valve will be actuated from motorized valve driver (see Fig 34). Note that if the red
line is horizontal, it means the valve is open. If its vertical, it means the valve is closed.
The heater indicator light will turn on when the heater is actuated.
The needle valve is used to drain the process control tank manually. Needle valve has more fine drain
as compared to drain valve.
The solenoid valve is used to drain the process control tank. It is actuated by Solenoid Valve Driver
(see Fig 36)
The level sensor with Linear Variable Differential Transformer (LVDT) is used to measure
level.
Pressure gauge gives readings of pressure in psi or bar. Another electronic pressure gauge is located
right next to this analog pressure gauge. Its readings are taken from pressure sensor interface (see Fig
28)
The overflow valve is used to handle overflow, as well air input when draining the process control
tank.
The float switch indicates whether a certain level is reached or not. Its reading is taken from float
switch output in level sensor interface (see Fig 26)
Figure 26 Sensor Interfaces, Control Modules (ON OFF and PID) and Actuators
The level sensor interface takes readings from level sensor LVDT (see Fig 19) and converts the phase
shift to DC output. The controller scheme in this training system is designed around DC voltages. The
output of the level sensor connected as input to signal conditioner which is a voltage to voltage
converter. Gain and offset can also be set in this level sensor interface. The output of float switch (fig
24) is also read from this level sensor interface.
Temperature sensor interface takes the readings from PT-100 RTD and gives output at pin 11 in DC
volts.
The digital PID controller can be connected to computer via USB and can be programmed to have
variable gains for KP, KI and KD. It can control one parameter through its analog output. It can also
operate two relays.
The ON-OFF controller with Hysteresis is used to control one output through ON-OFF control
scheme.
The set point 1 is a variable DC supply (0 to 10V), and set point 2 goes from -10 to +10 volts. Vcc
and Vee provide fixed voltages.
The motorized valve driver is used to take input as DC volts and is used to drive the motorized valve
driver (see Fig 11)
The solenoid valve driver is used to operate the solenoid valve to drain the process control tank. Its
input is in DC volts which is power amplified and fed to solenoid (see Fig 16)