PSO Note 2
PSO Note 2
o The total power generated must equal the power consumed by loads plus system
losses.
o Any imbalance affects the system frequency, which can lead to instability.
2. Regulate Frequency
o Frequency must be kept close to the standard (e.g., 50 Hz in Ghana, 60 Hz in the US).
o Generation side: Adjust power output to match demand using Automatic Load
Frequency Control (ALFC).
o Economic Dispatch means generating power at the lowest cost while meeting demand.
o Adaptive Control: Adjusts itself dynamically, ideal for systems with renewable energy
sources.
o Power must flow within planned limits to avoid overloading neighboring systems.
1
o Reducing system voltage slightly (brownout) can reduce demand without complete
blackouts.
Why is Frequency Control Linked to Active Power and Voltage Control Linked to Reactive Power?
What is frequency?
o Active power (real power, measured in MW) is what actually powers devices (lights,
machines, etc.).
o If demand suddenly increases, the system needs more power. If generation doesn’t
increase, the extra demand slows down the generators → frequency drops.
o To maintain a stable frequency, the generation must always match the demand (plus
losses).
What is voltage?
o Voltage is like the "pressure" that pushes electric current through the system.
o Reactive power (measured in VARs) doesn’t do "real work" but is needed to support
magnetic fields in transformers, motors, and transmission lines.
o If there isn’t enough reactive power, voltage drops (like weak water pressure in a pipe).
o If there’s too much reactive power, voltage rises beyond safe limits.
2
o Voltage must be controlled by balancing reactive power generation and demand using
capacitors, reactors, and voltage regulators.
Summary:
Voltage depends on reactive power because it affects the electric field strength needed to
maintain voltage levels.
In an electrical power system, active power (also called real power, measured in MW) is the actual
energy consumed by electrical devices like lights, motors, and heaters.
The goal of active power management in generation is to ensure that power generation always matches
the power demand, plus losses in the system. If this balance is not maintained:
If generation is higher than demand, frequency will increase (generators speed up).
If generation is lower than demand, frequency will decrease (generators slow down).
Since frequency affects the stability of the entire power system, we use Automatic Load Frequency
Control (ALFC) to regulate it.
Power plants use synchronous generators (hydro, thermal, nuclear, or gas) to produce
electricity.
These generators rotate at a fixed speed to maintain a constant frequency (e.g., 50 Hz or 60 Hz).
When demand increases or decreases, the rotational speed of the generator changes, causing a
frequency deviation.
The generator has a speed governor, which acts like a cruise control system for frequency.
3
If the frequency drops (demand > generation), the governor increases fuel or water flow to the
turbine to generate more power.
If the frequency rises (demand < generation), the governor reduces fuel or water flow.
2. It compares the actual frequency with the reference frequency (e.g., 50 Hz in Ghana).
4. This signal is amplified and sent to the turbine governor, which adjusts the fuel or water supply
to correct the frequency.
There are three main scenarios that the ALFC system must handle:
If the power demand exactly matches the generated power, the generator runs at a constant
speed, and frequency remains steady.
If generation exceeds demand, generators speed up, causing frequency to increase above 50 Hz.
The system detects this excess power and sends a corrective signal to reduce generator output.
In a thermal plant, this means closing the steam valve; in a hydro plant, it means closing the
water gate.
If demand exceeds generation, generators slow down, causing frequency to drop below 50 Hz.
4
Three possible solutions:
🔹 Action Taken: Increase generation, import power, or shed load to restore frequency.
LFC strategies help control frequency automatically. There are several approaches:
Works well for simple systems but not ideal for modern grids with renewable energy.
Uses machine learning algorithms like Particle Swarm Optimization (PSO), Genetic Algorithm
(GA), Grey Wolf Optimization (GWO), and Artificial Bee Colony (ABC).
Droop control means the governor reduces generator output as frequency increases and
increases generator output as frequency decreases.
5
This ensures that all generators share the load proportionally.
An infinite network is a large interconnected grid where frequency is stable and not affected by
a single generator.
Example: If a generator is added or removed, the overall system hardly changes in frequency.
To increase power output, simply increase turbine input (fuel or water flow).
A finite network is small, meaning frequency changes significantly when a generator's output
changes.
7. Example Calculations
If the operator wants to increase output by 5 MW, they simply increase the reference power
setting by 5 MW.
If the frequency drops by 0.1 Hz, how much power must be added?
6
o Substituting values: ΔP=0.10.04=5MW\Delta P = \frac{0.1}{0.04} = 5 MWΔP=0.040.1
=5MW
o So, the turbine power must increase by 5 MW to compensate for the frequency drop.
8. Summary
The Automatic Load Frequency Control (ALFC) system continuously adjusts generator output to
maintain a stable frequency.
Droop control ensures that all generators share the load proportionally.
Different control strategies (Traditional, AI-based, Optimal, Adaptive) are used to maintain
system stability.
Infinite networks (large grids) have stable frequencies, while finite networks (isolated grids)
experience larger frequency variations.
The Load Frequency Control (LFC) system is responsible for automatically adjusting the power
generation in a system to maintain a stable frequency and keep power flows within acceptable limits.
From the slides, the four key objectives of LFC are:
What this means: The system should always bring frequency back to normal (e.g., 50 Hz or 60
Hz) after a disturbance.
Why it’s important: If frequency remains too high or too low for too long, it can damage
equipment and cause system instability.
o The system should reach exactly the desired frequency with no long-term deviation
(this is called "zero steady-state error").
7
✅ Example: If a factory starts operating and demand increases, frequency might drop from 50 Hz to 49.5
Hz. The LFC system will adjust generator output until the frequency returns to 50 Hz with no long-term
error.
What this means: Power should only flow between different areas (regions or countries) as
planned.
Why it’s important: If power unexpectedly flows between areas, it can overload transmission
lines and cause blackouts.
o If too much or too little power is transferred, it adjusts local generation to correct the
flow.
✅ Example:
Ghana imports power from Côte d’Ivoire. If demand suddenly increases in Ghana, more power
might start flowing from Côte d’Ivoire without planning.
The LFC system detects this and increases Ghana’s local generation to reduce reliance on
imported power and avoid overloading the tie-line.
What this means: The system should quickly respond when demand changes.
Why it’s important: Electricity demand constantly changes throughout the day, and
disturbances (like a generator tripping) can happen at any time.
✅ Example:
8
The LFC system ensures that generation tracks these changes smoothly without large frequency
deviations.
What this means: If frequency changes suddenly, it should return to normal smoothly and
quickly without large swings (overshoot) or taking too long (settling time).
Why it’s important: If the system overreacts or is too slow, it can cause instability or frequent
fluctuations.
o Uses control techniques (like PID controllers or AI-based methods) to stabilize the
system efficiently.
✅ Example:
If a large industrial load suddenly disconnects, frequency might jump to 50.5 Hz before settling
back to 50 Hz.
The LFC system ensures that this overshoot is small and that frequency returns to normal in the
shortest possible time without unnecessary oscillations.
3. Track load Quickly respond to Adjusts generator output in As people turn on lights in the
demand and changing electricity real time based on demand morning, LFC ensures smooth
disturbances usage changes frequency regulation
9
Objective Purpose How LFC Helps Example
Final Thought
The Load Frequency Control (LFC) system is like the brain of the power grid, constantly making small
adjustments to keep frequency stable, avoid unnecessary power transfers, track demand changes, and
prevent excessive swings in frequency.
The Automatic Load Frequency Control (ALFC) System – Schematic Diagram (Explained Simply)
The ALFC system is responsible for automatically adjusting generation to maintain a stable power
system frequency. The schematic diagram in the slides represents the different components that work
together to detect, correct, and regulate frequency deviations.
The system has a frequency sensor that continuously measures the actual system frequency.
If the measured frequency is less than 50 Hz, it means demand exceeds generation (more load,
less supply).
If the measured frequency is greater than 50 Hz, it means generation exceeds demand (more
supply, less load).
The measured frequency is sent to a comparator, where it is compared with the reference
frequency (50 Hz in Ghana, 60 Hz in the US).
10
🔹 Why is this important?
If the error is positive, it means frequency is too high → Reduce generator output.
If the error is negative, it means frequency is too low → Increase generator output.
The small error signal is too weak to directly control the generator.
This amplified signal is then used to control the prime mover (turbine) of the generator.
Without amplification, the signal wouldn’t be strong enough to make physical adjustments to
the turbine.
The governor adjusts the input to the turbine based on the error signal:
o If frequency is too low → The governor opens the steam valve (thermal) or water gate
(hydro) to allow more fuel/water into the turbine → more power is generated.
o If frequency is too high → The governor closes the steam valve (thermal) or water gate
(hydro) to reduce turbine power output.
The turbine is what actually generates electricity. Without adjusting it, the system cannot
correct frequency deviations.
After the turbine adjusts, the generator increases or decreases power output as needed.
This restores the balance between generation and demand, bringing frequency back to normal.
The system must constantly adjust power output to match demand in real-time.
11
2. Summary of the ALFC Process
1. Frequency A sensor measures the actual system Detects if frequency is above or below
Measurement frequency. normal.
2. Frequency The actual frequency is compared to 50 Finds out whether generation needs to
Comparison Hz (or 60 Hz). increase or decrease.
The generator changes its output to Keeps the system frequency stable and
5. Power Adjustment
restore balance. reliable.
🔹 What happens?
The new factory increases demand, so the system needs more power.
4. Governor opens the fuel/water input to the turbine → More power is generated.
🔹 What happens?
The factory shutdown reduces demand, so too much power is being generated.
12
🔹 How ALFC responds?
4. Governor closes the fuel/water input to the turbine → Less power is generated.
Prevents blackouts: Without frequency control, large deviations can cause system failure.
Ensures power quality: Most electrical devices require stable frequency to operate properly.
Balances generation and demand: Avoids oversupply (wasted energy) and undersupply (power
shortages).
Supports grid reliability: Helps power plants work together to maintain grid stability.
5. Key Takeaways
✅ The ALFC system automatically regulates power generation to keep frequency stable.
✅ It works by detecting frequency changes, amplifying the error signal, and adjusting turbine power.
✅ It ensures that power generation always matches demand, preventing grid instability.
✅ Without ALFC, sudden load changes could lead to blackouts or power fluctuations.
This is the ideal condition in a power system where the power generated exactly matches the power
consumed by loads, including transmission losses.
When the power demand (load) is perfectly balanced with power generation, the following conditions
are met:
13
The system frequency remains stable (e.g., 50 Hz in Ghana, 60 Hz in the US).
Since frequency depends on generator speed, and speed is constant in this scenario:
The turbine governor does not need to open or close the steam/water input.
The power plants continue generating at the same level without changes.
Conclusion:
💡 The system is running in a perfectly stable state, so no changes are required.
4. Example Scenario
Assume a power grid supplies a city where normal evening demand is 1000 MW.
🔹 Result:
14
5. Key Takeaways
In this scenario, the power generated is greater than the power consumed by the loads in the system.
This results in excess energy that needs to be managed.
The extra generated power has nowhere to go, so the rotational speed of the generators
increases.
Since frequency is directly related to generator speed, the system frequency rises above
normal (e.g., it might increase from 50 Hz to 50.4 Hz).
This situation can damage electrical equipment, overload transmission lines, and cause
instability.
🔹 Key Problem: Frequency rises above the normal level (50 Hz or 60 Hz).
2. Less power is being used by consumers (factories shut down, households reduce usage, etc.).
If you keep pressing the accelerator (fuel supply remains high) but the road suddenly becomes
downhill (less resistance/load), the car speeds up beyond the desired limit.
Similarly, in a power system, when demand decreases but generation remains the same,
frequency rises because generators are still spinning at high speed.
15
To reduce the system frequency back to normal, the ALFC system takes corrective actions:
The turbine governor detects the increase in frequency and responds by reducing fuel/water
supply to the generator.
This slows down the generator, reducing power generation until it matches the demand.
In a thermal power plant, this means closing the steam valve slightly.
If the power system is interconnected with neighboring grids, the extra power can be exported
instead of reducing generation.
This is possible if other regions have higher demand and need more electricity.
🔹 Example:
Ghana produces excess power but Côte d’Ivoire needs more electricity. Instead of reducing
generation, Ghana can export power to Côte d’Ivoire, stabilizing frequency without wasting
energy.
If the grid has battery storage systems or hydropower reservoirs, the extra energy can be stored
instead of being wasted.
o Later, when demand increases, the stored water is released to generate electricity.
Some industries and large consumers can be signaled to increase power usage when there’s an
excess of generation.
This prevents frequency from rising too high and makes better use of the available power.
16
4. Example Scenario: A Factory Shuts Down Unexpectedly
🔹 What happens?
Power plants were still generating the original amount, leading to excess power in the system.
If storage is available Excess power can be stored Use pumped hydro storage or batteries
6. Key Takeaways
17
Case 3: Demand GREATER THAN Generation (1/2) (Generation Deficit)
This scenario occurs when electricity demand exceeds the available power generation. This creates a
generation deficit, which can cause system instability if not corrected.
The power system does not have enough generated power to meet the demand.
The synchronous generators slow down because the electrical load is trying to draw more
power than the system can supply.
Since frequency is directly related to generator speed, the system frequency drops below
normal (e.g., from 50 Hz to 49.6 Hz).
If the frequency drops too low, power plants and sensitive equipment can shut down, causing
blackouts.
🔹 Key Problem: Frequency drops below the normal level (50 Hz or 60 Hz).
1. More power is being drawn from the generators than they can supply.
3. If the frequency keeps dropping and no action is taken, entire power plants can trip, leading to a
blackout.
If you’re driving up a steep hill (increased demand) but don’t press the accelerator (insufficient
generation), the car slows down (frequency drops).
The system needs to increase fuel supply (more power generation) to keep moving at the
correct speed (50 Hz).
To increase system frequency back to normal, the ALFC system takes corrective actions:
18
The turbine governor detects the drop in frequency and responds by increasing fuel/water
supply to the generator.
This speeds up the generator, producing more power until it matches demand.
In a thermal power plant, this means opening the steam valve to allow more fuel to the boiler.
In a hydropower plant, this means opening the water gate to increase turbine speed.
If the power system is interconnected with neighboring grids, the deficit power can be imported
from another region.
🔹 Example:
Ghana experiences a power deficit, but Côte d’Ivoire has surplus power.
Instead of shutting down industries, Ghana imports extra power from Côte d’Ivoire.
If generation cannot be increased and power cannot be imported, the only option is to reduce
demand.
This means cutting off power to certain areas (load shedding) to bring demand back in balance
with generation.
🔹 Example:
If the power deficit is 200 MW, the system operator disconnects some non-essential consumers
(e.g., street lights, industrial plants) to reduce demand by 200 MW.
This prevents a complete blackout and allows essential services (hospitals, communication
centers) to keep running.
🔹 What happens?
19
A 500 MW power plant unexpectedly shuts down due to a technical fault.
The system was already operating close to full capacity, so this sudden loss creates a power
shortage.
Since demand is greater than generation, frequency drops from 50 Hz to 49.4 Hz.
6. Key Takeaways
20
Load Frequency Control (LFC) is a system that automatically adjusts power generation to maintain a
stable frequency (e.g., 50 Hz or 60 Hz) when demand changes.
How it Works
Tuning Methods
A common way to tune these controllers is the Ziegler-Nichols method, which adjusts the
controller settings based on system behavior.
Limitations
🔹 Example:
Imagine you are driving a car with cruise control.
If the car slows down too much, the system adds more fuel.
However, this method is not the most precise—it may overcorrect or respond slowly.
How it Works
✅ Particle Swarm Optimization (PSO) – Inspired by how birds move in a flock to find food efficiently.
✅ Genetic Algorithm (GA) – Inspired by evolution and natural selection.
21
✅ Grey Wolf Optimization (GWO) – Inspired by wolf hunting strategies.
✅ Artificial Bee Colony (ABC) – Inspired by how bees find food efficiently.
Advantages
🔹 Example:
Think of AI-based LFC like a smart traffic control system.
Instead of using fixed rules, the system monitors real-time traffic flow and adjusts signals
intelligently to reduce congestion.
How it Works
This method minimizes a cost function, meaning it finds the best way to control frequency with
minimum effort and energy loss.
✅ Model Predictive Control (MPC) – Predicts future demand and adjusts generation before a problem
occurs.
✅ Linear Quadratic Regulator (LQR) – Minimizes frequency deviations while using the least energy
possible.
Advantages
🔹 Example:
Think of it like Google Maps predicting traffic conditions.
Instead of reacting after a traffic jam occurs, it forecasts the problem and suggests the best
route in advance.
How it Works
22
This method automatically adjusts itself based on real-time power system conditions.
Advantages
🔹 Example:
Imagine a thermostat that adjusts room temperature automatically based on weather conditions.
Conclusion
23
The Turbine-Governor Control System (Droop Frequency Control) – Explained Simply
The Turbine-Governor Control System is a key part of Load Frequency Control (LFC). It adjusts generator
power output to maintain system frequency.
One important method used in power systems is Droop Frequency Control, which allows generators to
share load changes proportionally while keeping the grid stable.
Because as power output increases, the frequency slightly decreases instead of staying
constant.
The relationship between power output and frequency is a sloping line (droop).
The amount of droop is set by the droop constant (R), which is typically 3-5%.
The Turbine-Governor is responsible for controlling how much power a generator produces.
1️⃣ Speed Governor – Detects changes in generator speed (which affects frequency).
2️⃣ Turbine – Converts steam (thermal plants) or water flow (hydro plants) into mechanical power.
3️⃣ Fuel/Water Valve – Controls how much fuel (thermal) or water (hydro) enters the turbine.
4️⃣ Generator – Converts mechanical energy from the turbine into electrical energy.
24
The extra load causes generators to slow down, and frequency drops (e.g., from 50 Hz to 49.8
Hz).
The speed governor detects the drop and opens the fuel valve, increasing turbine power.
The frequency stabilizes but remains slightly lower than 50 Hz due to droop.
Less load means generators speed up, and frequency rises (e.g., from 50 Hz to 50.2 Hz).
The speed governor detects the rise and closes the fuel valve, reducing turbine power.
Where:
🔹 Example Calculation:
A generator has a droop setting of 4% (0.04 pu).
If system frequency drops by 0.1 Hz, how much should the generator increase its power output?
25
In a large, interconnected grid, frequency is almost constant because many generators share the
load.
If one generator increases or decreases output, the overall system frequency hardly changes.
🔹 Key Point: The turbine only responds to load changes, not frequency changes.
The droop constant (R) is very important because it determines how much each generator
should adjust.
🔹 Key Point: Generators must carefully share load to keep frequency stable.
✅ Ensures Stable Load Sharing – Multiple generators can operate together without conflict.
✅ Prevents Overcorrection – Instead of forcing frequency exactly to 50 Hz, the system adjusts smoothly.
✅ Allows Multiple Generators to Work Together – Each generator contributes based on its droop setting.
✅ Essential for Islanded Grids – Helps microgrids and standalone systems manage frequency without
external help.
Demand Increases (Factory starts, Frequency drops below Generator increases power output by
more load) 50 Hz opening fuel/water valve
Demand Decreases (Factory shuts Frequency rises above Generator reduces power output by
down, less load) 50 Hz closing fuel/water valve
26
8. Final Thoughts
Droop frequency control is a simple but powerful method to regulate generator output.
It helps stabilize frequency while allowing multiple generators to share load changes fairly.
Without droop control, generators could overreact, leading to instability or power failures.
Electricity is generated at power plants and transmitted over long distances through transmission lines
before reaching consumers. To ensure efficient delivery, active power flow (P-flow) must be managed
properly.
This section explains how active power is transmitted, how to maximize transmission capacity, and
how to minimize losses.
Active power (P) is the real power that actually does work (e.g., lighting, heating, running
machines).
🔹 Key Insights:
Larger phase angle difference (δ) → More power flow, but too large a δ can lead to instability.
27
2. How to Increase Transmission Capacity (Maximize Transmittable Power)
Since power flow depends on V₁ and V₂, increasing transmission voltage boosts capacity.
o Stronger insulation
o Upgraded switchgear
1. Use Parallel Transmission Lines – Adding extra lines reduces overall reactance.
Real power flows from the generator with the most leading voltage angle to the one with the
most lagging angle.
28
Typical range: δ is usually kept below 30-40° for stability.
✅ Advantage: A well-managed phase angle ensures maximum power transfer without instability.
Not all power generated reaches consumers—some is lost in the transmission lines. These losses must
be minimized.
Since losses depend on current (I) squared, reducing current greatly reduces losses.
How to reduce I?
✅ Advantage: Lower current reduces both power loss and heating of conductors.
Problem: Reactive power (Q) takes up transmission capacity and increases losses.
This keeps voltage stable and frees up space for active power (P-flow).
✅ Advantage: More of the transmission line capacity is used for real power, improving efficiency.
AC transmission suffers from reactive power losses, but HVDC does not.
29
HVDC lines reduce line losses by 30-50% compared to AC lines.
✅ Advantage: HVDC has lower losses and better control over power flow.
Minimize Power Losses Reduce current (I) Lower current means lower resistive losses
5. Final Thoughts
✅ Managing active power flow ensures reliable and efficient power delivery.
✅ Maximizing transmission capacity allows grids to handle more power without overloading.
✅ Minimizing losses improves efficiency and reduces energy waste.
✅ Techniques like HVDC, conductor bundling, and shunt compensation improve performance.
Power demand varies throughout the day, and sudden changes in demand can cause instability in the
power system. Managing active power demand in the distribution system is important for keeping the
grid stable and efficient.
30
One technique used for demand management is the Brownout Effect, which helps reduce power
consumption without completely cutting off electricity.
🔹 A brownout is a controlled reduction in system voltage to reduce power demand without causing a
total blackout.
🔹 Unlike a blackout (complete power loss), a brownout lowers voltage by a small percentage (e.g., 5% to
10%) so that consumers continue to receive electricity, but power-hungry appliances consume less
energy.
Motors are less sensitive to small voltage changes but still experience a small power reduction.
o But power consumption still reduces slightly (0.2% power drop for a 1% voltage drop).
✅ Effect: Lower power reduction than resistive loads, but still helps manage demand.
31
🔹 During peak demand hours, reducing voltage slightly can:
✅ Reduce total electricity consumption, easing stress on generators.
✅ Prevent blackouts by spreading available power across more consumers.
✅ Allow critical facilities (hospitals, emergency services) to keep running.
Imagine a city consuming 500 MW of electricity. The distribution company reduces voltage by 5%.
Power Reduction=(5% voltage drop)×2=10%\text{Power Reduction} = (5\% \text{ voltage drop}) \times 2
= 10\%Power Reduction=(5% voltage drop)×2=10%
If 300 MW of the city’s load is from impedance loads, power demand drops by:
300×0.1=30 MW300 \times 0.1 = 30 \text{ MW}300×0.1=30 MW
Power Reduction=(5% voltage drop)×0.2=1%\text{Power Reduction} = (5\% \text{ voltage drop}) \times
0.2 = 1\%Power Reduction=(5% voltage drop)×0.2=1%
If 200 MW of the city’s load is from motors, power demand drops by: 200×0.01=2 MW200 \
times 0.01 = 2 \text{ MW}200×0.01=2 MW
🔹 During power shortages – When power plants cannot meet demand, brownouts help avoid complete
blackouts.
🔹 During extreme weather – Heatwaves or cold spells cause high electricity use, and brownouts reduce
overload.
🔹 To balance power flow – Helps avoid system-wide failures when there’s an imbalance between
generation and demand.
32
Advantages Disadvantages
7. Final Thoughts
In power systems, impedance loads (such as heaters, incandescent bulbs, and some industrial
equipment) depend on voltage to determine how much power they consume. When voltage changes,
the power demand of these loads also changes.
🔹 Impedance loads are loads whose resistance (R) or impedance (Z) does not change significantly with
voltage.
Examples:
o Electric heaters
o Incandescent bulbs
I=VRI = \frac{V}{R}I=RV
Where:
33
o VVV = Voltage (V)
P=V2RP = \frac{V^2}{R}P=RV2
Key Observations:
✅ Example Calculation:
If voltage drops by 10%, power consumption drops by:
📌 Conclusion: A small change in voltage causes a larger change in power for impedance loads.
A 2 kW heater operates at 230V. If the voltage drops by 5%, how much power will it consume?
Pinitial=2302RP_{\text{initial}} = \frac{230^2}{R}Pinitial=R2302
Pnew=218.52RP_{\text{new}} = \frac{218.5^2}{R}Pnew=R218.52
34
4. Implications of Voltage Dependency for Impedance Loads
Helps reduce overall power demand without turning off loads completely.
Extends lifespan of resistive devices (since lower power means less heat stress).
5. Key Takeaways
✅ Impedance loads depend on voltage squared → Small voltage changes cause bigger power changes.
✅ Lowering voltage reduces power consumption, which can help balance the grid during high demand.
✅ Too much voltage drop can reduce efficiency in heating and lighting applications.
In power systems, some loads change their power consumption based on frequency variations.
Impedance loads (such as heating elements, incandescent bulbs, and certain industrial equipment) are
mainly affected by voltage changes, but they also have a small dependence on frequency because of
their reactance component.
🔹 Impedance loads are electrical devices where current flow is determined by total impedance (Z),
which includes:
Resistance (R) – For purely resistive loads like heaters and incandescent bulbs.
Reactance (X) – If the load contains inductance (L) or capacitance (C), its impedance also
depends on frequency.
35
Since reactance (X) depends on frequency (f), the overall impedance (Z) of the load can change if
frequency changes.
🔹 For loads with reactance (like inductive heating coils or fluorescent lamps)
Key Result:
Let’s assume an inductive load with a power factor of 0.8. If frequency drops by 1%, how much will the
real power change?
36
✅ Conclusion:
A 1% frequency drop causes a 0.4% increase in real power consumption for this load.
This worsens the power imbalance and can lead to grid instability.
This helps reduce stress on generators but can cause underloading issues.
🔹 Grid operators use Load Frequency Control (LFC) to manage frequency and prevent cascading failures.
5. Key Takeaways
Motor loads, also called motive loads, are electrical loads that involve rotating machines, such as:
Unlike impedance loads, which have a power consumption proportional to voltage squared (V²), motor
loads respond differently when voltage changes.
A. Current Response
When voltage decreases, an induction motor draws more current to maintain its power output.
However, motors are not 100% efficient, so extra current increases heating and losses.
37
If voltage drops too much, the motor cannot compensate, leading to slower speed, reduced
torque, and possible stalling.
Motor power consumption does not follow the same V² relationship as impedance loads. Instead:
For small voltage changes, xxx is close to 1 (power roughly proportional to voltage).
For larger voltage changes, the power reduction is less significant compared to resistive loads.
Using motor load equations, a 1% voltage drop reduces power demand by about 0.2%:
Small Voltage Drop (1-5%) Increased current, small power reduction (~0.2% per 1% drop)
Moderate Voltage Drop (5-10%) Motor efficiency drops, overheating risk, slower speed
Large Voltage Drop (10-15%) Motor may stall, high heating, possible damage
🔹 Compared to impedance loads, motors resist voltage reductions because they draw more current to
compensate.
38
4. Brownout Effect on Motors
Instead, motors draw more current, increasing the risk of overheating and damage.
✅ Solution: Instead of brownouts, utilities use Demand Response Programs to shut down non-essential
motor loads during peak demand.
5. Key Takeaways
39