0% found this document useful (0 votes)
15 views39 pages

PSO Note 2

The document outlines the objectives and mechanisms of Frequency and Active Load Control (LFC) in power systems, emphasizing the importance of maintaining active power balance and regulating frequency to ensure system stability. It details the roles of Automatic Load Frequency Control (ALFC) and various control strategies, including traditional and AI-based methods, to manage generation and demand effectively. Additionally, it explains the significance of reactive power in voltage control and the need for minimizing transmission losses and unscheduled power transfers.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
15 views39 pages

PSO Note 2

The document outlines the objectives and mechanisms of Frequency and Active Load Control (LFC) in power systems, emphasizing the importance of maintaining active power balance and regulating frequency to ensure system stability. It details the roles of Automatic Load Frequency Control (ALFC) and various control strategies, including traditional and AI-based methods, to manage generation and demand effectively. Additionally, it explains the significance of reactive power in voltage control and the need for minimizing transmission losses and unscheduled power transfers.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 39

Objectives of Frequency and Active Load Control (Simplified)

1. Maintain Active Power Balance

o The total power generated must equal the power consumed by loads plus system
losses.

o Any imbalance affects the system frequency, which can lead to instability.

2. Regulate Frequency

o If generation exceeds demand, frequency increases.

o If demand exceeds generation, frequency decreases.

o Frequency must be kept close to the standard (e.g., 50 Hz in Ghana, 60 Hz in the US).

3. Manage Active Power in Generation & Transmission

o Generation side: Adjust power output to match demand using Automatic Load
Frequency Control (ALFC).

o Transmission side: Ensure power flows efficiently while minimizing losses.

4. Optimize Power Flow & Economic Dispatch

o Power must be routed efficiently to minimize transmission losses.

o Economic Dispatch means generating power at the lowest cost while meeting demand.

5. Minimize Transmission Losses

o Higher voltage levels reduce power loss.

o Parallel transmission lines and compensation techniques (series and shunt


compensation) help maximize efficiency.

6. Implement Load Frequency Control (LFC) Strategies

o Classical Control: Uses PID controllers, but may be slow.

o AI-based Optimization: Uses advanced algorithms for better control.

o Adaptive Control: Adjusts itself dynamically, ideal for systems with renewable energy
sources.

7. Prevent Unscheduled Power Transfers

o Power must flow within planned limits to avoid overloading neighboring systems.

8. Use the "Brownout Effect" for Demand Management

1
o Reducing system voltage slightly (brownout) can reduce demand without complete
blackouts.

Why is Frequency Control Linked to Active Power and Voltage Control Linked to Reactive Power?

To understand this, let's break it down in simple terms.

1. Frequency Control = Active Power Balance

 What is frequency?

o In power systems, frequency (e.g., 50 Hz or 60 Hz) is determined by the rotational speed


of generators in the system.

o More power demand → generators slow down → frequency drops.

o Less power demand → generators speed up → frequency rises.

 Why does active power affect frequency?

o Active power (real power, measured in MW) is what actually powers devices (lights,
machines, etc.).

o If demand suddenly increases, the system needs more power. If generation doesn’t
increase, the extra demand slows down the generators → frequency drops.

o If demand decreases and generation remains high, generators speed up → frequency


rises.

o To maintain a stable frequency, the generation must always match the demand (plus
losses).

2. Voltage Control = Reactive Power Balance

 What is voltage?

o Voltage is like the "pressure" that pushes electric current through the system.

o Voltage fluctuations can damage equipment or cause power instability.

 Why does reactive power affect voltage?

o Reactive power (measured in VARs) doesn’t do "real work" but is needed to support
magnetic fields in transformers, motors, and transmission lines.

o If there isn’t enough reactive power, voltage drops (like weak water pressure in a pipe).

o If there’s too much reactive power, voltage rises beyond safe limits.

2
o Voltage must be controlled by balancing reactive power generation and demand using
capacitors, reactors, and voltage regulators.

Summary:

 Frequency depends on active power because it is directly tied to generator speed.

 Voltage depends on reactive power because it affects the electric field strength needed to
maintain voltage levels.

Active Power (P-Generated) Management in the Generation System

(For Control/Regulation of System Frequency)

1. Why Do We Need Active Power Management?

In an electrical power system, active power (also called real power, measured in MW) is the actual
energy consumed by electrical devices like lights, motors, and heaters.

The goal of active power management in generation is to ensure that power generation always matches
the power demand, plus losses in the system. If this balance is not maintained:

 If generation is higher than demand, frequency will increase (generators speed up).

 If generation is lower than demand, frequency will decrease (generators slow down).

Since frequency affects the stability of the entire power system, we use Automatic Load Frequency
Control (ALFC) to regulate it.

2. How Frequency is Controlled in a Power System

A. The Role of Synchronous Generators

 Power plants use synchronous generators (hydro, thermal, nuclear, or gas) to produce
electricity.

 These generators rotate at a fixed speed to maintain a constant frequency (e.g., 50 Hz or 60 Hz).

 When demand increases or decreases, the rotational speed of the generator changes, causing a
frequency deviation.

B. Speed Governors and ALFC

 The generator has a speed governor, which acts like a cruise control system for frequency.

3
 If the frequency drops (demand > generation), the governor increases fuel or water flow to the
turbine to generate more power.

 If the frequency rises (demand < generation), the governor reduces fuel or water flow.

C. The Automatic Load Frequency Control (ALFC) System

The ALFC automatically regulates frequency using the following process:

1. A frequency sensor measures the system frequency.

2. It compares the actual frequency with the reference frequency (e.g., 50 Hz in Ghana).

3. If there is a difference, an error signal is generated.

4. This signal is amplified and sent to the turbine governor, which adjusts the fuel or water supply
to correct the frequency.

3. Three Possible Generation-Demand Cases

There are three main scenarios that the ALFC system must handle:

Case 1: Demand Matches Generation (Balanced System)

 If the power demand exactly matches the generated power, the generator runs at a constant
speed, and frequency remains steady.

 No corrective action is needed.

🔹 Action Taken: Nothing. The system is already stable.

Case 2: Demand is Less than Generation (Generation Surplus)

 If generation exceeds demand, generators speed up, causing frequency to increase above 50 Hz.

 The system detects this excess power and sends a corrective signal to reduce generator output.

 In a thermal plant, this means closing the steam valve; in a hydro plant, it means closing the
water gate.

🔹 Action Taken: Reduce generator output to lower frequency.

Case 3: Demand is Greater than Generation (Generation Deficit)

 If demand exceeds generation, generators slow down, causing frequency to drop below 50 Hz.

 The system must correct this imbalance to restore frequency.

4
 Three possible solutions:

1. Increase generator output (by increasing fuel or water input).

2. Import power from neighboring grids (if available).

3. Load shedding (last resort: disconnect some consumers to reduce demand).

🔹 Action Taken: Increase generation, import power, or shed load to restore frequency.

4. Load Frequency Control (LFC) Strategies

LFC strategies help control frequency automatically. There are several approaches:

A. Traditional (Droop) Control

 Uses PID controllers (Proportional-Integral-Derivative controllers).

 Tuning methods like Ziegler-Nichols adjust parameters.

 Works well for simple systems but not ideal for modern grids with renewable energy.

B. AI-Based Optimization Control

 Uses machine learning algorithms like Particle Swarm Optimization (PSO), Genetic Algorithm
(GA), Grey Wolf Optimization (GWO), and Artificial Bee Colony (ABC).

 More adaptive and efficient in handling complex grids.

C. Optimal Control Methods

 Uses Mathematical Optimization to stabilize frequency with minimal effort.

 Examples: Model Predictive Control (MPC), Linear Quadratic Regulator (LQR).

 Especially useful in grids with renewable energy (wind, solar, etc.).

D. Adaptive and Self-Tuning Control

 Dynamically adjusts parameters to handle changing system conditions.

 Ideal for smart grids with renewable energy sources.

5. The Role of the Turbine-Governor System in Droop Frequency Control

 The turbine-governor system helps adjust the power output of generators.

 Droop control means the governor reduces generator output as frequency increases and
increases generator output as frequency decreases.

5
 This ensures that all generators share the load proportionally.

6. Network Types and Their Impact on Frequency Control

Case 1: Infinite Network (Large Grid System)

 An infinite network is a large interconnected grid where frequency is stable and not affected by
a single generator.

 Example: If a generator is added or removed, the overall system hardly changes in frequency.

 To increase power output, simply increase turbine input (fuel or water flow).

🔹 Key Point: Generator actions don’t affect system frequency much.

Case 2: Finite Network (Small Grid or Isolated System)

 A finite network is small, meaning frequency changes significantly when a generator's output
changes.

 If a generator increases power, frequency rises; if it reduces power, frequency drops.

 Load-sharing between multiple generators must be carefully managed.

🔹 Key Point: Generators must adjust carefully to maintain frequency stability.

7. Example Calculations

Example 1: Infinite Network

 A 100 MW generator operates in an infinite network.

 If the operator wants to increase output by 5 MW, they simply increase the reference power
setting by 5 MW.

 Since the system is large, the frequency remains unchanged.

Example 2: Finite Network

 A 100 MW generator has a regulation constant of 4% (0.04 pu).

 If the frequency drops by 0.1 Hz, how much power must be added?

 Using the droop equation: ΔP=ΔfR\Delta P = \frac{\Delta f}{R}ΔP=RΔf

o Where R = 0.04 pu, Δf = 0.1 Hz.

6
o Substituting values: ΔP=0.10.04=5MW\Delta P = \frac{0.1}{0.04} = 5 MWΔP=0.040.1
=5MW

o So, the turbine power must increase by 5 MW to compensate for the frequency drop.

8. Summary

 Active power affects frequency, so balancing generation and demand is crucial.

 The Automatic Load Frequency Control (ALFC) system continuously adjusts generator output to
maintain a stable frequency.

 Droop control ensures that all generators share the load proportionally.

 Different control strategies (Traditional, AI-based, Optimal, Adaptive) are used to maintain
system stability.

 Infinite networks (large grids) have stable frequencies, while finite networks (isolated grids)
experience larger frequency variations.

Objectives of the Load Frequency Control (LFC) System (Simplified Explanation)

The Load Frequency Control (LFC) system is responsible for automatically adjusting the power
generation in a system to maintain a stable frequency and keep power flows within acceptable limits.
From the slides, the four key objectives of LFC are:

1. Ensuring Zero Steady-State Error for Frequency Deviations

 What this means: The system should always bring frequency back to normal (e.g., 50 Hz or 60
Hz) after a disturbance.

 Why it’s important: If frequency remains too high or too low for too long, it can damage
equipment and cause system instability.

 How LFC helps:

o If demand suddenly increases and frequency drops, LFC increases generation.

o If demand suddenly decreases and frequency rises, LFC reduces generation.

o The system should reach exactly the desired frequency with no long-term deviation
(this is called "zero steady-state error").

7
✅ Example: If a factory starts operating and demand increases, frequency might drop from 50 Hz to 49.5
Hz. The LFC system will adjust generator output until the frequency returns to 50 Hz with no long-term
error.

2. Minimizing Unscheduled Tie-Line Power Flows

 What this means: Power should only flow between different areas (regions or countries) as
planned.

 Why it’s important: If power unexpectedly flows between areas, it can overload transmission
lines and cause blackouts.

 How LFC helps:

o Monitors power flowing between areas.

o If too much or too little power is transferred, it adjusts local generation to correct the
flow.

✅ Example:

 Ghana imports power from Côte d’Ivoire. If demand suddenly increases in Ghana, more power
might start flowing from Côte d’Ivoire without planning.

 The LFC system detects this and increases Ghana’s local generation to reduce reliance on
imported power and avoid overloading the tie-line.

3. Effective Tracking of Load Demands and Disturbances

 What this means: The system should quickly respond when demand changes.

 Why it’s important: Electricity demand constantly changes throughout the day, and
disturbances (like a generator tripping) can happen at any time.

 How LFC helps:

o Continuously monitors power demand.

o Detects sudden changes and adjusts generator output accordingly.

✅ Example:

 In the morning, people turn on lights and machines → demand increases.

 At night, industries shut down → demand decreases.

8
 The LFC system ensures that generation tracks these changes smoothly without large frequency
deviations.

4. Maintaining Acceptable Overshoot and Settling Time

 What this means: If frequency changes suddenly, it should return to normal smoothly and
quickly without large swings (overshoot) or taking too long (settling time).

 Why it’s important: If the system overreacts or is too slow, it can cause instability or frequent
fluctuations.

 How LFC helps:

o Ensures frequency corrections are fast but controlled.

o Uses control techniques (like PID controllers or AI-based methods) to stabilize the
system efficiently.

✅ Example:

 If a large industrial load suddenly disconnects, frequency might jump to 50.5 Hz before settling
back to 50 Hz.

 The LFC system ensures that this overshoot is small and that frequency returns to normal in the
shortest possible time without unnecessary oscillations.

Summary of the Four LFC Objectives:

Objective Purpose How LFC Helps Example

If demand increases and


Keep frequency Adjusts generator output to
1. Zero steady-state frequency drops to 49.5 Hz, LFC
exactly at 50 Hz (or correct frequency
error increases generation to bring it
60 Hz) deviations
back to 50 Hz

Controls local generation to If Ghana starts pulling extra


2. Minimize Prevent unexpected
match demand and avoid power from Côte d’Ivoire, LFC
unscheduled tie-line power transfers
overloading transmission increases local generation to
power flows between regions
lines reduce dependency

3. Track load Quickly respond to Adjusts generator output in As people turn on lights in the
demand and changing electricity real time based on demand morning, LFC ensures smooth
disturbances usage changes frequency regulation

4. Maintain Ensure frequency Uses advanced control If a factory disconnects, LFC

9
Objective Purpose How LFC Helps Example

acceptable prevents frequency from


stabilizes quickly techniques to avoid large
overshoot and overshooting too much before
and smoothly fluctuations
settling time stabilizing

Final Thought

The Load Frequency Control (LFC) system is like the brain of the power grid, constantly making small
adjustments to keep frequency stable, avoid unnecessary power transfers, track demand changes, and
prevent excessive swings in frequency.

The Automatic Load Frequency Control (ALFC) System – Schematic Diagram (Explained Simply)

The ALFC system is responsible for automatically adjusting generation to maintain a stable power
system frequency. The schematic diagram in the slides represents the different components that work
together to detect, correct, and regulate frequency deviations.

1. Understanding the ALFC System Step-by-Step

Step 1: Frequency Measurement

 The system has a frequency sensor that continuously measures the actual system frequency.

 In Ghana, for example, the normal frequency is 50 Hz.

🔹 Why is this important?

 If the measured frequency is less than 50 Hz, it means demand exceeds generation (more load,
less supply).

 If the measured frequency is greater than 50 Hz, it means generation exceeds demand (more
supply, less load).

Step 2: Frequency Comparison (Error Signal Generation)

 The measured frequency is sent to a comparator, where it is compared with the reference
frequency (50 Hz in Ghana, 60 Hz in the US).

 The comparator calculates an error signal:

Error Signal=Reference Frequency−Measured Frequency\text{Error Signal} = \text{Reference Frequency}


- \text{Measured Frequency}Error Signal=Reference Frequency−Measured Frequency

10
🔹 Why is this important?

 If the error is positive, it means frequency is too high → Reduce generator output.

 If the error is negative, it means frequency is too low → Increase generator output.

Step 3: Signal Amplification

 The small error signal is too weak to directly control the generator.

 A transducer (amplifier) increases the strength of the signal.

 This amplified signal is then used to control the prime mover (turbine) of the generator.

🔹 Why is this important?

 Without amplification, the signal wouldn’t be strong enough to make physical adjustments to
the turbine.

Step 4: Controlling the Prime Mover (Turbine Governor Action)

 The amplified error signal is sent to the turbine through a governor.

 The governor adjusts the input to the turbine based on the error signal:

o If frequency is too low → The governor opens the steam valve (thermal) or water gate
(hydro) to allow more fuel/water into the turbine → more power is generated.

o If frequency is too high → The governor closes the steam valve (thermal) or water gate
(hydro) to reduce turbine power output.

🔹 Why is this important?

 The turbine is what actually generates electricity. Without adjusting it, the system cannot
correct frequency deviations.

Step 5: Power Adjustment and System Stability

 After the turbine adjusts, the generator increases or decreases power output as needed.

 This restores the balance between generation and demand, bringing frequency back to normal.

🔹 Why is this important?

 The system must constantly adjust power output to match demand in real-time.

11
2. Summary of the ALFC Process

Step What Happens? Why It’s Important?

1. Frequency A sensor measures the actual system Detects if frequency is above or below
Measurement frequency. normal.

2. Frequency The actual frequency is compared to 50 Finds out whether generation needs to
Comparison Hz (or 60 Hz). increase or decrease.

Ensures the signal is strong enough to


3. Signal Amplification The error signal is amplified.
control the generator.

4. Prime Mover The turbine governor opens/closes Increases or decreases generation to


Control valves to adjust power. correct frequency.

The generator changes its output to Keeps the system frequency stable and
5. Power Adjustment
restore balance. reliable.

3. Example Scenario – ALFC in Action

Case 1: Sudden Increase in Load (Example: A Large Factory Starts Operation)

🔹 What happens?

 The new factory increases demand, so the system needs more power.

 If no action is taken, frequency drops (e.g., from 50 Hz to 49.6 Hz).

🔹 How ALFC responds?

1. Sensor detects frequency drop (49.6 Hz instead of 50 Hz).

2. Comparator generates a negative error signal (50 - 49.6 = +0.4 Hz).

3. Transducer amplifies the signal and sends it to the turbine governor.

4. Governor opens the fuel/water input to the turbine → More power is generated.

5. Frequency returns to 50 Hz.

Case 2: Sudden Decrease in Load (Example: A Factory Shuts Down at Night)

🔹 What happens?

 The factory shutdown reduces demand, so too much power is being generated.

 If no action is taken, frequency rises (e.g., from 50 Hz to 50.4 Hz).

12
🔹 How ALFC responds?

1. Sensor detects frequency rise (50.4 Hz instead of 50 Hz).

2. Comparator generates a positive error signal (50 - 50.4 = -0.4 Hz).

3. Transducer amplifies the signal and sends it to the turbine governor.

4. Governor closes the fuel/water input to the turbine → Less power is generated.

5. Frequency returns to 50 Hz.

4. Why is the ALFC System Important?

 Prevents blackouts: Without frequency control, large deviations can cause system failure.

 Ensures power quality: Most electrical devices require stable frequency to operate properly.

 Balances generation and demand: Avoids oversupply (wasted energy) and undersupply (power
shortages).

 Supports grid reliability: Helps power plants work together to maintain grid stability.

5. Key Takeaways

✅ The ALFC system automatically regulates power generation to keep frequency stable.
✅ It works by detecting frequency changes, amplifying the error signal, and adjusting turbine power.
✅ It ensures that power generation always matches demand, preventing grid instability.
✅ Without ALFC, sudden load changes could lead to blackouts or power fluctuations.

Case 1: Demand Equals Generation (Balanced System)

This is the ideal condition in a power system where the power generated exactly matches the power
consumed by loads, including transmission losses.

1. What Happens When Demand Equals Generation?

When the power demand (load) is perfectly balanced with power generation, the following conditions
are met:

 The speed of the synchronous generators remains constant.

13
 The system frequency remains stable (e.g., 50 Hz in Ghana, 60 Hz in the US).

 No additional adjustments to the generator output are needed.

This means the system is operating normally without any disturbances.

2. What Does This Mean for Frequency?

Since frequency depends on generator speed, and speed is constant in this scenario:

Frequency=Reference Frequency(50 Hz or 60 Hz)\text{Frequency} = \text{Reference Frequency} (50 \


text{ Hz or 60 Hz})Frequency=Reference Frequency(50 Hz or 60 Hz)

 No increase in load to slow down generators.

 No excess generation to speed up generators.

 The frequency remains steady because the system is in balance.

3. What Action is Taken?

🔹 Since everything is already balanced, NO corrective action is needed.

 The turbine governor does not need to open or close the steam/water input.

 The ALFC system does not need to adjust generator output.

 The power plants continue generating at the same level without changes.

Conclusion:
💡 The system is running in a perfectly stable state, so no changes are required.

4. Example Scenario

🔹 Normal Evening Load in a City

 Assume a power grid supplies a city where normal evening demand is 1000 MW.

 The power plants are generating exactly 1000 MW.

 Since generation = demand, the frequency remains at 50 Hz.

🔹 Result:

 No changes in power output are needed.

 The system remains stable and balanced.

14
5. Key Takeaways

✅ When demand = generation, the system frequency remains stable.


✅ No corrective action is needed from the ALFC system.
✅ The generators operate at a steady speed, and no load shedding or power imports are required.

Case 2: Demand LESS THAN Generation (Generation Surplus)

In this scenario, the power generated is greater than the power consumed by the loads in the system.
This results in excess energy that needs to be managed.

1. What Happens When Generation is Greater Than Demand?

 The extra generated power has nowhere to go, so the rotational speed of the generators
increases.

 Since frequency is directly related to generator speed, the system frequency rises above
normal (e.g., it might increase from 50 Hz to 50.4 Hz).

 This situation can damage electrical equipment, overload transmission lines, and cause
instability.

🔹 Key Problem: Frequency rises above the normal level (50 Hz or 60 Hz).

2. Why Does Frequency Increase?

1. Power plants keep generating at the same level.

2. Less power is being used by consumers (factories shut down, households reduce usage, etc.).

3. The extra power makes generators spin faster, increasing frequency.

⚡ Think of it like a car engine:

 If you keep pressing the accelerator (fuel supply remains high) but the road suddenly becomes
downhill (less resistance/load), the car speeds up beyond the desired limit.

 Similarly, in a power system, when demand decreases but generation remains the same,
frequency rises because generators are still spinning at high speed.

3. What Action is Taken? (Corrective Measures)

15
To reduce the system frequency back to normal, the ALFC system takes corrective actions:

Action 1: Reduce Generator Output (Primary Solution)

 The turbine governor detects the increase in frequency and responds by reducing fuel/water
supply to the generator.

 This slows down the generator, reducing power generation until it matches the demand.

 In a thermal power plant, this means closing the steam valve slightly.

 In a hydropower plant, this means partially closing the water gate.

🔹 Effect: Less power is produced, frequency decreases, and balance is restored.

Action 2: Export Power to Other Regions (If Possible)

 If the power system is interconnected with neighboring grids, the extra power can be exported
instead of reducing generation.

 This is possible if other regions have higher demand and need more electricity.

🔹 Example:

 Ghana produces excess power but Côte d’Ivoire needs more electricity. Instead of reducing
generation, Ghana can export power to Côte d’Ivoire, stabilizing frequency without wasting
energy.

Action 3: Store Excess Power (If Available)

 If the grid has battery storage systems or hydropower reservoirs, the extra energy can be stored
instead of being wasted.

 Pumped hydro storage is commonly used:

o Excess power is used to pump water up to a reservoir.

o Later, when demand increases, the stored water is released to generate electricity.

Action 4: Use Load-Shifting Strategies

 Some industries and large consumers can be signaled to increase power usage when there’s an
excess of generation.

 This prevents frequency from rising too high and makes better use of the available power.

16
4. Example Scenario: A Factory Shuts Down Unexpectedly

🔹 What happens?

 A factory consuming 200 MW suddenly shuts down.

 Power plants were still generating the original amount, leading to excess power in the system.

 Since generation > demand, frequency rises from 50 Hz to 50.4 Hz.

🔹 How ALFC responds?

1. Sensor detects frequency increase.

2. Comparator generates an error signal indicating the system is over-generating.

3. Transducer amplifies the signal and sends it to the turbine governor.

4. Governor reduces the fuel/water input → Power output decreases.

5. Frequency returns to 50 Hz.

5. Summary of Generation Surplus Case

Situation Effect on System Action Taken

Power generation Generators speed up → Reduce generator output by closing steam


exceeds demand frequency increases above 50 Hz valve (thermal) or water gate (hydro)

If the system is Power can be exported to other


Transfer excess power to neighboring grids
interconnected regions

If storage is available Excess power can be stored Use pumped hydro storage or batteries

If industrial consumers Load-shifting can balance


Increase industrial consumption temporarily
can help demand

6. Key Takeaways

✅ If generation exceeds demand, frequency increases above the normal level.


✅ The main corrective action is to reduce generator output.
✅ If possible, power can be exported, stored, or used in industrial processes to stabilize the grid.
✅ Without correction, high frequency can damage electrical devices and cause system instability.

17
Case 3: Demand GREATER THAN Generation (1/2) (Generation Deficit)

This scenario occurs when electricity demand exceeds the available power generation. This creates a
generation deficit, which can cause system instability if not corrected.

1. What Happens When Demand is Greater Than Generation?

 The power system does not have enough generated power to meet the demand.

 The synchronous generators slow down because the electrical load is trying to draw more
power than the system can supply.

 Since frequency is directly related to generator speed, the system frequency drops below
normal (e.g., from 50 Hz to 49.6 Hz).

 If the frequency drops too low, power plants and sensitive equipment can shut down, causing
blackouts.

🔹 Key Problem: Frequency drops below the normal level (50 Hz or 60 Hz).

2. Why Does Frequency Decrease?

1. More power is being drawn from the generators than they can supply.

2. This reduces generator speed, causing frequency to drop.

3. If the frequency keeps dropping and no action is taken, entire power plants can trip, leading to a
blackout.

⚡ Think of it like a car engine:

 If you’re driving up a steep hill (increased demand) but don’t press the accelerator (insufficient
generation), the car slows down (frequency drops).

 The system needs to increase fuel supply (more power generation) to keep moving at the
correct speed (50 Hz).

3. What Action is Taken? (Corrective Measures)

To increase system frequency back to normal, the ALFC system takes corrective actions:

Action 1: Increase Generator Output (Primary Solution)

18
 The turbine governor detects the drop in frequency and responds by increasing fuel/water
supply to the generator.

 This speeds up the generator, producing more power until it matches demand.

 In a thermal power plant, this means opening the steam valve to allow more fuel to the boiler.

 In a hydropower plant, this means opening the water gate to increase turbine speed.

🔹 Effect: More power is generated, frequency increases, and balance is restored.

Action 2: Import Power from Other Regions (If Possible)

 If the power system is interconnected with neighboring grids, the deficit power can be imported
from another region.

 This is helpful when local generators cannot ramp up quickly enough.

🔹 Example:

 Ghana experiences a power deficit, but Côte d’Ivoire has surplus power.

 Instead of shutting down industries, Ghana imports extra power from Côte d’Ivoire.

Action 3: Load Shedding (Last Resort)

 If generation cannot be increased and power cannot be imported, the only option is to reduce
demand.

 This means cutting off power to certain areas (load shedding) to bring demand back in balance
with generation.

🔹 Example:

 If the power deficit is 200 MW, the system operator disconnects some non-essential consumers
(e.g., street lights, industrial plants) to reduce demand by 200 MW.

 This prevents a complete blackout and allows essential services (hospitals, communication
centers) to keep running.

💡 Load shedding is always the last option because it affects consumers.

4. Example Scenario: A Power Plant Trips Unexpectedly

🔹 What happens?

19
 A 500 MW power plant unexpectedly shuts down due to a technical fault.

 The system was already operating close to full capacity, so this sudden loss creates a power
shortage.

 Since demand is greater than generation, frequency drops from 50 Hz to 49.4 Hz.

🔹 How ALFC responds?

1. Sensor detects frequency drop.

2. Comparator generates an error signal indicating power shortage.

3. Transducer amplifies the signal and sends it to the turbine governor.

4. Governor opens the fuel/water input → More power is generated.

5. If generation still isn’t enough, power is imported or load shedding is applied.

6. Frequency returns to 50 Hz.

5. Summary of Generation Deficit Case

Situation Effect on System Action Taken

Generators slow down →


Power demand exceeds Increase generator output by opening steam
frequency decreases below 50
generation valve (thermal) or water gate (hydro)
Hz

If local generation is More power is needed


Import power from neighboring regions
insufficient immediately

If neither generation nor Load shedding (disconnecting some


The grid is at risk of a blackout
import is enough consumers)

6. Key Takeaways

✅ If demand exceeds generation, frequency drops below the normal level.


✅ The main corrective action is to increase generator output.
✅ If possible, power can be imported to stabilize the grid.
✅ If no other option exists, load shedding is used to prevent total system failure.

Load Frequency Control (LFC) Strategies (Explained Simply)

20
Load Frequency Control (LFC) is a system that automatically adjusts power generation to maintain a
stable frequency (e.g., 50 Hz or 60 Hz) when demand changes.

There are four main strategies used to achieve this:

1. Traditional Control Method (Droop Control / PID Control)

How it Works

 This method uses simple controllers like Proportional-Integral-Derivative (PID) controllers to


regulate frequency.

 When frequency drops, the controller increases power generation.

 When frequency rises, the controller decreases power generation.

Tuning Methods

 A common way to tune these controllers is the Ziegler-Nichols method, which adjusts the
controller settings based on system behavior.

Limitations

❌ This method is not optimal for all systems.


❌ It is slow in responding to large disturbances.
❌ It struggles with complex, non-linear power systems (such as those with renewable energy).

🔹 Example:
Imagine you are driving a car with cruise control.

 If the car slows down too much, the system adds more fuel.

 If the car speeds up too much, the system reduces fuel.

 However, this method is not the most precise—it may overcorrect or respond slowly.

2. AI-Based Optimization Methods

How it Works

 Uses Artificial Intelligence (AI) algorithms to optimize frequency control.

 AI analyzes system behavior and makes smart adjustments.

Common AI Techniques Used:

✅ Particle Swarm Optimization (PSO) – Inspired by how birds move in a flock to find food efficiently.
✅ Genetic Algorithm (GA) – Inspired by evolution and natural selection.

21
✅ Grey Wolf Optimization (GWO) – Inspired by wolf hunting strategies.
✅ Artificial Bee Colony (ABC) – Inspired by how bees find food efficiently.

Advantages

✅ AI-based control is faster and more accurate than traditional methods.


✅ It can handle complex power systems with renewable energy sources.
✅ It learns and adapts to new conditions.

🔹 Example:
Think of AI-based LFC like a smart traffic control system.

 Instead of using fixed rules, the system monitors real-time traffic flow and adjusts signals
intelligently to reduce congestion.

3. Optimal Control Method

How it Works

 This method minimizes a cost function, meaning it finds the best way to control frequency with
minimum effort and energy loss.

 It stabilizes frequency and reduces power fluctuations.

Common Techniques Used:

✅ Model Predictive Control (MPC) – Predicts future demand and adjusts generation before a problem
occurs.
✅ Linear Quadratic Regulator (LQR) – Minimizes frequency deviations while using the least energy
possible.

Advantages

✅ Very efficient for modern power systems.


✅ Works well in grids with renewable energy (solar, wind, etc.).
✅ Reduces costs and energy wastage.

🔹 Example:
Think of it like Google Maps predicting traffic conditions.

 Instead of reacting after a traffic jam occurs, it forecasts the problem and suggests the best
route in advance.

4. Adaptive and Self-Tuning Control

How it Works

22
 This method automatically adjusts itself based on real-time power system conditions.

 The controller parameters update continuously, keeping the system optimized.

Advantages

✅ It handles changing demand conditions smoothly.


✅ It works well with renewable energy sources (which vary throughout the day).
✅ It is ideal for smart grids, where electricity generation and demand fluctuate.

🔹 Example:
Imagine a thermostat that adjusts room temperature automatically based on weather conditions.

 If it's getting hotter outside, the AC increases cooling.

 If it's getting cooler, the AC reduces power usage.

Comparison of LFC Strategies

LFC Strategy How It Works Advantages Limitations

Uses simple controllers to Slow response. Less


Traditional Control Easy to implement. Works
adjust frequency based on effective for complex
(PID, Droop Control) for simple grids.
deviations. power systems.

AI-Based Optimization Uses machine learning &


Fast, accurate, handles Requires advanced
(PSO, GA, GWO, ABC, AI algorithms to optimize
complex systems well. computing power.
etc.) control.

Minimizes energy usage Efficient, reduces energy


Optimal Control (MPC, More complex than
while keeping frequency waste, works well with
LQR) traditional methods.
stable. renewables.

Best for smart grids &


Adaptive & Self-Tuning Adjusts itself dynamically More difficult to
renewable energy. Very
Control to changing conditions. implement.
flexible.

Conclusion

✅ Traditional control (PID, Droop) is simple but not very efficient.


✅ AI-based control is more advanced, faster, and more accurate.
✅ Optimal control ensures minimum energy waste and maximum stability.
✅ Adaptive control is the most flexible and works well for modern smart grids.

23
The Turbine-Governor Control System (Droop Frequency Control) – Explained Simply

The Turbine-Governor Control System is a key part of Load Frequency Control (LFC). It adjusts generator
power output to maintain system frequency.

One important method used in power systems is Droop Frequency Control, which allows generators to
share load changes proportionally while keeping the grid stable.

1. What is Droop Frequency Control?

🔹 Droop control is a way to regulate generator output based on frequency changes.

 If demand increases, frequency drops → The generator increases output.

 If demand decreases, frequency rises → The generator reduces output.

 However, instead of forcing frequency exactly to 50 Hz or 60 Hz, each generator adjusts


proportionally.

🔹 Why is it called "droop"?

 Because as power output increases, the frequency slightly decreases instead of staying
constant.

 The relationship between power output and frequency is a sloping line (droop).

 The amount of droop is set by the droop constant (R), which is typically 3-5%.

2. How Does the Turbine-Governor System Work?

The Turbine-Governor is responsible for controlling how much power a generator produces.

Main Components of the System:

1️⃣ Speed Governor – Detects changes in generator speed (which affects frequency).
2️⃣ Turbine – Converts steam (thermal plants) or water flow (hydro plants) into mechanical power.
3️⃣ Fuel/Water Valve – Controls how much fuel (thermal) or water (hydro) enters the turbine.
4️⃣ Generator – Converts mechanical energy from the turbine into electrical energy.

3. How Droop Control Works in Two Cases

Case 1: Demand Increases (Frequency Drops)

🔹 Example: A large factory starts operation, increasing demand.

24
 The extra load causes generators to slow down, and frequency drops (e.g., from 50 Hz to 49.8
Hz).

 The speed governor detects the drop and opens the fuel valve, increasing turbine power.

 More electricity is generated, balancing supply and demand.

 The frequency stabilizes but remains slightly lower than 50 Hz due to droop.

Case 2: Demand Decreases (Frequency Rises)

🔹 Example: A factory shuts down, reducing demand.

 Less load means generators speed up, and frequency rises (e.g., from 50 Hz to 50.2 Hz).

 The speed governor detects the rise and closes the fuel valve, reducing turbine power.

 Less electricity is generated, bringing supply and demand back in balance.

 The frequency stabilizes but remains slightly above 50 Hz due to droop.

4. Mathematical Formula for Droop Control

Droop control follows this formula:

ΔP=ΔfR\Delta P = \frac{\Delta f}{R}ΔP=RΔf

Where:

 ΔP = Change in power output (MW)

 Δf = Change in frequency (Hz)

 R = Droop constant (pu or %)

🔹 Example Calculation:
A generator has a droop setting of 4% (0.04 pu).

 If system frequency drops by 0.1 Hz, how much should the generator increase its power output?

ΔP=0.10.04=2.5 MW\Delta P = \frac{0.1}{0.04} = 2.5 \text{ MW}ΔP=0.040.1=2.5 MW

So the generator must increase output by 2.5 MW to help restore balance.

5. Two Types of Networks in Droop Control

Case 1: Infinite Network (Large Grid System)

25
 In a large, interconnected grid, frequency is almost constant because many generators share the
load.

 If one generator increases or decreases output, the overall system frequency hardly changes.

🔹 Key Point: The turbine only responds to load changes, not frequency changes.

Case 2: Finite Network (Isolated System)

 In a small or isolated grid, frequency changes significantly when load changes.

 If one generator increases or decreases output, frequency shifts noticeably.

 The droop constant (R) is very important because it determines how much each generator
should adjust.

🔹 Key Point: Generators must carefully share load to keep frequency stable.

6. Why is Droop Control Important?

✅ Ensures Stable Load Sharing – Multiple generators can operate together without conflict.
✅ Prevents Overcorrection – Instead of forcing frequency exactly to 50 Hz, the system adjusts smoothly.
✅ Allows Multiple Generators to Work Together – Each generator contributes based on its droop setting.
✅ Essential for Islanded Grids – Helps microgrids and standalone systems manage frequency without
external help.

7. Summary of Droop Control

Condition What Happens? How Droop Control Responds?

Demand Increases (Factory starts, Frequency drops below Generator increases power output by
more load) 50 Hz opening fuel/water valve

Demand Decreases (Factory shuts Frequency rises above Generator reduces power output by
down, less load) 50 Hz closing fuel/water valve

Frequency stays nearly Generators adjust output based on load


Large grid (infinite network)
constant changes

Frequency changes Droop control helps share load between


Small grid (finite network)
significantly generators

26
8. Final Thoughts

 Droop frequency control is a simple but powerful method to regulate generator output.

 It helps stabilize frequency while allowing multiple generators to share load changes fairly.

 Without droop control, generators could overreact, leading to instability or power failures.

Active Power (P-Flow) Management in the Transmission System

(For Maximizing Transmission Capacity & Minimizing Line Losses)

Electricity is generated at power plants and transmitted over long distances through transmission lines
before reaching consumers. To ensure efficient delivery, active power flow (P-flow) must be managed
properly.

This section explains how active power is transmitted, how to maximize transmission capacity, and
how to minimize losses.

1. How Active Power (P) Flows in Transmission Lines

 Active power (P) is the real power that actually does work (e.g., lighting, heating, running
machines).

 Power flows through transmission lines between generators and loads.

 The amount of power transferred depends on:

1. Voltages at the sending and receiving ends (V₁ and V₂).

2. Reactance (X) of the transmission line.

3. Phase angle difference (δ) between sending and receiving ends.

Power Flow Equation

P=V1V2Xsin⁡(δ)P = \frac{V_1 V_2}{X} \sin(δ)P=XV1V2sin(δ)

🔹 Key Insights:

 More voltage (V) → More power can be transmitted.

 Smaller reactance (X) → More power can be transmitted.

 Larger phase angle difference (δ) → More power flow, but too large a δ can lead to instability.

27
2. How to Increase Transmission Capacity (Maximize Transmittable Power)

To increase how much active power a line can carry, we can:

A. Increase Transmission Voltage

 Since power flow depends on V₁ and V₂, increasing transmission voltage boosts capacity.

 However, increasing voltage requires:

o Stronger insulation

o Taller transmission towers

o Upgraded switchgear

 Common voltage levels:

o High Voltage (HV): 110 kV – 345 kV

o Extra High Voltage (EHV): 400 kV – 765 kV

o Ultra High Voltage (UHV): 800 kV – 1,200 kV

✅ Advantage: High voltage reduces current, which reduces power losses.

B. Reduce Line Reactance (X)

 Since X is in the denominator of the power equation, reducing X increases P-flow.

 Ways to reduce reactance:

1. Use Parallel Transmission Lines – Adding extra lines reduces overall reactance.

2. Use Conductor Bundling – Bundling conductors together reduces reactance.

3. Series Compensation (Capacitors) – Adding series capacitors cancels some of the


reactance.

✅ Advantage: Less reactance means more power can flow efficiently.

C. Optimize the Phase Angle Difference (δ)

 Real power flows from the generator with the most leading voltage angle to the one with the
most lagging angle.

 Too small δ → Not enough power transfer.

 Too large δ → System instability (risk of blackout).

28
 Typical range: δ is usually kept below 30-40° for stability.

✅ Advantage: A well-managed phase angle ensures maximum power transfer without instability.

3. How to Minimize Line Losses (Make Transmission More Efficient)

Not all power generated reaches consumers—some is lost in the transmission lines. These losses must
be minimized.

A. Reduce Line Current (I)

 Power loss equation: Ploss=I2RP_{\text{loss}} = I^2 RPloss=I2R

 Since losses depend on current (I) squared, reducing current greatly reduces losses.

 How to reduce I?

o Increase voltage (higher V means lower I for the same power).

o Use local power generation (distributed generation).

✅ Advantage: Lower current reduces both power loss and heating of conductors.

B. Use Thicker Conductors (Reduce R)

 Resistance (R) causes power loss.

 Thicker conductors have less resistance, which reduces losses.

 This is called "reconductoring" (replacing old conductors with larger ones).

✅ Advantage: Lower resistance means less power lost as heat.

C. Use Shunt Compensation (Reactive Power Control)

 Problem: Reactive power (Q) takes up transmission capacity and increases losses.

 Solution: Install shunt capacitors or reactors to reduce reactive power flow.

 This keeps voltage stable and frees up space for active power (P-flow).

✅ Advantage: More of the transmission line capacity is used for real power, improving efficiency.

D. Use High Voltage Direct Current (HVDC)

 AC transmission suffers from reactive power losses, but HVDC does not.

29
 HVDC lines reduce line losses by 30-50% compared to AC lines.

 Used for long-distance transmission (e.g., China’s 1,000 km HVDC lines).

✅ Advantage: HVDC has lower losses and better control over power flow.

4. Summary: Key Techniques for P-Flow Management

Goal Method How It Helps

Maximize Transmission Higher voltage reduces current and allows


Increase transmission voltage
Capacity more power transfer

Reduce line reactance (X) Lower reactance increases power transfer

Optimize phase angle difference Ensures maximum power transfer without


(δ) instability

Minimize Power Losses Reduce current (I) Lower current means lower resistive losses

Less resistance means less power lost as


Use thicker conductors
heat

Shunt compensation Reduces reactive power losses, freeing


(capacitors/reactors) capacity for real power

More efficient for long-distance


Use HVDC transmission
transmission

5. Final Thoughts

✅ Managing active power flow ensures reliable and efficient power delivery.
✅ Maximizing transmission capacity allows grids to handle more power without overloading.
✅ Minimizing losses improves efficiency and reduces energy waste.
✅ Techniques like HVDC, conductor bundling, and shunt compensation improve performance.

Active Power (P-Demand) Management in the Distribution System (Brownout Effect)

Power demand varies throughout the day, and sudden changes in demand can cause instability in the
power system. Managing active power demand in the distribution system is important for keeping the
grid stable and efficient.

30
One technique used for demand management is the Brownout Effect, which helps reduce power
consumption without completely cutting off electricity.

1. What is the Brownout Effect?

🔹 A brownout is a controlled reduction in system voltage to reduce power demand without causing a
total blackout.

🔹 Unlike a blackout (complete power loss), a brownout lowers voltage by a small percentage (e.g., 5% to
10%) so that consumers continue to receive electricity, but power-hungry appliances consume less
energy.

2. Why Does Lowering Voltage Reduce Power Demand?

Different types of electrical loads respond differently when voltage is reduced.

A. Impedance Loads (Resistive Loads like Heaters, Lights, etc.)

 Example: Incandescent bulbs, electric heaters, ovens.

 These loads follow Ohm’s Law: P=V2RP = \frac{V^2}{R}P=RV2

o If voltage decreases by 1%, power demand drops by 2%.

o If voltage decreases by 5%, power demand drops by 10%.

✅ Effect: Power consumption drops significantly, reducing overall system demand.

B. Motor Loads (Induction Motors in Fans, Refrigerators, etc.)

 Example: Air conditioners, refrigerators, water pumps.

 Motors are less sensitive to small voltage changes but still experience a small power reduction.

 When voltage drops:

o Current increases slightly to compensate for the lower voltage.

o But power consumption still reduces slightly (0.2% power drop for a 1% voltage drop).

✅ Effect: Lower power reduction than resistive loads, but still helps manage demand.

3. How Brownouts Help Manage Power Demand

31
🔹 During peak demand hours, reducing voltage slightly can:
✅ Reduce total electricity consumption, easing stress on generators.
✅ Prevent blackouts by spreading available power across more consumers.
✅ Allow critical facilities (hospitals, emergency services) to keep running.

4. Example Calculation: Brownout Effect on Power Demand

Imagine a city consuming 500 MW of electricity. The distribution company reduces voltage by 5%.

For Impedance Loads

Power Reduction=(5% voltage drop)×2=10%\text{Power Reduction} = (5\% \text{ voltage drop}) \times 2
= 10\%Power Reduction=(5% voltage drop)×2=10%

 If 300 MW of the city’s load is from impedance loads, power demand drops by:
300×0.1=30 MW300 \times 0.1 = 30 \text{ MW}300×0.1=30 MW

For Motor Loads

Power Reduction=(5% voltage drop)×0.2=1%\text{Power Reduction} = (5\% \text{ voltage drop}) \times
0.2 = 1\%Power Reduction=(5% voltage drop)×0.2=1%

 If 200 MW of the city’s load is from motors, power demand drops by: 200×0.01=2 MW200 \
times 0.01 = 2 \text{ MW}200×0.01=2 MW

Total Power Demand Reduction

30+2=32 MW30 + 2 = 32 \text{ MW}30+2=32 MW

🔹 Result: The system saves 32 MW just by lowering voltage by 5%.

5. When are Brownouts Used?

🔹 During power shortages – When power plants cannot meet demand, brownouts help avoid complete
blackouts.
🔹 During extreme weather – Heatwaves or cold spells cause high electricity use, and brownouts reduce
overload.
🔹 To balance power flow – Helps avoid system-wide failures when there’s an imbalance between
generation and demand.

6. Advantages & Disadvantages of Brownouts

32
Advantages Disadvantages

Prevents complete blackouts Can damage sensitive electronic devices

Motors (e.g., fridges, ACs) may overheat due to


Reduces system overload
increased current

Some devices (e.g., TVs, computers) may flicker or


Spreads available power fairly
malfunction

Allows essential services (hospitals, police) to


Long-term brownouts reduce appliance lifespan
keep running

7. Final Thoughts

✅ Brownouts are a controlled way to reduce power demand by lowering voltage.


✅ Different loads respond differently—impedance loads reduce power more than motor loads.
✅ Brownouts help prevent blackouts and ensure fair power distribution during crises.

Voltage Dependency of Impedance Loads (Explained Simply)

In power systems, impedance loads (such as heaters, incandescent bulbs, and some industrial
equipment) depend on voltage to determine how much power they consume. When voltage changes,
the power demand of these loads also changes.

1. What are Impedance Loads?

🔹 Impedance loads are loads whose resistance (R) or impedance (Z) does not change significantly with
voltage.

 Examples:

o Electric heaters

o Incandescent bulbs

o Resistive elements in industrial furnaces

🔹 These loads follow Ohm’s Law:

I=VRI = \frac{V}{R}I=RV

 Where:

o III = Current (A)

33
o VVV = Voltage (V)

o RRR = Resistance (Ω)

2. How Voltage Affects Power Consumption

The power consumed by an impedance load is given by:

P=V2RP = \frac{V^2}{R}P=RV2

Key Observations:

1. Power (P) is proportional to the square of voltage (V²).

2. If voltage increases, power consumption increases significantly.

3. If voltage decreases, power consumption decreases significantly.

✅ Example Calculation:
If voltage drops by 10%, power consumption drops by:

(0.1×2)=20%(0.1 \times 2) = 20\%(0.1×2)=20%

📌 Conclusion: A small change in voltage causes a larger change in power for impedance loads.

3. Example Scenario: Voltage Drop on a Heater

A 2 kW heater operates at 230V. If the voltage drops by 5%, how much power will it consume?

Step 1: Find Initial Power Consumption

Pinitial=2302RP_{\text{initial}} = \frac{230^2}{R}Pinitial=R2302

Step 2: Find New Voltage

Vnew=230−(0.05×230)=218.5VV_{\text{new}} = 230 - (0.05 \times 230) = 218.5VVnew


=230−(0.05×230)=218.5V

Step 3: Find New Power Consumption

Pnew=218.52RP_{\text{new}} = \frac{218.5^2}{R}Pnew=R218.52

Since power is proportional to V2V^2V2:

Pnew=Pinitial×(218.5230)2P_{\text{new}} = P_{\text{initial}} \times \left(\frac{218.5}{230}\right)^2Pnew


=Pinitial×(230218.5)2 Pnew=2000×(0.95)2P_{\text{new}} = 2000 \times (0.95)^2Pnew=2000×(0.95)2
Pnew=1805WP_{\text{new}} = 1805WPnew=1805W

✅ Conclusion: A 5% voltage drop reduces power consumption by 9.5%.

34
4. Implications of Voltage Dependency for Impedance Loads

A. Benefits of Voltage Reduction (Brownouts)

 Helps reduce overall power demand without turning off loads completely.

 Useful in power shortages (e.g., grid emergencies).

 Extends lifespan of resistive devices (since lower power means less heat stress).

B. Risks of Voltage Reduction

 Lighting becomes dimmer (incandescent bulbs will not be as bright).

 Heating devices take longer to reach the desired temperature.

5. Key Takeaways

✅ Impedance loads depend on voltage squared → Small voltage changes cause bigger power changes.
✅ Lowering voltage reduces power consumption, which can help balance the grid during high demand.
✅ Too much voltage drop can reduce efficiency in heating and lighting applications.

Frequency Dependency of Impedance Loads (Explained Simply)

In power systems, some loads change their power consumption based on frequency variations.
Impedance loads (such as heating elements, incandescent bulbs, and certain industrial equipment) are
mainly affected by voltage changes, but they also have a small dependence on frequency because of
their reactance component.

1. What Are Impedance Loads?

🔹 Impedance loads are electrical devices where current flow is determined by total impedance (Z),
which includes:

 Resistance (R) – For purely resistive loads like heaters and incandescent bulbs.

 Reactance (X) – If the load contains inductance (L) or capacitance (C), its impedance also
depends on frequency.

Total Impedance Formula:

Z=R2+X2Z = \sqrt{R^2 + X^2}Z=R2+X2

35
Since reactance (X) depends on frequency (f), the overall impedance (Z) of the load can change if
frequency changes.

2. How Frequency Affects Impedance Loads

🔹 For purely resistive loads (like heaters & bulbs)

 Resistive loads do NOT depend on frequency.

 Their power consumption is mainly affected by voltage, not frequency.

🔹 For loads with reactance (like inductive heating coils or fluorescent lamps)

 Inductive reactance increases with frequency:

XL=2πfLX_L = 2\pi f LXL=2πfL

o Higher f → Higher X_L → Higher Z → Less current → Less power consumption.

o Lower f → Lower X_L → Lower Z → More current → More power consumption.

 Capacitive reactance decreases with frequency:

XC=12πfCX_C = \frac{1}{2\pi f C}XC=2πfC1

o Higher f → Lower X_C → Lower Z → More current → More power consumption.

o Lower f → Higher X_C → Higher Z → Less current → Less power consumption.

Key Result:

P∝1fP \propto \frac{1}{f}P∝f1

🔹 If frequency increases, impedance increases, and power consumption decreases.


🔹 If frequency decreases, impedance decreases, and power consumption increases.

3. Example Calculation: 1% Frequency Drop Effect on Load Power

Let’s assume an inductive load with a power factor of 0.8. If frequency drops by 1%, how much will the
real power change?

Using the derived formula from the slides:

ΔPP=−2(1−cos⁡θ)Δff\frac{\Delta P}{P} = -2(1 - \cos\theta) \frac{\Delta f}{f}PΔP=−2(1−cosθ)fΔf

For a power factor cosθ = 0.8:

ΔPP=−2(1−0.8)×(−0.01)\frac{\Delta P}{P} = -2(1 - 0.8) \times (-0.01)PΔP=−2(1−0.8)×(−0.01)


=0.004=0.4% increase in power= 0.004 = 0.4\% \text{ increase in power}=0.004=0.4% increase in power

36
✅ Conclusion:

 A 1% frequency drop causes a 0.4% increase in real power consumption for this load.

4. Implications of Frequency Dependency in Power Systems

🔹 When frequency drops (f ↓), power demand increases (P ↑).

 This worsens the power imbalance and can lead to grid instability.

🔹 When frequency rises (f ↑), power demand decreases (P ↓).

 This helps reduce stress on generators but can cause underloading issues.

🔹 Grid operators use Load Frequency Control (LFC) to manage frequency and prevent cascading failures.

5. Key Takeaways

✅ Resistive loads (R-only) are NOT affected by frequency changes.


✅ Loads with reactance (L or C) change their impedance when frequency changes.
✅ Lower frequency increases power demand, making grid stability harder to maintain.
✅ Load Frequency Control (LFC) is needed to regulate frequency and avoid blackouts.

Voltage Dependency of Motor/Motive Loads (Explained Simply)

Motor loads, also called motive loads, are electrical loads that involve rotating machines, such as:

 Induction motors (used in fans, refrigerators, pumps, conveyors, etc.)

 Synchronous motors (used in industrial applications, large compressors, etc.)

Unlike impedance loads, which have a power consumption proportional to voltage squared (V²), motor
loads respond differently when voltage changes.

1. How Voltage Affects Motor Loads

When the voltage changes, motors experience the following effects:

A. Current Response

 When voltage decreases, an induction motor draws more current to maintain its power output.

 However, motors are not 100% efficient, so extra current increases heating and losses.

37
 If voltage drops too much, the motor cannot compensate, leading to slower speed, reduced
torque, and possible stalling.

B. Power Consumption Response

Motor power consumption does not follow the same V² relationship as impedance loads. Instead:

Pmotor∝VxP_{\text{motor}} \propto V^xPmotor∝Vx

 For small voltage changes, xxx is close to 1 (power roughly proportional to voltage).

 For larger voltage changes, the power reduction is less significant compared to resistive loads.

2. Example Calculation: 1% Voltage Drop on Motor Load

Let's assume a three-phase induction motor with the following parameters:

 Initial voltage = 480V

 Initial power consumption = 10 kW

 Slip = 0.04 (4%)

Using motor load equations, a 1% voltage drop reduces power demand by about 0.2%:

ΔPP=x×ΔVV\frac{\Delta P}{P} = x \times \frac{\Delta V}{V}PΔP=x×VΔV

For x≈0.2x \approx 0.2x≈0.2 (based on real-world data):

ΔPP=0.2×(−0.01)=−0.002=−0.2%\frac{\Delta P}{P} = 0.2 \times (-0.01) = -0.002 = -0.2\%PΔP


=0.2×(−0.01)=−0.002=−0.2%

✅ Conclusion: A 1% voltage drop only reduces power demand by 0.2%.

3. How Voltage Reduction Affects Different Motors

Voltage Change Induction Motor Effect

Small Voltage Drop (1-5%) Increased current, small power reduction (~0.2% per 1% drop)

Moderate Voltage Drop (5-10%) Motor efficiency drops, overheating risk, slower speed

Large Voltage Drop (10-15%) Motor may stall, high heating, possible damage

🔹 Compared to impedance loads, motors resist voltage reductions because they draw more current to
compensate.

38
4. Brownout Effect on Motors

A brownout is when voltage is intentionally reduced to reduce power demand.

🔹 Why impedance loads reduce demand more than motor loads?

 For a 1% voltage drop:

o Impedance loads reduce power by ~2%

o Motor loads reduce power by ~0.2%

🔹 Why this matters?

 Brownouts are not very effective for reducing motor loads.

 Instead, motors draw more current, increasing the risk of overheating and damage.

✅ Solution: Instead of brownouts, utilities use Demand Response Programs to shut down non-essential
motor loads during peak demand.

5. Key Takeaways

✅ Motors do not follow the V² rule like impedance loads.


✅ Voltage drops make motors draw more current, which increases losses.
✅ Motors reduce power less efficiently during brownouts compared to resistive loads.
✅ Severe voltage drops can cause stalling, overheating, and damage.

39

You might also like