Process Control Class Otes
Process Control Class Otes
Introduction
Process control is defined as the functions and operations necessary to change the
required materials either physically or naturally.
Every process must have one or more controlled variables and one or more
manipulated variable.
The following shows a block diagram of a process control system.
PROCESS CHARACTERISTICS
i) Process Load
This refers to the total amount of control agent needed to keep the process in a balanced
condition, e.g. in the milk pasteurization planta certain amount of steam is needed to
keep the milk at certain temperature.
This is the time taken for the controlled variable to reach a new value after a process
load.
In the last example, the control of the lube oil temperature may initially seem easy.
Apparently, the operator need only measure the lube oil temperature, compare the
actual temperature to the desired (setpoint), compute the amount of error (if any), and
Process time lags are caused by three properties of the process. They are: capacitance,
resistance, and transportation time.
In the figure below, for example, the walls of the tubes in the lube oil cooler, the
cooling water, and the lube oil can store heat energy. This energy-storing
property gives the ability to retard change. If the cooling water flow rate is
increased, it will take a period of time for more energy to be removed from the
lube oil to reduce its temperature.
b) Resistance is that part of the process that opposes the transfer of energy
between capacities. In Figure 9, the walls of the lube oil cooler oppose the
transfer of heat from the lube oil inside the tubes to the cooling water outside the
tubes.
Stability is the ability of a control loop to return a controlled variable to a steady, non-
cyclic value, following a disturbance or a process load.
Typically, an unstable system will cause the controlled variable to be above or below the
desired variable.
Oscillations describes this cyclic characteristic. There are three types of oscillations
that can occur in a control loop. They are decreasing amplitude, constant amplitude, and
increasing amplitude.
INDUSTRIAL CONTROLLERS
The basic characteristic of a controller is the way it acts to restore the controlled
variable to its desired value.
The different actions of control are called control modes. The common control modes
include:
The controller switches from its "OFF" state to its "ON" state when the measured
variable increases above the setpoint. Conversely, it switches from its "ON" state to its
"OFF" state when the measured variable decreases below the setpoint. This device
provides an output determined by whether the error signal is above or below the
setpoint. The magnitude of the error signal is above or below the setpoint. The
magnitude of the error signal past that point is of no concern to the controller.
The two-position control mode supplies energy in pulses to the process, thus, causing a
cycling of the controlled variable.
The amplitude of the cycling depends on three factors;
i) The capacitance of the process
ii) Dead time of the process
iii) Size of the load changes the process is capable of handling
Two-position control is simple and cheap, and is preferred whenever the cycling can be
reduced to an acceptable level.
A simple example below involves switching ON and OFF a heat supply with each
switching in both direction occurring at the same preset temperature.
In most controllers, it is found that the correcting element is not moved until the
temperature has actually passed the desired value.
The controller may be designed with an adjustable overlap so that the two
predetermined control actions are automated when the controlled condition passes
from one to the other of the two set-points chosen values as show below;
If the width of the overlap is increased, the frequency of oscillation is decreased but the
amplitude is increased. If this greater deviation from a desired value can be tolerated,
the less frequency operation of the valve, contactor or other correcting unit, and in turn
longer life for the equipment.
As the water level decreases initially, a point is reached where the measured variable
drops below the setpoint. This creates a positive error signal. The controller opens the
final control element fully. Water is subsequently injected into the tank, and the water
level rises. As soon as the water level rises above the setpoint, a negative error signal is
developed. The negative error signal causes the controller to shut the final control
element. This opening and closing of the final control element results in a cycling
characteristic of the measured variable.
Floating Control
This is a special application of the two-position control in which the final control
element is stationary as long as the error remains within the neutral zone.
When the controlled variable is outside the neutral, the final control element changes at
a constant rate in a direction determined by the sign of the error.
The final control element continues to change until the error returns to the neutral zone
or until the final control element reaches one of its extreme positions.
The main advantage of floating control is its ability to handle larger load changes by
gradually adjusting the final control element.
2. PROPORTIONAL CONTROL
Proportional control is used when the gain cannot be made large enough to counteract
the effect of the largest load change in the proportional offset.
Output, V = ke
Where, k = gain,
𝑅𝑓
K = 𝑅𝑖
e = error signal
𝑉
Transfer function, 𝑒 = k
Proportional Band
Suppose the final corrective device is a variable position value. Proportional band can
illustrated by the graph below;
Example
If the controller set-point can be adjusted between 600F and 3000F, and has an
adjustment of 2400F.
190−165
Proportional band =
300−60
25
= 240
= 0.104 or 10.4%
Therefore, proportional band is the range of the full controller range by which the
measured value must change in order to cause the correcting device to change by 100%.
Outside this band, the valve ceases to respond because it has reached its limit.
Where, k = gain
V0 = Output signal at t = 0, [Initial value of output]
An electronic integral controller can be constructed using OP –amp as shown below;
𝜏𝑖 = RiCi
1
Transfer function = 𝜏𝑖𝑠
Disadvantages of the integral control mode are that it responds relatively slowly to an
error signal and that it can initially allow a large deviation at the instant the error is
produced. This can lead to system instability and cyclic operation. For this reason, the
DERIVATIVE CONTROL
It changes the output of the controller at a rate proportional to the change of the error
signal.
This change may be caused by a variation in the measured variable, the set point on
both. The derivative mode contributes to the output of the controller only while the
error is changing.
For this reason, the derivative control is never used alone.
At every instant the output of the derivative control mode is proportional to the slope or
rate of change of the error signal. The step response indicates why an ideal derivative
control mode is never used alone.
The error curve has an infinite slope for a step change and the derivative mode must
respond with an infinite change in the controller output.
In actual practice, the response of the derivative action to rapidly changing signal is
limited. This greatly reduces the sensitivity of the controller to the unwanted noise
spikes which frequently occurs in actual practice.
The figure below shows an ideal and a practical differentiation.
𝑉 τds
Transfer function = 𝐸 = 𝑆𝑅𝐶+1
The term (1 + SR1Cd) limits the response product by rapidly changing signal.