T80 Series User Manual
T80 Series User Manual
⬛ Features
● Can input 22 type signals
RTD:Pt100, Cu50
Thermocouples: S/R/B/K/N/E/J/T with automatic cold junction temperature compensation。
Standard signals: 0-10mA/4-20mA/0-5V/1-5V
Linear non-standard signal: any signals within 0-100mV/0-400Ω, need set the range corresponding to input signal
● SCM intelligence
Can adjust the zero point and magnification manually, and there is no drift in linearity for long-term use
All parameters can be set freely as required
● Alarm control parameters can be set
Can use max four relay outputs
Can set each relay’s alarm value and hysteresis
Can set each relay’s alarm type (Upper alarm or lower alarm)
● Has various output
Transmission output type: 0-10mA/4-20mA/0-5V/1-5V/0-20mA
Can adjust light beam individually
MODBUS-RTU standard communication protocol。
⬛ Technical parameter
Measuring range: -1999-9999
Accuracy: ±0.5% of full scale
Supply voltage: AC0220(±10%); DC24V
Operating temperature:0-50℃
Operating humidity: 85% RH max, non-condensing
Power consumption: ≤5W
AHH
1 AH
AL
ALL
AH AHH PV SET 2
1 AL ALL 6 3
4
5
SET
PV
6
5 4 3 2
1) Indicator light AH light: The upper limit relay output; AHH light: The upper upper limit relay output
AL light: The lower limit relay output; ALL light: the lower lower limit relay output
2) Function key
3) Add key
4) Minus key
5) Shift key
6) Measurement and function menu display window
1
LEVEL CONTROLLER DISPLAY T80 SERIES
⬛ Model number legend
T 80 -□ □ □
controller Design Alarms: Communication Output type:
1: No alarm N: None N: None
2: 2 alarms R: RS485 C420: 4-20mA
3: 3 alarms C010: 0-10mA
V15: 1-5V
v05: 0-5V
Code Input type and Code Code Input type and Code
measured range measured range
00 S(0-1600℃) 08 Pt100(-200-850℃) 16 mV no standard
signal (0-100mV)
01 R(0-1600℃) 09 Cu50(-50-150℃) 17 Resistance no
standard signal
(0-400Ω)
02 B(200-1800℃) 10 0-5V(-1999-9999) 18 Frequency no
standard signal
(0-3000Hz)
03 K(0-1300℃) 11 1-5V(-1999-9999) 19 0-5V2(-1999-9999)
04 N(0-1300℃) 12 0-10V(-1999-9999) 20 1-5V2(-1999-9999)
05 E(0-800℃) 13 0-10mA(-1999-9999) 21 0-10mA2(-1999-9999)
06 J(0-650℃) 14 0-20mA(-1999-9999) 22 4-20mA2(-1999-9999)
07 T(-200-400℃) 15 4-20mA(-1999-9999) 23 Multiple input
2
Parameter Name Set range Description
Sn Input type 0-22 See input type table
dOt Decimal point dot=0 Without decimal point
dot=1 Ten decimals (show XXX.X)
dot=2 Hundred decimals (show
dot=3 XX.XX)
Thousand decimals (show
X.XXX)
PUL Lower limit of measured -999-9900 Set the input signal’s lower
range limit measured value
PUH Upper limit of measured -900-9999 Set the input signal’s upper
range limit measured value
FILt Filter coefficient 0.100-0.900 Can’t exceet0.900,otherwise
will be an error
K1 Input range’s magnification 0-1.999 magnification Set input range’s
magnification
OU-R First transmission output OU-R=0 No transmission Linear output corresponding
output to the measured value
OU-R=1 0-10mA
OU-R=2 4-20mA
OU-R=3 0-20mA
PH Upper limit alarm type Thousands place : 0 alarm Default is 0001
without flashing 1 alarm
with flashing
Hundreds place: 0 Monitor
PV
Tens place: 0 The relay is NC
stats 1 The relay is NO
stats
Ones place: 0 Forbid alarm 1
upper alarm 2 lower alarm
PL Lower limit alarm type Definition is the same as Default is 0002
PH
PHH Upper upper limit alarm type Definition is the same as Default is 0001
PH
PLL Lower lower limit alarm type Definition is the same as Default is 0002
PH
InPH Non-standard signal input 10-100mV; 10-400Ω; 2-300Hz Default is 100.0
Maximum
InPL Non-standard signal input 0-90mV; 0-390Ω; 0-2998Hz Default is 0.0
minimum
bRUd Communication baud rate 0=1200bps Communication speed
1=2400bps
2=4800bps
3=9600bps
Id Communication address 0-31 Cannot exceed 31
K Bar graph display input range 0.100-9.999 Only bar graph instrument
ratio has this parameter
3
⬛ Application description
The range selection of instrument and sensor: All sensor’s range must be same as instrument’s range, otherwise, the display
will display wrong value. For example: Liquid level transmitter range is 0-5m(According to the sensor label), output 4-20mA,
can set the instrument as the following: 1). enter the second-level parameters menu. 2). Set the parameters as follow:
Parameter Name Set value Description
Sn Input type 15 Must be same as the output
signal
Dot Decimal point 2 According to the accuracy
requirement
PuL Lower limit of measured 0.00 The lowest range of the
range sensor
PuH Upper limit of measured 5.00 The highest range of the
range sensor
Example 2: Require start pump when lower than 1m, stop pump when higher than 4m. Push down the SET key for 3 second,
enter the first-level parameters menu,the parameters are as follow:
Parameter Name Set value Description
AL Lower alarm value 1.00 The relay output is lower
alarm
dL Lower alarm hysteresis 3.00
Example 3: Require start pump when higher than 4m, stop pump when lower than 1m. Push down the SET key for 3 second,
enter the first-level parameters menu,the parameters are as follow: