≈. Jacket OD (mm)
≈. Jacket OD (mm)
≈. Jacket OD (mm)
≈. Jacket OD (mm)
≈. Jacket OD (mm)
≈. Jacket OD (mm)
≈. Jacket OD (mm)
2.0 # 14 2 9.000 4 6.36 25 6 7.64 25
3.5 # 12 2 5.060 4 6.96 30 6 8.24 30
5.5 # 10 3 3.240 4 7.56 40 6 8.84 40
8.0 # 8 4 2.250 6 9.68 55 6 9.96 55 18 14.10 80
14 # 6 5 1.260 6 10.88 70 7 11.16 70 18 15.30 115 28 18.72 110 110
22 # 4 6 0.801 6 12.08 90 7 13.12 90 18 16.50 150 28 19.92 155 155
30 # 2 7 0.606 6 12.98 115 7 14.02 115 18 17.40 180 28 20.82 185 44 26.06 185
38 # 1 8 0.461 7 16.12 130 7 16.14 130 18 18.50 210 28 21.92 215 44 27.16 215
50 # 1/0 9 0.368 7 17.12 150 7 17.14 150 18 19.50 250 28 22.92 250 44 28.16 250 64 33.20 250 84 39.16 250
60 # 2/0 10 0.295 7 18.12 170 7 18.14 170 18 20.50 280 28 23.92 280 44 29.16 280 64 34.20 280 84 40.16 280
80 # 3/0 12 0.223 7 19.62 205 7 19.64 205 18 22.00 330 28 25.42 335 44 30.66 335 64 35.70 335 84 41.66 335
100 # 4/0 13 0.175 7 21.12 225 7 21.14 225 18 23.50 385 28 26.92 385 44 32.16 385 64 37.20 380 84 43.16 380
125 250 MCM 15 0.138 8 24.34 265 10 23.60 265 18 25.20 440 28 28.62 440 44 33.86 440 64 38.90 435 84 46.38 435
150 300 MCM 16 0.115 8 25.74 295 10 25.00 295 18 26.60 490 28 30.02 490 44 35.26 490 64 40.30 485 84 47.78 485
200 400 MCM 18 0.090 8 27.84 355 10 27.10 350 18 28.70 600 28 32.12 595 44 37.36 595 64 42.40 590 84 49.88 590
250 500 MCM 21 0.070 8 30.34 400 10 29.60 400 18 31.20 690 28 34.62 680 44 39.86 680 64 44.90 675 84 52.38 675
500 1000 MCM 29 0.035 8 39.96 580 12 38.46 580 18 39.30 1,065 28 42.72 1,050 44 49.48 1,050 64 54.52 1,030 84 60.48 1,030
*Not more than Three Conductors in Raceway or Cable or Ground Direct Burial, based on Ambient Temp. of 30º C (for 600V/1KV to 2KV)
*Ampacities of Insulated Single Copper Conductor isolated in air based on Conductor Temperatures of 90ºC and Ambient Air Temperature of 40ºC (for 5KV to 35KV)
†This technical data sheet serves as a reference only. Consult Electrical Engineers or professional installers for proper use or application.
††Multi-conductor Power Cables are also available as per customer specification.
PB-HYPE-20170331