tutorial2
tutorial2
Figure 1:
2. The single line diagram of a power system is shown in Figure 2. The specifications are
given below.
G1: 80 MVA, 11 kV, X= 18 % ; T1: 20 MVA, 11/220 kV, X=12 % ; T2: 20 MVA,
220/11 kV, X=10 % ; T3: 20 MVA, 11/110 kV, X=8 % ; T4: 20 MVA, 110/11 kV, X=6
% ; M1= 40 MVA, 10.8 kV, X=15 % ;
Series reactances of line 1 and line 2 are 50 and 60 Ω respectively. Take generator ratings
T1 line1 T2 T3
as base quantities. [Xp.u = 0.48p.u, Xp.u = 0.0826p.u., Xp.u = 0.4p.u.,Xp.u = 0.32p.u.,
line2 T4 M1 load
Xp.u = 0.3966p.u., Xp.u = 0.24p.u., Xp.u = 0.289p.u., Zp.u = 3.2 + 2.4i]
Figure 2:
3. A 100 MVA, 13.8 kV, 3 phase generator has reactance of 20 %. The generator is con-
nected to a 3 phase transformer (T1) rated 100 MVA, 12.5 kV/110 kV with 10 %
reactance. The HV side of the transformer is connected to a transmission line of reac-
tance 100 Ω. The far end of the line is connected to a step-down transformer T2 made
of 3 single phase transformers, connected in Y - ∆, each rated 30 MVA, 66 kV/10 kV
with 10 % reactance. The generators supply two motors connected on the LV side of
T2. The motors are rated at 25 MVA and 50 MVA both at 10 kV with 15 % reactance.
Draw the reactance diagram showing all the values in p.u. Take generator rating as
T1 line T2 M1
base. [Xp.u = 0.0820p.u., Xp.u = 0.6780p.u., Xp.u = 0.0985p.u., Xp.u = 0.5319p.u.,
M2
Xp.u = 0.2659p.u. ]
4. A 3 bus system is given in Figure 3. The ratings of various components are listed below.
G1: 50 MVA, 13.8 kV, X=0.15 p.u.; G2: 40 MVA, 13.2 kV, X=0.2 p.u.; G3: 30 MVA,
11 kV, X=0.25 p.u.; T1: 45 MVA, 11 kV / 110 kV, X=0.1 p.u.; T2: 25 MVA, 12.5 kV
/ 115 kV, X=0.15 p.u.; T3: 40 MVA, 12.5 kV / 115 kV, X=0.1 p.u.
The line impedances are as shown in figure. Determine the reactance diagram based on
T1
50 MVA and 13.8 kV as base quantities in Generator 1. [Xp.u = 0.0705p.u.,
line12 line23 T2 G2 T3
Xp.u = 0.1312p.u., Xp.u = 0.0656p.u., Xp.u = 0.2083p.u., Xp.u = 0.1936p.u., Xp.u =
0.0868p.u]
Figure 3:
6. 3 single phase transformers, each of rating 11/33 kV, 100 MVA are connected in Y - ∆.
If the reactance of each single phase transformer is 6 Ω as referred to LV side, calculate
the p.u. reactance of the resulting 3 phase transformer. [Xp.u. = 4.9589p.u.]