Lower Anchor Details: Floor Plate Button Location Floor Plate With Comb

The document outlines specifications for an escalator system, including details on motor types, safety devices, control equipment, and operational requirements. It emphasizes the need for diagnostic capabilities, maintenance access, and environmental resilience. Additionally, it specifies fire protection measures and operational criteria for various load conditions.

Uploaded by

BATACAN JAMAICA
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
15 views1 page

Lower Anchor Details: Floor Plate Button Location Floor Plate With Comb

The document outlines specifications for an escalator system, including details on motor types, safety devices, control equipment, and operational requirements. It emphasizes the need for diagnostic capabilities, maintenance access, and environmental resilience. Additionally, it specifies fire protection measures and operational criteria for various load conditions.

Uploaded by

BATACAN JAMAICA
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

GENERAL NOTES:

PRIMARY BRAKE
PANEL SAFETY DEVICE
VITROFLOOR TILE
175 MOTORS
6 7/8" a. THE DRIVING MOTORS SHALL BE AC INDUCTION MOTORS WITH STARTERS.
10 VOLTAGE 480 VAC, THREE PHASE, FREQUENCY 60 HZ.
3/8"
b. THE MOTORS SHALL BE TOTALLY ENCLOSED WITH EXTERNAL COOLING FINS.
PANEL SAFETY DEVICE GAP TO CLOSE
c. THE MOTOR PROTECTION CLASS SHALL BE EQUIVALENT TO IP55 INSULATION
ELECTROSOLDED MESH
OVERSPEED LIMITER GROUP F.
d. DRIVING MOTORS AND MOTOR SWITCHGEAR SHALL PROVIDE A SMOOTH

5 5/16"
135
DEFLECTOR COMB PLATE SAFETY DEVICE INTERLOCKED CORRUGATED STEEL FLOOR DECK START.

DRIVE CHAIN BREAKAGE DEVICE STRUCTURE LIMIT FOR CASTING CONTROLLER


HANDRAIL BELT SPEED CHECKER e. THE ESCALATOR CONTROL EQUIPMENT SHALL CONTAIN DIAGNOSTIC
ATTACHMENT BRAKE
HANDRAIL BELT BREAKAGE SAFETY DEVICE CAPABILITIES AS REQUIRED FOR THE EASE OF COMPLETE MAINTENANCE. THE
STEP SAFETY DEVICES REVISIONS
UPPER END ENTRANCE FOR THE SUPPLY OF ELECTRICITY AND LIGHT DIAGNOSTIC SYSTEM SHALL BE AN INTEGRAL PART OF THE CONTROLLER AND
40 PROVIDE USER-FRIENDLY INTERACTION BETWEEN THE SERVICE PERSON AND THE
CONTROLS. ALL SUCH SYSTEMS SHALL BE FREE FROM DECAYING CIRCUITS THAT
HANDRAIL STRAP MUST BE PERIODICALLY REPROGRAMMED BY THE MANUFACTURER.
f. SWITCHGEAR SHALL BE MOUNTED IN NEMA 4X CABINETS WITH STRIP
SKIRT A LOWER ANCHOR DETAILS HEATERS AND LABELED TERMINAL STRIPS.
STEP SCALE NTS g. THE MAIN CONTROLLER SHALL USE A PROGRAMMABLE LOGIC CONTROLLER
(PLC) TO CONTROL AND MONITOR THE STATUS OF THE ESCALATOR. THE PLC SHALL
STEPPER WHEEL
175 BE DESIGNED TO COMMUNICATE OVER ETHERNET OR APPROVED EQUAL.
6 7/8" h. THE PLC RACKS SHALL PROVIDE SPACE FOR TWO FUTURE SINGLE-SLOT
STEP SINKING SAFETY DEVICES 10
MODULES.
COMB PLATE VITROFLOOR
3/8"
i. THE PLC IN THE REMOTE CONTROL PANEL SHALL ALSO HAVE HARDWARE AND
STICKY TILE FIRMWARE PROVISIONS TO COMMUNICATE WITH INTERACTIVE OPERATOR
SAFETY SWITCHES BELOW GAP TO CLOSE INTERFACE (MONITOR).
j. THE PLC SHALL STORE THE LAST 99 SAFETY DEVICE FAULTS, ACCESSIBLE VIA

5 5/16"
135
TRUSS
LAPTOP CONNECTION, PANEL VIEW OR REMOTE COMMUNICATIONS.
k. A COPY OF ALL WORKING PROGRAMS ON APPROVED COMPUTER MEDIUM, AS
WELL AS A PRINTED PROGRAM LISTING, SHALL BE PROVIDED.
l. THE PLC SHALL HAVE ONE DEDICATED SERIAL PORT, WHICH SUPPORTS
RS-232-C SIGNALS. IT SHALL BE ACCESSIBLE IN LADDER LOGIC AND PROVIDE
SUPPORT FOR POINT-TO-POINT AND SLAVE SCADA COMMUNICATION PROTOCOL
SYSTEMS. ALTERNATIVELY, IT MUST BE USABLE FOR PROGRAMMING PURPOSES OR
FOR ACCESS TO REMOTE PROGRAMMERS VIA MODEMS.
PIT HANDRAIL ENTRY 40
1 9/16"

B TOP ANCHOR DETAIL MAIN CONTROL SWITCHGEAR:


m. THE MAIN CONTROL SWITCHGEAR OF AN ESCALATOR SHALL CONTAIN AT
SCALE NTS LEAST THE FOLLOWING DEVICES:
n. LOCKABLE MAIN SWITCH THERMAL AND MAGNETIC MOTOR PROTECTION
STARTER FOR UP AND DOWN TRAVEL, HOUR COUNTER, AUXILIARY CONTACTORS,
1 ESCALATOR ISOMETRIC DETAIL PHASE FAILURE DEVICE, PHASE SEQUENCE MONITOR AND GROUND FAULT DRAWING
MONITOR.
M-4 SCALE NTS
o. THE CONTROLLER CABINET SHALL CONTAIN A PERMANENTLY MOUNTED
ESCALATOR ISOMETRIC DETAIL
SECTION DETAIL
FLOOR PLATE WITH COMB BUTTON LOCATION FLOOR PLATE FULL-COLOR VIEW PANEL CAPABLE OF PROVIDING FAULT AND OPERATING DATA.
PLAN
p. THE INDICATION SHALL BE LOCKED AUTOMATICALLY. RESET SHALL BE DONE
BY A SEPARATE SWITCH INSTALLED IN THE CONTROLLER. THE EMERGENCY STOP
LOWER ANCHOR DETAIL
SHALL NOT BE LOCKED. TOP ANCHOR DETAIL
PROJECT TITLE
q. ALL TERMINALS SHALL HAVE IDENTIFICATION MARKINGS, AND ALL CABLES
SHALL BE PROVIDED WITH CABLE MARKERS.
r. THE CONTROLLER SHALL BE EQUIPPED A FULL-TIME REGENERATIVE
VARIABLE FREQUENCY DRIVE (VFD) CAPABLE OF FULL-SPEED CONTROL FOR Residential development
MAINTENANCE AND FUTURE “SLEEP MODE” OPERATION.
s. ELECTRIC POWER RECEPTACLES SHALL BE FURNISHED AND INSTALLED IN
THE UPPER AND LOWER PITS. EACH RECEPTACLE SHALL BE OF THE GFCI DUPLEX CLIENT
TYPE, WATERPROOF, GROUNDED, AND RATED FOR ONE 120 VOLTS AT 20 AMPERES.
THE RECEPTACLES IN THE PITS SHALL BE SURFACE-MOUNTED ON THE WALLS, NOT Ar. Aristeo Garcia
LESS THAN 30 IN. FROM THE FLOOR. AR154P_A54_2T2425
MAINTENANCE ACCESS t. RELAYS SHALL BE PROVIDED WITH VISUAL INDICATION THAT THEY ARE
ENERGIZED.
u. CONTROLLERS IN ESCALATOR PITS SHALL HAVE A FLEXIBLE LIQUID TIGHT PROJECT ADDRESS
2 ESCALATOR SECTION DETAIL CONNECTION OF SUITABLE LENGTH TO PERMIT REMOVAL FOR MAINTENANCE

M-4 SCALE NTS PURPOSES.


v. THE CONTROLLER SHALL BE CAPABLE OF OPERATING THE ESCALATOR IN
Rainbow Avenue, Cypress
Caloocan, Metro Manila

1000
VARIABLE RATED SPEED OPERATION AS PER ASME A17.1-2010 REQUIREMENT
6.1.4.1.1, REGARDLESS OF THE ASME A17.1 CODE IN EFFECT.
CAD REF. DATE
DESIGN CRITERIA:
Mar 3 2025

1155
1. OPERATIONAL REQUIREMENTS
MACHINE ROOM - HOURS OF OPERATION SHALL BE CONSIDERED AS 24 - HOURS PER DAY,
DRAWING No. SCALE
SEVEN DAYS PER WEEK. M-5 NTS
- DIRECTION OF TRAVEL SHALL BE CONSIDERED AS EITHER DIRECTION, AND
UNIT SHALL BE UP-AND-DOWN REVERSIBLE. DRAWN

M-4
- RATED SPEED SHALL NOT EXCEED 100 FEET PER MINUTE (FPM). THE LA
NO-LOAD-TO-FULL-LOAD SPEED SHALL NOT EXCEED 4 PERCENT OF THE
2300

RATED SPEED. CHECKED


- ESCALATOR COMPONENTS SHALL BE DESIGNED BASED ON THE DESIGN AG
LOADS, FOLLOWING APPLIED DUTY CYCLE DURING OPERATION:
- THREE HOURS WITH 100 PERCENT DESIGN LOAD
84

- SIX HOURS WITH 50 PERCENT DESIGN LOAD


2

- FIFTEEN HOURS WITH 25 PERCENT DESIGN LOAD


2. ENVIRONMENTAL REQUIREMENTS
- ESCALATORS SHALL BE CAPABLE OF OPERATING WITH FULLY SPECIFIED
98

PERFORMANCE CAPABILITY WHILE EXPOSED TO THE FOLLOWING CLIMATIC Fig Design Architectural Firm
2

AND ENVIRONMENTAL CONDITIONS:


- INTERIOR INSTALLATIONS: ESCALATORS SHALL BE DESIGNED TO OPERATE IN
A TEMPERATURE RANGE OF 5 TO 120 ºF, DRY BULB, AND ALL CONDITIONS OF Arriola, Lourdes Bernadeth
60

RELATIVE HUMIDITY WHILE EXPOSED TO AIRBORNE DUST AND DEBRIS.


(M
1000

- EXTERIOR INSTALLATIONS: ESCALATORS SHALL BE DESIGNED TO OPERATE


IN)

WHILE EXPOSED TO THE NATURAL ELEMENTS OF WEATHER, INCLUDING t: 09XX XXX XXXX
SUNLIGHT, RAIN, SLUSH, SNOW AND ICE; ALL CONDITIONS OF RELATIVE e: [email protected]
HUMIDITY WHILE EXPOSED TO SALT, DEICING CHEMICALS, AIRBORNE DUST, w: website.com
AND DEBRIS, AND CORROSIVE ELEMENTS; AND IN A DRY-BULB TEMPERATURE
1155

3 ESCALATOR PLAN
3.
RANGE OF -10 TO 105 ºF.
FIRE PROTECTION
M-4 SCALE NTS - NO WOOD OR WOOD PRODUCTS SHALL BE USED IN ESCALATORS.
60 (MIN)

- LSHF (LOW-SMOKE, HALOGEN FREE) WIRING SHALL BE USED WHERE


COMMERCIALLY AVAILABLE THROUGHOUT THE ESCALATOR INSTALLATION.
- PVC MAY NOT BE USED IN THE ESCALATOR INSTALLATION.