Introduction To Reinforced Concrete
Introduction To Reinforced Concrete
(a) (b)
Fig: Book cover page, (a) NSCP 2015 (ASEP, 2015) & (b) ACI 318-14M (ACI, 2015)
CONCRETE DESIGN PROPERTIES (NSCP 2015 SECTION 419.2)
SPECIFIED COMPRESSIVE STRENGTH (NSCP 2015 SECTION 419.2.1)
• 419.2.1.1 The value of 𝒇′𝒄 shall be specified in construction documents and shall be in accordance with (a) through
(c):
a. Limits in Table 419.2.1.1;
b. Durability requirements in Table 419.3.2.1;
c. Structural strength requirements
Table 419.2.1.1
Limits for 𝒇′𝒄
Application Concrete Minimum 𝒇′𝒄 , 𝑴𝑷𝒂 Maximum 𝒇′𝒄 , 𝑴𝑷𝒂
Normal weight and Light
General 17 None
weight
Special moment frames Normal weight 21 None
and special structural
walls Light weight 21 35[1]
[1] The limit is permitted to be exceeded where demonstrated by experimental evidence that members made with lightweight concrete provide strength
and toughness equal to or exceeding those of comparable members made with normal weight concrete of the same strength.
• 419.2.2.1 Modulus of Elasticity, 𝑬𝒄 , for concrete shall be permitted to be calculated as (a) or (b):
a. For values of 𝒘𝒄 , between 1440 and 2560 kg/m3
• 425.2.1 For parallel non-prestressed reinforcement in a horizontal layer, clear spacing shall be at least the greater
of 25 mm, db, and (4/3) dagg.
• 425.2.2 For parallel non-prestressed reinforcement placed in two or more horizontal layers shall be placed directly
above reinforcement in the bottom layer with a clear spacing between layers of at least 25 mm.
• 425.2.3 For longitudinal reinforcement in columns, pedestals, struts, and boundary elements in walls, clear spacing
between bars shall be at least greatest of 40 mm, 1.5db, and (4/3) dagg.
• 425.6.1.1 Groups of parallel reinforcing bars bundled in contact to act as a unit shall be limited to four in any one
bundle.
• 425.6.1.2 Bundled bars shall be enclosed within transverse reinforcement. Bundled bars in compression members
shall be enclosed by transverse reinforcement at least 12 mm ø in size.
• 425.6.1.4 Individual bars within a bundle terminated within a span of flexural members shall terminate at different
points with at least 40 db stagger.
• 425.6.1.5 Development length for individual bars within a bundle, in tension or compression, shall be that of the
individual bar, increased 20 percent for a three-bar bundle, and 33 percent for a four-bar bundle.
• 425.6.1.6 A unit bundled bars shall be treated as a single bar with an area equivalent to that of the bundle and a
centroid coinciding with that of the bundle. The diameter of equivalent bars shall be used for db in (a) through (e):
• 420.6.1.3.1 Non-prestressed cast-in-place concrete members shall have specified concrete cover for reinforcement
at least that given in Table 420.6.1.3.1
Table 420.6.1.3.1
Specified Concrete Cover for the Cast-in-Place
Non-Prestressed Concrete Members
Concrete Exposure Member Reinforcement Specified cover, mm
Cast against and
permanently in contact All All 75
with ground
20 mm ø through 58 mm ø bars 50
Exposed to weather or in
All 16 mm ø bar, MW200 or
contact with ground 40
MD200 wire, and smaller
40 mm ø and 58 mm ø bars 40
Slabs, joists, and walls
36 mm ø bar and smaller 20
Not exposed to weather or
Beams, columns,
in contact with ground Primary reinforcement, stirrups,
pedestals, and tension 40
ties, spirals, and hoops
wires
• 420.6.1.3.2 Cast-in-place prestressed concrete members shall have specified concrete cover for reinforcement, ducts
and end fittings at least that given in Table 420.6.1.3.2.
Table 420.6.1.3.2
Specified Concrete Cover for the Cast-in-Place
Prestressed Concrete Members
Concrete Exposure Member Reinforcement Specified cover, mm
Cast against and
permanently in contact All All 75
with ground
Exposed to weather or in Slabs, joists, and walls All 25
contact with ground All others All 40
Slabs, joists, and walls All 20
Not exposed to weather or Primary reinforcement 40
Beams, columns, pedestals,
in contact with ground Stirrups, ties, spirals, and
and tension wires 25
hoops
• 420.6.1.3.4 For bundled bars, specified concrete cover shall be at least the smaller of (a) and (b):
a. The equivalent diameter of the bundle
b. 50 mm
and for concrete cast against and permanently in contact with ground, the specified cover shall be 75 mm.
• 421.2.1 Strength reduction factor ø shall be in accordance with Table 421.2.1 except as modified by Sections
421.2.2, 421.2.3, and 421.2.4.
Table 421.2.1
Strength Reduction Factor ø
Action or Structural Element ø Exceptions
Near ends of pretensioned
members where strands are
Moment, axial force, or combined 0.65 to 0.90 in accordance with
(a) not fully developed, ø shall
moment and axial force Section 421.2.2
be in accordance with
Section 421.2.3
Additional requirements
are given in Section
(b) Shear 0.75 421.2.4 for structures
designed to resist
earthquake effects.
(c) Torsion 0.75 -
(d) Bearing 0.65 -
(e) Post-tensioned and anchorage zones 0.85 -
(f) Brackets and Corbels 0.75 -
Struts, ties, nodal zones, and bearing areas
(g) designed in accordance with strut-and-tie 0.75 -
method in Section 423
Components of connections of precast
(h) members controlled by yielding of steel 0.90 -
elements in tension
(i) Plain concrete elements 0.60 -
0.45 to 0.75 in accordance with
(j) Anchors in concrete elements -
Section 417
• 421.2.2 Strength reduction factor for moment, axial force, or combined moment and axial force shall be in
accordance with Table 421.2.2
Table 421.2.2
Strength Reduction Factors, ø, for Moment, Axial Force, or Combined Moment and Axial Force
ø
Net Tensile Strain Type of Transverse Reinforcement
Classification
𝜺𝒕 Spirals conforming to
Other
Section 425.7.3
Compression
𝜺𝒕 ≤ 𝜺𝒕𝒚 0.75 (a) 0.65 (b)
controlled
(𝜺𝒕 − 𝜺𝒕𝒚 ) (𝜺𝒕 − 𝜺𝒕𝒚 )
𝜺𝒕𝒚 < 𝜺𝒕 < 𝟎. 𝟎𝟎𝟓 Transition [1] 0.75 + 0.15 € 0.65 + 0.25 (d)
(0.005 − 𝜺𝒕𝒚 ) (0.005 − 𝜺𝒕𝒚 )
Tension
𝜺𝒕 > 𝟎. 𝟎𝟎𝟓 0.90 € 0.90 (f)
controlled
[1] For section classified as transition, it shall be permitted to use ø corresponding to compression-controlled sections.
• 421.2.2.1 For deformed reinforcement, 𝜺𝒕𝒚 shall be 𝒇𝒚 /𝜺𝒔 . For Grade 280 deformed reinforcement, it shall be
permitted to take 𝜺𝒕𝒚 equal to 0.002.
• DEAD LOADS - are loads of constant magnitude that remain in one position. They include the weight of the
structure under consideration as well as any fixtures that are permanently attached to it. For a reinforced concrete
building, some dead loads are frames, wall, floors, ceilings, stairways, roofs, and plumbing. Unit weight of concrete
= 23.54 kN/m3
• LIVE LOADS - are loads that can change in magnitude and position. They include occupancy loads, warehouse
materials, construction loads, overhead service cranes, equipment operating loads, and many others. In general, they
are induced by gravity.
• ENVIRONMENTAL LOADS - are loads caused by the environment where the structure is located. For buildings,
they are caused by rain, wind, temperature change, and earthquake. In fact, these are also live loads, but they are
the result of environment where the structure is located. Although they do vary with time, they are not all caused
by gravity or operating conditions, as is typical with other live loads.
NSCP 2015 SECTION 203.3 presents the load factors and combinations that are to be used in design of reinforced concrete
structures using Strength Design Method. The required strength must at least equal to the largest value obtained by
substituting into NSCP Equations 203-1 to 203-7. On the other hand, NSCP 2015 SECTION 203.4 presents the load factors
and combinations using Working Stress Design and must at least equal to the largest value obtained by substituting into
NSCP Equations 203-8 to 203-12.
LOAD COMBINATIONS USING STRENGTH DESIGN OR LOAD AND RESISTANCE FACTOR DESIGN
(NSCP 2015 SECTION 203.3)
• 203.3.1 Where strength design or load and resistance factor design is used, structures and all portions thereof shall
resist the most critical effects from the following combinations of factored loads:
1.4(D + F) (203 – 1)
1.2 (D + F + T) + 1.6(L + H) + 0.5(Lr or R) (203 – 2)
1.2D + 1.6(Lr or R) + f1L or 0.5W) (203 – 3)
1.2D + 1.0W + f1L + 0.5(Lr or R) (203 – 4)
1.2D + 1.0E + f1L (203 – 5)
0.9D + 1.0W +1.6H (203 – 6)
0.9D + 1.0E +1.6H (203 – 7)
where;
D = Dead Load
L = Live Load
W = Wind Load
E = Earthquake Load
Lr = Roof Live Load
T = Temperature Load
F = Fluid Load
• 203.4.1 Where allowable stress or allowable strength design is used, structures and all portions thereof shall resist
the most critical effects from the following combinations of loads:
D+F (203 – 8)
D+H+F+L+T (203 – 9)
D + H + F + (Lr or R) (203 – 10)
D + H + F + 0.75[L + T + (Lr or R)] (203 – 11)
D + H + F + (0.6W or E/1.4) (203 – 12)
PROBLEMS
Problem 1: Draw the details of the most efficient beam in terms of flexure if the beam is cast-in-place, non; prestressed and
not exposed to weather or in contact with the ground. Beam section: 250 mm x 360 mm reinforced with 10 mm ø stirrups
and 6 – 16 mm ø longitudinal bottom bars.
Problem 2: Draw the details of the most efficient beam in terms of flexure if the beam is cast-in-place, non-prestressed and
not exposed to weather or in contact with the ground. Beam section: 300 mm x 450 mm reinforced with 12 mm ø stirrups
and 6 – 32 mm ø longitudinal top bars.
Problem 3: Draw the details of the most efficient beam in terms of flexure if the beam is cast-in-place, non-prestressed and
not exposed to weather or in contact with the ground. Beam section: 280 mm x 480 mm reinforced with 10 mm ø stirrups,
area of required steel reinforcement, As = 3122 mm2. Bending moment is negative. Use 20 mm ø longitudinal bars. Vertical
spacing between the layers of bars should be 25 mm minimum.