Three Phase Delta Connection
Three Phase Delta Connection
LECTURE 13
Chapter 12: Polyphase Circuits
2
Outline
• Delta Connection
• Δ Phasor Diagram
• Current Voltage Relationships
• Δ & Y load relationships for Y Source
• Δ Source
• Y to Δ Load Conversion
• Summary
3
.
4
Y-Δ Example
Determine the amplitude of the line current in a three-phase system
with a line voltage of 300 V that supplies 1200 W to a Δ–connected
load at a lagging PF of 0.8; then find the phase impedance.
We have,
VL = 300 V
PL = 1200 W; therefore, PP = 400 W
PF = 0.8
Hence, phase angle of the load is θ = cos-1(0.8) = 36.86o
Average power per phase in a delta connected load is:
Pp= VL x Ip x cos θ,
Hence, 400 = 300 x Ip x 0.8 or Ip = 1.667 A,
Since Line current is 𝐼𝐿 = 3𝐼𝑃 therefore, IL = 2.89 A
Load Impedance in each phase shall be:
𝑉𝐿 300
𝑍𝑃 = ∠θ𝑜 = ∠36.86𝑜 = 180 ∠36.86𝑜 = 144 + j108 Ω
𝐼𝑃 1.667
7
• Therefore,
-150
-270
11
S1 /3 ∗ 32+j24 ×1000/3 ∗
(b) 𝐈𝐀𝐁𝟏 = = = 𝟑𝟎. 𝟑∠ −𝟔. 𝟖𝟕𝒐 𝑨𝒎𝒑
VAB 440∠30o
S2 /3 ∗ 24−j11.624 ×1000/3 ∗
(c) 𝐈𝐀𝐁𝟐 = = = 𝟐𝟎. 𝟐∠𝟓𝟓. 𝟖𝟒𝒐 𝑨𝒎𝒑
VAB 440∠30o
3 Δ Connected Source
• The source may also be connected in a Delta configuration
• This is not typical, however, for a slight unbalance in the source phases
can lead to large currents circulating in the Delta loop
• For example, let us call the three single phase sources Vab, Vbc, and Vcd
• Before closing the Delta by connecting d to a, let us determine the
unbalance by measuring the sum Vab + Vbc + Vca
• Suppose that the amplitude of the result is only 1 percent of the line
voltage
• The circulating current is thus approximately 1/3 percent of the line
voltage divided by the internal impedance of any source
• How large is this impedance apt to be? It must depend on the current that
the source is expected to deliver with a negligible drop in terminal
voltage
• If we assume that this maximum current causes a 1 percent drop in the
terminal voltage, then the circulating current is one-third of the maximum
current!
• This reduces the useful current capacity of the source and also increases
the losses in the system
13
ZAB
ZCA ZBC
15
Summary (1/3)
• The majority of electricity production is in the form of three-phase
power
• Most residential electricity in North America is in the form of single
phase alternating current at a frequency of 60 Hz and rms voltage of
115 V
• Elsewhere, 50 Hz at 230/240 V rms is most common
• Double-subscript notation is commonly employed in power systems
for both voltages and currents
• Three-phase sources can be either Y- or Δ- connected
• Both types of sources have three terminals, one for each phase; Y-
connected sources have a neutral connection as well
• In a balanced three-phase system, each phase voltage has the same
magnitude, but is 120o out of phase with the other two
• Loads in a three-phase system may be either Y- or Δ-connected
19
Summary (2/3)
• In a balanced Y-connected source with positive (“abc’’) phase
sequence, the line voltages are:
• In a system with a Y-connected load, the line currents are equal to the
phase currents
• In a Δ-connected load, the line voltages are equal to the phase
voltages
• In a balanced system with positive phase sequence and a balanced Δ-
connected load, the line currents are
20
Summary (3/3)
• Most power calculations are performed on a per-phase basis,
assuming a balanced system; otherwise, nodal/mesh analysis is
always a valid approach
• The instantaneous power in any balanced three-phase system is
constant