Galvanic Catodic Protection
Galvanic Catodic Protection
m m W
87 , 600
yr DAT
mm W
87 . 6
yr DAT
where W is the weight loss in milligrams, D is the density in g/cm3, A is the
area in cm2, and T is the time of exposure in hours.
This Means:
Zn + 2(H++Cl) Zn++ +2Cl+H2 (2)
i.e. The net result of this reaction is:
Zn Zn++ + 2e (3)
And 2H+ + 2 e 2H H2 (4)
For iron
Fe Fe++ + 2e (anodic) (5)
For dissolved oxygen
O2 + 2H2O + 4 e 4 OH- (cathodic) (6)
- Zn corrosion in air-free & aerated HCl
- When Fe+++ ions are added to dilute aerated HCl.
Fe+++ + e Fe++ (7)
- Typical anodic reactions:
M M++ + 2 e (8)
M M+ + e (9)
- Typical cathodic reactions:
M+ + e M (10)
M++ + 2 e M (11)
2H+ + 2 e H2 (12)
O2 + 2H2O + 4 e 4 OH- (13)
O2 + 4H- + 4 e 2H2O (14)
Activation polarization:
Concentration polarization:
Thermodynamic Aspects
In electrochemical reactions:
G = - nEF
E = Cell potential
F = Faraday’s constant
Electronic copy available at: https://ssrn.com/abstract=4739017
Hydrogen-reduction reaction under activation control
0 . 059
E o log C
n
Where Eo = Standard Electrode potential
ions in gm ion/liter.
Introduction:
From an engineering point of view, the major interest is the
kinetics, or rate of corrosion.
Tafel slopes.
Behaviour of metal M in acid solution containing ferric salts showing effect of oxidizer
exchange current density
* Case 3, is the most desirable from the engineering point of view. This
system will spontaneously passivate and crossed very slowly.
Galvanic couple between an active-passive metal and platinum in air-free acid solution
Tafel Extrapolation
O 2 2H 2 O 4e 4OH
The electrode potential, often called the corrosion or
mixed potential (Ecorr).
Fig. 7: Schematic diagram of cathodic protection using sacrificial anodes. In practice the
anode, which will be mounted on a steel core, can be attached directly to the structure
a The driving voltage to bare steel. i. e. protection potential of steel- anode operating potential
b US Military Specification
Note: It is often important to control impurities and specially Fe, Cu, Ni and Si although a controlled
Si to some aluminum alloy
Current density
Environment (A/m2)
a This value will decay to less than 0.05 A/m2 if the calcareous deposit forms.
• The higher the pH of the seawater the greater will the proportion
of carbonate ions present (since as the pH increases, so the H+
concentration decreases, thereby moving the equilibrium to the
right). It follows that at a surface under cathodic protection, the
hydroxyl ion produced has effect of increasing the local
carbonate ion concentration.
• Seawater also contains calcium ions which form an insoluble
carbonate with carbonate ions:
Ca 2 CO32
CaCO3
Where
DEo is the change in potential at the drainage point
DEx is the change of potential at a distance from the point
... x = half protected distance:
protected.
alloys)
Anode Requirements
Si - - - 0.125 max
10 2 7 10
20 2 15 30
30 2 25 60
40 2 40 90
[ E 2 E1 ]
I
R
Where I= anode output (A)
E1= operating potential of the anode (V)
E2= protection potential (V)
R= anode resistance (ohm)
The protection potential of steel in aerobic environments is taken as -0.80V (vs.
Ag/AgCl/seawater).
MU
L
IE
backfill.
Breakdown
potentials of
Electrolyte and conditions commercially pure
titanium
(V)
Tests in pure seawater at ambient temperatures 8.5-15
Tests in NaCl from 5 g / l to saturated below 60C 8.5-15
Sea water 9-14
Sulphuric acid 80-100
Chloride 8
Sulphate 60
Carbonate 60
Phosphate 60
Fluoride 50
Bromide 2-3
Iodide 2-3
Sulphate >80
Phosphate >80
Ratio of sulphate plus carbonate to chloride ions, 4:1 >35
River water 50
Tap water 80
Examples:
Platinized Silver
• Used only in sea water or similar chloride –
containing electrolytes.
• An anode consisting of Pt-10 Pd on Ag was tried
as substitute for rapidly consumed aluminum for
use as a trailing wire anode for the cathodic
protection of ship hulls, and has been operated at
1900 Am-2.
• With the advent of hull mounted anodes this
material has been replaced by the superior
platinized titanium and niobium anodes.
Conductive Polymers
• The anode, marketed under the trade name
Anodeflex, consists of a continuous stranded
copper conductor (6AWG) which is encased in a
thick jacket of carbon loaded polymer, overall
diameter 12.5mm.
• The major applications for this material are tank
protection, internal protection, mitigation of poor
current distribution and hot spot protection, i.e. to
supplement conventional cathodic protection
systems and provide increased levels of cathodic
protection in areas that exhibit low levels of
protection.
Hybrid Systems
Offshore structures are often
protected by hybrid systems using
both sacrificial anodes and
impressed-current.
8. Consider facilities for monitoring 8. Calculate circuit, resistance and system d.c.
performance volts,
9. Consider facilities required for control/
monitoring
Group 1
Group 2
Platinized-titanium, platinized-
niobium, lead and lead-platinum
anodes used for submerged structures,
ships and power stations.
4L
RH n 1
and 2L d
8L
R n 1
2 L
v
d
Resistance of a single vertical rod anode
a) Sacrificial Anodes
Fig. 9
E
RL
I
RS
RL
rs = Resistivity of steel.
t = Thickness of the pipeline, m.
D = Diameter of the pipeline, m.
RK (equivalent) = RS . RL
E
g
Iprot. (Protection current) = RK
2 . y
g = resistivity of soil.
y = distance between anode and pipe.
Vprot = Iprot. (RX + RA + RP)
Calculations
S 1.35 x 107
RS 0.55 x 105 / m.
(D t) t 3.14 (0.72 0.011) 0.011
RS 0.55 x 105
1.12 x 104
RL 442
4500
Rv K x 0.0175 9.844
L 8
Then for the total of one – row of 17 anodes
1 P 1 0.00150
Rn Rv x 9.844 4500 x
n S 17 20
= 0.579 + 0.338 = 0.917
= Total resistance between all anodes and soil
= 0.9A
Total current requirements to maintain protection of entire structure in
the tidal, submerged and soil zones after 20 years
=4+7.4+0.9 = 12.3A
Anode Design Calculations:
Average total current to maintain protection of the entire structure for 20
- year life:
initial current (after polarization) final current 2.8 12.3
= 9.1A
2 2
Total weight of high purity zinc anode material required for 20 year life
expectancy:
Where CR x L x ATC
W
E xU
W = Total weight in pounds
CR = Consumption rate, lb/Ay
L = Life, years
ATC = Average Total Current, A
E is the efficiency factor, U is the utilization factor
23.585 x 20 x 9.1
W 5611 Ib
0.9 x 0.85
Based on the structure description and the amount of zinc
required, it can be determined that for this structure: 8
Strings of 2 (390 lb each) Anodes (10 x 10 x 15 in) zinc
anodes (6240 lb).
Suspended at locations shown in (Fig. 11) should afford
adequate protection for 20 - year life expectancy
The other factor to consider: is the amount of current that
can be discharged from anodes:
Resistance of the Anode System:
•Submerged Zone
Assume 5% coating damage, then the current required:
• Soil Zone
• Assume coat is 40% intact
• Current required:
The final current requirements are calculated for the 20 - year life expectancy
assuming: 2% per year coating deterioration in the tidal zone, 1% in the
submerged zone, and 0.5% in the soil zone.
Then, the final current requirement after 20 years would be:
Tidal Zone :
= 640 (0.45 x 35 + 0.55 x 5) = 11.9 A
Submerged Zone ;
= 7200 (0.25 x 10 + 0.75 x 1.5) = 26.1 A
Soil Zone :
= 8000 (0.7x1.5 + 0.3x0.5) = 9.6 A
Then, total current required to maintain protection of the entire structure at the
end of the 20 - year period:
The header cable length is divided by 2 because the total current is not
flowing through the entire length of cable. The current is being dropped
off in equal amounts at equal distances. The wire unit resistance is
0.000254W / ft
In this case, the anode has a trapezoidal cross section, and the equivalent
radius is calculated by using Eq 2, as follows:
90.25
R 5.36 in.
0.45 V
I 10.54 A
0.0427
The initial structure current density is determined as follows:
0.25 V
I 5 .6 A
0.0441
28 641 lb
N water 25.2
1135 lb / anode
41 045 lb
N mud 36.2
1135 lb / anode
N tota l 26 37 63 anodes
n p
2 0.00261
3 0.00289
4 0.00283
5 0.00268
6 0.00252
7 0.00237
8 0.00224
9 0.00212
10 0.00201
12 0.00182
14 0.00186
16 0.00155
18 0.00145
29 0.00135
22 0.00128
24 0.00121
26 0.00114
28 0.00109
30 0.00104
Zinc 81 10.8
Magnesium 1100 7.9
Failure Analysis:
• SEM examination showed a quasi-cleavage-like
brittle fracture with several secondary creaks.
• Binocular and SEM investigation indicated that
crack initiation took place at the outer surface of the
pipe. The jagged crack appearance with a tending
toward stepwise cracking suggested hydrogen in the
cracking process.
• No plastic deformation.
• Type of crack: trans-granular.
• Hydrogen was evolved during cathodic protection.
17 Air 67 14 44 30
18 air 70 16 48 55
1 i.c.p.c 59 17 48 10
2 i.c.p. 62 16 47 55
3 -900 36 14 42 25
4 -900 38 13 39 12
9 -950 39 10 31 55
10 -950 36 11 34 40
11 -1000 40 11 39 55
12 -1000 32 12 39 15
7 -1100 22 11 34 25
8 -1100 28 12 36 5
13 -1150 28 12 38 55
14 -1150 25 10 36 24
5 -1250 28 10 33 35
15 -1250 23 11 36 35
16 -1250 30 8 30 25
Platform
The sub-sea platform structure was coated with a tank-lining-type epoxy
system. Surface preparation was done to Steel Structures Painting Council
white metal blast (SSPC-SP 5). Two coats were used, each 4 mils (102 m)
thick. Surface preparation, anchor profiles, weather conditions, coating
times, etc., were monitored throughout the entire job.
Einit 0.5
I 14.2 A
RA 0.0352
Table (2): Drilling Platform 52A Potentials Determined One Month after Installation
Location Potential vs Ag/AgCl(V)
295 ft(A) 455 ft 610 ft
Leg A1 -0.998 -0.957 -0.945
Leg B1 -.0993 -0.947 -0.908
Leg A4 -1.00 -0.944 -0.900
Leg B4 -0.993 -0.936 -0.905
Leg C2 -1.00 -0.880 -0.882
Leg C3 -0.990 -0.860 -0.883
(B) -0.990 -0.860 -0.788
Cost Effectiveness
• 1ry Cost Effective Objective of coating: Eliminate risk of premature retrofit.
• Minor retrofitting in Deep waters Result in Costs Exceeding the costs of original protection
system.
• Secondary cost effectiveness achieved is reflected) in comparison of as installed cost compared
to the uncoated standard design.
• Table (1)
• Coating Cost ~ $ 1.9/ft2(20.45$/m2)
• Installation cost of anode = $ 800/anode
• Coating load based on a coat thickness of 8 mils.
Protection System Evaluation
The protection on each leg of the 52A drilling platform was monitored one month after
installation.
Legs with no anodes: Worst Condition (least polarization).
Points on Table 2 represent those furthest from anodes and where the shielding from the C.P.
was greatest.
Areas most affected (least polarization): conductor bay (Table2).
Where:
Lt = effective lifetime in years,
W = net weight of anode (900 lb),
Q = anode capacity = 1250 A h/Ib (2756 A h/Kg),
F = anode utilization factor (0.9),
I = mean current output during lifetime, and,
8760 = number = of hours in one year.
The main current output is determined by ohm's low:
V
L
Rd
Conclusions
A unique combination of coatings and CP has been used to protect the sub-sea portion of two
deep water platforms. Potential surveys undertaken after installation demonstrates protection
well beyond the minimum protective potential. The primary objective, namely the
elimination of the retrofit risk, has been achieved. Additionally, cost and weight savings,
when compared to conventional design, were of the order of $200.000 and 400.000 pounds,
respectively. The system life will exceed the design life of 20 year.
• Fig. 8 :
Data on five of these pairs (on the Zn- sea water scale).
Three electrodes show slower polarization than the other two.
The first : in an environmentally affected area (-21m).
The second: coating was deliberately removed (-7 4m) The third
:mounted on a "bottle neck" leg just above the top of the piles.
Current Monitoring
• High initial current, decreasing, gradually, average current
consumption: 105 mA/m2 on jacket surface (5% bare
initially).
• Each anode current: 180mA/m2 , and the average current
output from the 20 n10nitored anodes in less than this.
Problem of monitoring:
Inability to place portable reference electrode in close proximity to the
underside.
Placement of ref. electrodes at the perimeter: may yield erroneous
results, especially when using distributed anodes installed along the
periphery.
Table (1): Actual measurements showing a potential difference of ~
300 mV between perimeters a center of tank.
So, recommended: At least one measurement taken at tank center.