Al175ul Dip
Al175ul Dip
Installation Guide
Altronix Corp.
140 58th St. Brooklyn, NY
Specifications:
Agency Listings: Battery Backup:
• UL Listed for Access Control Systems (UL294*). • Maximum charge current: 400mA.
cUL Listed - CSA Standard C22.2 • Automatic switch over to stand-by battery
No.205-M1983, Signal Equipment. when AC fails.
• CSFM - California State Fire Marshal Approved. Supervision:
• MEA - NYC Dept. of Buildings Approved. • AC fail supervision (form “C” contacts).
• NFPA 101 (Life Safety). • Dry trigger output (form “C” contacts).
Input: Fire Alarm Interface:
• Input 115VAC, 60Hz, 0.6A. • Dry trigger input.
Output: Visual Indicators:
• 12VDC or 24VDC selectable output. • AC input and DC output LED indicators.
• Class 2 Rated power-limited outputs. Added Features:
• 1.75A continuous supply current @ 12VDC or 24VDC. • Includes power supply, transformer, and enclosure.
• Aux relay output (form “C” contacts).
• Filtered and electronically regulated output. Enclosure Dimensions:
• Short circuit and thermal overload protection. 8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm).
Stand-by Specifications:
Output 4 hr. of Stand-by and 5 Minutes of Alarm
12VDC / 7 AH Battery Stand-by = 1.25A
24VDC / 7 AH Battery Alarm = 1.25A
Installation Instructions:
The AL175UL should be installed in accordance with article 760 of The National Electrical Code or NFPA 72 as
well as all applicable Local Codes.
See Terminal Identification Chart on page 4 for a description of each terminal function.
1. Mount the unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes
in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the
enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two
holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper
keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws
(Enclosure Dimensions, pg. 8).
2. Connect AC power to the black and white flying leads of the transformer. Secure green wire lead to earth
ground. Green “AC” LED on power supply board will turn on. This light can be seen through the LED lens
on the door of the enclosure. Use 18 AWG or larger for all power connections (Battery, AC input, DC outputs).
Use 22 AWG to 18 AWG for power-limited circuits (trigger inputs, dry outputs).
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper
voltage level (see Power Supply Output Specifications Chart).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified
voltage both at the battery terminal and at the board terminals marked [+ BAT –] to
ensure that there is no break in the battery connection wires.
Note: Maximum charging current under discharges is 400mA.
Note: Expected battery life is 5 years; however, it is recommended changing batteries in
4 years or less if needed.
Terminal Identification:
Terminal Legend Function/Description
Connects to the normally closed outputs of an access control or fire alarm relay.
TRG1 & TRG2 These terminals control [LOCK +], and [STRIKE +], as well as AL175UL output relay
contacts [NC, NO, C].
Provides DC output voltage when [TRG1] and [TRG2] are shorted together and are
LOCK +
typically used to power Mag Locks.
Provides DC output voltage when [TRG1] and [TRG2] are unshorted and are typically
STRIKE +
used to power Electric Strikes.
Isolated dry form “C” contacts. Shorting [TRG1] and [TRG2] together causes these
NC, NO, C contacts to switch. They are typically used for controlling multiple AL175ULs with fire
alarm tie-in (Fig. 5 and Fig. 6, pg. 7).
Continuous positive (+) DC power output voltage.
AUX +
It is not affected by TRG1, TRG2 operation.
COM – Common negative (–) output (ground).
FACP Spare wiring terminal used for fire alarm tie-in application (Fig. 4, pg. 7).
+ BAT – Stand-by battery connections.
AC FAIL Indicates loss of AC, e.g connect audible device or alarm panel.
NC, C, NO Relay normally energized when AC power is present. Contact rating 1A @ 28VDC.
SW1 ON - 24V
OFF - 12V
ON
SW1
NC NO C
NC NO C TRG1 TRG2
AC
DC
VR1
AL175ULB
Black
Lead
Green Lead
Input 115VAC (ground)
60Hz, 0.6A
White
Lead
DOOR
STRIKE
LOCK +
STRIKE +
MAG LOCK
COM – PROX/CARD
READER
AUX +
ACCESS
CONTROL
DEVICE
AUX –
TRG2
TRG1 FACP
Fig. 3 Typical dual mag lock installation with fire alarm tie-in using trigger controlled outputs:
ACCESS CONTROL
DEVICE
STRIKE +
FACP
TRG2
TRG1
ACCESS
CONTROL
DEVICE
MAG LOCK
AUX +
FACP +
FACP
AUX –
ACCESS
CONTROL
DEVICE
LOCK +
STRIKE +
MAG LOCK
COM –
FACP
TRG2
TRG1
NO NO RESET
SWITCH
NC
NO TRG1
NC TRG2
1.25”
(31.8mm)
3.5” (88.9mm)
1.25”
(31.75mm) 0.6” (15.2mm) 0.6” (15.2mm)
6.05” (153.7mm)
1.125” 1.125”
2” (50.8mm)
(28.6mm) (28.6mm)
2” (50.8mm)
8.125” (206.4mm)
1” 1”
(25.4mm) (25.4mm)
1”
(25.4mm)
1” 5.25” (133.35mm) 1”
(25.4mm) (25.4mm)