Al175ul Dip

The Altronix AL175UL is a power-limited power supply/charger that converts 115VAC input into two PTC protected 12VDC or 24VDC outputs, designed for access control systems and fire alarm interfaces. It features battery backup, supervision, and various safety protections, and must be installed according to electrical codes. The installation guide includes detailed instructions, specifications, and application diagrams for proper setup and maintenance.

Uploaded by

Louai Asfar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
48 views8 pages

Al175ul Dip

The Altronix AL175UL is a power-limited power supply/charger that converts 115VAC input into two PTC protected 12VDC or 24VDC outputs, designed for access control systems and fire alarm interfaces. It features battery backup, supervision, and various safety protections, and must be installed according to electrical codes. The installation guide includes detailed instructions, specifications, and application diagrams for proper setup and maintenance.

Uploaded by

Louai Asfar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

AL175UL

Access Control Power Supply/Charger

Installation Guide

Altronix Corp.
140 58th St. Brooklyn, NY

Rev. 052019 More than just power.TM

Installing Company: ________________ Service Rep. Name: ___________________________________


Address: ______________________________________________ Phone #: ___________________
Overview:
Altronix AL175UL is a power-limited power supply/charger which converts 115VAC, 60Hz input into two individually
PTC protected auto-resettable 12VDC or 24VDC outputs (see specifications). It is intended for use in applications
requiring UL Listing for Access Control (UL294) and applications requiring an interface with the Fire Alarm Control
Panels. It must be installed in accordance with National and Local Electrical Codes and Regulations.

Specifications:
Agency Listings: Battery Backup:
• UL Listed for Access Control Systems (UL294*). • Maximum charge current: 400mA.
cUL Listed - CSA Standard C22.2 • Automatic switch over to stand-by battery
No.205-M1983, Signal Equipment. when AC fails.
• CSFM - California State Fire Marshal Approved. Supervision:
• MEA - NYC Dept. of Buildings Approved. • AC fail supervision (form “C” contacts).
• NFPA 101 (Life Safety). • Dry trigger output (form “C” contacts).
Input: Fire Alarm Interface:
• Input 115VAC, 60Hz, 0.6A. • Dry trigger input.
Output: Visual Indicators:
• 12VDC or 24VDC selectable output. • AC input and DC output LED indicators.
• Class 2 Rated power-limited outputs. Added Features:
• 1.75A continuous supply current @ 12VDC or 24VDC. • Includes power supply, transformer, and enclosure.
• Aux relay output (form “C” contacts).
• Filtered and electronically regulated output. Enclosure Dimensions:
• Short circuit and thermal overload protection. 8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm).

* ANSI/UL 294 7th Ed. Access Control Performance Levels:


Destructive Attack - I; Endurance - N/A; Line Security - I; Stand-by Power - I, IV.

Power Supply Output Specifications:


Output Max. Stand-by Max. Alarm Battery
Switch Position
VDC Load DC Load DC (optional)
12VDC SW1 OFF 1.75A 1.75A 12VDC
24VDC SW1 ON 1.75A 1.75A 24VDC

Stand-by Specifications:
Output 4 hr. of Stand-by and 5 Minutes of Alarm
12VDC / 7 AH Battery Stand-by = 1.25A
24VDC / 7 AH Battery Alarm = 1.25A

Installation Instructions:
The AL175UL should be installed in accordance with article 760 of The National Electrical Code or NFPA 72 as
well as all applicable Local Codes.
See Terminal Identification Chart on page 4 for a description of each terminal function.
1. Mount the unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes
in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the
enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two
holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper
keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws
(Enclosure Dimensions, pg. 8).
2. Connect AC power to the black and white flying leads of the transformer. Secure green wire lead to earth
ground. Green “AC” LED on power supply board will turn on. This light can be seen through the LED lens
on the door of the enclosure. Use 18 AWG or larger for all power connections (Battery, AC input, DC outputs).
Use 22 AWG to 18 AWG for power-limited circuits (trigger inputs, dry outputs).

-2- AL175UL Installation Guide


Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, Battery
Wires). Minimum 0.25” spacing must be provided.
CAUTION: Do not touch exposed metal parts.
Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.
3. Set the AL175UL to the desired DC output voltage by setting switch SW1 to the appropriate position
(Power Supply Output Specification Table).
4. Measure output voltage before connecting devices. This helps avoiding potential damage.
5. Connect battery to the terminals marked [+ BAT –] (battery leads included).
Use two (2) 12VDC batteries connected in series for 24VDC operation.
Note: For Access Control applications batteries are optional.
When batteries are not used, a loss of AC will result in the loss of output voltage.
When the use of stand-by batteries are desired, they must be lead acid or gel type.
6. Connect appropriate signaling notification devices to AC Fail supervisory relay outputs marked [NC, NO, C].
Note: To meet UL requirements, AC Supervisory outputs must be connected to the zone of Alarm Control
Panel or to visual AC trouble indicator.
7. For Access Control Device & Fire Alarm Interface connections refer to desired Application Diagrams (pg. 6-7)
and Terminal Identification Chart (pg. 4).

Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper
voltage level (see Power Supply Output Specifications Chart).
Battery Test: Under normal load conditions check that the battery is fully charged, check specified
voltage both at the battery terminal and at the board terminals marked [+ BAT –] to
ensure that there is no break in the battery connection wires.
Note: Maximum charging current under discharges is 400mA.
Note: Expected battery life is 5 years; however, it is recommended changing batteries in
4 years or less if needed.

AL175UL Installation Guide -3-


LED Diagnostics:
Red (DC) Green (AC) Power Supply Status
ON ON Normal function.
ON OFF Battery backup is powering output.
OFF ON No DC output.
OFF OFF Loss of AC. Discharged or missing stand-by battery. No DC output.

Terminal Identification:
Terminal Legend Function/Description
Connects to the normally closed outputs of an access control or fire alarm relay.
TRG1 & TRG2 These terminals control [LOCK +], and [STRIKE +], as well as AL175UL output relay
contacts [NC, NO, C].
Provides DC output voltage when [TRG1] and [TRG2] are shorted together and are
LOCK +
typically used to power Mag Locks.
Provides DC output voltage when [TRG1] and [TRG2] are unshorted and are typically
STRIKE +
used to power Electric Strikes.
Isolated dry form “C” contacts. Shorting [TRG1] and [TRG2] together causes these
NC, NO, C contacts to switch. They are typically used for controlling multiple AL175ULs with fire
alarm tie-in (Fig. 5 and Fig. 6, pg. 7).
Continuous positive (+) DC power output voltage.
AUX +
It is not affected by TRG1, TRG2 operation.
COM – Common negative (–) output (ground).
FACP Spare wiring terminal used for fire alarm tie-in application (Fig. 4, pg. 7).
+ BAT – Stand-by battery connections.
AC FAIL Indicates loss of AC, e.g connect audible device or alarm panel.
NC, C, NO Relay normally energized when AC power is present. Contact rating 1A @ 28VDC.

-4- AL175UL Installation Guide


Fig. 1 - AL175UL

SW1 ON - 24V
OFF - 12V
ON
SW1
NC NO C

NC NO C TRG1 TRG2

AC
DC
VR1

AL175ULB

LOCK + STRIKE + COM -- AUX + FACP AUX -- + BAT -- AC AC

Switched Constant output Stand-by


DC output (Not affected Battery
(trigger control) by trigger) (optional)

Black
Lead
Green Lead
Input 115VAC (ground)
60Hz, 0.6A
White
Lead

AL175UL Installation Guide -5-


Typical Application Diagrams:
Fig. 2 Typical single mag lock or door strike installation with fire alarm tie-in using trigger controlled output:

DOOR
STRIKE

LOCK +

STRIKE +
MAG LOCK

COM – PROX/CARD
READER

AUX +
ACCESS
CONTROL
DEVICE
AUX –

TRG2

TRG1 FACP

Fig. 3 Typical dual mag lock installation with fire alarm tie-in using trigger controlled outputs:

ACCESS CONTROL
DEVICE

LOCK + MAG LOCK

STRIKE +

COM – MAG LOCK

FACP
TRG2

TRG1

-6- AL175UL Installation Guide


Typical Application Diagrams:
Fig. 4 Typical mag lock with fire alarm tie-in using aux output installation:

ACCESS
CONTROL
DEVICE

MAG LOCK
AUX +

FACP +
FACP

AUX –

Fig. 5 Latching fire alarm tie-in with manual reset:

ACCESS
CONTROL
DEVICE

LOCK +

STRIKE +
MAG LOCK
COM –

FACP

TRG2

TRG1

NO NO RESET
SWITCH

NC

Fig. 6 Multiple AL175UL(X) power supply connections:

NO TRG1

NC TRG2

AL175UL Installation Guide -7-


Enclosure Dimensions (H x W x D approximate):
8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm)
7.25” (184.2mm)
3.625” (92mm)

1.25”
(31.8mm)

3.5” (88.9mm)
1.25”
(31.75mm) 0.6” (15.2mm) 0.6” (15.2mm)
6.05” (153.7mm)

1.125” 1.125”
2” (50.8mm)

(28.6mm) (28.6mm)
2” (50.8mm)
8.125” (206.4mm)

1” 1”
(25.4mm) (25.4mm)

6.05” (153.7mm) 1.25”


0.6” (15.2mm) 0.6” (15.2mm)
(31.75mm)
3.5” (88.9mm)

1”
(25.4mm)

1” 5.25” (133.35mm) 1”
(25.4mm) (25.4mm)

Altronix is not responsible for any typographical errors.


––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: [email protected] | Lifetime Warranty
IIAL175UL F29U MEMBER
-8- AL175UL Installation Guide