Standard PLC: C0-01DD1-D $139.00
Standard PLC: C0-01DD1-D $139.00
1-800-633-0405
Standard PLC
Built-in I/O Specifications - Inputs
C0-01DD1-D $139.00 Inputs per Module 8 (Sink/Source)
Operating Voltage Range 24VDC
8 DC Input/6 Sinking DC Output Micro PLC
Input Voltage Range 21.6–26.4 VDC
X1-2: Typ 5mA @ 24VDC
Input Current
X3-8: Typ 4mA @ 24VDC
Wiring Diagram
X1-2: 6.0 mA @ 26.4 VDC
Maximum Input Current
C0-01DD1-D 24VDC X3-8: 5.0 mA @ 26.4 VDC
X1-2: 4.7 kΩ @ 24VDC
Input Impedance
X3-8: 6.8 kΩ @ 24VDC
+
X1-2: > 19VDC
ON Voltage Level
+
X3-8: > 19VDC
PWR
X1-2: < 4VDC
RUN OFF Voltage Level
ERR
X3-8: < 7VDC
X1-2: 4.5 mA
+
Minimum ON Current
X3-8: 3.5 mA
+
PORT1
TX1 X1-2: 0.1 mA
Maximum OFF Current
RX1 X3-8: 0.5 mA
X1-2: Typ 5µs Max 20µs
L OFF to ON Response
TX2
X3-8: Typ 2ms Max 10ms
RX2 L
X1-2: Typ 5µs Max 20µs
PORT2 L 5 - 27VDC ON to OFF Response
+
L 24VDC
+
8
Inputs
6
Outputs ZL-RTB20 20-pin
Points
Optical Isolator
4
feed-through
* connector module
OUTPUT
+ Y2-Y4
L
5 - 27 VDC * 2
C3 COM
0
0 10 20 30 40 50 55 °C
32 50 68 85 104 122 131 °F
Optical Isolator
OUTPUT Surrounding Temperature (°C/°F)
+ Y5-Y6
L * Use every other input/output.
5 - 27 VDC
*
20-pin connector cable
ZL-C0-CBL20 (0.5 m length)
C4 COM
ZL-C0-CBL20-1 (1.0 m length)
Note: C3 & C4 are not internally connected.
ZL-C0-CBL20-2 (2.0 m length)
* Zener Diode Power Dissipation: 200 mW
Products
32°F to 140°F [0°C to 60°C];
Operating Temperature All other modules:
32°F to 131°F [0°C to 55°C],
These general specifications apply to IEC 60068-2-14 (Test Nb, Thermal Shock)
all CLICK PLCs and optional power
supply products. Please refer to the –4°F to 158°F [–20°C to 70°C]
IEC 60068-2-1 (Test Ab, Cold)
appropriate I/O temperature derating Storage Temperature
IEC 60068-2-2 (Test Bb, Dry Heat)
charts under both the PLC and I/O IEC 60068-2-14 (Test Na, Thermal Shock)
module specifications to determine
Ambient Humidity 30% to 95% relative humidity (non–condensing)
best operating conditions based on the
ambient temperature of your particular Environmental Air No corrosive gases. Environmental pollution level is 2 (UL840)
application. MIL STD 810C, Method 514.2, EC60068-2-27, Category [f],
Vibration Procedure[VIII]
JIS C60068-2-27 (Sine wave vibration test)
MIL STD 810C, Method 516.2, IEC60068-2-27,
Shock
JIS C60068-2-27, Category [f], Procedure[VIII]
<EN61131-2>
EN61000-4-2 (ESD)
EN61000-4-3 (RFI)
EN61000-4-4 (FTB)
EN61000-4-5 (Surge)
Noise Immunity EN61000-4-6 (Conducted)
EN61000-4-8 (Power frequency magnetic field immunity)
<Local Test>
Impulse noise 1μs, 1000V
RFI: No interference measured at 150 and 450 MHz (5w/15cm)
Emissions EN55011:1998 Class A; EN61000-6-4:2007+A1:2011
UL508, UL61010-2-201 (File No. E157382, E316037); CE (EN61131-
Agency Approvals
2); CUL Canadian C22.2
Other RoHS 2011/65/EU Amendment (EU)2015/863
CLICK Specifications
CLICK PLC Hardware/Software Compatibility
CLICK PLCs require a minimum software version of v2.50 for the PID function. The
table below shows the most recent software and hardware versions required for the
High-Speed input operation capability to be accessible.
IN 24V
C1
1
2
6.5mA
Slot Module if desired.
3
4
C2
5
6
7
8
OUT 5-27V
C3
1
2
3
0.1A
4
C4
5
6
+V
D2-DSCBL
USB-CBL-AMICB6 C5E-STPYL-C3 (crossover)
C5E-STPYL-S3 (straight through)
or
SE-ANT210
Wi-Fi/Bluetooth Whip Antenna
(C2-02CPU & C2-03CPU only)
(nonmetal enclosure only)
Power Supplies
Power Supplies CLICK 24VDC Power Supply Ratings
The CLICK PLC family offers two 24VDC power Part Number Output Current Price
supplies. They are identical except for the output C0-00AC 0.5 A $51.00
current. C0-01AC 1.3 A $63.00
It is not mandatory to use one of these CLICK
power supplies for the CLICK/CLICK PLUS PLC C0-00AC
system. You can use any other 24VDC power
Power Supply Input Specifications
supply that Automationdirect.com offers, Part Number C0-00AC C0-01AC
including the PSP24-DC12-1 12 to 24 VDC Input Voltage Range 85–264 VAC
converter shown below. Input Frequency 47–63 Hz
C0-00AC Power Supply Input Current (typical)
0.3 A @ 100VAC, 0.9 A @ 100VAC,
Limited auxiliary AC power supply allows you to 0.2 A @ 200VAC 0.6 A @ 200VAC
power the 24VDC CLICK C0 and C2 series PLCs Inrush Current 30A
with 100–240 VAC supply power. The 0.5 A DC Efficiency 80% typical
power supply is capable of controlling the PLC
plus a limited configuration based on the power
budget of each I/O module. The C0-00AC is
Power Supply Output Specs
a low-cost solution for applications requiring Part Number C0-00AC C0-01AC
only minimal I/O and power consumption. This Output Voltage Range 23–25 VDC
power supply will not support a fully-populated Output Current 0.5 A 1.3 A
CLICK PLC system with all possible I/O module Ripple 200mV p-p max (0–55°C)
combinations. C0-01AC Ripple Noise 300mV p-p max (0–55°C)
C0-01AC Power Supply Over Current Protection
@ 0.65 A @ 1.6 A
Expanded auxiliary AC power supply allows you (automatic recovery) (automatic recovery)
to power the 24VDC CLICK C0 and C2 series PLCs Over Voltage Protection @ 27.6 V (clamped by Zener diode)
with 100–240 VAC supply power. The 1.3 A DC Start-up Time 1000ms max at rated input and load
power supply is capable of supporting a fully- Hold-up Time 10ms minimum at 85VAC, I=max
populated CLICK PLC system with all possible I/O
module
combinations, with no concerns for exceeding the Power Supply General Specs
power budget. Part Number C0-00AC C0-01AC
PSP24-DC12-1 DC-DC Converter Ambient Operating
32–131°F [0–55°C]
With this DC-DC converter you can operate the Temperature
CLICK/CLICK PLUS PLC with 12VDC input power. Storage Temperature -4–158°F [-20–70°C]
Humidity 30–95%, non-condensing
Vibration Resistance JIS C60068-2-6, sine wave vibration
Shock Resistance JIS C60068-2-27
Voltage Withstand
CLICK Power Supply CLICK PLC Input-Output 1500VAC, 5mA cutoff current
Input-Ground 1500VAC, 5mA cutoff current
Output-Ground 500VAC, 5mA cutoff current
Insulation Resistance
Input-Output 10MΩ minimum, 500VDC
Input-Ground 10MΩ minimum, 500VDC
Output-Ground 5MΩ minimum, 500VDC
Noise Immunity FCC Class A, EN55022:1998 Class A
5P terminal block, Fujicon UF2362AX
Input/Output Interface
series or equivalent
UL508, UL1604, EN61010-1 (IEC 1010-1),
Agency Approvals
CAN/CSA E60079-15:02, JIS C0025
Drawing Link PDF PDF
Weight 5.3 oz [150g] 6.0 oz [170g]
PSP24-DC12-1
www.automationdirect.com CLICK PLCs tCLP-18
For the latest prices, please check AutomationDirect.com.
1-800-633-0405
Power Budgeting
Power Budgeting
There are two factors to consider when determining the It is strongly recommended that the power source for the logic
power required to operate a CLICK PLC system. The first is side be separate from the power source for the field side to help
the power required by the PLC and internal logic-side power eliminate possible electrical noise.
provided through the PLC. This includes the CPU’s own Power budgeting requires the calculation of the total current the
I/O, any connected I/O modules that are powered through 24VDC power source needs to provide to CLICK’s logic side. A
the PLC expansion port, plus any device, such as a C-more separate calculation is required to determine the total current
Micro-Graphic panel, that is powered through one of the required for all devices operating from the field side of the
communications ports. PLC system.
The second area is the power required by all externally- Refer to the Power Budgeting example shown on the following
connected I/O devices. This should be viewed as the field-side page. The table shows required current for a CLICK PLUS PLC,
power required. The field-side power is dependent on the two I/O modules, and a C-more Micro. Use the total amperage
voltage used for a particular input or output device as it relates values to select a suitable power supply.
to the wired I/O point and to the calculated load rating of the
connected device.
Power Budgeting
Power Consumption for CLICK Stackable I/O Modules
I/O Module Current I/O Module Current Consumption
Consumption (mA) (continued) (mA)
Power Budget External Power Budget External
Part Number 24VDC 24VDC Part Number 24VDC 24VDC
(logic side) (field side) (logic side) (field side)
Discrete Input Modules Discrete Combo I/O Modules
C0-08SIM 50 0 C0-16CDD1 80 50
C0-16CDD2 80 0
C0-08ND3 30 0
C0-08CDR 80 0
C0-08ND3-1 30 0
Analog Input Modules
C0-16ND3 40 0 C0-04AD-1 20 65
C0-08NE3 30 0 C0-04AD-2 23 65
C0-16NE3 40 0 C0-04POT 30 0
C0-08NA 30 0 C0-04RTD 25 0
Discrete Output Modules C0-04THM 25 0
C0-08TD1 50 15 Analog Output Modules
C0-04DA-1 20 145
C0-08TD2 50 0
C0-04DA-2 20 85
C0-16TD1 80 100
Analog Combo I/O Modules
C0-16TD2 80 0
C0-4AD2DA-1 25 75
C0-08TA 80 0 C0-4AD2DA-2 20 65
C0-04TRS 100 0 C-more Micro-Graphic Panel
C0-04TRS-10 120 0 Monochrome only 90 0
C0-08TR 100 0
C0-08TR-3 90 0
I/O Module
(C0-16ND3) Power Budgeting Example
Accessories
C2-USER-M $0.00 EA-MG-PGM-CBL $52.00 C0-3TB $10.00
CLICK PLUS PLC Hardware User Manual PC to Panel Programming Cable Spare 3-Pole Terminal Block
Assembly for C-more Micro-Graphic
Manual covers all CLICK PLUS PLC Replacement 3-pole terminal block for the
Panels and CLICK/CLICK PLUS PLCs
and I/O module installation and 3-wire RS-485 Port 3 on CLICK Standard
wiring, specifications, error codes and The 6-ft cable assembly connects a and Analog PLCs as well as the CLICK
troubleshooting guide. The CLICK PLUS personal computer to any C-more Micro- PLUS C2-03CPU. Sold in packs of 2.
PLC Hardware User Manual can be Graphic panel, CLICK PLC, or select CLICK
downloaded free at the AutomationDirect PLUS PLC for setup and programming.
Web site; www.AutomationDirect.com Note: This cable assembly uses the PC’s USB port and
converts the signals to serial transmissions. The USB port
supplies 5VDC to the Micro-Graphic panel for configuration
operations. C0-4TB $10.00
Assembly includes standard USB A-type Spare 24VDC Power Terminal Block
connector to B-type connector cable, Replacement terminal block for the
custom converter, and an RS232C cable 24VDC supply power to the PLC. Sold in
with an RJ12 modular connector on packs of 2.
each end.
C0-USER-M $0.00
CLICK PLC Hardware User Manual
Manual covers all CLICK PLC and C0-8TB $16.50
I/O module installation and wiring, Spare 8-Point I/O
specifications, error codes and Terminal Block
troubleshooting guide. The CLICK
PLC Hardware User Manual can be Replacement terminal
downloaded free at the AutomationDirect block for the 8-point
Web site; www.AutomationDirect.com USB-CBL-AMICB6 $5.25 I/O modules. Sold in
USB A to USB microB Programming packs of 2.
Cable Assembly (CLICK PLUS Only)
Programming cable, USB A to USB
microB, 6ft (1.83 m) length. For use with
C0-8TB-1 $19.50
CLICK PLUS PLCs and most USB devices.
Spare 13-Point I/O Terminal Block
The USB port supplies 5VDC to the CLICK
PLUS CPU for programming. Replacement terminal block for the 8-point
I/O relay modules. Sold in packs of 2.
C0-PGMSW $12.00
Programming Software USB
The programming software can be
downloaded free at the AutomationDirect D2-DSCBL $35.00
Web site, or the USB can be purchased Programming Cable for CLICK/CLICK
from the AutomationDirect online Web PLUS and DirectLOGIC PLCs C0-16TB $23.00
store. www.AutomationDirect.com Spare 16-Point I/O
12ft. (3.66 m) RS232 shielded PC
Terminal Block
programming cable for CLICK, select
CLICK PLUS PLCs, DL05, DL06, DL105, Replacement terminal
DL205, D3-350, D4-450, D4-454, and block for the 16-point I/O
Do-more H2 and T1H series CPUs. 9-pin modules and PLC built-in
D-shell female connector to an RJ12 6P6C I/O. Sold in packs of 2.
connector.
C2-6TB $16.50
Spare 6-pt Terminal Block
Replacement terminal
Note: If your PC has a USB port but does not have a serial port, block for the C2-DCM
you must use programming cable EA-MG-PGM-CBL to connect serial ports.
to CLICK PLCs. For CLICK PLUS PLCs, you may also use Sold in packs of 2.
USB-CBL-AMICB6
Accessories
SE-ANT250 $37.00 C2-FILL $8.50 MSD-SLC16G $100.00
Wi-Fi/Bluetooth Dome Antenna CPU Option Slot Cover 16GB microSD card, industrial grade,
3D NAND Flash (with SLC Mode),
2.4 GHz antenna, IP67, panel mount, Snap-on cover
85°C [185°F] max operating temp.
9.8 ft (3m) cable length, for external for CLICK PLUS
mounting when CLICK PLUS PLC is CPU Option Slot
installed in a metallic enclosure. in applications
without an
Option Slot
module present.