Module 1
Module 1
Module 1
Introduction
The transformer is a device that transfers electrical energy from one electrical circuit to another electrical circuit.
The two circuits may be operating at different voltage levels but always work at the same frequency. Basically,
the transformer is an electromagnetic energy conversion device, that is commonly used in electrical power
systems and distribution systems. It can change the magnitude of alternating voltage or current from one value
to another. This useful property of transformer is mainly responsible for the widespread use of alternating
currents rather than direct currents i.e., electric power is generated, transmitted, and distributed in the form of
alternating current. Transformers have no moving parts, rugged and durable in construction, thus requiring very
little attention. They also have a very high efficiency as high as 99%.
Necessity of transformers:
➢ For the power grid, transformers are essential for power transmission over long distances. Without them,
our power grid simply would not be able to scale up to meet growing demand. This is because long lines
enable power generation to be located at its energy or cooling source (a hydroelectric dam or nuclear
facility, say). The generated power can then be efficiently sent to where it's needed (major population
centres).
➢ Here's how it works. High-current low voltage AC power at the generator is stepped up with
transformers into high voltage /low current - 220 kilovolts or more at 100A or so - then sent down the
high-tension lines.
➢ The lower current is key: it allows practical wire sizes to be used in the overhead lines, and it reduces
wire losses (sometimes called I2R or voltage drop loss) and allows more of the generated power to make
it to the load and for lower cost.
➢ But 220kV voltage isn't practical to use in the home. So transformers are used to step the voltage back
down to manageable levels. This is done in two stages:
➢ Receiving substations use transformers to step down the voltage to 13kV – 430 V or so for local
distribution on utility poles or underground.
➢ Buildings take their feeds from still another set of transformers that take the utility voltage down to 430
to 220V. These transformers are the familiar canister-shaped devices mounted on the power poles.
➢ In electronics, small transformers perform a variety of duties: mixing, coupling. impedance matching,
isolation, and power supply. These jobs aren't quite as dramatic as those done by the large power grid
transformers but they're no less essential for dealing with AC in these systems.
Principle of operation:
1
BEE304 Module-1_ Single Phase Transformer
The working principle of the transformer is It depends upon Faraday's law of electromagnetic induction. Mutual
induction between two or more winding is responsible for transformation action in an electrical transformer.
The basic concept of the transformer: Whenever we apply alternating current to an electric coil, there will be
an alternating flux surrounding that coil. If we bring another coil near the first one, there will be an alternating
flux linkage with that second coil. As the flux is alternating, there will be a rate of change in flux linkage with
respect to time in the second coil. As per Faraday's law of electromagnetic induction an e.m.f will be induced
in it.
The winding which takes electrical power from the source, is known as primary winding of transformer. The
winding which the winding which gives the desired output voltage due to mutual induction in the transformer,
is known as secondary winding of transformer.
In open air very tiny portion of the flux of the first winding will link with second coil. The current that flows
through the closed circuit of second coil, will be so small in amount that it will be difficult to measure. The rate
of change of flux linkage depends upon the amount of linked flux with the second winding. We desire almost
all flux of primary winding to link with the secondary winding. This is effectively and efficiently done by
placing one low reluctance path common to both winding. This low reluctance path is core of transformer,
through which maximum number of fluxes produced by the primary is passed through and linked with the
secondary winding.
FIGURE
2
BEE304 Module-1_ Single Phase Transformer
Transformers can be classified on different basis, like types of construction, types of cooling etc.
3
BEE304 Module-1_ Single Phase Transformer
4
BEE304 Module-1_ Single Phase Transformer
N1 = primary turns
N2 = secondary turns
5
BEE304 Module-1_ Single Phase Transformer
Øm= maximum value of the flux in the core linking both the windings
= BmA
Where maximum flux density in the core (Wb/ m 2)
A = area of cross-section of the core (m2)
f = frequency of AC input in hertz (Hz)
The induced emf in the primary winding of N1 turns is
ⅆ𝜙
𝑒1 = −𝑁1 …….(1)
ⅆ𝑡
As the primary applied voltage is sinusoidal in nature, the current it drives and the resulting flux produced are
also sinusoidal. The equation for the flux is given by,
𝜙 = 𝜙𝑚 sin 𝜔𝑡……(2) 𝜋
𝑐𝑜𝑠 𝜃 = 𝑠𝑖𝑛 ( − 𝜃)
2
Substituting this value of flux Ø in equation (1), we get
− 𝑐𝑜𝑠 𝜔𝑡 = 𝑠𝑖𝑛(𝜔𝑡 − 𝜋⁄2)
ⅆ(𝜙𝑚 sin 𝜔𝑡)
𝑒1 = −𝑁1
ⅆ𝑡
= -N1Øm 𝜔 𝑐𝑜𝑠 𝜔𝑡
From equation (2) & (3), we find that induced emf lags the flux by 90 0
The magnitude of the maximum value of the emf induced in the primary winding is given by,
𝑒1 =2𝜋𝑓 N1Øm
The rms value of the emf induced in the primary winding is given by,
𝑒1 2𝜋𝑓𝑁1 𝜙𝑚
𝐸1 = =
√2 √2
𝐸1 =4.44𝑓 N1Øm
Similarly the rs value of the emf induced in the secondary winding is given by
𝐸2 =4.44𝑓 N2Øm
Transformation ratio
The ratio of secondary voltage to the primary voltage is called the transformation ratio or turns ratio, K.
6
BEE304 Module-1_ Single Phase Transformer
Losses in Transformer: In transformer, 'loss' can be defined as the difference between input power and
output power. An electrical transformer is an static device, hence mechanical losses (like windage or friction
losses) are absent in it. The losses in a transformer are: iron losses and copper losses.
Iron loss or Core Loss (Pi): This is the power loss that occurs in the iron part. This loss is due to the
alternating frequency of the emf. Iron loss in further classified into two other losses.
7
BEE304 Module-1_ Single Phase Transformer
8
BEE304 Module-1_ Single Phase Transformer
Stray loss: The eddy currents, produced in the transformer by leakage flux, produce losses known as stray
losses. You may be familiar with the hum or buzzing noise near your machines. It is due to the stray fields
that cause the components of the tank to vibrate. This type of loss can be reduced by using thin sheets of
insulated iron.
Dielectric loss: Dielectric loss can be observed in the insulating materials of the transformer. If the oil gets
deteriorated or the solid insulation gets damaged it decreases the quality of the system. It also affects the
overall efficiency of the transformer. An effective way to reduce dielectric loss is to test the oil regularly and
also maintain the insulation quality.
• Eddy current losses within a transformer core can not be eliminated completely, but they can be
greatly reduced and controlled by reducing the thickness of the steel core.
• Instead of having one big solid iron core as the magnetic core material of the transformer or coil, the
magnetic path is split up into many thin pressed steel shapes called "laminations".
• The losses of energy, which appear as heat due both to hysteresis and to eddy currents in the magnetic
path, is known commonly as "transformer core losses".
Method to decrease Copper losses:
• Transformers with high voltage and current ratings require conductors of large cross-sections to help
minimize their copper losses.
• Increasing the rate of heat dissipation (better cooling) by forced air or oil, or by improving the
transformers insulation so that it will withstand higher temperatures can also increase a transformers
VA rating.
Efficiency of Transformer:
Due to the losses in a transformer, the output power of a transformer is less than the input power supplied
= Power output + 𝑊𝑖 + 𝑊𝑐
The efficiency of any device is defined as the ratio of power output to power input. So for a transformer the
efficiency can be expressed as
The transformer supplies full load of current 𝐼2 and with terminal voltage 𝑉2
Let us determine,
10
BEE304 Module-1_ Single Phase Transformer
Ideal Transformer
To understand the working of a transformer it is always instructive, to begin with the concept of an ideal
transformer with the following properties.
11
BEE304 Module-1_ Single Phase Transformer
This is core loss component which is in phase with V1. The magnitude of the no load current is given by
It may be noted that the current I0 is very small, about 3 to 5 % of the full load rated current. Hence the primary
copper loss is negligibly small hence I c is called core loss or iron loss component. Hence power input Wo on
no load always represents the iron losses, as copper loss is negligibly small. The iron losses are denoted as P i
and are constant for all load conditions.
12
BEE304 Module-1_ Single Phase Transformer
When the transformer is loaded, the current I2 flows through the secondary winding. The magnitude and phase
of I2 is determined by the load. If load is inductive, I 2 lags V2 If load is capacitive, I2 leads V2 while for resistive
load, I2 is in phase with V2.
There exists a secondary m.m.f. N2 I2 due to which secondary current sets up its own flux Ø2. This flux opposes
the main flux Ø which is produced in the core due to magnetising component of no-load current. Hence the
m.m.f. N2 I2 is called demagnetising ampere-turns.
The flux Ø2 momentarily reduces the main flux Ø, due to which the primary induced emf E1 also reduces. Hence
the vector difference 𝑉̅1 − ̅̅̅
𝐸1 increases due to which primary draws more current from the supply. This
additional current drawn by primary is due to the load hence called load component of primary current denoted
as I2’
This current I2’ is in antiphase with I2. The current I2’ sets up its own flux Ø2’ which opposes the flux Ø2, and
helps the main flux Ø. This fiux Ø2’ neutralises the flux Ø2 produced by I2. The m.m.f. ie. ampere turns N1 I2’
balances the ampere turns N2 I2. Hence the net flux in the core is again maintained at constant level.
The load component current I2’ always neutralises the changes in the load. As practically flux in core is constant,
the core loss is also constant for all the loads. Hence the transformer is called constant flux machine.As the
ampere turns are balanced we can write,
N2 I2 = N1 I2’
𝑵𝟐
𝑰𝟏𝟐 = 𝑰 = 𝑲𝑰𝟐
𝒏′ 𝟐
Thus when transformer is loaded, the primary current I1 has two components:
1. The no load current I0 which lags V1 by angle Ø0. It has two components Im and Ic
2. The load component I2’ which is in antiphase with I2. And phase of I2 is decided by the load.
13
BEE304 Module-1_ Single Phase Transformer
When the load is connected to the transformer then secondary current I 2 flows. This causes voltage drop
across R2 and X2. Due to I2, primary draws an additional current I2’= I2 / K. Now I1 is the phasor addition of
Io and I2’. This I1 causes the voltage drop across primary resistance R1 and reactance X1.
But in the equivalent circuit, windings are not shown and it is further simplified by transferring all the values
to the primary or secondary.
14
BEE304 Module-1_ Single Phase Transformer
𝑅 𝑋 𝑍
𝑅2′ = 𝐾22 𝑋2′ = 𝐾22 𝑍2′ = 𝐾22
𝐸 𝑁
While 𝐸2′ = 𝐾 2 𝐼2′ = 𝐾𝐼2 where 𝐾 = 𝑁2
1
15
BEE304 Module-1_ Single Phase Transformer
The total equivalent circuit of the transformer is obtained by adding in the primary impedance as
shown in –Fig.
And It can be simplified the terminals shown in above fig & further simplify the equivalent circuit is
shown in fig.
The phasor diagram for the transformer on load depends on the nature of the load power factor.
17
BEE304 Module-1_ Single Phase Transformer
As load power factor is lagging cos Ø2, the current I2 lags V2 by angle Ø2 . So only change in drawing the
phasor diagram is to draw I2 lagging V2 by Ø2 in step 5 discussed earlier. Accordingly directions of I2 R2,
I2 X2, I2’, I1, I1 R1 and I1 X1, will change. Remember that whatever may be the power factor of load, I2 X2
leads I2 by 90° and I1 X1, leads I1 by 900.
19
BEE304 Module-1_ Single Phase Transformer
Voltage Regulation:
Because of the voltage drop across the primary and secondary impedances it is observed that the secondary
terminal voltage drops from its no load value (E2) to load value (V2) as load and load current increases. This
decrease in the secondary terminal voltage expressed as a fraction of the no load secondary terminal voltage is
called regulation of a transformer.
20
BEE304 Module-1_ Single Phase Transformer
The secondary terminal voltage does not depend only on the magnitude of the load current but also on the
nature of the power factor of the load. If V2 is determined for full load and specified power factor condition
the regulation is called full load regulation.
As load current IL increases, the voltage drops tend to increase and V2 drops more and more. In case of
lagging power factor V2 < E2 and we get positive voltage regulation, while for leading power factor E 2 < V2
and we get negative voltage regulation.
21
BEE304 Module-1_ Single Phase Transformer
Under no load conditions the PF is very low (near to 0) in lagging region. By using the above data we can
draw the equivalent parameter shown in Figure
Thus open-circuit test enables us to determine iron losses and parameters R 0 and X0 of the transformer.
22
BEE304 Module-1_ Single Phase Transformer
voltage is applied to the primary as shown in Fig. The low input voltage is gradually raised till at voltage V SC,
full-load current I1 flows in the primary. Then I2 in the secondary also has full-load value since I1/I2 = N2/N1.
Under such conditions, the copper loss in the windings is the same as that on full load. There is no output from
the transformer under short-circuit conditions. Therefore, input power is all loss and this loss is almost entirely
copper loss. It is because iron loss in the core is negligibly small since the voltage VSC is very small. Hence, the
wattmeter will practically register the full load copper losses in the transformer windings.
23
BEE304 Module-1_ Single Phase Transformer
24
BEE304 Module-1_ Single Phase Transformer
Current flows from high voltage point to low voltage point due to the potential difference between them.
Here, electrical polarity comes into the picture. Electrical polarity simply describes the direction of the current
flow. When we look into DC system, we find that one pole is always positive and the other one is always
negative that imply that the current flows in one direction only. But when we look into an AC system, the
terminals are changing their polarity periodically, and the direction of the current also changes accordingly.
We use dot convention to identify the voltage polarity of the mutual inductance of two windings. The two
used conventions are:
1. If a current enters the dotted terminal of one winding, then the voltage induced on the other winding
will be positive at the dotted terminal of the second winding.
2. If a current leaves the dotted terminal of one winding, then the polarity of the voltage induced in the
other winding will be negative at the dotted terminal of the second winding.
When we look into the operations of the distribution transformers, we find that they need to work all the time
and also need to supply at high demand at peak times. So, to cope up with these situations, we connect the
transformers in parallel.
Paralleling is done by connecting same polarity terminals of the primary winding together. A similar
procedure is done for the secondary winding. Paralleling will increase the power supplying capacity and also
the reliability of the system. We do polarity test on parallel transformers to ensure that we connect the same
polarity windings and not the opposite ones. If we accidentally connect the opposite polarities of the
windings, it will result in a short circuit and eventually damage the machine.
1. Additive Polarity
2. Subtractive Polarity
Additive Polarity: In additive polarity, the voltage (Vc) between the primary side (Va) and the secondary side
(Vb) will be the sum of both high voltage and the low voltage, i.e. we will get V c = Va + Vb
Subtractive Polarity:
In subtractive polarity, the voltage (Vc) between the primary side (Va) and the secondary side (Vb) will be the
difference of both high voltage and the low voltage, i.e. we will get V c = Va – Vb In subtractive polarity, if
Vc = Va – Vb, it is a step-down transformer and if Vc = Vb – Va, it is a step-up transformer.
25
BEE304 Module-1_ Single Phase Transformer
We use additive polarity for small-scale distribution transformers and subtractive polarity for large-scale
transformers.
Connect the circuit as shown above with a voltmeter (Va) across primary winding and another
voltmeter (Vb) across the secondary winding.
2. If available, take down the ratings of the transformer and the turn ratio.
3. We connect a voltmeter (Vc) between primary and secondary windings.
4. We apply some voltage to the primary side.
5. By checking the value in the voltmeter (Vc), we can find whether it is additive or subtractive
polarity.
If additive polarity – Vc should be showing the sum of Va and Vb.
If subtractive polarity – Vc should be showing the difference between Va and Vb.
Caution: Be careful that the max. measuring the voltage of voltmeter Vc should be greater than the sum of Va
(Primary winding) and Vb (Secondary winding) otherwise during the additive polarity, the sum of Va and Vb
comes across it.
Note: If we require additive polarity, but we have subtractive polarity, we can simply change it by keeping
any of the primary or secondary windings in the same fashion and reversing the winding connection of the
other one. Similarly, if we require subtractive polarity but have additive polarity, we could do the same
procedure as above.1
Sumpner’s test:
Sumpner's test or back to back test on transformer is another method for determining transformer
efficiency, voltage regulation and heating under loaded conditions. Short circuit and open circuit tests on
transformer can give us parameters of equivalent circuit of transformer, but they can not help us in finding the
heating information. Unlike O.C. and S.C. tests, actual loading is simulated in Sumpner's test. Thus the
Sumpner's test give more accurate results of regulation and efficiency than O.C. and S.C. tests.
Sumpner's test or back to back test can be employed only when two identical transformers are available. Both
transformers are connected to supply such that one transformer is loaded on another. Primaries of the two
identical transformers are connected in parallel across a supply. Secondaries are connected in series such that
emf's of them are opposite to each other. Another low voltage supply is connected in series with secondaries
to get the readings, as shown in the circuit diagram shown below.
26
BEE304 Module-1_ Single Phase Transformer
In above diagram, T1 and T2 are identical transformers. Secondaries of them are connected in voltage
opposition, i.e. EEF and EGH. Both the emf's cancel each other, as transformers are identical. In this case, as
per superposition theorem, no current flows through secondary. And thus the no load test is simulated. The
current drawn from V1 is 2I0, where I0 is equal to no load current of each transformer. Thus input power
measured by wattmeter W1 is equal to iron losses of both transformers.
i.e. iron loss per transformer Pi = W1/2.
Now, a small voltage V2 is injected into secondary with the help of a low voltage transformer. The voltage V2
is adjusted so that, the rated current I2 flows through the secondary. In this case, both primaries and
secondaries carry rated current. Thus short circuit test is simulated and wattmeter W 2 shows total full load
copper losses of both transformers.
i.e. copper loss per transformer PCu = W2/2.
From above test results, the full load efficiency of each transformer can be given as –
27
Significance of voltage regulation of a transformer
Voltage regulation of a transformer is a critical aspect of its performance and
has significant implications for electrical systems. Here’s a detailed look at its
significance:
3. Protection of Equipment
Preventing Damage: Sensitive electrical equipment can be damaged
by voltage spikes or drops. Effective voltage regulation protects such
equipment by ensuring that they operate within their specified voltage
range.
Longevity of Components: Consistent voltage levels can extend the
lifespan of transformers and connected devices by preventing
overheating and other stress-related issues.
4. System Reliability
Increased Reliability: A transformer with good voltage regulation
contributes to the overall reliability of the electrical system. It helps in
maintaining the quality of power supplied to consumers.
Reduced Outages: By maintaining steady voltage levels, voltage
regulation can help minimize the risk of outages and system failures.
5. Compliance with Standards
Regulatory Compliance: Many electrical standards and regulations
require specific voltage levels. Good voltage regulation ensures
compliance with these standards, which is essential for utility
companies and industrial plants.
6. Economic Factors
Cost Savings: Improved voltage regulation can lead to lower
operational costs by reducing energy losses and minimizing the need
for additional equipment to correct voltage issues.
Better Load Management: With effective voltage regulation, utilities
can manage loads more effectively, enhancing the economic viability
of their operations.
Conclusion
In summary, the significance of voltage regulation in transformers encompasses
stability, efficiency, equipment protection, system reliability, compliance, and
economic benefits. It is a fundamental aspect of transformer design and
operation, impacting both the quality of power delivered and the overall
performance of electrical systems.