14 Bus System
14 Bus System
DIgSILENT PowerFactory *
This paper describes the 14 Bus System in Pow- The 14 Bus System consists of 14 buses (nodes), 5
erFactory. The parameters of the individual ele- generators, 11 loads, 16 lines, 5 transformers and one
ments like generators, loads, shunts, transform- shunt. 3 of these 5 transformers are used to repre-
ers and lines are explained. Results for the load sent one single 3-winding transformer. Figure 1 shows
flow calculation are presented. the single line diagram. It is a simplified model of the
transmission system in the Midwest United States.
Load_0013
Load_0014
Load_0012
Line_0006_0013
Load_0011
Load_0010
Shnt_0009
Load_0009
Gen_0001 Line_0010_0011
Load_0006
~
SG
Trf_0007_0009
Trf_0007_0008
Gen_0008
Gen_0006
Trf_0005_0006
Trf_0004_0009
SG
~
SG
~
Load_0005
Trf_0004_0007
Load_0004
Line_0003_0004
Load_0002
SG
~
Gen_0002
Voltage Levels
132 kV
33 kV
Load_0003
11 kV
SG
1 kV ~
Gen_0003
Data have been taken from [1] and have been com- For the PowerFactory model input data are required
pleted by assuming the following typical values as in Ω/km and 𝜇S/km (or 𝜇F/km) respectively. Line data
nominal voltages: have been recalculated for the network model with a
nominal voltage 𝑈n given in Table 4 using Equations
• Bus 1 - Bus 5: 132 kV (1) – (4).
• Bus 6, Bus 9 - Bus 14: 33 kV As there is no line length given in [1], the length of
• Bus 7: 1 kV each line in the PowerFactory model has been set to
1 km. Line data of the PowerFactory model are repre-
• Bus 8: 11 kV sented in Table 4. The rated current of each line is not
known and therefore assumed to be 1 kA.
The nominal frequency of the 14 Bus System is 60 Hz.
In [1] the network parameters are given in per unit The line between bus 1 and bus 2 is a double circuit,
values based on 100 MVA. Loads and generation are and has therefore been modelled as two parallel lines
given in MW and Mvar. with adapted parameters in the PowerFactory model.
2.4 Transformers
2.2 Generators
Transformer data are given in per unit (p.u.) as rep-
Generator “Gen_0001” is the slack generator, there- resented in Table 6 based on the base power 𝑆b =
fore voltage magnitude and voltage angle are given 100 MVA [1]. The rated power of each transformer is
(1.060 p.u., 0.0 degrees). The other generators are assumed as 𝑆r = 100 MVA.
configured to control the active power injection and
voltage magnitudes at the connected buses. There- Transformer parameters of the PowerFactory model
fore the active power dispatch and controlled voltage are given in Table 6. In addition tap changers are mod-
magnitudes at their terminals are given. The data elled in order to achieve the transformer taps as given
have been taken from [1] and are listed in Table 2 and in Table 6.
3. The machines at the buses 3, 6 and 8 are syn-
chronous condensers. The three 2-winding transformers connected to Bus_-
0007 represent a 3-winding transformer [1]. The
3-winding transformer model of PowerFactory can
2.3 Transmission Lines be used instead of three 2-winding transformers.
This is done in the Study Case “02 - Load Flow
Case 3-Winding Trf”, which activates the Variation
Line data are given in per unit (p.u.) based on the “3-Winding Transformer”. The input parameters for
base power 𝑆b = 100 MVA as represented in Table 5, the impedances (short-circuit voltages 𝑢 ) of the 3-
k
without information about the line length [1]. The sus- winding transformer model have been calculated with
ceptance 𝑏 in p.u. is twice the given line charging 𝑞c/2 Equations (5), (6) and (6). Figure 2 shows the corre-
sponding simplified electrical circuit of the 3-winding
Rev.1 2
14 BUS SYSTEM
LV MV
References
Figure 2: Simplified electrical circuit of a 3-winding
transformer (positive sequence)
[1] A. S. L.L. Freris, Investigation of the load-flow
problem, 10th ed. PROC. IEE, 1968.
Rev.1 3
14 BUS SYSTEM
DIgSILENT
1,12
1,09
1,06
1,03
1,00
0,97
01
02
03
04
05
06
07
08
09
10
11
12
13
14
00
00
00
00
00
00
00
00
00
00
00
00
00
00
s_
s_
s_
s_
s_
s_
s_
s_
s_
s_
s_
s_
s_
s_
Bu
Bu
Bu
Bu
Bu
Bu
Bu
Bu
Bu
Bu
Bu
Bu
Bu
Bu
Voltage, Magnitude in p.u.
DIgSILENT
250,00
200,00
150,00
100,00
50,00
0,00
1
8
00
00
00
00
00
_0
_0
_0
_0
_0
n
n
Ge
Ge
Ge
Ge
Ge
Active Power in MW
80,00
60,00
40,00
20,00
0,0000
-20,00
1
8
00
00
00
00
00
_0
_0
_0
_0
_0
n
n
Ge
Ge
Ge
Ge
Ge
Rev.1 4
14 BUS SYSTEM
Minimum Maximum
Generator Bus Type Voltage in p.u.
capability in MVA capability in MVA
Gen_0001 Slack 1.060 N.A. N.A.
Gen_0002 PV 1.045 -40.0 50.0
Gen_0003 PV 1.010 0.0 40.0
Gen_0006 PV 1.070 -6.0 24.0
Gen_0008 PV 1.090 -6.0 24.0
Rev.1 5
14 BUS SYSTEM
Table 6: Data of transformers given in [1] based on 100 MVA, with rated voltages added in the PowerFactory
model
Rev.1 6
14 BUS SYSTEM
Rev.1 7
14 BUS SYSTEM