HVAC System Control
HVAC System Control
Data 2019
HVAC System Control
period one
Fundamentals of Automatic Control
Terminology
controlled
variable
airflow
sensor
controller
controlled
device
controlled
agent
Open Loop
outdoor-air
sensor
airflow
controller
chilled
water
valve
Closed Loop
discharge-air
temperature sensor
airflow
controller
valve
chilled
water
Control Reset
discharge-air
outdoor-air
temperature sensor
sensor
airflow
controller
valve
chilled
water
Control "Points"
• Two-position (on/off)
• Floating
• Proportional
• Proportional–Integral (PI)
• Proportional–Integral–Derivative (PID)
controlled-variable controller output
Two-Position (On/Off)
100%
0%
A on
+ 5°F
deviation
time
controlled-variable controller output
Floating
100%
0%
switch differential
A B open
+ 5°F
deviation
stop
0°F setpoint differential
D stop
- 5°F
C close
time
controlled-variable controller output
Proportional
100%
0%
+ 5°F
deviation
A offset
throttling
0°F setpoint
range
- 5°F
time
controlled-variable controller output
deviation
+ 5°F
0°F
100%
- 5°F
0%
setpoint
time
B
Integral
controlled-variable controller output
Proportional–Integral (PI)
PI
100%
integral proportional
0%
+ 5°F
deviation
0°F setpoint
- 5°F
time
controlled-variable controller output
deviation
+ 5°F
0°F
100%
- 5°F
0%
A
B
setpoint
C
time
Derivative
Proportional–Integral–Derivative
(PID)
controlled-variable controller output
PID
100%
PI
derivative
0%
+ 5°F
deviation
0°F setpoint
- 5°F
time
Comparison of Control Actions
controlled-variable deviation
offset
PID
setpoint
PI overshoot
time
Controller Technologies
• Pneumatic
• Analog-electric
• Microprocessor-based
Pneumatic Control System
pressure-
reducing valve
main line
compressor
air branch line
air
drier filter
controller
storage
tank controlled
device
drain
Pneumatic Controller
bimetal
element
nozzle flapper
set
screw
actuator
chamber
branch line
valve
stem
diaphragm
spring
plug
valve
seat
Analog-Electric Controller
Electronic Controlled Device
actuator
valve
stem
plug
valve
seat
Microprocessor-Based Controller
DDC Controlled Device
Comparison of Technologies
Pneumatic Microprocessor-
• No communication based
capabilities • Allows system-wide
• Expensive and communication
complicated to provide • Fewer hardware
complex control components
strategies
• Easily accommodates
• Inherently proportional complex control
• Extensive maintenance strategies
requirements • Provides many types of
control action
• Fewer maintenance
requirements
HVAC System Control
period two
Automatic Control of HVAC Systems
building
management
system-level
control
unit-level control
Benefits of Unit-Level Control
• Stand-alone control
• Safeties, alarms, and diagnostics
• Installed, tested, and commissioned in
factory
unit-level control
Unit-Level Control
VAV air handler
Discharge-Temperature Control
Loop
discharge-air
temperature sensor
valve
controller
VAV air handler
Ventilation Control Loop
return-air damper
outdoor-air
damper
controller
VAV air handler
Economizer Control Loop
outdoor-air
temperature sensor controller
VAV air handler
Mixed-Air-Temperature Control
Loop
controller
VAV air handler
Static-Pressure Control Loop
duct static-
supply fan pressure sensor
controller
VAV air handler
Building-Pressure Control Loop
relief fan
indoor-
pressure
sensor
outdoor-
pressure
sensor
controller
VAV air handler
Pneumatic Controls
unit-
level
controlle
r
air-cooled
water chiller
System-Level Control
system-level
control
unit-level control
Chilled-Water VAV System
VAV air
handler
exhaust fan
water-cooled pumps
chiller
system-level
controller
boiler
System-Level Operating Modes
system-level
controller
Morning Warm-Up
system system
on off
occupie
d
setpoint zone
occupied hours temperatur
unoccupie e
d
setpoint
6 AM Noon 6 PM
Air-Cooled Chiller, Fan-Coil
System
dedicated
outdoor-air unit
fan-coil
units
air-cooled
system-level chiller
controller
pumps
boiler
Two-Pipe Changeover
Requirements
140°F
(60°C)
supply-water temperature
deadband
120°F
(49°C) 15°F
hot water (8°C)
80°F
(27°C)
30°F
(17°C)
40°F
(4°C) chilled water
0°F 20°F 40°F 60°F 80°F
(-18°C) (-7°C) (4°C) (16°C) (27°C)
outdoor dry-bulb
Water-Source Heat-Pump
System
exhaust fan
cooling
tower
dedicated
outdoor-air unit
pumps
water-source
boiler heat pumps
system-level controller
Loop Temperature Control
cooling tower
off
pumps on
boiler off
heat pumps in
heat pumps in heating mode
cooling mode
System Optimization
system-level
control
unit-level control
VAV system
Fan-Pressure Optimization
damper
static- position
pressure s
supply
fan sensor
fan speed or
inlet-vane
position
VAV
system-level terminal units
controller
rooftop VAV system
Optimum Start
time clock
optimum
occupie start
d
setpoint zone
temperatur
occupied hours e
unoccupie
d
setpoint
6 AM Noon 6 PM
air-cooled chiller, fan-coil system
Chilled-Water Reset
air-cooled
chiller leaving-water
temperature
47°F
(8.3°C)
constant-
volume coil
pump54°F
(12.2°C)
valve
position system-level
controller
water-source heat-pump system
Optimized Loop Control
100
combined energy use, kW
90 coolin
g
80 tower
70 heat
pump
60 s
50
90°F optimized
(32°C) control
loop water-temperature setpoint
failure recovery
Sequences of Operation
chiller-plant
controller
failure recovery
Stand-Alone Operation
heat pump with
unit-level controller
system-level
controller
thermostat
failure recovery
Selection of Controlled Devices
• Normally-closed actuator
• Normally-open actuator
• Position-maintained actuator
HVAC System Control
period three
Building Automation Systems
building
management
system-level
control
unit-level control
Responding to Comfort
Complaints
Graphical User Interface
Time-of-Day Scheduling
Centralized Alarms and
Diagnostics
Remote Access
• Alarm notification
• Dial-in access
Reports
• Trend logs
• Alarm activity
• Building energy
use
• After-hours
tenant
occupancy
• Equipment
diagnostics and
performance
Preventive Maintenance
Integration with Other Systems
return-
air
damper
smoke-
control
dampers
• Centralized
monitoring
• Diagnose or
predict problems
with systems
• Combine energy
usage for
negotiating
energy contracts
HVAC System Control
period four
Interoperability
node node
node server
node
Dedicated Versus Shared
Networks
• Dedicated network
– Easier to design and install
– More expensive
• Shared network
– Less expensive (shares infrastructure)
– More difficult to ensure security
LAN Versus WAN
building A building B
router router
Intranet Versus Internet
building A building B
router router
firewall
Internet
"Tiered" BAS Architecture
PC workstation
LAN for
system controllers
HVAC
system lighting
controller LAN for system
unit controller
controllers fire- security
protection system
system controlle
controller r
• Proprietary
– Used, produced, or marketed under exclusive
legal right of an individual or organization
• Open
– Available to public domain and is shared among
vendors
• Standard
– Open protocol that has been formalized by a
governing body
Gateways
PC workstation
proprietary protocol
LAN
gateways
lightin
HVAC fire
proprietary g
protocol LAN protectio securit
gateways n y
System-Level Interoperability
PC workstation
open, standard protocol
LAN
lightin
HVAC fire
proprietary g
protocol LAN protectio securit
gateways n y
Unit-Level Interoperability
PC workstation
proprietary protocol
LAN
gateways
lightin
HVAC fire
open, standard g
protocol LAN protectio securit
n y
Interchangeability
• Plug-and-play
• Standard object
types Binary input
Binary output
– Analog input
– Analog output Binary value
– Analog value Loop
– Multi-state input Command
– Multi-state output File
– Device Calendar
– Event enrollment Schedule
– Notification class Program
– Trend
– Group
LonTalk
PC workstation
BACnet protocol
lightin
HVAC fire
g
LonTalk protocol protectio securit
n y
"Flat" BAS Architecture
PC workstation
controlled
variable
airflow
sensor
controller
controlled
device
controlled
agent
Review—Period Two
building
management
system-level
control
unit-level control
Review—Period Three
• Building
automation system
functions
– Respond to
comfort
complaints
– Centralize
scheduling
– Receive alarms
and diagnostics
– Provide remote
access
Review—Period Four
PC workstation
LAN for
system controllers
lightin
HVAC LAN for fire
unit
g
controllers protectio securit
n y
Notas finais