Electromagnetic Flowmeter

The Electromagnetic Flowmeter Type 8045 is designed for measuring flow rates in conductive liquids within pipes of diameter DN06 to DN400, featuring solid-state technology and a backlit display. It supports various outputs, including 4...20 mA current output and digital outputs, and is suitable for high-pressure and high-temperature applications with options for aggressive fluids. The device is compliant with FDA and KTW standards, making it suitable for food processing and wastewater treatment applications.

Uploaded by

Dhp Cia
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
26 views7 pages

Electromagnetic Flowmeter

The Electromagnetic Flowmeter Type 8045 is designed for measuring flow rates in conductive liquids within pipes of diameter DN06 to DN400, featuring solid-state technology and a backlit display. It supports various outputs, including 4...20 mA current output and digital outputs, and is suitable for high-pressure and high-temperature applications with options for aggressive fluids. The device is compliant with FDA and KTW standards, making it suitable for food processing and wastewater treatment applications.

Uploaded by

Dhp Cia
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 7

8045

Electromagnetic Flowmeter

• Sensor in solid state technology


• Shows both flow rate and volume
• Simulation of all output signals
• Clean in place (CIP), FDA or KTW approved
• Version with Alloy C22 electrodes
Type 8045 can be combined with...

Type S020 Type S020 Type 2030 Type 8802-GD Type 8644 PLC
INSERTION Spigot Diaphragm valve TopControl System Valve islands with
T-fitting electronic I/O

The electromagnetic flowmeter Type 8045 is Technical data


designed for pipes with diameter sizes ranging
from DN06 to DN400 and is intended exclu- General data
sively to measure flow rate in liquids having a Compatibility with fittings S020 (see corresponding data sheet)
conductivity > 20 µS/cm. Materials
Housing, cover, nut / seal
The flowmeter has a backlit display, a keyboard PVDF sensor version PC (glass fibre reinforced for housing) / NBR
Stainless steel sensor version Black PPA (glass fibre reinforced) / NBR
and is equipped with a 4... 20 mA current out-
Front panel foil Polyester
put, a digital output (pulse output by default)
Protection lid / seal
and two totalizers. Some versions are equipped PVDF sensor version PC / silicone
with two relay outputs and one digital input. Stainless steel sensor version PSU / silicone
Screws / Cable glands / Seal Stainless steel / PA / Neoprene
The version with a stainless steel sensor has Wetted parts materials
been designed for applications with high Sensor holder PVDF or Stainless steel 1.4404/316L
pressures (PN16) and high temperatures (up to Electrodes Stainless steel 1.4404/316L or Alloy C22
110°C). Seal FKM (FDA agreements) [EPDM (KTW agreements)]
Earth ring (PVDF sensor version) Stainless steel 1.4404/316L or Alloy C22
Electrode holder (St. St. sensor version) PEEK (FDA agreements)
The version with Alloy C22 electrodes has
Electrical connections 2 cable glands M20 x 1.5
been designed for applications with aggressive
fluids (chemicals) and especially sea water ap- Recommended cable 0.5 to 1.5 mm2 cross-section, shielded cable,
6... 12 mm diameter (if only one cable is used per cable gland) or
plications.
4 mm diameter (if two cables are used per cable gland with using the
supplied multi-way seal)

Environment
Ambient temperature -10 to +60°C (14 to 140°F) (operating)
-20 to +60°C (-4 to 140°F) (storage)
Relative humidity < 85%, without condensation
Height above sea level max. 2000 m

www.burkert.com p. 1/7
8045

Complete device data (Fitting S020 + flowmeter)


Pipe diameter DN06 to DN400
Measuring range 0.2 to 10 m/s
Sensor element Electrodes
Medium temperature see Pressure/Temperature diagram
PVDF sensor version 0 to 80°C (32 to 176°F) (depends on fitting)
Stainless steel sensor version -15 to 110°C (5 to 230°F) (depends on fitting)
Medium pressure max. see Pressure/Temperature diagram
PVDF sensor version PN10 (145.1 PSI)
Stainless steel sensor version PN10 (145.1 PSI) (with plastic fitting) - PN16 (232.16 PSI) (with metal fitting)
Conductivity min. 20 S/cm
Measurement error (for measured value from 1 to 10 m/s)
Teach-In ±0.5% of Reading1)
Standard K-factor ±4% of Reading1)
Linearity ±0.5% of F.S.*1)
Repeatability ±0.25% of Reading1)

Electrical data
Operating voltage 18 - 36 V DC filtered and regulated (3 wires)
oscillation rate: ±0.5%
Reversed polarity of DC protected
Current consumption  300 mA
Digital input DI1 Supply voltage: 18 - 36 V DC, input impedance 15 k
min. pulse duration: 200 ms
Galvanic insulation, protected against polarity reversals
of DC and voltage spikes
Digital outputs
Transistor (DO1) Type: NPN or PNP (wiring dependent), open collector
Function: pulse output (by default), user configurable
0 - 250 Hz, 5 - 36 V DC, 100 mA max.,
duty cycle if frequency > 2 Hz: 1/2; min. pulse duration if
frequency < 2 Hz: 250 ms
Galvanic insulation, protected against polarity reversals
of DC and short-circuits
Relay (DO2 and DO3) 2 normally open relays, freely adjustable (hysteresis by de-
fault), 250 V AC/3 A or 30 V DC/3 A (resistive load), max.
cutting power of 750 VA (resistive load); life span of min.
100000 cycles
Analogue output
Current (AO1) 4... 20 mA, sink or source (wiring dependent), 22 mA to
indicate a fault
max. loop impedance: 1300  at 36 V DC, 1000  at
30 V DC, 700  at 24 V DC, 450  at 18 V DC

Standards, directives and approvals


Protection class IP65, device wired and cable glands tightened and lid * For the 97/23/CE pressure directive, the device can
screwed tight only be used under following conditions (depend on max.
pressure, pipe diameter and fluid).
Standards and directives
EMC EN 61000-6-2, EN 61000-6-3 Type of fluid Conditions
Low voltage EN 61010-1 Fluid group 1, §1.3.a Forbidden
Pressure Complying with article 3 of §3 from 97/23/CE directive.* Fluid group 2, §1.3.a DN 32, or
Vibration EN 60068-2-6 DN > 32 and PN*DN 1000
Shock EN 60068-2-27 Fluid group 1, §1.3.b PN*DN 2000
Approvals FDA (only for device with FKM seal and PEEK electrode holder) Fluid group 2, §1.3.b DN 200 or
KTW (only for device with EPDM seal and PVDF sensor holder) DN 10 or
CSA-Approved for US and Canada (on request) PN*DN 5000
1)
Under reference conditions i.e. measuring fluid=water, ambient and water temperature = 20°C (68°F), applying the
minimum inlet and outlet pipe straights, matched inside pipe dimensions.

* F.S.= of Full scale (10 m/s)

p. 2/7
8045

Pressure/Temperature diagram
Please be aware of the fluid pressure/temperature dependence according to the respective fitting + flowmeter material as shown in the diagrams.

8045 with a PVDF sensor 8045 with a stainless steel sensor


(depending on the fitting material) (depending on the fitting material)

Pressure Pressure
(Bar) A (Bar) A
16
PVDF (PN10) / Metal
10 15
Metal (PN16)
9 14
13
8 PVC + PP 12
7 11
10
6
PVC (PN10) 9
5 PVDF
8
7 PVC + PP PVDF (PN10)
4
6
3
PP (PN10) 5
2 4
3 PVC (PN10)
1
2
0 Temperature 1 PP (PN10)
+10 +30 +50 +70 (°C) Temperature
0
-10 +10 +30 +50 +70 +90 +110 (°C)

A: Application range for complete device (fitting + flowmeter)

Sofware main features Possible applications

Choice of the display language Flow control of fluids, contaminated or not:


International measuring units
Waste water treatment
Teach-In for a better accuracy, or K-factor setting
4... 20 mA current output (AO1) Flow control of drinking water (FDA approval)

Transistor output (DO1)


Laundries: measurement and control of the water consumption
2 relays (DO2 and DO3 - if equipped)
Detection of flow direction possible Swimming pools: pump protection and flow control

ON/OFF digital input (DI1 - if equipped) Food-processing industry: monitoring of the cleaning cycles (FDA approval)
Filter function
Irrigation
Reset both totalizers (main and daily)
Low flow “Cut-Off” Application with sea water: desalination, fish farms
Brightness of the display
Password for parameter settings
Warning and fault messages generating
Simulation mode to adjust Zero and Span and simulate flow in dry-run
condition

Design

The magnetic system inside the sensor induces a magnetic field into the fluid, which is perpendicular to the direction of flow.
Two electrodes are in galvanic contact with the liquid. Based on the Faraday law a voltage can be measured between these
electrodes once a liquid (min. conductivity of 20 µS/cm) flows along the pipe.
This voltage is proportional to the flow velocity.
Using the K-factor for the individual pipe diameter the speed of flow is converted into volume per time.

p. 3/7
8045

Description of the navigation keys and the status LEDs

Large digital display with 8 characters


Scrolling up the parameters (4 digital characters and 4 alphanumeric characters)
within a level or a menu indicating:
increase the figure selected - the measured flow
- the value of the current output
- the value of the main totalizer
- the value of the daily totalizer

Selecting the displayed


Device status LED: parameters
see following table Validating the settings

Scrolling down the parameters


Status LED of relay DO3
within a level or a menu
(LED ON = contact closed)
Selecting the figure on the left
Reading the messages in the Status LED of relay DO2
information menu (LED ON = contact closed)

Device status LED Status of the device


Green The device operates correctly
Orange A warning messages is generated in the information menu.
Red A fault message is generated and a 22 mA current is sent on the current output.
Blinking, whatever the colour The DI1 digital input is active
or a check for the correct behaviour of the outputs is running
or a flow zero point calibration procedure is running
or the daily totalizer is kept at zero

Installation

The 8045 can easily be installed into any Bürkert INSERTION fitting system (S020) by just fixing the main nut.
Minimum straight upstream and downstream distances must be observed. According to the pipe’s design, necessary distances can be bigger or use a
flow conditioner to obtain the best accuracy. For more information, please refer to EN ISO 5167-1.

EN ISO 5167-1 prescribes the straight inlet and outlet distances that must be complied with when installing fittings in pipe lines in order to achieve
calm flow conditions. The most important layouts that could lead to turbulence in the flow are shown below, together with the associated prescribed
minimum inlet and outlet distances. These ensure calm, problem-free measurement conditions at the measurement point.

DN = pipe diameter Flow direction -->

Pipe diameter
Control valve 2 x 90° elbow joint
expansion
ÖXÖ$. ÖXÖ$. ÖXÖ$. ÖXÖ$. ÖXÖ$. ÖXÖ$.

2 x 90° elbow joint 90° elbow joint Pipe diameter


3 dimensional or T-piece reduction
ÖXÖ$. ÖXÖ$. ÖXÖ$. ÖXÖ$. ÖXÖ$. ÖXÖ$.

Ê

It is advisable to mount the flowmeter at a 45° angle to the horizontal centre of the pipe to avoid
having deposits on the electrodes and false measurements due to air bubbles
Ê

p. 4/7
8045

Installation (continued) Diagram Flow/Velocity/DN

The device can be installed into either horizontal or vertical pipes. Example:
Mount the 8045 in these correct ways to obtain an accurate flow
measurement. • Flow: 10 m3/h
• Ideal flow velocity: 2... 3 m/s

For these specifications, the diagram indicates a pipe size of DN40 [or DN50 for
Correct Incorrect (*) mentioned fittings]

Flow rate of fluid


53ÖGPM MH
LMIN

 
$.Ö
 $.Ö
 $.Ö
 
$.Ö
Incorrect  
 $.Ö
Correct
 $.Ö
 
$.Ö

 $.Ö
 
$.Ö
  $.Ö

$.ÖÖ$.

Incorrect  
$.ÖÖ$.

 $.ÖÖ$.

Correct $.ÖÖ$.
  $.ÖÖ$.


 $.ÖÖ$.Ö
  ORÖ$.


 $.Ö

 

$.Ö

 
Correct Incorrect




 

Pressure and temperature ratings must be in accordance to the

selected fitting material. The suitable pipe size is selected using  
the diagram Flow/Velocity/DN.


The flowmeter is not designed for gas flow measurement. 

 

       MS
       FPS
Flow velocity

* for following fittings with:


• external thread acc. to SMS 1145
• weld end acc. to SMS 3008, BS 4825/ASME BPE or DIN 11850 Series 2
• Clamp acc. to SMS 3017/ISO 2852, BS 4825/ASME BPE or DIN 32676

p. 5/7
8045

Dimensions [mm]










 


DN H
T-Fitting Saddle Plastic Metal
spigot spigot
06 182
08 182
Note: The length of the sensor finger depends on the fitting used. 15 187
See data sheet Type S020 or available fitting DN diagram on next page. 20 185
25 185
32 188
40 192 188
50 198 223 193
65 198 222 206 199
80 226 212 204
100 231 219 214
110 227
125 234 254 225
150 244 261 236
180 268
(

200 280 282 257


250 300 317
300 312 336
350 325 348
400 340

Ordering chart for flowmeter Type 8045 - for fitting S020 (see corresponding data sheet)

All these versions have as minimum


a 4... 20 mA current output (AO1) and
a digital output (DO1)
Relay output
Digital input

connection
Operating

Electrode

Electrical
Housing
material

material

Item no.
voltage

version
Sensor
Seal

18 - 36 V DC No No PC FKM Short, PVDF Stainless steel 2 cable glands M20 x 1.5 426 498
Long, PVDF Stainless steel 2 cable glands M20 x 1.5 426 499
1 2 PC FKM Short, PVDF Stainless steel 2 cable glands M20 x 1.5 426 506
(DI1) (DO2, DO3) Long, PVDF Stainless steel 2 cable glands M20 x 1.5 426 507
No No PPA FKM Short, st. steel (FDA) Stainless steel 2 cable glands M20 x 1.5 449 670
Long, st. steel (FDA) Stainless steel 2 cable glands M20 x 1.5 449 672
1 2 PPA FKM Short, st. steel (FDA) Stainless steel 2 cable glands M20 x 1.5 449 671
(DI1) (DO2, DO3) Long, st. steel (FDA) Stainless steel 2 cable glands M20 x 1.5 449 673
No No PC FKM Short, PVDF Alloy C22 2 cable glands M20 x 1.5 558 675
Long, PVDF Alloy C22 2 cable glands M20 x 1.5 558 676

Note: 1 Kit 558 102 and 1 EPDM seal are supplied with each flowmeter.

p. 6/7
8045

Ordering chart - accessories for flowmeter Type 8045 (has to be ordered separately)

Specifica-

Item no.
tions
Set with 2 cable glands M20 x 1.5 + 2 neoprene flat seals for cable gland or plug + 2 screw-plugs M20 x 1.5 + 449 755
2 multiway seals 2 x 6 mm
Set with 2 reductions M20 x 1.5 /NPT1/2” + 2 neoprene flat seals for cable gland or plug + 2 screw-plugs M20 x 1.5 551 782
Set with 1 stopper for unused cable gland M20 x 1.5 +1 multiway seal 2 x 6 mm for cable gland + 1 green FKM seal for the 558 102
sensor + 1 mounting instruction sheet
Snap ring 619 205
PC union nut 619 204
PPA union nut 440 229
Set with 1 green FKM + 1 black EPDM seals 552 111
3 points calibration certificate (device combined with a S020 fitting, only for DN  200) 550 676
FDA - Approval (only stainless steel sensor version) 449 788

Interconnection possibilities with other Bürkert flow sensors

Type 8802-DF -
Diaphragm
control valve with
TopControl Type 6213 -
Solenoid valve Type 6027 -
Solenoid valve

4-20 mA current
output Relay output Relay output

Type S020 -
Insertion fitting
(see corresponding
data sheet)
Type 8045 -
Electromagnetic
flowmeter

DN06 DN50 DN65 DN100 DN200 DN350 DN400


(1) Short sensor
Available S020 fitting DN

T-fitting

Short sensor Long sensor


Welding tab

Short sensor Long sensor


Fusion spigot

Long sensor
Screw-on S020

Long sensor
Saddle S020

(1) DN06 and DN08 in stainless steel S020 only, 8045 with stainless steel sensor recommended

To find your nearest Bürkert office, click on the orange box www.burkert.com

In case of special application conditions, Subject to alteration.


please consult for advice. © Christian Bürkert GmbH & Co. KG 1211/15_EU-en_00891790

p. 7/7