Macchia 2019
Macchia 2019
Abstract— In order to enhance the control ability of HVDC traditionally realized through synchronous generators in
systems, more and more attention is devoted to Voltage Source power plants, can be realized by VSC-HVDC. In fact, VSC-
Converters (VSCs), enabling instantaneous control of large HVDC terminals can be utilized to provide primary
amounts of power with improved stability features and frequency support to AC grids [11], mainly by means of a
providing ancillary services to the AC system. A crucial issue droop characteristic analogous to synchronous generators.
in VSC control is represented by their synchronization with the The control method is supposed to be local and autonomous,
AC grid usually obtained by phase locked loop techniques. In in order to react quickly in the case of network contingency
this paper, the Virtual Synchronous Machine concept is and to operate properly even if a communication failure
exploited through Power-Synchronization Method (PSM),
occurs [12].
aiming to mimic the behavior of synchronous generators with
VSCs. Therefore, a full and detailed dynamic model of a PSM- In order to realize frequency and voltage support, two
controlled VSC is developed, tuned and tested by means of main control procedures have been proposed in literature,
time domain simulations. either based on the master-slave method, allowing DC
voltage control for only one converter, and the voltage-droop
Keywords— Voltage source converter, Power method, enabling both converters to control active power and
Synchronization Method, Dynamic stability DC voltage at the same time [11]. However, the voltage
I. INTRODUCTION droop affects frequency control, modifying the desired
dynamic response [13].
The increasing interest in Voltage Source Converter
(VSC) for HVDC technology lies in its ability to produce AC In this paper, a detailed dynamic model of a PSM-
voltage wave independently on system connection, eluding controlled VSC is developed. The model involves different
limitations from weak AC networks [1][2] and in the full, control loops, aiming to obtain fast and stable response in the
fast and precise control of both active and reactive power. presence of different disturbances [14]. Moreover, a
This involves the possibility to provide support to the modified VSC model is developed to provide primary
connected AC system without any extra-cost [3][4]. In order voltage and frequency regulation. Control parameters are
to provide stable connection and to prevent over-currents, the tuned in order to get the desired response features with
vector current control has been widely adopted to determine changes in direct/alternating voltage or active/reactive
voltage references from current levels [5]. power. The effectiveness of the proposed models and
regulation is initially tested on a simple HVDC link between
A critical element in the design of a HVDC converter is two synchronous generators considering master-slave and
its synchronization with the AC system, in order to avoid voltage-droop configuration of converters. A further
short-circuit current caused by phase difference. The VSC demonstration is provided by inserting the HVDC link in a
phase-angle synchronization is traditionally carried out by realistic power system consisting of two asynchronous parts.
the phase-locked loop, but it suffers from several issues due
to nonlinearity and mutual interactions, particularly on weak II. PSM MASTER SLAVE MODEL
networks [6]-[8]. Therefore, efforts to investigate on
effective alternatives have been put in force. A. Model description
In the complete VSC control scheme, shown in Fig. 1,
An important step is provided by the concept of virtual the following control loops are included:
synchronous machine, implementing synchronous generator
features into the VSC control system [6][9][10]. In this • Power Synchronization Loop (PSL);
sense, the development of Power Synchronization Model • Alternating-Voltage Control (AVC);
(PSM), based on integral equation linking electric power to • Reactive Power Control (RPC);
angular frequency, reveals to be immediate and effective.
• Current Reference Control (CRC);
In this way, the provision of important ancillary services • Vector Current Control (VCC);
for the AC systems such as frequency and voltage support,
KQ
s
(
ΔVref = K PQ + I ⋅ Qref − Q ) (4)
However, RPC and AVC, even designed as cascading,
are actually alternative. In fact, in the presence of a stiff AC
network, with negligible voltage variations, the RPC is active
and Vref − V = 0 in (3), whereas in the case of a weak AC
network, RPC is switched off and ΔVref = 0 .
Fig. 1. Overall control scheme of the VSC The CRC is implemented in order to obtain current
reference values, whereas VCC should avoid the risk of
The PSL is characterized by the following equation: overcurrent in the presence of the PLL. The following
ωC − ωref (ωN + ΔωC ) − ωref equations implement CRC, where LC is phase reactor
θC = = = inductance and α C is the desired closed-loop bandwidth:
s s
(1)
( )
K P ⋅ Pref − P + ΔPV + 1 ⋅ ωN − ωref vCd − vd + ωC ⋅ LC ⋅ iq
= idref = + id (5.a)
DC
s αC ⋅ LC
where ΔωC is proportional to the difference between actual −vq + ωC ⋅ LC ⋅ id
active power P and reference value Pref .
iqref = + iq (5.b)
α C ⋅ LC
It is worth noting that, differently from the conventional After properly limiting idref and iqref at ± I max , VCC is
swing equations, only one integration is present in (1) to realized through the following equations:
avoid stability issues. However, the PSL actually operates
until the current flowing through the VSC is within its
maximum and minimum limits. In the case of overcurrent,
( )
vCd = αC ⋅ LC ⋅ idref − id − ωC ⋅ LC ⋅ iq + vd (6.a)
the control system will be automatically switched to the PLL vCq = αC ⋅ LC ⋅ ( iqref − iq ) − ωC ⋅ LC ⋅ id + vq (6.b)
operating mode.
The difference between master and slave controllers lies This formulation allows to perform AVC in normal
in the response to variation of DC voltage. In master control, operation, where the limit on ± I max is not attained and (5)-
DC voltage changing yields active power variation ΔPVDC (6) are inactive, and to implement VCC in the case of
overcurrent.
added to active power difference in the PSL, but in slave
configuration this term is neglected. The component ΔPVDC Then, a high-pass filter (HP) fed by current components
is exploited to improve damping of transmission network:
comes out from the DVC, where a PI controller acts on the
difference between actual DC voltage value VDC and s
HP ( s ) = K HP ⋅ (7)
reference value VDCref : s + α HP
Finally, the presence of phase reactor, with inductance
K DC
s
(
ΔPVDC = K PDC + I ⋅ VDCref − VDC )
(2) LC and resistance RC , involves equations relating voltage
and current in the dq frame.
The goal of the AVC is to control the AC voltage at grid The time domain simulations are carried out by means of
connection, mimicking the exciter control of a synchronous RAMSES, a power system dynamic simulator software
machine. However, it is found to be more beneficial to have developed by University of Liège based on the phasor
integral process for the VSC to suppress high-frequency approximation, operating in the xy synchronous reference
disturbances [1][14]. The AVC involves the difference frame [15]. For this reason, dq-xy coordinate conversions
between measured voltage magnitude V at grid connection (and vice versa) exploiting the phase angle estimation are
point and reference value Vref , providing in output the d present.
B. Parameter tuning LTOT LTOT
In order to tune the PSL proportional gain K P , all other III. FREQUENCY REGULATION SCHEMES
control loops are considered inactive. Starting from a zero Frequency regulation action of the VSC is aimed at
power-flow from the converter to the grid, at t = 0.1 s the replicating the frequency droop features of conventional
VSC is required to increase its active power from 0 to 0.1 synchronous generators, by a negative relation between grid
p.u. by a step change in the active power reference Pref . frequency deviation and active power variation through the
parameter R f . Similarly, the DC voltage can be regulated by
Results are reported in Fig. 3, where it can be seen that the
response is slow for K P < 0.05 and unstable for K P > 0.1 . a voltage droop characteristic, by a parameter RDC , making
active power increase along with DC voltage.
The general scheme reported in Fig. 1 is modified in the
PSL part to include the frequency droop, as reported in Fig.
5, where the droop R f is applied to ΔωC to obtain active
power deviation ΔPω , subtracted to active power difference
in (1). Moreover, LP(s) is a low-pass filter with a delay Tω
= 5 s aimed to reduce the influence of ΔPω on AC voltage
and current controls already set. In the new steady-state
condition, the closed-loop gain of the PSL is
Fig. 3. Time domain response of VSC control to active power step change
under different PSL regulations.
(
K Pf = K P / 1 + K P ⋅ R f . )
Analogous tests are carried out to tune the gain of AVC
(by a step reduction of AC voltage by 0.01 p.u.) and RPC
parameters (by a step increase of reactive power by 0.1 p.u.).
In a successive stage, the HP filter is tailored to damp fast
oscillations and to reduce overshoot of the three response.
In order to inspect the case of DC voltage variation, the
Test System 2, shown in Fig. 4, is considered. In this system,
the AC part of Test System 1 is replicated (where Fig. 5. Modification of the PSL to include frequency droop.
LTOT = LC + Lline ) and two VSCs are connected by a DC
The described control is applied to the VSCs in the Test
link, composed by two shunt capacitors ( C = 200 μF) and a System 3, reported in Fig. 6. It is analogous to Test System
resistance ( RDC = 10 Ω). 2, with VSC2 as Master and VSC1 as Slave, but the TEs are
replaced by 10-TVA synchronous machines (SM) with a
round-rotor standard model, including a speed governor with
power-frequency droop δ = 0.04 p.u. [16], and a constant
admittance load at each generator bus is added.
1
LTOT LTOT ΔPC = K PDC ⋅ ΔvDC + + R f ⋅ Δf (10)
KP
The mutual interactions of frequency and voltage droops
on both sides of an HVDC should be analyzed. By
neglecting DC link resistance, ΔPC1 + ΔPC 2 = 0 and ΔvDC is
equal on both sides, therefore the following relations hold
Fig. 6. Scheme of the Test System 3. (neglecting Δf 2 ):
LTOT LTOT
Fig. 12. Double Nordic Test System. Trends of VSC1 active power (A) and
Fig. 11. Scheme of the Double Nordic Test System. Center-of-Inertia angular speed of each Nordic (B) in the presence of
load ramp with subsequent loss of generator g1-b.
Simulations are carried out according to the scenario
As regards the g1-b tripping, a comparison is carried out
described hereinafter:
on the Nordic - b system in the absence of the HVDC link
- Initially the two systems are balanced (Case 1) with the considered Double Nordic (Case 2).
independently, and no power exchange across the HVDC
The valuable VSC contribution to the frequency support
link is present;
can be seen in Fig. 13.A, since both the undershoot and the
steady-state value of ωCOI −b are reduced for Case 2. The the participation of VSC-HVDC in proper secondary
comparison of AC voltage at HVDC connection bus is regulation actions could be investigated, as well as the
illustrated in Fig. 13.B. It is evident that the VSC has a behavior within a synchronous network.
strong ability to control the AC voltage, since in Case 2 it has ACKNOWLEDGMENT
better performances than in Case 1 (in terms of oscillations,
overshoot and steady state value). Authors want to thank Prof. T. Van Cutsem and Dr. L.
Papangelis from University of Liège for the support in
developing theoretical aspects and simulations in RAMSES
software during a joint Erasmus program.
REFERENCES
[1] L. Zhang, “Modeling and Control of VSC-HVDC Links Connected to
Weak AC Systems,” KTH, Stockholm, 2010.
[2] M. Bahrman, B. Johnson, “The ABCs of HVDC transmission
technologies” IEEE Power Energy Mag., vol. 5, no. 2, pp. 32–44,
A Mar. 2007.
[3] D. Jovcic and K. Ahmed, “High-Voltage Direct-Current
Transmission” Chichester, UK: John Wiley & Sons, 2015.
[4] B. Weedy, B. Cory, N. Jenkins, J. Ekanayake, G. Strbac, “Electric
Power Systems”, 5th Edition, John Wiley & Sons, 2012
[5] M. P. Kazmierkowski, L. Malesani, “Current control techniques for
three-phase voltage-source PWM converters: a survey”, IEEE Trans.
Ind. Electron., vol. 45, no. 5, pp. 691–703, 1998.
[6] Q.-C. Zhong, “Virtual Synchronous Machines: A unified interface for
grid integration,” IEEE Power Electron. Mag., vol. 3, no. 4, pp. 18–
27, Dec. 2016.
B [7] M. Ashabani, F. D. Freijedo, S. Golestan, J. M. Guerrero,
“Inducverters: PLL-less converters with auto-synchronization and
emulated inertia capability,” IEEE Trans. Smart Grid, vol. 7, no. 3,
pp. 1660–1674, 2016.
Fig. 13. Double Nordic Test System. Trends of VSC1 active power (A) and [8] A. Yazdani, R. Iravani, “Voltage-Sourced Converters in Power
Systems”, John Wiley & Sons, 2010.
Center-of-Inertia angular speed of each Nordic (B) in the presence of
load ramp with subsequent loss of generator g1-b. [9] Q. C. Zhong, G. Weiss, “Synchronverters: Inverters that mimic
synchronous generators,” IEEE Trans. Ind. Electron., vol. 58, no. 4,
pp. 1259–1267, 2011.
V. CONCLUSIONS
[10] S. D’Arco, J. A. Suul, O. B. Fosso, “A Virtual Synchronous Machine
An effective method to control a VSC-based HVDC link implementation for distributed control of power converters in
based on PSM has been developed in this work, to provide SmartGrids,” Electr. Power Syst. Res., vol. 122, pp. 180–197, 2015.
the phase reference similarly to the synchronous generators [11] T. M. Haileselassie, K. Uhlen, “Primary Frequency Control of
in AC systems. Control parameters have been tuned in order Remote Grids Connected by Multi-terminal HVDC,” Proc. of IEEE
PES General Meeting, 25-29 July 2010, Providence, RI, U.S.A., pp.
to obtain fast and stable response for each control quantity 1-6..
(AC and DC voltage, active and reactive power). VSC [12] L. Papangelis, M. Debry, P. Panciatici, T. Van Cutsem, “A receding
frequency regulation is achieved by including a delayed horizon approach to incorporate frequency support into the AC/DC
frequency droop in the PSL. converters of a multi-terminal DC grid,” Electr. Power Syst. Res., vol.
148, pp. 1–9, Jul. 2017.
In the master-slave configuration, only the slave [13] S. Akkari, M. Petit, J. Dai, X. Guillaud, “Interaction between the
converter is able to perform the frequency regulation action, voltage-droop and the frequency-droop control for multi-terminal
therefore a communication system between VSCs should be HVDC systems,” IET Gener. Transm. Distrib., vol. 10, no. 6, pp.
adopted to provide bidirectional frequency support. On the 1345–1352, Apr. 2016.
other hand, in the voltage-droop configuration, both VSCs [14] L. Zhang, L. Harnefors, H. P. Nee, “Power-synchronization control of
can control the active power and the DC voltage, achieving grid-connected voltage-source converters,” IEEE Trans. Power Syst.,
vol. 25, no. 2, pp. 809–820, 2010.
voltage control with a local method. In addition, the desired
VSC contribution can be obtained by setting the frequency- [15] P. Aristidou, T. Van Cutsem, “Algorithmic and computational
advances for fast power system dynamic simulations,” IEEE Power
droop parameter. Energy Soc. Gen. Meet., 27-31 July 2014, National Harbor, MD,
U.S.A., pp. 1-5.
The frequency regulation ability between two
[16] P. Kundur, “Power System Stability And Control”, McGraw-Hill,
asynchronous areas has been further demonstrated on a Inc., 1994.
realistic system. It has been shown that the presence of the
[17] T. Van Cutsem, L. Papangelis, “Description, modeling and simulation
VSC-HVDC link contributes to achieve both smaller results of a test system for voltage stability analysis,” 2013. [Online].
overshoot and steady state value of voltage and frequency Available: https://orbi.uliege.be/handle/2268/141234.
locally established after a generator tripping.
Further investigation can be envisaged in the presence of
multiple VSC and in multi-terminal DC networks. Moreover,