Identifying - Inrush - Currents - From - Internal Faults by Using Symmetrical Components
Identifying - Inrush - Currents - From - Internal Faults by Using Symmetrical Components
1
item. There are factors affect the differential current in fault conditions. The way to method to achieve this is a two
transformers and can be considered due to differential step process as below [11]:
protection. They are as follows [12]: 1. Phasing- Using suitable ∆/Y CT units to ensure that the
1. Magnetizing inrush current-In magnetizing inrush condition primary and secondary currents are in phase.
the peak amplitude of current can be as high as 8-30 times the 2. Ratio Adjustment- Having decided on the CT connections,
rated current, which is depending upon the transformer and the CT ratio and the relay tap is selected so as to have
system resistance. Normal magnetizing current is 2-5 times of minimum relay operating current.
the rated current.
2. Over excitation- It relates to generator-transformer units III. METHODOLOGY
(voltage/frequency unit). Also it came back to transmission Symmetrical components are commonly used for three-
transformers where line capacitance is more than inductance phase electrical power systems analysis [11]. If the phase
and some light load conditions can lead to high voltage on the quantities are expressed in phasor notation using complex
transformer. Transformers are normally designed to operate numbers, a vector can be formed for the three phase quantities.
just below the flux saturation level. Any increase from the For example, a vector for three phase voltages can be written
V a
max voltage (voltage/frequency ratio), can leads to core as follows:
V b
saturation.
3. CT Saturation- External faults near to transformer often
V abc (1)
V c
lead to CT saturation. Distortion of the saturated CT current
leads to mal-operation of differential relays. Also, values of
harmonic current in the saturated CT can cause a delay in the
operation of the differential relay during internal faults. A Therefore, the three symmetrical components phasors
proper CT selection ratio is essential to minimize problems arranged into a vector are as follows:
due to the saturation.
V 0
Different primary and secondary voltage levels, phase
V 1
displacement in ∆/Y transformers, control taps of voltage
transformer and phase shift in regulating transformers are V 012 (2)
V 2
another factors affect the differential current.
B. Percentage Differential Relay
Differential relays with percentage characteristics in the Where the subscripts 0, 1, and 2 in (2) respectively refer to
range of 15 to 60% are applied to transformers to account for the zero, positive, and negative sequence components. A phase
the variables less sensitive percentage. Moreover, in numeric rotation operator 'a' is defined in (3) to rotate a phasor vector
relays, harmonic restraints can be used. The second harmonic forward by 120 degrees. Matrix A can be defined using this
is the dominant harmonic in the magnetic inrush current. operator to transform the phase vector into symmetrical
Therefore, a second harmonic restraint is utilized to prevent components:
1 1 1
relay from operating during the inrush condition. Over
A 1 a 2 a
excitation includes high magnitudes of the odd harmonic,
normally 25% of the third component and 11% of the fifth
(3)
1 a a 2
component. In over excitation condition, relay has been used
the fifth harmonic signal to block the differential trip signal.
Otherwise, it is used to restraint the relay operation. Moreover,
to the fixed the percentage differential relays, variable
percentage relays are also used [12]. The phase voltages are generated by the sequence equation.
2
Fault
Fault
Fault
Fault
FAULTS
FAULTS
FAULTS
FAULTS
FT1 FT2 FT4
FT3
C
A
B
C
A
B
BUS1
ardestan
T
A i1 I1a A A I1aa i11 A
50[MVA] Line 1
va
B i2 I2b B B I2bb i22 B
#1 #2 T RRL
BRK vb
Ea Line 2
C i3 I3c C 33.0 [kV] C I3cc i33 C
11.0 [kV]
vc
A
Dial Position:
RRL
Main ... Fault Location and Type Start Duration i1 i1ct 1=> A-g
FT5
jaryan hojomi Fault location Fault Type Flt start Flt duration Rf 2=> B-g
8 10 1 2 50 i2 i2ct
3=> C-g A
OFF ON 7 9
6 8 4=> AB-g
7
ohm
5 6 5=> AC-g
s
4 5 B
3 4 i3 i3ct 6=> BC-g Fault
2 3
2 7=> ABC-g
1 1 0 0 0.001 FAULTS
1 3 0 0.2 1.96 0.001 i11 i11ct 8=> AB C
9=> AC
A
10=> no fault (0)
i22 i22ct
jenobe esf
i33
FT6
Fault
30 [MW]20.0 [MVAR]
where:
30
1 1 1
ida
1
idb
Amplitude(KA)
A 1 a
(A)
1
a2
20
idc
3
(6)
Amplitude
1 a a
2
10
0
When transformer is switched, inrush current will happen.
This current have some features, which it is enough for -10
0 0.1 0.2
identify itself. In this paper, with extract these features, a new Time(s)
criterion is proposed to discriminate inrush currents from
internal faults in power transformers. The point is the value of Fig. 2. Typical inrush current.
Z 0 3Z f
I 2 (I 1 )
negative sequence is different from positive sequence in faulty
Z 0 Z 2 3Z f
conditions. Helping this rule, the criterion is introduced. Every (11)
voltage and current can be written as follows:
I 0 1 1 1
1 2
Replacement (10) to (9), threshold of phase to ground fault,
I 1 3 1
the criterion will be almost zero, and for the threshold of phase
(7)
I 2
1
to phase to ground have:
2Z 2 (Z 2 3Z f )
2
I 2 I1
vf
Z 0 Z 1 Z 2 3Z f
1) Normal Condition
(10)
In normal condition, differential current is near to zero. So,
Where Zf is impedance between phase and ground, Z0 is zero the values of the positive, negative and zero sequence do not
sequence impedance, Z1 is positive sequence impedance and strongly change. Fig 3 shows the sequence current in nominal
Z2 is negative sequence impedance. In phase to phase to condition.
ground fault have:
3
Current Amplitude(kA)
Amplitude(kA)
Positive Sequence Positive Sequence
0.5 0.5
0 0
0 0.05 0.1 0.15 0.2 0.25 0 0.05 0.1 0.15 0.2
Time(s) Time(s)
Amplitude(kA)
Amplitude(kA)
Negative Sequence Negative Sequence
Current
0.02 0.2
0.01 0.1
0 0
0 0.05 0.1 0.15 0.2 0.25 0 0.05 0.1 0.15 0.2
Time(s) Time(s)
Amplitude(kA)
Amplitude(kA)
-5
x 10 Zero Sequence -5 Zero Sequence
2 x 10
4
1 2
0 0
0 0.05 0.1 0.15 0.2 0.25 0 0.05 0.1 0.15 0.2
Time(s) Time(s)
Fig. 3. Sequence currents for Idiff in normal condition. Fig. 5. Sequence currents for Idiff for inrush condition.
Criterion
Criterion 1.2
1.2
1
1
0.8
0.8
Criterion
Criterion
0.6
0.6
0.4
0.4
0.2
0.2
0
0 0 0.05 0.1 0.15 0.2
0 0.05 0.1 0.15 0.2
Time(s)
Time(s)
Fig. 6. Criterion value for Idiff for inrush condition.
Fig. 4. Criterion value for Idiff in normal condition.
Amplitude(kA)
Positive Sequence
Fig. 4 shows the calculated criterion for Idiff in normal
50
condition for phase A. 0
0 0.05 0.1 0.15 0.2
Time(s)
Amplitude(kA)
100
50
0
During switching, inrush current happens, and current are 0 0.05 0.1 0.15 0.2
Time(s)
Amplitude(kA)
produced like Fig. 5. This Fig shows the typical inrush current. Zero Sequence
20
But the values of the positive, negative and zero sequence for 10
0
inrush current are different from normal operation (Figs. 5). It 0 0.05 0.1 0.15 0.2
Time(s)
is because of this truth that a disturbance is imposed to
network. Anyway, the criterion will be like Fig. 6. But Fig. 7. Sequence currents for Idiff for internal fault (AB).
threshold value of it is like equation (12). It calculated in this Criterion
network and is 0.256. Then, if the criterion is more than 0.256, 1.2
disturbance will be inrush current. In general condition, the
criterion can be varied due to 0.15 to 0.25. 1
4
Criterion Criterion
1.2 1.2
1 1
0.8 0.8
Criterion
Criterion
0.6 0.6
0.4 0.4
0.2 0.2
0 0
0 0.05 0.1 0.15 0.2 0 0.05 0.1 0.15 0.2
Time(s) Time(s)
Fig. 9. Criterion value for Idiff for external fault with CT saturation Fig. 11. Criterion value for Idiff for over-flux condition.
condition.
Output CTs
4) External Fault Condition
Some extreme external faults near to transformer cause to Calculate
CT saturation. During the CT saturation, currents are not in Ida, Idb, Idc
common formation, so the rms value of them changes. n=n=+1
Moreover, introduced harmonics cause mal-operation of Ida, Idb , Idc >
Next Sample
relays. Fig. 9 shows the result for external fault with CT Thereshold
saturation. It can be found from Fig. 9 that the criterion value YES NO
in CT saturation condition is different in compare to internal
fault. Using the introduced criterion in saturation condition, Positive ,and Negative
relays can work more reliable with more accuracy. Calculation
5) Over-Flux Condition
In over-flux condition, values of the positive, negative and Criterion
>Threshold
zero sequence for differential have sudden changes. So, it can
help us to detect this situation. In this case, criterion value is NO YES
over 0.15 and cannot lead to signal trip. Figs. 10 show
sequence currents and Fig. 11 shows the calculated criterion
for over-flux condition. Internal Fault Inrush Current
As discussed, in all cases, this criterion can discriminate
inrush currents from internal faults. Therefore, flowchart in Trip NO Trip
Fig. 12 proposed to this algorithm. This algorithm reduces the
time of blocking transformer in inrush current due to
switching time in power system. If the calculated criterion is Fig. 12. Proposed algorithm flowchart.
less than 0.256, disturbance will be internal fault and relay
will trip. V. CONCLUSION
Transformer switching can cause some problems because
Amplitude(kA)
Negative Sequence
criterion introduced to discriminate inrush currents from
Current
0.1
0.05 internal faults. Power system simulated is a real network.
0
0 0.05 0.1 0.15 0.2
Time(s)
Moreover, it was shown that, this criterion have the ability to
Amplitude(kA)
-5
x 10 Zero Sequence work properly in CT saturation or over-flux condition.
5 Simulation results obtained with the developed models were
0 presented and it is found almost in all cases, new criterion
0 0.05 0.1 0.15 0.2
Time(s) works well.
Fig. 10. Sequence currents for Idiff in over-flux condition.
5
REFERENCES
[1] P. Arboleya, G. Diaz, J. Aleixandre,and C. Moran, "A solution to the
dilemma inrush/fault in transformer relaying using MRA and
wavelets,"Electric Power Compo. Syst., pp: 285–301, 2006.
[2] G. Baoming, A. Almeida, Z. Qionglin, and W. Xiangheng, ”An equivalent
instantaneous inductance-based technique for discrimination between
inrush current and internal faults in power transformers,”IEEE
Transactions on Power Delivery, vol. 20, no. 4, October 2005.
[3] H. Verma,and G. Kakoti, "Algorithm for harmonic restraint differential
relaying based on the discrete Hartley transform," Electric Power Syst.
Res., pp.125–129, 1990
[4] P. Liu, O. Malik, D. Chen, G. Hope,and Y. Guo, "Improved operation of
differential protection of power transformers for internal faults, "IEEE
Trans. Power Del., pp-4-7,October 1992.
[5] Z. Moravej, D. Vishwakarma, and S. Singh, "Applicability of artificial
neural networks to power transformer protection-an overview," in:
Proceedings of 14th National Convention of Electrical Engineering, pp.
230-236, 1998.
[6] J. Philer, B. Grcar, and D. Dolinar, "Improved operation of power
transformer protection using ANN," IEEE Trans. Power Del., pp. 1128–
1136, May 1997.
[7] S. Saleh,and M. Rahman, "Modeling and protection of a three-phase
power transformer using wavelet packet transform," IEEE Trans. Power-
Del., pp. 1273–1282,2005.
[8] M. Eissa, "A novel digital directional transformer protection technique
based on wavelet packets," IEEE Trans. Power Del., pp.1830–1836,
2005.
[9] Y. Sheng,and S. Rovnyak, "Decision trees and wavelet analysis for power
transformer protection," IEEE Trans. Power Del., pp: 429–433, 2002.
[10] S. Lotfi-fard, J. Faiz, R. Iravani, "Improved Over-current Protection
using Symmetrical Components," IEEE Transactions on Power Delivery,
vol. 22, no. 2, April 2007.
[11]J. Blackburn,and T. Domin, "Protective Relaying Principles and
Applications", 3rd Edition.1995.
[12] IEEE Std. C37.91-2000, IEEE Guide for Protective Relay Applications to
Power Transformers.