ECE522 4-Frequency
ECE522 4-Frequency
Spring 2021
• References:
– Chapter 11.1 of Kundur’s book
– Chapter 12 of Saadat’s book
– Chapter 4 (Frequency Control) of EPRI Tutorial
P=rT
• Under the rated condition:
r=0=1 pu, Pm=Pe=P0=0T0 =T0=Tm=Te
• Under a small change (r <<0) around the rated condition:
r=1+r pu, Pm-Pe=Pm-Pe =(1+r)(Tm-Te ) ≈ Tm-Te=Tm-Te
© 2021 Kai Sun 7
Consider both generator and load
• Generator:
d ( r )
2H Tm Te Pm Pe Pm Pe
dt
1 d
= r
0 dt
r , T and P in pu, in rad, H and t in sec.
2Hsr =Pm-Pe=Pm-PL-Dr
• Load:
(2Hs+D)r =Pm-PL
Pe=PL +Dr 𝑃𝑒 𝑃𝑍𝐼𝑃 1 𝐾 𝑓
0.75 pu -0.01 pu
10 sec
(load varies by 0.75% by 1 % change in of frequency (e.g. a 1MW decrease of 100MW unit)
0.0133x60=0.8Hz
Speed changer
Linkage mechanism
Speed governor
Hydraulic Amplifier
𝐺𝑇 𝑡
T is in 0.2-2.0 seconds
𝑟(s)
PL Req
1
R1 / / R2 / / / / Rn
ss 1 1 1
D 1/ Req
R1 R2 Rn
© 2021 Kai Sun 14
𝑟(s)
Saadat’s Example 12.1
s3 1 10.56
7.08 0.8 + K
s2
73.965- K
s1 0
7.08
s0 0.8 + K 0
• Routh-Hurwitz criterion:
Number of roots of the equation having positive real parts = Number of times • s1 row>0 if K<73.965
of sign changes in the 1st column of the Routh table • s0 row>0 since K>0
• Necessary & sufficient condition for stability of a linear system: • So R=1/K>1/73.965=0.0135
The 1st column has all positive numbers
© 2021 Kai Sun 16
Root‐Locus Method
When s=j3.25,
Conclusions (see Saadat’s B2.22 for details): Rmin=1/K=0.0135 (R>0.0135)
• The loci of roots of 1+KG(s)H(s) begins at KG(s)H(s)’s
poles and ends at its zeros as K=0.
• Number of separate loci = Number of poles; root loci must
be symmetrical with respect to the real axis.
• The root locus on the real axis always lies in a section of the
real axis to the left of an odd number of poles and zeros.
• Linear asymptotes of loci are centered at a point (x, 0) on
the real axis with angle with respect to the real axis.
where x=[ j=1…n( pj) i=1…m( zi) ]/(n m)
=(2k+1)/(n m) k=0, 1, …, (nm1)
R=0.0135
High
pressure
Low
pressure
=1/R
𝑓
PD
f PL R
Dwss
DPm1 =-
R1 D Pm 1 R
= 2
D Pm 2 R1
Dwss
DPm2 =-
R2
1 PL
Meq =2Heq= 2(H1+ … +Hn) Req ss
1 / R1 1 / Rn D 1/ Req
• Frequency response characteristic (FRC), also called Frequency bias factor
=D+1/Req =|PL/f | (Unit: MW/0.1 Hz)
• FRC tells how much MW change may cause a 0.1Hz frequency derivation, and it can
be developed for either the whole system or any section of the system.
• FRC depends on:
– The governor droop settings (Req) of all on-line units in the system.
– The frequency response (D) of the connected load in the system.
– The condition of the system (includes current generator output levels, transmission
line outages, voltage levels, etc.) when the frequency deviation occurs.
© 2021 Kai Sun 25
FRCs of Different Interconnections
=
=
=
E1 E2 X T X 1 X tie X 2
P12 = sin d12
XT 12 1 2
dP12
DP12 » Dd12 = Ps Dd12 = Ps (Dd1 -Dd2 )
d d12 d120
Ps
= (Dwr1 -Dwr 2 )
s P12
P12,max
E1 E2 Slope=Ps
dP
Ps = 12 = cos Dd120
d d12 d120
XT P12,0
Dw = Dw1 = Dw2
Ps
DPm1 -DP12 -DPL1 = Dw D1 DP12 = (Dw1 -Dw2 )
s
DPm 2 + DP12 - 0 = Dw D2
DP12 = Dw D2 -DPm 2
æ -å DPLj
ç 1 ö÷
DPi = -DPLi - çç Di + ÷÷ Dw = -DPLi - bi Dw DPi = -DPLi - bi Dw = -DPLi - bi
j
è R ÷ø i åb j
j
i i
çè i ÷ø åb
j
j
-å DPLi -å DPLi
= i Example 12.4: PL10 and PL2=0
Dw = i
æ ö
å bii
çç D + 1 ÷÷
åi çè i R ÷÷ø DP12 = DP1 =
-DPL1 (b1 + b2 ) + b1 (DPL1 + 0)
b1 + b2
i
b2
= (-DPL1 )
© 2021 Kai Sun b1 + b2 30
Limitations of Governor Frequency Control
• Governors do not recover frequency back to the scheduled value (60Hz) due to the required % droop
characteristic.
• Governor control does not adequately consider the cost of power production so control with governors
alone is usually not the most economical alternative.
• Governor control is intended as a primary means of frequency control and is not suited to fine adjustment
of the interconnected system frequency.
• Other limitations of a governor (see Sec. 4.3 in EPRI Tutorial)
– Spinning Reserve is not considered;
– Has a dead-band, typically 60Hz 0.03-0.04 Hz , in which it stops functioning;
– Depends on the type of generation unit (Hydro: very responsive; Combustion turbine: may or may not be
responsive; Steam: varies depending on the type);
– May be blocked: a generator operator can intentionally prevent a unit from responding to a frequency disturbance.
• From studies on EI and WECC in 2011-2013, 70-80% units are modeled with governors but only 30-50%
of units actually have governor responses (governors of the others are either turned off or inactive due to
dead-bands).
• During large disturbances and emergencies, AGC is bypassed and other emergency controls are applied.
𝑟(s)
b2 -DPL1
ACE1 = DP12 + b1Dw = (-DPL1 ) + b1 = -DPL1
b1 + b2 b1 + b2
b2 -DPL1 Pref2
ACE 2 = -DP12 + b2Dw = - (-DPL1 ) + b2 =0
b1 + b2 b1 + b2
2~0 2~0
2~0
ì
ï
ï= 0 with AGC and sufficient reserve
ACE i = Bi Df + DPi-others í
ï
î¹ 0 otherwise
ï
ì
ï= 0 with AGC and sufficient reserve
ACE i = Bi Df + DPi-others ï
í
ï
î¹ 0 otherwise
ï
D PRsrv ,i PRsrv ,i
=
D PG ,i PG ,i
833.33500=333.33MW
© 2021 Kai Sun 45
Spinning reserve: 1000
1,937.50 Spinning reserve:
1,000 of 4,000MW
1,000 of 10,000MW
B1=250MW/0.1Hz
B2=500MW/0.1Hz
Loss of 2,000MW
generation that do not ìï= 0 with AGC and sufficient reserve
carry spinning reserve ACE i = Bi Df + DPi-others ïí
ïïî¹ 0 otherwise
0
Df
-DPLi = Di Df + + DPi-others
Ri
1 2H
K= , T=
D D
DPm -
Dt
Df = (1- e 2 H )
D
df DPm - 2DtH
(Hz/sec) = e ´ 60
dt t =0 2H t =0
DPm
= ´ 60 (Hz / sec)
2H
© 2021 Kai Sun 49
Underfrequency Load Shedding (UFLS)
References
• “Balancing and Frequency Control,” NERC resources Subcommittee, January 26, 2011
http://www.nerc.com/docs/oc/rs/NERC%20Balancing%20and%20Frequency%20Control%20040520111.pdf
Source: “Balancing and Frequency Control,” NERC resources Subcommittee, Jan 26, 2011