5 Software
5 Software
Distribution Substation
3
CDEGS Program
Current Distribution Electromagnetic Interference
Grounding and Soil Structure Analysis
RESAP
6
>
>
10
Soil Structure
Volume of
Medium
Resistivity Soil
Overview
1. Introduction
2. Description of the Laksi Substation Grounding System
3. Soil Characteristic
4. Case Study
5. Applicability
6. Conclusion
17
1. Introduction
Based on MEA's statistical data, one of the main causes of
sustain interruptions is short circuits on electrical substations.
A short circuit generates large currents that flow in the
aboveground structures and grounding system and dissipate
in the soil. The high currents may cause damage to
equipment and may be dangerous to personnel working
nearby. It is there-fore important to consider and incorporate
safe step and touch voltage limitations into electrical designs
in order to achieve a safe electrical system without potential
electrical hazards after installation.
18
3. Soil Characteristic
Soil Resistivity Result
The soil layer characteristics of
the Laksi substation were
analyzed by a built-in module
in the CDEGS program called
Rural Electric Safety
Accreditation Program module
(RESAP), logarithmically shown
in Figure.
21
ρ2 Deep layer
2.96 Ω ⋅ m
22
4. Case Study
Safety Criteria for 50 kg Body Weight
Fault Clearing Time
Surface 0.1 sec Foot
Layer Touch Step Voltage Resistance:
Resistivity Voltage (V) 1 Foot
(Ω ⋅ m) (Ω)
(V)
None 367.9 603.9 44.2
514.2 587.3 1,481.7 1,562
1,014.2 806.7 2,359.2 3,079.2
3,014.2 1,684.2 5,869.3 9,148.3
23
T1
30
Economic Analysis
Rod Investment Cost (Million Baht)
Length Configuration Cross-Section Area of Ground Grid
(m) (mm2)
240 185 120 95
without grid 1.08 0.86 0.59 0.46
2.4
with grid 1.23 0.98 0.67 0.52
without grid 1.10 0.88 0.61 0.48
3.0
with grid 1.25 1.00 0.68 0.54
without grid 1.17 0.95 0.68 0.55
6.0
with grid 1.32 1.07 0.76 0.61
34
1.40 1.32
1.10 1.17
1.23 1.25
1.20
1.08 1.07
Investment Cost (Million Baht)
0.88 0.95
0.98 1.00
1.00
0.86
0.76
0.80 0.61 0.68
0.67 0.68 0.61
0.59 0.48 0.55
0.60
0.52 0.54
0.46
0.40
0.20
-
240 185 120 95
Cross Section Area (sq.mm)
Rod 2.4m (Existing) Rod 2.4m External Ground Grid
Rod 3.0m Rod 3.0m External Ground Grid
Rod 6.0m Rod 6.0m External Ground Grid
35
5. Applicability
1) The new safety criteria can replace the existing
ones for new substations in MEA without
significant change in GPR, touch voltage and step
voltage; for example, reducing the cross section
area of ground grid from 240 mm2 to 95 mm2 or
increasing the length of ground rod from 2.4 m to
3 m or 6 m.
36
Applicability (con’t)
2) The work carried out in this paper takes into
consideration the safety criteria based on IEEE-Std
80-2000 for the construction of substations in the
MEA service areas. Because soil characteristics in
the MEA service areas obtained from several field
tests are not much physically different the
presented method can be, to certain extent, used
for substations only in the areas.
37
Applicability (con’t)
3) However, if the method were to be applied in
any other areas in Thailand, measurement of soil
resistivity would be strongly recommended as it is
one of the most important factors in the
calculation of safety criteria.
38
6. Conclusion
1) These three parameters are investigated to ensure
that they satisfy the safety criteria defined in the IEEE
Std 80-2000.
2) On the basis of the test results, a ground rod of 6 m
and ground grid with a cross-section area of 95 mm2
could be a suitable option for the grounding system.
3) However, as far as installation costs should financially
reflect incremental total cost and worth for various
alternatives while respecting the established safety
criteria.
39
Conclusion (con’t)
4) However, if the method were to be applied in any
other areas in Thailand, measurement of soil resistivity
would be strongly recommended as it is one of the
most important factors in the calculation of safety
criteria.
40
Overview
1. Introduction
2. Description of the Bangkrachao Substation
3. Soil Characteristic
4. Case Study
5. Conclusion
42
1.Introduction
Based on MEA's statistical data, one of the main causes of
sustain interruptions is short circuits on electrical substations.
A short circuit generates large currents that flow in the
aboveground structures and grounding system and dissipate
in the soil. The high currents may cause damage to
equipment and may be dangerous to personnel working
nearby. It is there-fore important to consider and incorporate
safe step and touch voltage limitations into electrical designs
in order to achieve a safe electrical system without potential
electrical hazards after installation.
43
3. Soil Characteristic
Soil resistivity model.
46
Planning Criteria
MEA has power distribution improvement and expansion plans to
reinforce its power distribution system to accommodate load
growth in the future. The plans consist of the construction of
terminal stations, distribution substations, subtransmission lines,
and distribution feeders as well as the installation of new
equipment (e.g., transformers, circuit breakers) in the
subtransmission and distribution systems. This expansion plan
will increase the effective short-circuit current at the BC
substation.
49
4. Case Study
51
Criteria
Touch=1,144 V
Step=3,709 V
52
5. Conclusion
The ground grid design for the BC substation is examined with
the main objective to assess its grounding system condition in
terms of ground potential rise, touch voltage and step
voltage. These three parameters are analyzed to ensure that
they satisfy the safety criteria defined in the IEEE Std 80-2000
with three scenarios classified by fault levels: 7.8 kA for the
existing configuration, 25 kA in Expansion Plan No.12 (years
2017-2021) and 40 kA for the interrupting capacity of 69 kV
circuit breakers in MEA.
65
5. Conclusion (con’t)
As far as installation costs and other necessary expenses in
grounding system planning is concerned, the length of ground
rods, the size of conductor, the short circuit current and IC
of 69 kV circuit breakers should financially reflect incremental
total cost and worth for various alternatives while respecting
the established safety criteria.
66
Overview
1. Introduction
2. Description of the Pathumwan Substation
3. Soil Characteristic
4. Case Study
5. Conclusion
68
1.Introduction
69
GIS AIS
Small AIS
substation
70
Shopping
Mall AIS
Mass Transit
71
Shopping
Mall AIS
Mass Transit
72
Shopping
Mall AIS
Mass Transit
73
Shopping
Mall AIS
Mass Transit
74
Shopping
Mall
Mass Transit
75
Shopping
Mall
Mass Transit
76
Shopping
Mall
Mass Transit
77
Industry University
The Renovation of AIS to GIS
Shopping
Mall
Mass Transit
78
The ground grid system for the PM substation was modelled using
the CDEGS program as shown in Figure
81
3. Soil Characteristic
Soil resistivity model
The soil layer characteristics of
the PM substation were
analyzed by a built-in module
in the CDEGS program called
Rural Electric Safety
Accreditation Program module
(RESAP), logarithmically shown
in this Figure.
82
Summary of
Soil resistivity
a a a
4. Case Study
Effect of Nearby Auxiliary Grounding System of Substation
The ground grid of the substation that is still energized is called
main ground grid (energized electrical power site) whereas that of
the under construction substation (temporary or permanent
distribution substation) is called auxiliary grounding system
(auxiliary ground grid). During the time of disconnecting of these
ground grids, the under construction distribution substation is de-
energized, the substation surrounding area then exposes to the risk
of high GPR caused by the main distribution substation which is still
in operation. The GPR’s steepness is located between the main and
auxiliary ground grid.
85
3-Dimension Ground Potential Rise for Case 1 2-Dimension Ground Potential Rise for Case 1
3-Dimension Ground Potential Rise for Case 2 2-Dimension Ground Potential Rise for Case 2
3-Dimension Ground Potential Rise for 2-Dimension Ground Potential Rise for Case 3
Case 3
3-Dimension Ground Potential Rise for 2-Dimension Ground Potential Rise for Case 4
Case 4
3-Dimension Ground Potential Rise for Case 5 2-Dimension Ground Potential Rise for Case 5
Table Configuration of Auxiliary Table GPR, Touch Voltage and Step Voltage for Different
Grounding System of Substation Configuration
95
0
96
Safety criteria
3D:GPR Case 3 Touch=804.9 V, Step=2,352 V
Distance=74.4 m
Distance increase
• GPR (444.26V), decease
•Touch (381.25) , decease
2D:GPR
Touch:Spot 2D
100
Safety criteria
3D:GPR Case 3 Touch=804.9 V, Step=2,352 V
Distance=144.4 m
Distance increase
• GPR (393.24V) ), decease
•Touch (340.68) ), decease
2D:GPR
Touch:Spot 2D
101
Safety criteria
Case 5 Touch=804.9 V, Step=2,352 V
3D:GPR
Distance=74.4 m
Distance increase
GPR M/R=3.68% , de
(M:1,166.6V,R:42.89V), de
•Touch (1,097.55), in
2D:GPR
Touch:Spot 2D
102
Safety criteria
3D:GPR Case 5 Touch=804.9 V, Step=2,352 V
Distance=144.4 m
Distance increase
• GPR M/R=2.11%, de
(M:1,166.6V,R:24.26V), de
•Touch (1,122.18), in
2D:GPR
Touch:Spot 2D
103
5. Conclusion
1. The ground grid design for the PM substation has thoroughly
examined with the main objective to assess its grounding
system condition in terms of ground potential rise, touch
voltage and step voltage. These three parameters are
analyzed to ensure that they satisfy the safety criteria
defined in the IEEE Std 80-2000 with three scenarios
classified by 25 kA in Expansion Plan No.11
104
Conclusion (con’t)
2. Found that when ground grid is installed, only whether the
existing outdoor substation or the small AIS substation or
two neighbouring substations interconnected or isolated it
should have had considering design to safety. This creates
GPR to be steep at the main ground grid and can be harmful
to personal operating due to high voltage difference.
3. The first important is the accurate soil resistivity from
measurement in field test.
105
Overview
1. Introduction
2. Description of Pathumwan Substation
3. Optimal Design Principal of Grounding System
4. Process of Safety Analysis
5. Case Study
6. Conclusion
107
1. Introduction
Pathumwan (PM) - a 30-year, 69-kV AIS
Security and to build a new substation that is in
harmony with the environment.
The substation will be then changed to be 115-kV,
gas-insulated switchgear (GIS), indoor type
substation in 2015.
108
Objective
This paper presents a safety design of MEA’s new
Pathumwan distribution substation – a 3x60 MVA,
115/24-12 kV substation’s grounding system. Safety step
and touch voltage are analyzed with reference to safety
criteria based on body weight defined in IEEE Std. 80-
2000.
109
i=0
...
dmax di
i=0 1 2… m
112
>
>
115
5. Case Study
5.1 Resistivity Measurements
6. Conclusion
1. Compare the 3-m ground rod configuration with distributed
(scenario1) and edged laying (scenario2) with its compression ratio
intervals, we found that at 0.1 to 0.3; the maximum touch voltage
of the edged laying is lower, whereas 0.3 to 1.0; the maximum
touch voltage of the edged laying is higher.
2. Compare the 3-m ground rod (scenario1) with 6-m ground rod
(scenario 3) of the same distributed laying, we found that given the
same total length of the ground rod, the smaller number of longer
ground rods supersede the larger number of shorter ground rods
for the former provides lower touch voltage than the later for all
compression ratios.
132
6. Conclusion (con’t)
3. Compare the 3-m ground rod distributed laying (scenario1) with
6-m ground rod edged laying (scenario 4), we found that given the
same total length of the ground rod, the smaller number of longer
ground rods supersede the larger number of shorter ground rods
for the former provides lower touch voltage than the later for all
compression ratios. For scenario 4, all maximum touch voltages are
within the safety criteria for all compression ratios.
133
6. Conclusion (con’t)
4. Both the maximum touch and step voltages of scenario 5
exceed the safety criteria, because of the lack of ground rods that
allow the fault current to penetrate into the ground as of scenario
1-4. Such kind of design even you put in excessive amount of
conductors to the grid until it equal to that of the base scenario,
the touch voltage will still exceed the safety criteria. However, if we
bury such ground grid lower than usual, would its performance be
improve? This issue will be studied in the future.
134
6. Conclusion (con’t)
Given equal total length of conductors in a grounding system, as
per the configurations suggested in scenario 1 and 3, compression
ratio 0.7 seem to provide lowest touch voltage, and the one with
longer ground rods have 27.43% lower in touch voltage, and can
save up to 30.78% in ground rod length to achieve the same touch
voltage.
As far as installation costs and other necessary expenses in
grounding system planning is concerned, the length of ground rods,
the size of conductor, the amount of short circuit current directly
and financially reflect the incremental cost and worth of various
alternatives while conforming to the established safety criteria.
135
[email protected]
02-348-5629
089-968-6079