HEMK DS 2.

Easy maintenance.
Multilevel topology.
Advanced grid support.
Full power voltage range.
Bus Plus. Combine Solar and Storage.
HEMK

COMMON FEATURES
FRAME 2 3 4
Max. AC Output Current (A) @40°C 1837 2756 3674
Operating Grid Frequency (Hz) 50/60Hz
AC
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (CosPhi) [1] 0.5 leading … 0.5 lagging adjustable / Reactive power injection at night
Maximum DC Voltage 1500V
Number of Inputs Up to 20 Up to 30 Up to 40
DC Max. DC Continuous Current (A) [2] 2295 3443 4590
Max. DC Short Circuit Current (A) [2] 3470 5205 6940
Number of Freemaq DC/DC [2] Up to 4
Dimensions [WxDxH] (ft) 9.8 x 6.5 x 7.2
Dimensions [WxDxH] (m) 3.0 x 2.0 x 2.2
CABINET Weight (lbs) 11465 11795 12125
Weight (kg) 5200 5350 5500
Type of Ventilation Forced air cooling
Degree of Protection NEMA 3R / IP55
Operating Temperature Range [3] From -25°C to +60°C, >40°C power derating
ENVIROMENT Operating Relative Humidity Range From 4% to 100% non-condensing
Storage Temperature Range From -40°C to +60°C
Max. Altitude (above sea level) 2000m / >2000m power derating (Max. 4000m)
Communication Protocol Modbus TCP
CONTROL
Power Plant Controller Optional
INTERFACE
Keyed ON/OFF Switch Standard
Ground Fault Protection GFDI and isolation monitoring device
Humidity Control Active heating
PROTECTIONS General AC Protection & Disconn. Circuit breaker
General DC Protection & Disconn. Fuses, Motorized DC disconnect switches
Overvoltage Protection Type 2 protection for AC and DC
Safety UL 1741 / CSA 22.2 No.107.1-16 / IEC 62109-1 / IEC 62109-2
CERTIFICATIONS Installation NEC 2023 / IEC
& STANDARDS UL 1741 SA & SB / RULE 21 / RULE 14H
Utility Interconnect
/ IEEE 1547.1 2020 / IEC 62116:2014
690V 660V 645V
FRAME 2 3 4 2 3 4 2 3 4
REFERENCES FS2195K FS3290K FS4390K FS2101K FS3151K FS4200K FS2055K FS3080K FS4105K
AC Output Power (kVA/kW) @40°C [4] 2195 3290 4390 2100 3150 4200 2055 3080 4105
AC AC Output Power (kVA/kW) @50°C [4] 2035 3055 4075 1950 2925 3900 1905 2855 3810
Operating Grid Voltage (VAC) 690V ±10% 660V ±10% 645V ±10%
DC DC Voltage Range [5] 976V - 1500V 934V - 1500V 913V - 1500V
Efficiency (Max) (η) [6] 98.94% 98.96% 98.81%
EFFICIENCY
Euroeta (η) [6] 98.51% 98.53% 98.41%
630 V 615 V 600 V
FRAME 2 3 4 2 3 4 2 3 4
REFERENCES FS2005K FS3005K FS4010K FS1955K FS2935K FS3915K FS1910K FS2865K FS3820K
AC Output Power (kVA/kW) @40°C [4] 2005 3005 4010 1955 2935 3915 1910 2865 3820
AC AC Output Power (kVA/kW) @50°C [4] 1860 2790 3720 1815 2725 3635 1775 2660 3545
Operating Grid Voltage (VAC) 630V ±10% 615V ±10% 600V ±10%
DC DC Voltage Range [5] 891V - 1500V 870V - 1500V 849V - 1500V
Efficiency (Max) (η) [6] 98.88% 98.77% 98.78%
EFFICIENCY
Euroeta (η) [6] 98.45% 98.37% 98.35%

NOTES [1] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).


[2] Consult Power Electronics for Freemaq DC/DC connection configurations.
[3] Optional available for temperatures down to -35ºC.
[4] Values at 1.00·Vac nom and CosPhi=1. Consult Power Electronics for derating curves.
[5] Consult Power Electronics for derating curves. In the event of overvoltage in the grid,
the minimum DC voltage will vary proportionally with the AC voltage.
[6] Consult Power Electronics for Frame 2 and Frame 3 efficiencies.