DFR PF00610
DFR PF00610
SEL-3350
Scalable
Apply up to 16 protection-class CT/PT modules supporting 96 analog inputs in
one Axion system for recording fault data at up to 24 kHz. Merge digital status
tags from Axion I/O modules with multiple CT/PT module fault records using the
Recording Group configuration to create system-level event reports.
SCADA
HMI
SEL-3555
Engineering Access
SEL-735 SEL-2411
Applications
Record Disturbances and Exceed NERC PRC-002 Requirements
Capture power system data to support event analysis and locate faults. Easily
exceed requirements for standards such as NERC PRC-002. Our advanced
DFR solutions generate and collect event reports, capture synchrophasors for
dynamic disturbance data, record SOE data, and calculate fault locations using
an impedance-based algorithm.
acSELerator
RTAC software
DMA Disturbance
Monitoring
applications on
SEL Blueframe
Data Visualization and Analysis
View and analyze 3 kHz continuous oscillography data and synchrophasor
data in real time using SEL-5703 Synchrowave Monitoring software. Access
and analyze event reports with SEL-5601-2 synchroWAVe Event software.
Synchrowave software provides comprehensive visualization capabilities,
such as viewing multiple event files simultaneously and time-aligning
synchrophasor data with event reports.
Synchrowave
Operations
software
synchroWAVe
Event software
Complete Solution With Supporting Software
Synchrophasor and Automated Event Event
Continuous Oscillography and SOE Collection Analysis
Visualization
SEL-3350
SEL-3555 SEL-3350
SEL-3350 RTAC
Processor: Quad-core 1.6 GHz
RAM: 8 GB 3350#4MD8
Storage: 2 TB
Continuous Recorder license
SEL-2240 Axion
Preassembled Axion with 19" rack-mount backplane, Power Coupler with Ethernet, 2240#T4E2
four AC Protection Modules (12 current and 12 voltage channels), and one Digital Input
Module (24 digital input channels)
Additional Options
(24, 48, 110, 125, 220, and 250 Vac/Vdc) Continuous Record currents, voltages, and frequency
Standard digital output: 16 standard Recorder inputs up to 250 times a second for
control outputs dynamic disturbance records.
All Form A, all Form B, or mixed Record continuous oscillography analog
data at 3,000 samples per second.
Configuration Use the DFR library extension in
Store up to 2 TB of data (more than
acSELerator RTAC software to configure
hardware, channels, fault recording 10 days of continuous oscillography with
triggers, SOE logging, dynamic 96 channels).
disturbance recording, fault locating,
and more. Synchrophasors Conformance: IEEE C37.118.1-2011 as
amended by IEEE C37.118.1a-2014,
Fault Recording Sampling rates: 1, 2, 4, 8, and 24 kHz, IEEE C37.118.2-2011
software-selectable Accuracy: Level 1 as specified by
Transient Fault Record Length IEEE C37.118
Prefault time: 0.05 s – (max. event Message rates: 1 to 120 Hz
length – 0.05 s)
Measurements: Software-selectable
Individual records as long as: (P or M class)
24 seconds for 24 kHz
72 seconds for 8 kHz Phase voltages
144 seconds for 4 kHz Phase currents
288 seconds for 2 kHz
576 seconds for 1 kHz Positive-sequence current, frequency,
df/dt
Data format:
IEEE C37.111-2013 COMTRADE
Fault Location Determine the distance to the fault using
File naming: IEEE C37.232 COMNAME the SEL RTAC impedance-based fault
Store up to 10,000 COMTRADE events. location library.