Transformers
Transformers
POWE425
Single phase Transformers
Ossama Dankar
1
OBJECTIVES
• Understand the purpose of a transformer in a power system.
• Know the voltage, current, and impedance relationships across the
windings of an ideal transformer.
• Understand how real transformers approximate the operation of an ideal
transformer.
• Use a transformer equivalent circuit to find the voltage and current
transformations across a transformer.
• Be able to calculate the losses and efficiency of a transformer.
• Be able to calculate the voltage regulation of a transformer.
• Understand three-phase transformers.
• Understand transformer ratings.
2
Transformer : definition
A transformer is a device that changes ac electric power at one frequency and voltage level
to ac electric power at the same frequency and another voltage level through the action of a
magnetic field.
3
Transformer applications
• Power transformers are given a variety of different names, depending on their
use in power systems. A transformer connected to the output of a generator and
used to step its voltage up to transmission levels (110 + kV) is sometimes
cal1ed a unit transformer.
• The transformer at the other end of the transmission line, which steps the
voltage down from transmission levels to distribution levels (from 2.3 to 34.5
kV), is called a substation transformer.
• Finally, the transformer that takes the distribution voltage and steps it down to
the final voltage at which the power is actually used (110, 208, 220 V, etc.) is
called a distribution transformer.
4
Ideal Transformer
We consider a lossless transformer
with an input (primary) winding Is
Ip
having Np turns and a secondary
winding of Ns turns.
The relationship between the voltage Vp Vs ZL
(current) applied to the primary winding
vp(t) and the voltage (current) produced
NP NS
on the secondary winding vs(t) is
v p (t ) Np i p (t ) 1
= =a =
vs (t ) Ns is (t ) a
p = s =
Both windings of an ideal transformer have the same power factor.
Vp Ip 1
=a = Vp Vs ZL
Vs Is a
- -
NP NS
The phase angles of primary and secondary voltages are the same. The phase angles of
primary and secondary currents are the same also. The ideal transformer changes
magnitudes of voltages and currents but not their angles.
Impedance transformation
The impedance is defined as a following ratio of phasors: Z L = VL I L
- -
Vp aVs 2 Vs NP NS
ZL ' = = =a = a2ZL
I p Is a Is + ZL’ +
Vp Vs
- -
It is possible to match magnitudes of impedances (load and a transmission line)
by selecting a transformer with the proper turn ratio.
Analysis of circuits containing ideal
transformers
A simple method to analyze a circuit containing an ideal transformer
is by replacing the portion of the circuit on one side of the
transformer by an equivalent circuit with the same terminal
characteristics.
Next, we exclude the transformer from the circuit and solve it for
voltages and currents.
The solutions obtained for the portion of the circuit that was not
replaced will be the correct values of voltages and currents of the
original circuit.
4800
=
0.18 + j 0.24 + 4 + j 3
4800
= = 90.8 − 37.8 A
5.2937.8
Vload = Iload Zload = ( 90.8 − 37.8) (4 + j3) = ( 90.8 − 37.8)(536.9) = 454 − 0.9 V
The line losses are: Ploss = I line
2
Rline = 90.82 0.18 = 1484 W
b) We will eliminate transformer T2 by referring the load over to the transmission line’s
voltage level. Eliminate transformer T1 by referring the transmission line’s
2
10
'
Zload = a22 Zload = ( 4 + j 3) = 400 + j 300
1
The total impedance on Z eq = Zline + Zload
'
p = m + Lp
average primary flux mutual flux
The primary and secondary voltages due to the mutual flux are:
d d
es (t ) = N s m
e p (t ) dm es (t )
e p (t ) = N p m = =
dt dt Np dt Ns
e p (t ) Np
= =a
es (t ) Ns
The magnetization current (Real)
Even when no load is connected to the secondary coil of the transformer, a current will
flow in the primary coil. This current consists of:
1. The magnetization current im needed to produce the flux in the core;
2. The core-loss current ih+e hysteresis and eddy current losses.
The Magnetization Current in a Real Transformer
When an ac power source is connected to the primary, a current flows
in its primary circuit, even when there is no current in the secondary.
The transformer is said to be on no-load. If the secondary current is
zero, the primary current should be zero too. However, when the
transformer is on no-load, excitation current flows in the primary
because of the core losses and the finite permeability of the core.
Ic
E1
Excitation current, Io o
Magnetization current IM
(current required to IM
produce flux in the core) Io
Core-loss current Ih+e
(current required to make IM is proportional to the flux
up for hysteresis and eddy Ic = Ih+e = Core loss/E1
current losses)
The exact equivalent circuit of a real transformer
Cooper losses are modeled by
the resistors Rp and Rs.
Leakage flux in a primary
winding produces the voltage:
dLp
eLp (t ) = N p
dt
Since much of the leakage flux pass through air, and air has a constant reluctance that is
much higher than the core reluctance, the primary coil’s leakage flux is:
The transformer’s
equivalent circuit
However, the exact circuit is not very
practical.
Vs ,nl − Vs , fl V p a − Vs , fl
VR = 100% = 100%
Vs , fl Vs , fl
Where Vs,nl and Vs,fl are the secondary no load and full load voltages.
A transformer operating at a
unity power factor:
It is seen that VR > 0
Pout Pout
= 100% = 100%
Pin Pout + Ploss
Note: the same equation describes the efficiency of motors and generators.
Considering the transformer equivalent circuit, we notice three types of losses:
1. Copper (I2R) losses – are accounted for by the series resistance
2. Hysteresis losses – are accounted for by the resistor Rc.
3. Eddy current losses – are accounted for by the resistor Rc.
a) Calculate the full-load voltage regulation at 0.8 lagging power factor, at 1.0 power
factor, and at 0.8 leading power factor. Draw the phasor diagram
b) Plot the voltage regulation as load is increased from no load to full load at power
factors of 0.8 lagging, 1.0, and 0.8 leading.
c) What is the efficiency of the transformer at full load with a power factor of 0.8
lagging?
a. The full-load current on the secondary
side of the transformer is
Srated 15 000
I S , rated = = = 65.2 A
VS , rated 230
Vp
= VS + Req I S + jX eq I S
a
At PF = 0.8 lagging, current
I s = 65.2 − cos −1 (0.8) = 65.2 − 36.9 A
Vp
and = 2300 + 0.0445 ( 65.2 − 36.9 ) + j 0.0645 ( 65.2 − 36.9 ) = 234.850.40 V
a
The resulting voltage regulation is, therefore: V p a − VS , fl
VR = 100%
VS , fl
234.85 − 230
= 100%
230
= 2.1%
At PF = 1.0, current I s = 65.2 cos −1 (1.0) = 65.20 A
Vp
and = 2300 + 0.0445 ( 65.20 ) + j 0.0645 ( 65.20 ) = 232.941.04 V
a
The resulting voltage regulation is, therefore:
V p a − VS , fl 232.94 − 230
VR = 100% = 100% = 1.28%
VS , fl 230
VLP 3V P
= =a
VLS 3V S
3-phase transformer connections
2. Y- connection:
The primary voltage on each phase of
the transformer is
VLP
V P =
3
The secondary phase voltage is
VLS = V S
VLP 3V P
= = 3a
VLS V S
3-phase transformer connections
3. -Y connection:
The primary voltage on each phase of
the transformer is
V P = VLP
VLP V P a
= =
VLS 3V S 3
V P = VLP
VLP V P
= =a
VLS V S
Solution:
The high-voltage side is delta, thus the high-voltage side voltage rating is 20 kV
The high-voltage side current rating is 1.732*(10 kVA)/(20 kV) = 0.866 A.
the low-voltage side Y voltage rating is 1.732*200 V = 346 V
The low-voltage side current rating is (10 kVA)/(200 V) = 50 A.
The 3-phase transformer's core loss = 3 * 50 W = 150 W.
The 3-phase transformer's winding loss = 3 * 100 W = 300 W.