5.3 During use, the consumed foam concentrate shall be replenished in time.After
filling, close the Foam Liquid Adding Ball Valve,open the Reflux Ball Valve.
5.4 After connecting the fire water to the foam device and closing the electric
butterfly valve at the outlet of the mixed liquid, open the foam liquid outlet ball valve.
The foam device is in a ready state.
6. On Site Debugging
7. Operation
Figure 9
1 Foam pump inlet three-way ball valve ②Foam pump outlet three-way ball
valve③Flush ball valve ④air release valve
Figure 10
1 Foam pump inlet three-way ball valve ②Foam pump outlet three-way ball valve
2 Flush ball valve
17
7.2 Remote control: After confirming the fire according to the information of the fire
alarm system, manually open the start button of the foam device in the fire control
room. After the device control system receives the command, the main mixed liquid
outlet valve (normally closed), and when the pressure detected by the pressure
transmitter at the outlet of the main foam pump does not reach the set value or the
electric valve fails to open, the device system will alarm, At the same time, the main
system stops, and the main mixing outlet valve is closed and automatically switches
to the standby system. When any control equipment in the main system of the
device malfunctions, an alarm will be triggered and the backup system will be
started.
7.3 Local control: Switch the local/remote button on the control cabinet to "local",
and operate the "one-click start" button on the control cabinet to put the system
direct start device into operation. The operation of the device is automatically
controlled by the control cabinet program. Control cabinet program control flow is
the same as 7.2. If the startup fails, it can be manually opened by mechanical means.
18
Valve are opened, and the standby foam tank's Foam Liquid Outlet Ball Valve and
Reflux Ball Valve are closed. When the remaining amount of foam liquid in the main
foam tank is less than 10%, switch to the standby foam tank. First open the spare
foam tank's Foam Liquid Outlet Ball Valve, then close the main foam tank's Foam
Liquid Outlet Ball Valve Reflux Ball Valve. Then turn on the Reflux Ball Valve of the
spare foam tank.
If the fire is not controlled, the foam system needs to continue to work, and the foam
tank should be filled with foam liquid.
Refer to 5.2 for the filling process
7.7 Rinse
When the system is finished, flush the foam pump and mixed liquid pipeline.
First close Foam Liquid Outlet ball valve, Reflux Ball Valve, switch Foam pump inlet
three-way ball valve to "Flushing", Open the Flush ball valve, switch the
corresponding electric valve behind the water-motor to manual mode, turn the
handle, and make the butterfly valve open to 30~45°, so that the fire water passes
through the water-motor and drives the foam pump to work.
After 2 to 3 minutes, close the electric butterfly valve and switch back to the remote
control mode. Close the Flush ball valve and switch the Foam pump inlet three-way
ball valve to "Proposition". Open the discharge valve on the Foam Liquid Import line
and the discharge valve on the mixed liquid pipeline inside the pry bar, and close it
19