Full Set Structural Drawing-26 Feb-2025
Full Set Structural Drawing-26 Feb-2025
STRUCTURAL DRAWING.
Revised Drawing-February,2025
GENERAL NOTES - 1
1. GENERAL 4. MORTAR :
SHALL BE USED FOR BRICK WALL
· DESIGN METHOD IS USD/LRFD FOR STRUCTURAL & ASD FOR FOUNDATION ACCORDING
TO BANGLADESH NATIONAL BUILDING CODE (BNBC) 2020, ASCE 7-05 AND ACI 318-08 MIX RATIO (CEMENT : SAND)
= 1 : 3 (INTERIOR WALL)
· ALL THE STRUCTURAL DRAWINGS SHALL BE READ IN CONJUNCTION WITH RELEVANT = 1 : 3 (EXTERIOR WALL) - USE WATER PROOFING ADMIXTURE FOR
ARCHITECTURAL DRAWINGS BETTER PERFORMANCE
· FOLLOW BNBC (2020) FOR SPECIFICATIONS OR STRUCTURAL REQUIREMENTS NOT
MENTIONED IN THE DRAWINGS OR IN THIS NOTE. ANY DETAILS NOT SHOWN IN THE 5. CEMENT
DRAWING SHOULD BE DONE ACCORDING TO ACI DETAILING MANUAL
PORTLAND COMPOSITE CEMENT / BDS EN 197-1 : 2011 CEM II-A/M (PCC)
BASIC DESIGN AND DETAILING DATA
1 DESIGN CODE: BNBC 0 0 6. CONCRETE AGGREGATE
IND S EED:
a. FINE AGGREGATES: MINIMUM FM=2.50
EART A E ONE COE ICIENT: 0 ONE- II
b. COARSE AGGREGATES: 20mm DOWN WELL GRADED
SEIS IC DESIGN CATEGORY: SDC- D RA E B ILDING RA E
STONE CHIPS TO BE USED AS COARSE AGGREGATE
OT ER LOADS A BNBC 0 0
2. FOUNDATION 7. WATER
FOUNDATION TYPE - PILE FOUNDATION
POTABLE WATER TO BE USED IN CONCRETE MIX
IN-SITU PILE CAPACITY 75 TON FOR 20" PILE AS PER SOIL
TEST REPORT DEPTH OF FOUNDATION AS PER FOUNDATION DRAWING
8. STEEL REBARS
3. CONCRETE : i) ALL REBAR IS GRADE 60 (fy=60 ksi or 413 MPa) EXCEPT CONFINEMENT REBAR
ii) YIELD STRENGTH OF STEEL REBAR CONFORMED TO ONE OF THE
AVERAGE AND MINIMUM CONCRETE COMPRESSIVE STRENGTH (CYLINDER)
CONSIDERED AS FOLLOWS : FOLLOWING SPECIFICATIONS :i) BDS ISO 6935-2, ii) ASTM A615/A615M
iii) THE FOLLOWING TESTS FOR REINFORCING BARS FROM RANDOM
a. FOR PILE CAP : DESIGN f'c = 4000 psi
WHICH ARE TO BE CONFIRMED BY TRIAL MIX DESIGN SAMPLES SHALL BE CONDUCTED AS PER BDS ISO 6935-2/ASTM A615M AND
TEST RESULT SHALL BE SUBMITTED TO THE ENGINEER IN-CHARGE FOR CHECKING
b. FOR COLUMN & SHEAR WALL: DESIGN f'c = 4000 psi
AND RECORD
WHICH ARE TO BE CONFIRMED BY TRIAL MIX DESIGN
c. FOR BEAM, SLAB AND STAIR: DESIGN f'c = 3500 psi a. TENSILE STRENGTH TEST
WHICH ARE TO BE CONFIRMED BY TRIAL MIX DESIGN
b. PERCENTAGE ELONGATION TEST
d. FOR LINTEL, FIN, SIL, FALSE SLAB etc: DESIGN f'c = 3000 psi c. BEND/REBEND TEST
WHICH ARE TO BE CONFIRMED BY TRIAL MIX DESIGN
REVISION NO. :
S EET NO :
CONSULTANT : PROJECT INFORMATION : Structural Engineer Architect DRAWING TITLE : DISCLAIMER :
RO ECT NA E : OMEGA
E S N GENERAL NOTE
Rev-00
STR CT RAL DRA ING AS BEEN DONE AS ER
ARC ITECT RAL DRA ING RO IDED BY CLIENT
S-01
RO ECT TY E: RO OSED -STORIED RESIDENTIAL B ILDING STR CT RAL CONS LTANT ARE NOT RES ONSIBLE
S E S B ET OR ANY IOLATION O CODE COND CT OR T E CAD BY:
CORE DESIGN ADVISOR'S
-1 R - S - T D -1 0 RO ECT ADDRESS: LOT NO - ROAD NO-10 BLOC -C
IEB D INB SCALE: RES ECTI E A T ORITY
: 01 1- BAS ND ARA RESIDENTIAL AREA D A A C : 01 1 0 10 NOT TO SCALE DATE : EBR ARY 0
:
GENERAL NOTES - 2
9. LAP LENGTH (CLASS A) 15. LAP LOCATION
UNLESS OTHERWISE MENTIONED IN THE DRAWINGS, LAP LENGTH a. FOR BEAM BOTTOM BAR, LAP NOT TO BE PROVIDED AT MIDDLE THIRD
ZONE OF THE SPAN
Development Length Lap Splice Length
Beam Slab
Bar ldh with b. FOR BEAM TOP BAR, LAP MAY BE PROVIDED AT MIDDLE THIRD ZONE OF
l in Tension ld in Tension Tension Compression TensionCompression
Dia Standard Hook d Column THE SPAN
[Concrete≤300] [Concrete>300] (in)
(in) in Tension (in) Bottom Top 60 Grade 60 Grade
(in) (in) (in) (in) (in) (in)
(in)
c. NOT MORE THAN 50% OF THE BARS SHALL BE SPLICED AT ONE PLACE
10 8 16 21 16 16 21 12 16 12
12 10 20 25 20 20 25 14 20 14 d. LAP SPLICES ARE TO BE CONFINED BY HOOPS WITH MAXIMUM SPACING OR
16 13 26 34 26 26 34 19 26 19
20 16 41 53 41 41 53 24 41 24
PITCH OF d/4 OR 4"mm WHERE d IS THE EFFECTIVE DEPTH OF THE BEAM
25 20 51 66 51 51 66 30 - -
28* 23 57 74 57 57 74 34 - -
32* 26 65 84 65 65 84 38 - - lapping prohibited Middle third
*FOR Ø28 & Ø32 DIA BAR COUPLER SHOULD BE USED IN LAP SPLICE ldh
within ld Splice*
*NOTE:
E EN T E N E E O N E N O N E
E EN T E N E E O E
12db
d
E T N O T E E E T ONE O T ON E TE T N E E
h
T ONE O T ON T EN N E E E ENT O T E E E EN T
12. CHAIRS
USE CHAIRS OF NECESSARY DIMENSION MADE OF Ø12/Ø16 BAR
TO SUPPORT TOP BARS @ 30" C/C.
b
13. DEVELOPMENT LENGTH a
a
ALL BEAM AND SLAB REBARS SHOULD BE EXTENDED INTO THE SUPPORT UPTO L/5 b a
DEVELOPMENT LENGTH. a
b a a = TOP BARS
14. ADMIXTURE a
b = BOTTOM BARS
b a=b
WATER PROOFING ADMIXTURE, PLASTICISER AND JOINTING ADMIXTURE SHALL BE USED
L = LONGER CLEAR SPAN
AS MENTIONED IN THE RESPECTIVE DRAWINGS AND IN THE SPECIFICATION AFTER
APPROVAL BY THE ENGINEER. b SPACING OF CORNER BARS = SPACING OF MAXIMUM POSITIVE BARS
REVISION NO. :
SHEET NO :
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : DISCLAIMER :
PROJECT NAME : OMEGA
COLUMN
Side 3"
water face 2.5"
Foundation
3"
2.5" 2.5"
Bottom 3"
2.5"
3"
UNDERGROUND
12db
WATER RESERVOIR
1.5"
2.5"
in contact
2.5" BEAM column that receives
with
Above ground level *1.5"
1.5"
ground bars of main beam or
1.5"
foundation beam
1.5" *See the details drawing
Column
2.5"
SECTION
16. SLAB END REINFORCING DETAILS
2.5"
below
2.5"
ground level *2.5" FREE END OF SLAB INCAPABLE OF EMBEDDING OF STEEL BAR IN BEAM/WALL
2.5"
17B. SCOPE OF EMBEDMENT
2"
slab slab
*2"
10"
12db
all face : SLAB beam that receives bars of slab
6"
6"
6"
Grade beam 1.5"
2"
2"
min 4"
top, side & bottom 1.5"
10"
Floor beam
1.5"
12db
min 6"
SECONDARY Primary beam that
outdoors face : min 6"
10"
**1.5" BEAM receives bars of
top, side & bottom (3b) slab thickness
<8"
secondary beam
1.5" min 6"
SECTION
slab
0.75"
PRIMARY BEAM
10"
10"
Slab and stair top and bottom 0.75"
slab
0.75"
Lift Pit RCC Wall 17. RECOMMMENDED END HOOKS IN LAYERS OF 6"mm AND COMPACTED TO 95% STD. PROCTOR DRY DENSITY
1.5"
4db anchorage
lap splice
2" depth (D)mm D < 24" 24"≤D<36" 36"≤D<48" D³48"
water face 2"
2" fastening bar
2"
OVERHEAD
135° r = 1.25db stirrups additional bar not necessary 2-Ø10 4-Ø12 n-Ø12
tie/stirrups 6 to
db
6d
<12"
D
primary SECTION
90° r = 2.5db 6 to embedment
2"
12db
reinf.
db
32 bend-up for
B
BASE SLAB
3"
/ MAT
in contact with ground 3"
8 to
slab 45° r = 5db slab bend
fastening Ø6 mm @ 24"
db
r 20
bar in
* from tie ** from stirrups
REVISION NO. :
S EET NO :
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : DISCLAIMER :
RO ECT NA E : OMEGA
E S N GENERAL NOTE
Rev-00
STR CT RAL DRA NG AS BEEN DONE AS ER
ARC TECT RAL DRA NG RO DED BY CL ENT
S-03
STR CT RAL CONS LTANT ARE NOT RES ONS BLE
RO ECT TY E: RO OSED -STOR ED RES DENT AL B LD NG
S E S B ET
CORE DESIGN ADVISOR'S OR ANY OLAT ON O CODE COND CT OR T E CAD BY:
- 3 R - S - T D - 30 EB D NB SCALE: RES ECT E A T OR TY
RO ECT ADDRESS: LOT NO - 3 ROAD NO- 0 BLOC -C
:0 -
: BAS ND ARA RES DENT AL AREA D A A C : 0 0 0 NOT TO SCALE DATE : EBR ARY 0
GENERAL NOTES - 4
20. COLUMN SPLICE LOCATION
TIE ARRANGEMENTS IN COLUMN :
stirrups/ties
S
"
³3
main reinforcement
6d b 15"
splice
S
lap
A
H
SO
FLOOR LEVEL on adjacent corners of the
Joint hoops may be spaced at up to 6" for the
l0
column as shown
SO/2
d) STANDARD BAR HOOKS :
column
l0
-
i) MAIN REINFORCEMENT :
SO
12 d
21. END HOOK OF STIRRUPS SO = - 8db (db=smallest longitudinal bar diameter)
-
180° 90° - 24db (db=tie bar diameter)
2SO
clear height of column
S≤
main bar
- 12"
4 d> 2.5"
/
SO
24"
d d
- larger dimension of column
1
l0 - of clear height of column
l0
SO/2
ii) STIRRUPS AND TIES : 6
135° - 18" Cross
00°
6d tie
.
135
25mmØ BAR OR SMALLER fastening bar
additonal bar
6db³3"
stirrup
6d
END HOOKS OF STIRRUPS ARE LOCATED ALTERNATELY AT TOP
b
³3
d CORNER BAR OF THE SECTION.
"
Structural Engineer REVISION NO. :
S EET NO :
CONSULTANT : PROJECT INFORMATION : DRAWING TITLE : DISCLAIMER :
RO ECT NA E :OMEGA
E S N
GENERAL NOTE
Rev-00
STR CT RAL DRA NG AS BEEN DONE AS ER
ARC TECT RAL DRA NG RO DED BY CL ENT
S-04
RO ECT TY E: RO OSED -STOR ED RES DENT AL B LD NG STR CT RAL CONS LTANT ARE NOT RES ONS BLE
CORE DESIGN ADVISOR'S S E S B ET OR ANY OLAT ON O CODE COND CT OR T E CAD BY:
SCALE:
- R - S - T D - 0
RO ECT ADDRESS: LOT NO - ROAD NO- 0 BLOC -C EB D NB RES ECT E A T OR TY
:0 -4
BAS ND ARA RES DENT AL AREA D A A DATE : EBR ARY 0
: C : 0 0 0 NOT TO SCALE
GENERAL NOTES - 5
22. CONFINEMENT REQUIREMENTS OF BEAM AT JOINTS 23. DETAILS OF REBARS AT SLAB OPENING
NOTE: UP TO OPENNING SIZE OF 24"x24"
FOR EARTHQUAKE LOADING RCC Slab (Typ.)
d/4
s<
24 db(hoop bar)
d
l
l
d
2" 300 mm
d
h opening
min. 4-12Ø ( Top & Bottom )
2h s≤d/2
d
l
l
d
Note : This stirrup spacing shall be mentioned
min. 4-12Ø( Top & Bottom )
as a minimum requirment.
6db³3"
stirrup/ties
6db³3"
ld
ld
ld
min. 2-16Ø
NOTE: UP TO OPENNING SIZE OF 24"x24" 25. Flat-Roof shall have 1% Drainage Slope
S EET NO :
CONSULTANT : PROJECT INFORMATION : DRAWING TITLE : DISCLAIMER :
RO ECT NA E : OMEGA E S
S E
N
S B ET GENERAL NOTE Rev-00
STR CT RAL DRA NG AS BEEN DONE AS ER
ARC TECT RAL DRA NG RO DED BY CL ENT
S-05
RO ECT TY E: RO OSED -STOR ED RES DENT AL B LD NG STR CT RAL CONS LTANT ARE NOT RES ONS BLE
EB D NB OR ANY OLAT ON O CODE COND CT OR T E CAD BY:
CORE DESIGN ADVISOR'S
SCALE:
- R - S
:0 5 - 5
- T D - 0
RO ECT ADDRESS: LOT NO - ROAD NO- 0 BLOC -C
C : 0 0 0 RES ECT E A T OR TY
: BAS ND ARA RES DENT AL AREA D A A NOT TO SCALE DATE : EBR ARY 0 5
A B C D E F G H
2'-3"
4'-8" 11'-5" 4'-7" 16'-7" 5'-1" 7'-1" 3'-8" 4'-8"
7'-2"
6"
1
6"
6"
C4=12"X30"
C8=20"X20" C1=12"X20"
12'-4"
7"
6"
2'-0"
2
6"
C3=15"X25"
C6=15"X30"
8'-4"
6" 1'-3"
3
6"
6"
4'-6"
C5=15"X30" 1'-3"
C2=12"X25"
8"
4
3'-7"
9"
9"
5
4'-3"
C5=15"X30" C3=15"X25"
6"
C2=12"X25"
6
6"
8'-4"
C2=12"X25"
SW=10"X45"
6"
10"
1'-8"
1'-3"
7
2'-4"
6"
C2=12"X25" 5"
8
5'-8"
7'-4"
6"
4'-2"
10"
6"
9
5"
3'-8"
10"
4'-6"
6"
6" C7=20"X25"
9"
11
1'-2"
C1=12"X20" C6=15"X30"
8'-6"
6" 6"
12
6"
6"
C2=12"X25"
C8=20"X20"
12'-2"
C1=12"X20"
C8=20"X20"
C2=12"X25"
1'-2"
1'-2"
1'-3"
6"
4"
13
6"
6'-2"
S
N COLUMN LAYOUT PLAN (UP TO PL)
E
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
phone: 01521-456877
mail: [email protected]
A B C D E F G H
2'-3"
4'-8" 11'-5" 4'-7" 16'-7" 5'-1" 7'-1" 3'-8" 4'-8"
4'-8"
7'-2"
6"
1
6"
6"
C4=12"X30"
C8=20"X20" C1=12"X20"
12'-4"
7"
6"
2'-0"
2
6"
C3=15"X25"
C6=15"X30"
8'-4"
6" 1'-3"
3
6"
6"
4'-6"
C5=15"X30" 1'-3"
C2=12"X25"
8"
4
3'-7"
9"
9"
5
4'-3"
6"
C5=15"X30" C3=15"X25"
C2=12"X25"
6
6"
8'-4"
C2=12"X25"
SW-1=10"X45"
6"
1'-8"
7
2'-4"
6"
C2=12"X25"
8
6"
4'-2"
6"
9
5"
3'-8"
1'-3"
SW-1=10"X45" C2=12"X25"
1'-6"
10
10"
4'-6"
6"
6" C7=20"X25"
9"
11
1'-2"
C1=12"X20"
C6=15"X30"
8'-6"
6" 6"
12
6"
6"
C2=12"X25"
C8=20"X20"
12'-2"
C1=12"X20"
C8=20"X20"
C2=12"X25"
1'-2"
1'-2"
1'-3"
6"
4"
13
6"
6'-2"
S
N COLUMN LAYOUT PLAN (TYPICAL )
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
phone: 01521-456877
mail: [email protected]
A B C D E F G H
2'-3"
4'-8" 11'-5" 4'-7" 16'-7" 5'-1" 7'-1" 3'-8" 4'-8"
7'-2"
1'-7" 3'-5"
2'-1" 2'-11"
1'-1"
1'-1"
P1 P1 2'-6" 2'-6" P2
P1 P1 P2
2'-11" 1'-5"
1
3'-3"
3'-3"
P1 P1
P2
12'-4"
11"
5"
P1 P1
3'-5"
3'-1" 2'-0"
2
1'-7"
P1 P1
P1 2'-6"
8'-4"
2'-6" P1
P1 P1
3
3'-1"
4"
4'-6"
P1 P1
P1 2'-6" 2'-6" 3'-5" 11"
4
P1 P1 P1
2'-9"
3'-7"
1'-4"
2'-6"
2'-6"
2'-6"
P1
5
2'-6"
2'-6"
2'-6"
P1 P1 P1 P1
4'-3"
2'-0" 3'-1"
P1 P1 P1 P1
6
P1 P1
8'-4"
1'-10" 1"
8" 5'-0" 5'-0"
P3 P3 P3
1'-4"
7
2'-4"
2'-0" 3'-1"
3'-2"
8
P3
4'-2"
P1
3'-5"
P1 P3 3'-2" P3 2'-7" P3
1'-7" 4'-3" 2'-7" 3'-3"
9
3'-8"
1'-1"
2'-8"
P1 P1 P1 P3 P3 P3
10
1'-9"
1'-4"
4'-6"
P1
P1
2'-10"
2'-9"
4" P1
11
1'-8"
2'-2"
P1
P1
8'-6"
P1 P1
2'-6" 2'-6"
P3
3'-1" 2'-0"
1'-9"
P3
12
3'-3"
P3 P3
P3 P3
12'-2"
5"
P1 P2
2'-10"
3'-3"
1'-10" 3'-3"
1'-1"
13
2'-2"
P1 P1 P1
6'-2"
2'-11" 2'-1" P1 P2
S
N PILE POINT LAYOUT PLAN
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
phone: 01521-456877
mail: [email protected]
EGL/ROAD LEVEL EGL/ROAD LEVEL
2'-0"
2'-0"
2'-0"
±3'-0"
±3'-0"
20"
Breaking level. Breaking level. 3" 3"
10mm Ø@4"c/c
4-20+4-16mm Ø
20'-0"
20'-0"
CROSS SECTION (A-A)
20"
10mmØ@4"c/c
10mmØ@4"c/c
3" 3"
10mm Ø@7"c/c
8-16mm Ø
A A A A CROSS SECTION (B-B)
JOINT DETAILS
80'-0"
75'-0"
750 Lapping
18"
20" 20"
LONG SCETION OF PILE-P1 LONG SECTION OF PILE-P2
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
4'-0"
4'-0"
±3'-0"
Breaking level.
20'-0"
10mmØ@4"c/c
20"
3" 3"
A A 10mm Ø@4"c/c
4-20+4-16mm Ø
3" 3"
750 Lapping
8-16mm Ø
2. All Reinforcement bars should be deformed bar having yield strength, fy=40000 psi
3. Concrete mix ratio = 1:1.5:3 with
4. Spiral must be spot welded to main vertical alternate bars.
5. Block or M.S. bar welded to main bar to facilitate clear cover 3" around the steel
case.
6. Slump for Concrete = 6"mm,
7. After completion of bore hole, it must be washed with clean water
from seperate chamber.
B B 8. Allowable pile capacity=150 kip per pile which should be conformed by Pile Load Test
18"
20"
LONG SCETION OF PILE-P3
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
2'-3"
4'-8" 11'-5" 4'-7" 16'-7" 5'-1" 7'-1" 3'-8" 4'-8"
2'-1"
2'-1"
2'-1"
2'-1"
3'-1"
2'-9"
1
8"
1'
8"
5'-7"
6'-5
4'-11"
4'-7"
6'-5
"
6'-5
PC3
"
"
PC3
12'-4"
1"
7" 1'-5" 1'-11" 1' 1'
PC3A
5'-1"
4'-9" 3'-7"
1'-8" 1'-8"
2
3'-3"
PC2
8'-4"
PC4
3'-7"
3'-3"
4'-5"
3
7'-8"
4'-6"
PC8
4'-6"
4'-9"
3'-7"
4'-2"
4'-2"
PC2 4'-5"
5
4'-3"
3'-8" 4'-8"
4'-2"
4'-2"
1'-8" 1'-8"
6"
6
PC4 PC4A
5"
PC2 14'
8'-4"
2'-11"
UGWR
6'-6
"
6'-6
7
"
2'-4"
11"
8
4'-2"
"
6'-6
1'
6'-6
9
5"
PC2
2'-9"
"
3'-8"
4'-4"
11"
10
4'-6"
4'-6"
4'-6"
PC8
11
3'-4"
3'-10"
8'-6"
3'-11" 4'-5"
1'-8" 1'-8" 3'-3" 6'-10" 4'-11"
4'-8" 3'-8"
3'-5"
PC2
1'-8" 1'-8"
12
4'-11"
PC2
12'-2"
1'-5"
7"
PC4 1'-8" 1'-8"
4'-11"
8" 4'-11"
"
3'-5" 4'-11"
6'-5
4'-6"
1'-8" 1'-8"
13
SOCK WELL
2'-9"
2'-1"
3'-10"
6'-2"
S
N PILE CAP LAYOUT PLAN
E
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
phone: 01521-456877
mail: [email protected]
PARKING LEVEL
GB
ROAD LEVEL
PARKING LEVEL
A
GB B
ROAD LEVEL
2-d12 BINDER
T
A
B
75 C C
2-d12 BINDER
T
75 C C
B
A
B
A A A
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
SHEET NO :
STRUCTURAL DRAWING HAS BEEN DONE AS PER
ARCHITECTURAL DRAWING PROVIDED BY CLIENT.
Engr.Suraya Nasrin PILE CAP DETAILS Rev-00 STRUCTURAL CONSULTANT ARE NOT RESPONSIBLE
PROJECT TYPE: PROPOSED 9-STORIED RESIDENTIAL BUILDING FOR ANY VIOLATION OF CODE & CONDUCT OR THE
CORE DESIGN ADVISOR'S M.Sc Engg.(Structural),BUET RESPECTIVE AUTHORITY. CAD BY:
House-13, Road-9,Sector-6,Uttara Model Town,Uttara,Dhaka-1230 SCALE:
phone: 01521-456877 PROJECT ADDRESS: PLOT NO - 369, ROAD NO-10, BLOCK-C FIEB, DMINB Structural Drawing
mail: [email protected] BASHUNDHARA RESIDENTIAL AREA, DHAKA. DATE : FEBRUARY ,2025
Cell: +8801716780910 NOT TO SCALE
PARKING LEVEL PARKING LEVEL
GB GB
ROAD LEVEL ROAD LEVEL
A A
B B
T
2-d12 BINDER 2-d12 BINDER
T
75 C C
75 C C
B A
C C D D
A
B
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
SHEET NO :
STRUCTURAL DRAWING HAS BEEN DONE AS PER
ARCHITECTURAL DRAWING PROVIDED BY CLIENT.
Engr.Suraya Nasrin PILE CAP DETAILS Rev-00 STRUCTURAL CONSULTANT ARE NOT RESPONSIBLE
PROJECT TYPE: PROPOSED 9-STORIED RESIDENTIAL BUILDING FOR ANY VIOLATION OF CODE & CONDUCT OR THE
CORE DESIGN ADVISOR'S M.Sc Engg.(Structural),BUET RESPECTIVE AUTHORITY. CAD BY:
House-13, Road-9,Sector-6,Uttara Model Town,Uttara,Dhaka-1230 SCALE:
phone: 01521-456877 PROJECT ADDRESS: PLOT NO - 369, ROAD NO-10, BLOCK-C FIEB, DMINB Structural Drawing
mail: [email protected] BASHUNDHARA RESIDENTIAL AREA, DHAKA. DATE : FEBRUARY ,2025
Cell: +8801716780910 NOT TO SCALE
PARKING LEVEL LIFT LOBBY LEVEL
PARKING LEVEL
10mmØ@10"c/c.
12mmØ@6"c/c.
C A
D B
D B
C A
T
2-d12 BINDER
T
2-d12 BINDER
3" C C
3" C C
C
E E
A B
F D F
C
D A
B
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
S-14
SHEET NO :
PROJECT NAME : OMEGA
STRUCTURAL DRAWING HAS BEEN DONE AS PER
Engr.Suraya Nasrin PILE CAP DETAILS Rev-00 ARCHITECTURAL DRAWING PROVIDED BY CLIENT.
PROJECT TYPE: PROPOSED 9-STORIED RESIDENTIAL BUILDING STRUCTURAL CONSULTANT ARE NOT RESPONSIBLE
CORE DESIGN ADVISOR'S M.Sc Engg.(Structural),BUET
House-13, Road-9,Sector-6,Uttara Model Town,Uttara,Dhaka-1230 FOR ANY VIOLATION OF CODE & CONDUCT OR THE CAD BY:
SCALE:
phone: 01521-456877
mail: [email protected] PROJECT ADDRESS: PLOT NO - 369, ROAD NO-10, BLOCK-C FIEB, DMINB Structural Drawing
RESPECTIVE AUTHORITY.
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
SHEET NO :
STRUCTURAL DRAWING HAS BEEN DONE AS PER
ARCHITECTURAL DRAWING PROVIDED BY CLIENT.
Engr.Suraya Nasrin PILE CAP SCHEDULED Rev-00 STRUCTURAL CONSULTANT ARE NOT RESPONSIBLE
PROJECT TYPE: PROPOSED 9-STORIED RESIDENTIAL BUILDING FOR ANY VIOLATION OF CODE & CONDUCT OR THE
CORE DESIGN ADVISOR'S M.Sc Engg.(Structural),BUET RESPECTIVE AUTHORITY. CAD BY:
House-13, Road-9,Sector-6,Uttara Model Town,Uttara,Dhaka-1230 SCALE:
phone: 01521-456877 PROJECT ADDRESS: PLOT NO - 369, ROAD NO-10, BLOCK-C FIEB, DMINB Structural Drawing
mail: [email protected] DATE : FEBRUARY ,2025
BASHUNDHARA RESIDENTIAL AREA, DHAKA.
Cell: +8801716780910 NOT TO SCALE
COLUMN SCHEDULE
COLUMN UP TO PL GROUND FLOOR 1ST TO 2ND FLOOR 3RD TO 4TH FLOOR 5TH TO 6TH FLOOR 7TH TO ROOF
NO
TYPE
SIZE 22"X14" 20"X12" 20"X12" 20"X12" 20"X12" 20"X12"
NOTE
C1 d16mm
12-20mm 12-20mm 12-20mm 12-20mm 6-20mm+6-16mm 4-20mm+8-16mm
SIZE 27"X14"
25"X12" 25"X12" 25"X12" 25"X12" 25"X12" d20mm
C2 d25mm
CLASS "B"
C3 LAP
SPLICES
C4 135
6db , 3"(75mm)MIN.
14-20mm
HOOPS
JOINT
1.D.=4db FOR #3,#4,#5(#10,#13#16)
db
COLUMN HOOP HOOKES AT EACH END
COLUMN HOOPS
SIZE 32"X17" 30"X15" 30"X15" 30"X15" 30"X15" 30"X15"
COLUMN HOOPS MUST BE PROVIDED (N ALL JOINTS
C5 Sh=4"
AND IN THE COLUMNS FOR A DISTANCE.lo, ABOVE
AND BELOW JOINTS.SEE VERTICAL ELEVATION.
HOOPS
COL.
lo TIES REQUIRED TO RESIST SHEAR SHALL BE HOOPS,
AND SPACING SHALL NOT EXCEED d/2)
10mmØ Stirrup
4-25mm+12-20mm 4-25mm+12-20mm 16-20mm 10-20mm+6-16mm 6-20mm+10-16mm 4-20mm+12-16mm
WHEN MECHANICAL SPLICES OR WELDED
SPLICES ARE USED, NOT MORE THEN
SIZE 32"X17" 30"X15" 30"X15" 30"X15" 30"X15" 30"X15" ALTERNATE BARS MAY BE SPLICED AT ANY
SECTION WITH VERTICAL DISTANCE
BETWEEN SPLICES 24(N.(600mm)OR MORE
CLEAR HEIGHT
OF COLUMN
3"(75 mm)MIN
C6
b
6d
COL.
TIES
6db
16-25mm 16-25mm 10-25mm+ 6-25mm+ 8-20mm+ 135
90
db
6-20mm 10-20mm 16-20mm 8-16mm
SIZE 27"X22" 25"X20" 25"X20" 25"X20" 25"X20" 25"X20"
St=8"
SUPPLEMENTARY CEOSSTIES
(ALTERNATE 90"AND 135` ENDS
ON CONSECUTIVE CROSSTIES
C7
HOOPS
Sh=4"
COL.
lo
6 db (>3in.) 6 db extention
6 db (>3in.)
- 6 db extention
-
SEC. OF TIE DETAIL
Offset bars from
column below
Notes for Column:
Bars in column above 1. Concrete should have a 28 days compressive strength, f'c = 4000 psi.
X X X
Clear spacing
2. All Reinforcement bars should be deformed bar having yield strength, fy = 60,000 psi.(60 Grade)
X=14"
X X X (a) Offset column bars 4. If any information is not given should be taken from General Notes.
X=14in
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
SHEET NO :
PROJECT NAME : OMEGA
STRUCTURAL DRAWING HAS BEEN DONE AS PER
S-16
Engr.Suraya Nasrin COLUMN SCHEDULE Rev-00 ARCHITECTURAL DRAWING PROVIDED BY CLIENT.
3'-11" 3'-9"
1'-0" 1'-0" 1'-0" 1'-0"
1'-0"
10"
8-20mm 8-20mm
8-20mm 8-20mm
12mm@4"c/c both side 12mm@4"c/c both side
16mm@5"c/c
16mm@5"c/c
3'-9" 3'-9"
1'-0" 1'-0" 1'-0" 1'-0"
10"
10"
8-20mm 8-20mm
8-20mm 8-20mm
12mm@4"c/c both side 12mm@6"c/c both side
16mm@5"c/c
16mm@5"c/c
REVISION NO. :
SHEET NO :
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : DISCLAIMER :
PROJECT NAME : NABIL TOWER
C2=12"X25"
C2=12"X25"
FLOOR BEAM
FLOOR BEAM
FLOOR BEAM
4'-9"
5'-8"
SW-1=10"X45"
SW-1=10"X45"
3'-9"
3'-9"
FLOOR BEAM
5"
REINF.DETAILS OF LIFT CORE WALL TYPICAL 10" 5'-8" 10"
REINF.DETAILS OF LIFT CORE WALL BELOW PL
12mm@5"c/c both side
8-20mm 10mm@5"c/c 8-20mm
1'-4"
4'-4"
10mm@5"c/c
Column Column
12mm@6"c/c
16mm@5"c/c both side
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
phone: 01521-456877
mail: [email protected]
Notes for UGWR:
1. Concrete should have a 28 days compressive strength, f'c = 4000 psi.
2. All Reinforcement bars should be deformed bar having yield strength, fy = 60,000 psi.(60 Grade)
4. If any information is not given should be taken from General Notes.
12mmØ@8"c/c. 12mmØ@8"c/c.
10mmØ@6"c/c. 10mmØ@6"c/c.
24" Manhole 24" Manhole
Cover Cover
1 A 1
(B)
A A
B
A A
(A)
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
2'-3"
4'-8" 11'-5" 4'-7" 16'-7" 5'-1" 7'-1" 3'-8" 4'-8"
7'-2"
GB1-12"X20" GB1-12"X20"
1
GB9-12"X20"
GB1
12'-4"
0 -1
GB8-12"X20"
2"X
20"
GB2-12"X20"
2
8'-4"
GB10-12"X20"
GB9
-1
GB
2"X2
GB3-12"X20"
3
8-1
2"
4'-6"
X2
0"
0"
GB7-12"X20"
4
GB3-1
3'-7"
2"X20
"
0"
"X2 GB3-12"X20"
5
2
A-1
B3
4'-3"
GB10-12"X20"
6"
GB9-12"X20"
6
GB8-12"X20"
8'-4"
14'-0"
15'-0"
UGWR GB4A-12"X20"
GB10-12"X20"
7
2'-4"
8
0 "
2"X2
4'-2"
GB -1
4-1 GB4
GB7-12"X20"
2"X
20"
9
3'-8"
10
20"
"
20
4'-6"
"X
-12"X
12
5-
GB5-12"X20" GB G
B5
GB9
11
-1
2"
X2
0"
8'-6"
GB5-12"X20"
GB8A-12"X20"
12
GB1
GB9-12"X20"
0-12
12'-2"
20" "X
13
GB6-12"X20" GB6-12"X20"
6'-2"
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
phone: 01521-456877
mail: [email protected]
B E G E H
2-16mmØext 1-16mmØext 1-16mmØext 2-16mmØext
2-20mmØst 2-16mmØext 2-16mmØext 2-20mmØst
7'-3" 7'-3" 3'-2" 3'-2" 4'-6" 4'-6"
4-20mmØst
10Ø@4"/7"/4" c/c
2-20mm+2-16mmØst
10Ø@4"/7"/4" c/c 2-20mm+2-16mmØst 3'-9" 7'-9" 1'-0"
10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c
1'-0" 9'-8" 2'-6" 4'-4" 2'-1" 19'-7" 2'-6" 2'-1"
LONG SECTION OF GRADE BEAM-GB-4A-{12"x20"}
LONG SECTION OF GRADE BEAM-GB-3-{12"x20"}
A D F
A D 2-16mmØext 2-16mmØext
1-20mmØext 2-20mmØst 2-20mmØst
2-20mmØst 5'-2" 5'-2" 6'-6" 6'-6"
5'-2" 5'-2"
4-20mmØst
3-20mmØst 10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c
10Ø@4"/7"/4" c/c
2'-1" 15'-5" 2'-1" 2'-1" 15'-5" 2'-1" 19'-7" 3'-9"
LONG SECTION OF GRADE BEAM-GB3A-{12"x20"} LONG SECTION OF GRADE BEAM-GB-4-{12"x20"}
A C E E H
2-16mmØext 2-16mmØext 2-16mmØext
2-20mmØst 2-20+2-16mmØst 2-20mmØst 2-20mmØst
3'-6" 3'-6" 4'-10" 4'-10" 4'-7" 4'-7"
3-20mmØst 3-20mmØst
10Ø@4"/7"/4" c/c 10Ø@4" c/c 10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c
1'-0" 10'-3" 2'-6" 3'-9" 2'-1" 14'-7" 1'-8" 13'-9" 2'-1"
LONG SECTION OF GRADE BEAM-GB-5-{12"x20"}
B F H
2-16mmØext 2-16mmØext
2-16mmØst
6'-10" 6'-10" 3'-5" 3'-5"
3-20mmØst 3-20mmØst
10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c
1'-8" 20'-5" 2'-1" 9'-11" 1'-0"
SHEET NO :
CONSULTANT : PROJECT INFORMATION : DRAWING TITLE : DISCLAIMER :
PROJECT NAME : OMEGA Engr.Suraya Nasrin
M.Sc Engg.(Structural),BUET GRADE BEAM DETAILS Rev-00
STRUCTURAL DRAWING HAS BEEN DONE AS PER
ARCHITECTURAL DRAWING PROVIDED BY CLIENT.
S-21
PROJECT TYPE: PROPOSED 9-STORIED RESIDENTIAL BUILDING STRUCTURAL CONSULTANT ARE NOT RESPONSIBLE
FIEB, DMINB FOR ANY VIOLATION OF CODE & CONDUCT OR THE CAD BY:
CORE DESIGN ADVISOR'S SCALE:
House-13, Road-9,Sector-6,Uttara Model Town,Uttara,Dhaka-1230 PROJECT ADDRESS: PLOT NO - 369, ROAD NO-10, BLOCK-C
Cell: +8801716780910 RESPECTIVE AUTHORITY.
phone: 01521-456877
mail: [email protected] BASHUNDHARA RESIDENTIAL AREA, DHAKA. NOT TO SCALE DATE : FEBRUARY ,2025
11 8 6 3
2-20mmØext 2-20mmØext 2-20mmØext
2-20mmØst 2-20mmØst 2-20mmØst
3'-7" 3'-7" 3'-3" 3'-3" 3'-5" 3'-5"
4-20mmØst
10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c
1'-8" 10'-8" 1'-0" 9'-8" 1'-0" 10'-3" 2'-1"
LONG SECTION OF GRADE BEAM-GB-7-{12"x20"}
10 8 6 4 13 11
2-16mmØext 2-16mmØext
2-16mmØext
2-20mmØst 2-20mmØst 2-20mmØst
6'-1" 6'-6"
8'-3" 8'-3" 6'-4" 6'-4"
13 12 9 7 4 2 1
2-20mmØext
2-20mmØext 2-20mmØext 2-20mmØext 2-20mmØext 2-20mmØst
2-20mmØst 2-20mmØst 2-20mmØst 2-20mmØst
3'-6" 3'-6" 5'-3" 5'-3" 3'-11" 3'-11" 5'-1" 5'-1" 3'-3" 3'-3"
4-20mmØSt 4-20mmØSt
10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c
1'-0" 10'-6" 1'-8" 15'-9" 10" 5'-8" 10" 11'-8" 15'-4" 9'-8" 1'-0"
4-20mmØSt 4-20mmØSt
10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c
1'-8" 10'-6" 1'-0" 15'-7" 1'-0" 5'-8" 2'-1" 10'-5" 14'-11" 10'-8" 1'-8"
SHEET NO :
CONSULTANT : PROJECT INFORMATION : DRAWING TITLE : DISCLAIMER :
PROJECT NAME : OMEGA Engr.Suraya Nasrin
M.Sc Engg.(Structural),BUET GRADE BEAM DETAILS Rev-00
STRUCTURAL DRAWING HAS BEEN DONE AS PER
ARCHITECTURAL DRAWING PROVIDED BY CLIENT.
S-22
PROJECT TYPE: PROPOSED 9-STORIED RESIDENTIAL BUILDING STRUCTURAL CONSULTANT ARE NOT RESPONSIBLE
FIEB, DMINB FOR ANY VIOLATION OF CODE & CONDUCT OR THE CAD BY:
CORE DESIGN ADVISOR'S SCALE:
House-13, Road-9,Sector-6,Uttara Model Town,Uttara,Dhaka-1230 PROJECT ADDRESS: PLOT NO - 369, ROAD NO-10, BLOCK-C
Cell: +8801716780910 RESPECTIVE AUTHORITY.
phone: 01521-456877
mail: [email protected] BASHUNDHARA RESIDENTIAL AREA, DHAKA. NOT TO SCALE DATE : FEBRUARY ,2025
Ø8 STI. @ 5" C/C Ø8 STI. @ 5" C/C
R.C.C .MANHOLE
COVER (M)
SCHEDULE OF SEPTIC TANK
2.5"
2.5"
12"
6"
RCC.TOP SLAB. DIMENSION
12"
10"
2-Ø16
12"
16mm Ø MS. LENGTH = L 19'-6"
13"
STEP BAR.
2-Ø16 175 75
12"
3'-7" BREATH = B 8'-3"
2.5"
12"
6"
2.5"
Note:all dimensions as per architectural drawing.
6" DETAILS OF STRUT.
DETAILS OF BAFFEL WALL' PART CROSS SEC.
OF SEPTIC TANK
THROUGH MANHOLE. Ø10 mm Both way.
7"
VARIABLE
Ø10 @ 5" C/C t&b
Ø10 @ 5" C/C t&b Ø10 @ 5" C/C t&b
Ø10 @ 175C/C t
900 900
T=7"
EQ
R.C.C. STRUT ( 6"WIDE )
EQ
PLASTER 1:3 INCLUDING
SIMULTANEOUS NEAT
CEMENT FINISHING
3" 3"
Note:use 10mmØ@8" c/c as a binder where required.
6"
TOP SLAB REINFORCEMENT PLAN.
10" B 10"
(M)
Ø10mm@ 7" C/C
24"
F.G.L.
SECTION ON B-B
2.5"
7"
7"
REVISION NO. :
SHEET NO :
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : DISCLAIMER :
PROJECT NAME : OMEGA
D = DEPTH OF INVERT
(VARIABLE)
(M) R.C.C .MANHOLE COVER (M)
7"
5"
D 5" 6" OUTLET PIPE. D
FALL IN LEVEL.
6"
4"
6"
3"
15"
3"
6"
12"
E E
15"
INLET PIPE.
12"
12"
16mm Ø M.S. BAR STEPS
6'-6" + D
9"
12"
C C
.5" THICK CEMENT SAND .5"THICK CEMENT SAND
12"
PLASTER 1:3 INCLUDING PLASTER 1:3 INCLUDING
SIMULTANEOUS NEAT SIMULTANEOUS NEAT
CEMENT FINISHING. CEMENT FINISHING.
3"
3"
3" 6"
C.C. IN 1:3:6
EQ EQ
10"
L
Y
EQ EQ
uPVC PIPE
OUTLET
450x5" R.C.C. BAFFLE WALL.
A A
10"
600x600 MAN HOLE
Y
6"X 375 STRUTS
REVISION NO. :
SHEET NO :
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : DISCLAIMER :
PROJECT NAME : OMEGA
2'-6"
d12 @ 4" C/C 10" LOAD BEARING
7"
1'- BRICK WALL
d12 @ 4" C/C
d10 @ 8" C/C
d12 @ 4" C/C SEC. A-A STAIR(1ST FLIGHT)
AS ACTUAL
6"
3'-0"
d12 @ 8" C/C
2'-
3" d12 @ 4" C/C
d10 @ 8" C/C
22"
d12 @ 8" C/C d12 @ 4" C/C
2-d20 ext.
2-d20 ext.
"
22
6"
1'-
2'-0"
22"
d12 @ 8" C/C FB 3-d20 st. 0"
d10 @ 6" C/C d10 @ 8" C/C
2-d20 ext.
d12 @ 4" C/C
LB
SEC. D-D STAIR (4TH FLIGHT)
10mmØ@4", 6", 4" c/c
LB SECTION(10"X22")
D
LB=10"X22" B
C C
STAIR
10'-10"X11'-8"
A A
UP
B
D
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
phone: 01521-456877
mail: [email protected]
d12 @ 8" C/C
d12 @ 8" C/C
7" 0"
1'- gap
2'-6"
d12 @ 4" C/C 10" LOAD BEARING
7"
1'- BRICK WALL
d12 @ 4" C/C
d10 @ 8" C/C
3'-0"
d12 @ 8" C/C
2'-
3" d12 @ 4" C/C
d10 @ 8" C/C
22"
d12 @ 8" C/C
d12 @ 4" C/C 2-d20 ext.
2-d20 ext.
"
22
1'-
2'-0"
22"
d12 @ 8" C/C FB 3-d20 st. 0"
d10 @ 6" C/C d10 @ 8" C/C
2-d20 ext.
d12 @ 4" C/C
LB
SEC. D-D STAIR(4TH FLIGHT)
10mmØ@4", 6", 4" c/c
LB SECTION(10"X22")
D
LB=10"X22" B
C C
STAIR
10'-10"X11'-8"
A A
UP
B
D
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
phone: 01521-456877
mail: [email protected]
A B C D E F G H
2'-3"
11'-5" 4'-7" 16'-7" 5'-1" 7'-1" 3'-8" 4'-8"
1
B1=12"X24"
B11=12"X24"
B14=12"X24"
B9=12"X24"
12'-4"
2
B2=12"X24" B2=12"X24"
B9=12"X24"
8'-4"
B12=12"X24"
B15=12"X24"
3
B3=12"X24"
4'-6"
B3
A=
B8=12"X24"
12
"X
4
24
3'-7"
" B4=12"X24"
B5=12"X24"
5
4'-3"
B6=12"X24"
6
B10=15"X24"
8'-4"
B12=12"X24"
B7=12"X24"
B13=12"X24"
7
2'-4"
8
B6=12"X24"
4'-2"
B8=12"X24"
9
3'-8"
B7=12"X24"
4 "
X2 B4=12"X24"
2"
10
1
A=
4'-6"
B3
B12=12"X24"
B16=12"X24"
B3=12"X24"
11
8'-6"
B2=12"X24" B2=12"X24"
12
B9=10"X24"
B11=12"X24"
B14=12"X24"
12'-2"
B1=12"X24" B1=12"X24"
13
S
N 1ST FLOOR BEAM LAYOUT
E
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
phone: 01521-456877
mail: [email protected]
B E H
3-20mmØext 2-20mmØext
B E G 2-20mmØst
2-20mm+2-16mmØst
10Ø@4"/7"/4" c/c
4-20mmØst 4-20mmØst
LONG SECTION OF 1ST FLOOR BEAM-B4-{12"x20"}
10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c 4'-4" 2'-1" 19'-7" 1'-0"
1'-8" 21'-10" 2'-6" 9'-6" 1'-0"
LONG SECTION OF 1ST FLOOR BEAM-B1-{12"x20"}
B E H F 2-20mmØext H
A B 2-16mmØext
1-20mmØext
3-20mmØext 2-20mmØst
2-20mmØext 2-20mmØext 2-20mmØext 2-20mmØst 3-20mmØext 2-20mmØst
2-20mmØst 4'-6" 4'-6" 2'-8" 2'-8"
6'-9"
3'-3" 3'-3"
4-20mmØst
4-20mmØst 4-20mmØst
2-20mm+2-16mmØst 10Ø@4"/7"/4" c/c
10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c 2'-6" 7'-11" 2'-1"
10Ø@4"/7"/4" c/c 1'-0" 20'-3" 1'-8" 13'-9" 2'-1"
1'-0" 9'-8" 2'-6" LONG SECTION OF 1ST FLOOR BEAM-B2-{12"x24"} LONG SECTION OF 1ST FLOOR BEAM-B5-{12"x24"}
LONG SECTION OF 1ST FLOOR BEAM-B3/B3A-{12"x24"}
A D E 2-16mmØext
H
2-20mmØext 2-16mmØext
3-20mmØst 2-20mmØst
5'-6" 2'-5" 2'-5"
3-20mmØst 2-20mm+2-16mmØst
10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c
2'-1" 16'-6" 1'-0" 2'-11" 8'-7" 1'-0"
LONG SECTION OF 1ST FLOOR BEAM-B6-{12"x24"} LONG SECTION OF 1ST FLOOR BEAM-B7-{12"x24"}
3 1
3-20mmØext 2-20mmØext 3-20mmØext
11 8 6 3
2-20mmØst 2-20mmØext 2-20mmØext 2-20mmØext
2-20mmØst 2-20mmØst 2-20mmØst
6'-4" 6'-4"
3'-7" 3'-7" 3'-3" 3'-3" 3'-5" 3'-5"
4-20mmØst
4-20mmØst
10Ø@4"/7"/4" c/c
1'-8" 19'-0" 1'-0" 10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c
1'-8" 10'-8" 1'-0" 9'-8" 1'-0" 10'-3" 2'-1"
LONG SECTION OF 1ST FLOOR BEAM-B9-{12"x24"}
LONG SECTION OF 1ST FLOOR BEAM-B-8-{12"x24"}
SHEET NO :
CONSULTANT : PROJECT INFORMATION : DRAWING TITLE : DISCLAIMER :
PROJECT NAME : OMEGA Engr.Suraya Nasrin
M.Sc Engg.(Structural),BUET 1ST FLOOR BEAM DETAILS Rev-00
STRUCTURAL DRAWING HAS BEEN DONE AS PER
ARCHITECTURAL DRAWING PROVIDED BY CLIENT.
S-28
PROJECT TYPE: PROPOSED 9-STORIED RESIDENTIAL BUILDING STRUCTURAL CONSULTANT ARE NOT RESPONSIBLE
FIEB, DMINB FOR ANY VIOLATION OF CODE & CONDUCT OR THE CAD BY:
CORE DESIGN ADVISOR'S SCALE:
House-13, Road-9,Sector-6,Uttara Model Town,Uttara,Dhaka-1230 PROJECT ADDRESS: PLOT NO - 369, ROAD NO-10, BLOCK-C
Cell: +8801716780910 RESPECTIVE AUTHORITY.
phone: 01521-456877
mail: [email protected] BASHUNDHARA RESIDENTIAL AREA, DHAKA. NOT TO SCALE DATE : FEBRUARY ,2025
2 2-20mmØext 1 10 4
2-20mmØext
3-20mmØext 2-25mmØext 3-20mmØext
2-20mmØst 2-25mmØst
3'-6" 3'-6" 8'-3" 8'-3"
4-20mmØst 3-20mmØSt
3-25mmØSt
10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c
1'-0" 10'-6" 1'-8"
LONG SECTION OF 1ST FLOOR BEAM-B11-{12"x24"} 1'-8" 24'-8" 1'-8"
LONG SECTION OF 1ST FLOOR BEAM-B10-{15"x24"}
12 9 7 5 2
2-20mmØext 2-20mmØext 2-20mmØext 2-20mmØext 2-20mmØext
2-20mmØst 2-20mmØst 2-20mmØst
5'-3" 5'-3" 3'-11" 3'-11" 5'-1" 5'-1"
4-20mmØSt 4-20mmØSt
10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c
1'-0" 15'-9" 10" 5'-8" 10" 11'-8" 1'-0" 15'-7" 1'-0"
LONG SECTION OF 1ST FLOOR BEAM-B12-{12"x24"}
9 7
13 12
3-20mmØSt
2-25+2-20mmØSt
3-20mmØSt
4-20mmØSt 10Ø@4"/7"/4" c/c
10Ø@4"/7"/4" c/c 10" 6'-6" 10"
1'-8" 11'-6"
LONG SECTION OF 1ST FLOOR BEAM-B13-{12"x24"}
LONG SECTION OF 1ST FLOOR BEAM-B14-{12"x24"}
7 4 2
12 9 2-25mmØext 2-20mmØext 2-25mmØext 2-20mmØext 2-25mmØext
1-25mmØext 2-20mmØst 2-20mmØst
3-20mmØext 3-20mmØext
2-20mmØst 3'-6" 3'-6" 5'-1" 5'-1"
5'-2" 5'-2"
2-25+2-16mmØSt
3-20mmØSt
3-20mmØSt 10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c
10Ø@4"/7"/4" c/c
2'-1" 10'-5" 15'-2"
1'-0" 15'-7" 1'-0"
LONG SECTION OF 1ST FLOOR BEAM-B16-{12"x24"} LONG SECTION OF 1ST FLOOR BEAM-B15-{12"x24"}
SHEET NO :
CONSULTANT : PROJECT INFORMATION : DRAWING TITLE : DISCLAIMER :
PROJECT NAME : OMEGA Engr.Suraya Nasrin
M.Sc Engg.(Structural),BUET 1ST FLOOR BEAM DETAILS Rev-00
STRUCTURAL DRAWING HAS BEEN DONE AS PER
ARCHITECTURAL DRAWING PROVIDED BY CLIENT.
S-29
PROJECT TYPE: PROPOSED 9-STORIED RESIDENTIAL BUILDING STRUCTURAL CONSULTANT ARE NOT RESPONSIBLE
FIEB, DMINB FOR ANY VIOLATION OF CODE & CONDUCT OR THE CAD BY:
CORE DESIGN ADVISOR'S SCALE:
House-13, Road-9,Sector-6,Uttara Model Town,Uttara,Dhaka-1230 PROJECT ADDRESS: PLOT NO - 369, ROAD NO-10, BLOCK-C
Cell: +8801716780910 RESPECTIVE AUTHORITY.
phone: 01521-456877
mail: [email protected] BASHUNDHARA RESIDENTIAL AREA, DHAKA. NOT TO SCALE DATE : FEBRUARY ,2025
A B C D E F G H
2'-3"
11'-5" 4'-7" 16'-7" 5'-1" 7'-1" 3'-8" 4'-8"
1'-6"
1'-6"
A 1
2'-10" 2'-10" 1'-5" 1'-5"
12'-4"
1
1 1
1'-6"
1'-6"
2
1'-6"
2'-0"
A 1
8'-4"
1
3'-4" 3'-4" 1'-4" 1'-4"
3
1 1
1'-6"
4'-6"
1'-6"
4
1
3'-7"
3'-3"
2'-0"
2'-2" 1 2'-2" 2'-5"
2'-5"
4'-3"
1'-6"
C
1
6
T=6"
1'-2"
8'-4"
1 1
1'-2"
7
2'-4"
8
2'-5"
1'-4"
2'-5"
4'-2"
2'-2" 2'-2"
9
2'-0"
1
3'-8"
3'-3"
1
10
1'-6"
1'-4"
4'-6"
1 1
11
A
1'-4" 1'-4"
3'-2" 1
3'-2"
8'-6"
2'-0"
1'-6"
12
1'-5"
1
1
1 1
12'-2"
B
2'-8" 2'-8" 1'-5" 1'-5"
13
1'-5"
N
1ST FLOOR SLAB REINF. (BOTTOM BAR)
W SLAB THICKNESS=5" UNLESS SHOWN IN DRAWING
S
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
phone: 01521-456877
mail: [email protected]
A B C D E F G H
2'-3"
11'-5" 4'-7" 16'-7" 5'-1" 7'-1" 3'-8" 4'-8"
3'-9"
3'-9"
4
4
1 2
12'-4"
3'-9"
7'-6" 3'-9"
7'-6"
2 2
3'-9"
3'-9"
2
3'-10"
5'-2"
2 3
8'-4"
1
8'-11" 3'-6" 3'-6"
8'-11"
2
3
3'-10"
4'-6"
3'-9"
5'-2"
4
2
3'-7"
5'-10" 1 2
3 5'-10" 6'-6"
5
8'-8"
4'-3"
3'-9"
1
2 6'-6"
6
3'-3"
2
8'-4"
T=6"
5'-10"
5'-10" 6'-6"
3
3'-3"
7
2'-4"
8
1
4'-2"
3'-9"
2
8'-8"
9
5'-10"
3'-8"
5'-10"
5'-3"
1
3
10
4'-6"
3'-9"
1
3'-11"
2
2 3
11
3
8'-5"
8'-6"
3'-6" 3'-6"
8'-5"
5'-3"
2
3'-11"
12
3'-9"
3'-9"
2 2
1 2
12'-2"
3'-9"
7'-0" 7'-0" 3'-9"
1
3'-9"
3'-9"
4
4
13
W
N TOP DIMENTION OF SLAB REINF.
S
LEGEND FOR SLAB BAR
(1)12mmØ @ 4"c/c
E
(2)12mmØ @ 6"c/c
(3)10mmØ @ 6"c/c Slab Outline as per
(4)10mmØ @ 7"c/c Architectural Drawing
Use 10mmØ @ 8" c/c as a binder
where required
N
W 1ST FLOOR SLAB REINF. (TOP BAR) SLAB THICKNESS=5"
UNLESS SHOWN IN DRAWING
S
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
phone: 01521-456877
mail: [email protected]
A B C D E F G H
2'-3"
11'-5" 4'-7" 16'-7" 5'-1" 7'-1" 3'-8" 4'-8"
12'-4"
2
8'-4"
3
4'-6"
4
3'-7"
5
4'-3"
6
8'-4"
7
2'-4"
8
4'-2"
9
3'-8"
10
4'-6"
11
8'-6"
12
12'-2"
1
13
1
T=5"
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
phone: 01521-456877
mail: [email protected]
A B C D E F G H
2'-3"
11'-5" 4'-7" 16'-7" 5'-1" 7'-1" 3'-8" 4'-8"
1
B1=12"X24"
B11=12"X24"
B14=12"X24"
B9=12"X24"
12'-4"
2
B2=12"X24" B2=12"X24"
B9=12"X24"
8'-4"
B12=12"X24"
B15=12"X24"
3
B3=12"X24"
4'-6"
B8=12"X24"
4
3'-7"
B4=12"X24"
B5=12"X24"
5
4'-3"
B6=12"X24"
6
B15=12"X24"
8'-4"
B12=12"X24"
B7=12"X24"
B13=12"X24"
7
2'-4"
8
B6=12"X24"
4'-2"
B8=12"X24"
9
3'-8"
B7=12"X24"
B4=12"X24"
10
4'-6"
B12=12"X24"
B16=12"X24"
B3=12"X24"
11
8'-6"
B2=12"X24" B2=12"X24"
12
B9=10"X24"
B11=12"X24"
B14=12"X24"
12'-2"
B1=12"X24" B1=12"X24"
13
S
N TYPICAL FLOOR BEAM LAYOUT
E
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
phone: 01521-456877
mail: [email protected]
B E H
3-20mmØext 2-20mmØext
B E G 2-20mmØst
2-20mm+2-16mmØst
10Ø@4"/7"/4" c/c
4-20mmØst 4-20mmØst 4'-4" 2'-1" 19'-7" 1'-0"
10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c
1'-8" 21'-10" 2'-6" 9'-6" 1'-0" LONG SECTION OF TYPICAL FLOOR BEAM-B4-{12"x20"}
LONG SECTION OF TYPICAL FLOOR BEAM-B1-{12"x20"}
B E H F 2-20mmØext H
A B 2-16mmØext
1-20mmØext
3-20mmØext 2-20mmØst
2-20mmØext 2-20mmØext 2-20mmØext 2-20mmØst 3-20mmØext 2-20mmØst
2-20mmØst 6'-9" 4'-6" 4'-6" 2'-8" 2'-8"
3'-3" 3'-3"
4-20mmØst
4-20mmØst 4-20mmØst
2-20mm+2-16mmØst 10Ø@4"/7"/4" c/c
10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c 2'-6" 7'-11" 2'-1"
10Ø@4"/7"/4" c/c 1'-0" 20'-3" 1'-8" 13'-9" 2'-1" LONG SECTION OF TYPICAL FLOOR BEAM-B5-{12"x24"}
1'-0" 9'-8" 2'-6" LONG SECTION OF TYPICAL FLOOR BEAM-B2-{12"x24"}
LONG SECTION OF TYPICAL FLOOR BEAM-B3/B3A-{12"x24"}
11 8
A D E 2-16mmØext
H 2-20mmØext
1-20mmØext
2-20mmØext 1-20mmØext 2-20mmØst
3-20mmØst 2-20mmØst
3'-7" 3'-7"
5'-6" 2'-10" 2'-10"
4-20mmØst
3-20mmØst 2-20mm+2-16mmØst
10Ø@4"/7"/4" c/c
10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c 1'-8" 10'-8" 1'-0"
2'-1" 16'-6" 1'-0" 2'-11" 8'-7" 1'-0"
LONG SECTION OF TYPICAL FLOOR BEAM-B7-{12"x24"} LONG SECTION OF TYPICAL FLOOR BEAM-B8-{12"x24"}
LONG SECTION OF TYPICAL FLOOR BEAM-B6-{12"x24"}
3 1
3-20mmØext 2-16mmØext 3-20mmØext
2-20mmØst
4-20mmØst
SHEET NO :
CONSULTANT : PROJECT INFORMATION : DRAWING TITLE : DISCLAIMER :
PROJECT NAME : OMEGA Engr.Suraya Nasrin
M.Sc Engg.(Structural),BUET TYPICAL FLOOR BEAM DETAILS Rev-00
STRUCTURAL DRAWING HAS BEEN DONE AS PER
ARCHITECTURAL DRAWING PROVIDED BY CLIENT.
S-34
PROJECT TYPE: PROPOSED 9-STORIED RESIDENTIAL BUILDING STRUCTURAL CONSULTANT ARE NOT RESPONSIBLE
FIEB, DMINB FOR ANY VIOLATION OF CODE & CONDUCT OR THE CAD BY:
CORE DESIGN ADVISOR'S SCALE:
House-13, Road-9,Sector-6,Uttara Model Town,Uttara,Dhaka-1230 PROJECT ADDRESS: PLOT NO - 369, ROAD NO-10, BLOCK-C
Cell: +8801716780910 RESPECTIVE AUTHORITY.
phone: 01521-456877
mail: [email protected] BASHUNDHARA RESIDENTIAL AREA, DHAKA. NOT TO SCALE DATE : FEBRUARY ,2025
2 2-20mmØext 1 10 4
2-20mmØext
3-20mmØext 2-25mmØext 3-20mmØext
2-20mmØst 2-25mmØst
3'-6" 3'-6" 8'-3" 8'-3"
4-20mmØst 3-20mmØSt
3-25mmØSt
10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c
1'-0" 10'-6" 1'-8"
LONG SECTION OF TYPICAL FLOOR BEAM-B11-{12"x24"} 1'-8" 24'-8" 1'-8"
LONG SECTION OF TYPICAL FLOOR BEAM-B10-{15"x24"}
12 9 7 5 2
2-20mmØext 2-20mmØext 2-20mmØext 2-20mmØext 2-20mmØext
2-20mmØst 2-20mmØst 2-20mmØst
5'-3" 5'-3" 3'-11" 3'-11" 5'-1" 5'-1"
4-20mmØSt 4-20mmØSt
10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c
1'-0" 15'-9" 10" 5'-8" 10" 11'-8" 15'-7"
LONG SECTION OF TYPICAL FLOOR BEAM-B12-{12"x24"}
9 7
13 12
2-20+1-16mmØSt
2-25+2-20mmØSt
2-20+1-16mmØSt
4-20mmØSt 10Ø@4"/7"/4" c/c
10Ø@4"/7"/4" c/c 10" 6'-6" 10"
1'-8" 11'-6"
LONG SECTION OF TYPICAL FLOOR BEAM-B14-{12"x24"} LONG SECTION OF TYPICAL FLOOR BEAM-B13-{12"x24"}
12 9 7 4 2
3-20mmØext 1-25mmØext 3-20mmØext 2-25mmØext 2-20mmØext 2-25mmØext 2-20mmØext 2-25mmØext
2-20mmØst 2-20mmØst 2-20mmØst
5'-2" 5'-2" 3'-6" 3'-6" 5'-1" 5'-1"
3-20mmØSt
3-20mmØSt 2-25+2-16mmØSt
10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c 10Ø@4"/7"/4" c/c
SHEET NO :
CONSULTANT : PROJECT INFORMATION : DRAWING TITLE : DISCLAIMER :
PROJECT NAME : OMEGA Engr.Suraya Nasrin
M.Sc Engg.(Structural),BUET TYPICAL FLOOR BEAM DETAILS Rev-00
STRUCTURAL DRAWING HAS BEEN DONE AS PER
ARCHITECTURAL DRAWING PROVIDED BY CLIENT.
S-35
PROJECT TYPE: PROPOSED 9-STORIED RESIDENTIAL BUILDING STRUCTURAL CONSULTANT ARE NOT RESPONSIBLE
FIEB, DMINB FOR ANY VIOLATION OF CODE & CONDUCT OR THE CAD BY:
CORE DESIGN ADVISOR'S SCALE:
House-13, Road-9,Sector-6,Uttara Model Town,Uttara,Dhaka-1230 PROJECT ADDRESS: PLOT NO - 369, ROAD NO-10, BLOCK-C
Cell: +8801716780910 RESPECTIVE AUTHORITY.
phone: 01521-456877
mail: [email protected] BASHUNDHARA RESIDENTIAL AREA, DHAKA. NOT TO SCALE DATE : FEBRUARY ,2025
A B C D E F G H
2'-3"
11'-5" 4'-7" 16'-7" 5'-1" 7'-1" 3'-8" 4'-8"
1'-6"
1'-6"
2'-10" A 2'-10" 1'-5" 1 1'-5"
12'-4"
1
1 1
1'-6" 1'-6"
1'-6"
2
2'-0"
A 1
8'-4"
1
T=6" 3'-4" 3'-4" 1'-4" 1'-4"
3
1 1
1'-6"
4'-6"
1'-6"
4
1
3'-7"
3'-3"
2'-0"
3-12mmØst
2'-2"
4'-3"
1'-6"
C
6
1
8'-4"
T=6"
1
7
2'-4"
8
2'-6"
1'-4"
2'-6"
4'-2"
2'-2"
1'-6"
9
2'-0"
3-12mmØst
1
3'-8"
3'-3"
1
1
10
1'-4"
1'-6"
4'-6"
1 1
11
A 1 1'-4"
T=6" 3'-2" 1'-4"
3'-2"
8'-6"
2'-0"
1'-6"
12
1'-5"
1
1
1 1
12'-2"
B
2'-8" 2'-8" 1'-5" 1'-5"
1'-5"
T=6"
13
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
phone: 01521-456877
mail: [email protected]
A B C D E F G H
2'-3"
11'-5" 4'-7" 16'-7" 5'-1" 7'-1" 3'-8" 4'-8"
1
4
3'-9"
3'-9"
4
T=6"
4
1 2
12'-4"
3'-9"
7'-6" 3'-9"
7'-6"
2 1
3'-9"
3'-9"
2
3'-10"
5'-2"
3
8'-4"
3
8'-10" 3'-6" 3'-6"
T=6" 8'-10"
2
2
3
3'-10"
3'-9"
4'-6"
5'-2"
4
1
3'-7"
5'-10"
2
3 5'-10" 6'-6"
5
8'-8"
3'-9"
4'-3"
3
2 6'-6"
2
6
2
8'-4"
T=6"
6'-6"
7
2'-4"
8
4'-2"
3'-9"
3
8'-8"
9
5'-10"
5'-10"
3'-8"
5'-3"
3
3
10
3'-9"
4'-6"
1
3'-11"
2
2 3
11
3 8'-5"
T=6"
8'-6"
3'-6" 3'-6"
8'-5"
5'-3"
2
3'-11"
12
3'-9"
3'-9"
2
2
1 1
3'-9"
12'-2"
3'-9"
4
4
T=6"
13
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
phone: 01521-456877
mail: [email protected]
A B C D E F G H
2'-3"
11'-5" 4'-7" 16'-7" 5'-1" 7'-1" 3'-8" 4'-8"
1
12'-4"
2
8'-4"
3
6'-0"
T=6"
4'-6"
4
3'-7"
B4=12"X24"
B5=12"X24"
5
4'-3"
6
B15=12"X24"
B12=12"X24"
B7=12"X24"
B13=12"X24"
7
2'-4"
8
4'-2"
9
3'-8"
B7=12"X24"
B4=12"X24"
10
4'-6"
6'-0"
11
8'-6"
12'-2"
13
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
phone: 01521-456877
mail: [email protected]
A B C D E F G H
2'-3"
11'-5" 4'-7" 16'-7" 5'-1" 7'-1" 3'-8" 4'-8"
1
12'-4"
2
8'-4"
3
T=6"
4'-6"
4
3'-7"
3'-3" 2'-7"
5
2'-7"
4'-3"
A
6
T=6"
8'-4"
B
7
2'-4"
8
2'-7"
2'-7"
4'-2"
9
3'-8"
3'-3"
10
4'-6"
T=6"
11
8'-6"
S
N 8TH FLOOR SLAB (COMMUNITY HALL) REINF. (BOTTOM BAR)
E
12
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
phone: 01521-456877
mail: [email protected]
A B C D E F G H
2'-3"
11'-5" 4'-7" 16'-7" 5'-1" 7'-1" 3'-8" 4'-8"
1
12'-4"
2
8'-4"
T=6"
3
6'-0"
6'-0"
4'-6"
4
3'-7"
1
6'-8"
5
7'-0"
8'-8"
4'-3"
7'-0"
1
6
T=6"
2
8'-4"
T=6"
7'-0"
7
2'-4"
8
4'-2"
1
8'-8"
9
3'-8"
10
4'-6"
6'-0"
11
T=6"
8'-6"
W
8TH FLOOR SLAB (COMMUNITY HALL) REINF. (TOP BAR)
12
S
N
CONSULTANT : PROJECT INFORMATION : Structural Engineer DRAWING TITLE : REVISION NO. : DISCLAIMER :
phone: 01521-456877
mail: [email protected]
(Shown in Plan) WATER TANK TOP SLAB
BEAM
5"
10mmØ@8"c/c 10mmØ@8"c/c
10mmØ@8"c/c 10mmØ@8"c/c
10mmØ@6"c/c
10mmØ@6"c/c
6'-2"
MACHINE 10mmØ@4"c/c 10mmØ@4"c/c
ROOM
3'-1"
3'-4" 3'-4"
6"
BEAM BEAM
8"
8'-0"
5'-8"
ROOF SLAB
SECTION OF X-X
X
IB-01
10'-6"
IB-03
OHWT
11'-11"
IB-04
IB-02
5'-8"
MACHINE
ROOM
4'-0"
5'-0"
12'-6"
O H WT & MACHINE
ROOM ROOF PLAN
X
SHEET NO :
CONSULTANT : PROJECT INFORMATION : DRAWING TITLE : DISCLAIMER :
PROJECT NAME : OMEGA Engr.Suraya Nasrin
M.Sc Engg.(Structural),BUET OHWT DETAILS Rev-00
STRUCTURAL DRAWING HAS BEEN DONE AS PER
ARCHITECTURAL DRAWING PROVIDED BY CLIENT.
S-41
PROJECT TYPE: PROPOSED 9-STORIED RESIDENTIAL BUILDING STRUCTURAL CONSULTANT ARE NOT RESPONSIBLE
FIEB, DMINB FOR ANY VIOLATION OF CODE & CONDUCT OR THE CAD BY:
CORE DESIGN ADVISOR'S SCALE:
House-13, Road-9,Sector-6,Uttara Model Town,Uttara,Dhaka-1230 PROJECT ADDRESS: PLOT NO - 369, ROAD NO-10, BLOCK-C
Cell: +8801716780910 RESPECTIVE AUTHORITY.
phone: 01521-456877
mail: [email protected] BASHUNDHARA RESIDENTIAL AREA, DHAKA. NOT TO SCALE DATE : FEBRUARY ,2025
X
X
IB-01
X
IB-01
1'-8"
1 1 10'-6"
4'-0"
IB-03
2 2
OHWT
IB-03
3'-8" 3'-8"
1'-6"
11'-11"
T=6" 1'-6" T=6"
A
IB-04
1
IB-04
A
4'-0"
1'-8"
IB-02 B-05
IB-02
A
B-07
B-08
T=8"
5'-8"
5'-8"
MACHINE
5'-8"
ROOM
MACHINE
ROOM A 4'-0"
4'-0"
4'-0"
B-06
5'-0"
5'-0"
5'-0"
12'-6" 12'-6"
X
O H W T BOTTOM & STAIR ROOM (TOP & BOTTOM BAR)
TOP SLAB(TOP BAR) O H WT & MACHINE LEVEL 5'-8" FROM ROOF SLAB)
X
2-16mmØext
1-20mmØext 1-20mmØext
L/3 L/3 L/3 L/3
2-16mmØst. 2-16mmØst.
3-20mmØst.
10Ø@5"c/c.
10Ø@5"c/c. 10Ø@5"c/c.
3-20mmØst.
SECTION OF BEAM,IB-02-{10"x20"}
SECTION OF BEAM ,IB-01-{10"x20"}
2-16mmØext 2-16mmØext
1-20mmØext 1-20mmØext
L/3 L/3 L/3 L/3
2-16mmØst. 2-20mmØst.
1-20mmØext 1-20mmØext
1-20mmØext 2-20mmØst. 2-20mmØst.
3-20mmØst. L/3 L/3 L/3 L/3
L/3
2-20mmØst. L/3
SHEET NO :
CONSULTANT : PROJECT INFORMATION : DRAWING TITLE : DISCLAIMER :
PROJECT NAME : OMEGA Engr.Suraya Nasrin
M.Sc Engg.(Structural),BUET OHWT BOTTOM SLAB DETAIL Rev-00
STRUCTURAL DRAWING HAS BEEN DONE AS PER
ARCHITECTURAL DRAWING PROVIDED BY CLIENT.
S-42
PROJECT TYPE: PROPOSED 9-STORIED RESIDENTIAL BUILDING STRUCTURAL CONSULTANT ARE NOT RESPONSIBLE
FIEB, DMINB FOR ANY VIOLATION OF CODE & CONDUCT OR THE CAD BY:
CORE DESIGN ADVISOR'S SCALE:
House-13, Road-9,Sector-6,Uttara Model Town,Uttara,Dhaka-1230 PROJECT ADDRESS: PLOT NO - 369, ROAD NO-10, BLOCK-C
Cell: +8801716780910 RESPECTIVE AUTHORITY.
phone: 01521-456877
mail: [email protected] BASHUNDHARA RESIDENTIAL AREA, DHAKA. NOT TO SCALE DATE : FEBRUARY ,2025
1'-8"
2
4'-0"
1
1 2
3'-8" 3'-8"
1'-6"
1'-6" T=6"
A
1
A 1
T=6"
4'-0"
1'-8"
5'-8"
5'-8"
B-09
B-09
B-09
B-09
4'-0"
1
4'-0"
B-10
B-10
3'-6" 3'-6"
5'-0"
C
1
12'-6"
12'-6"
BOTTOM DIMENTION OF SLAB REINF. TOP DIMENTION OF SLAB REINF.
O H W T & MACHINE ROOM LEGEND FOR SLAB BAR LEGEND FOR SLAB BAR
(A)10mmØ @ 16"c/c O H W T & MACHINE ROOM (1)10mmØ @ 6"c/c
TOP SLAB(BOTTOM BAR) (B)10mmØ @ 17"c/c TOP SLAB(TOP BAR) (2)10mmØ @ 7"c/c
(C)10mmØ @ 6"c/c st bottom.
(1)1-10mmØ ext. bottom
1-16mmØext
2-16mmØst.
2'-1" 2'-1"
3-16mmØst.
10Ø@6"c/c.. 3-16mmØst.
3-16mmØst. 10Ø@6"c/c..
SECTION OF BEAM-09-{10"x18"} SECTION OF BEAM-10-{10"x18"}
SHEET NO :
CONSULTANT : PROJECT INFORMATION : DRAWING TITLE : DISCLAIMER :
PROJECT NAME : OMEGA Engr.Suraya Nasrin
M.Sc Engg.(Structural),BUET
OHWT TOP SLAB WITH
Rev-00
STRUCTURAL DRAWING HAS BEEN DONE AS PER
ARCHITECTURAL DRAWING PROVIDED BY CLIENT.
S-43
PROJECT TYPE: PROPOSED 9-STORIED RESIDENTIAL BUILDING MACHINE ROOM DETAIL STRUCTURAL CONSULTANT ARE NOT RESPONSIBLE
FIEB, DMINB FOR ANY VIOLATION OF CODE & CONDUCT OR THE CAD BY:
CORE DESIGN ADVISOR'S SCALE:
House-13, Road-9,Sector-6,Uttara Model Town,Uttara,Dhaka-1230 PROJECT ADDRESS: PLOT NO - 369, ROAD NO-10, BLOCK-C
Cell: +8801716780910 RESPECTIVE AUTHORITY.
phone: 01521-456877
mail: [email protected] BASHUNDHARA RESIDENTIAL AREA, DHAKA. NOT TO SCALE DATE : FEBRUARY ,2025
10mmØ@7"c/c
10mmØ@8"c/c
20"
20"
10" 10"
10mmØ@7"c/c
PLAN AC BOTTOM SLAB
10mmØ@8"c/c
2.5"
6"
10mmØ@7"c/c
2½"
10mmØ@8"c/c
AS REQUIRE
10mmØ@7"c/c
10mmØ@8"c/c
3"
AS REQUIRE
6"
AS REQUIRE
20"
FLOOR
SHEET NO :
CONSULTANT : PROJECT INFORMATION : DRAWING TITLE : DISCLAIMER :
PROJECT NAME : OMEGA Engr.Suraya Nasrin
M.Sc Engg.(Structural),BUET FALSE SLAB DETAILS Rev-00
STRUCTURAL DRAWING HAS BEEN DONE AS PER
ARCHITECTURAL DRAWING PROVIDED BY CLIENT.
S-44
PROJECT TYPE: PROPOSED 9-STORIED RESIDENTIAL BUILDING STRUCTURAL CONSULTANT ARE NOT RESPONSIBLE
FIEB, DMINB FOR ANY VIOLATION OF CODE & CONDUCT OR THE CAD BY:
CORE DESIGN ADVISOR'S SCALE:
House-13, Road-9,Sector-6,Uttara Model Town,Uttara,Dhaka-1230 PROJECT ADDRESS: PLOT NO - 369, ROAD NO-10, BLOCK-C
Cell: +8801716780910 RESPECTIVE AUTHORITY.
phone: 01521-456877
mail: [email protected] BASHUNDHARA RESIDENTIAL AREA, DHAKA. NOT TO SCALE DATE : FEBRUARY ,2025
10mmØ8"C/C
A RB
10mmØ7"C/C A
RB SCHEDULE OF LINTEL
S.L SPAN.
10mmØ4"C/C No. A H RA RB RC
H
5" 1 10'-12' 6" 9" 2-16mmØ 2-12mmØ 10mmØ4"C/C
H
RC 2-16mmØ 2-12mmØ
as per arch. drawing 10" 8" 10mmØ4"C/C
RA 2-12mmØ 2-12mmØ
7'-9' 6" 8" 10mmØ4"C/C
2
10" 7" 2-12mmØ 2-12mmØ 10mmØ4"C/C
RA
6" 6" 2-12mmØ 2-10mmØ 10mmØ4"C/C
3 5'-6'
TYPICAL SECTION OF LINTEL SECTION OF SUNSHADE 2-12mmØ 2-10mmØ 10mmØ4"C/C
10" 6"
SHEET NO :
CONSULTANT : PROJECT INFORMATION : DRAWING TITLE : DISCLAIMER :
PROJECT NAME : OMEGA Engr.Suraya Nasrin
M.Sc Engg.(Structural),BUET LINTEL AND SUNSHADE Rev-00
STRUCTURAL DRAWING HAS BEEN DONE AS PER
ARCHITECTURAL DRAWING PROVIDED BY CLIENT.
S-45
PROJECT TYPE: PROPOSED 9-STORIED RESIDENTIAL BUILDING STRUCTURAL CONSULTANT ARE NOT RESPONSIBLE
FIEB, DMINB FOR ANY VIOLATION OF CODE & CONDUCT OR THE CAD BY:
CORE DESIGN ADVISOR'S SCALE:
House-13, Road-9,Sector-6,Uttara Model Town,Uttara,Dhaka-1230 PROJECT ADDRESS: PLOT NO - 369, ROAD NO-10, BLOCK-C
Cell: +8801716780910 RESPECTIVE AUTHORITY.
phone: 01521-456877
mail: [email protected] BASHUNDHARA RESIDENTIAL AREA, DHAKA. NOT TO SCALE DATE : FEBRUARY ,2025