Energy Meter Testing Reports
Energy Meter Testing Reports
Inspection of EM
Test Object-Device Setting
Station/Bay Information:
Station Name: Scope Delhi Office Station Address: Bay Name: Bay Address: Tester: Scope
Device Information:
Device Name: Energy Meter Testing Device Model: E3M055 with 0.5s Accuracy Device Address: XXX Manufacturer: Secure Serial Number: HSE50342 Setting List Number: 1 Additional Info: XXX
Nominal Values:
Vnom: 63.509V Inom: 5.000A Fnom: 50.000Hz Vdc: 0.000V V Primary: 220.000kV Debounce Time: 0ms I Primary: 500.000A
Page 1
2.Error curve(1A)
Test Items: LABC Voltage: 63.509V(100.0%Vnom) Trel 0.06250000kWh Power Angle: 30.000deg Load: Inductive Stab. time: 5.000s Current 1.0000A Error -0.161400% Assess Passed Pulses: 10 Waveform: Sinus Current: 1.000A(20.0%Inom) Power Factor: 0.866
3.Error curve(2A)
Test Items: LABC Voltage: 63.509V(100.0%Vnom) Trel 0.62500000kWh Power Angle: 30.000deg Load: Inductive Stab. time: 5.000s Current 2.0000A Error -0.226100% Assess Passed Pulses: 100 Waveform: Sinus Current: 2.000A(40.0%Inom) Power Factor: 0.866
4.Error curve(3A)
Test Items: LABC Voltage: 63.509V(100.0%Vnom) Trel 0.62500000kWh Power Angle: 30.000deg Load: Inductive Stab. time: 5.000s Current 3.0000A Error -0.170600% Assess Passed Pulses: 100 Waveform: Sinus Current: 3.000A(60.0%Inom) Power Factor: 0.866
5.Error curve(4A)
Test Items: LABC Voltage: 63.509V(100.0%Vnom) Trel 0.62500000kWh Power Angle: 30.000deg Load: Inductive Stab. time: 5.000s Current 4.0000A Error -0.175700% Assess Passed Pulses: 100 Waveform: Sinus Current: 4.000A(80.0%Inom) Power Factor: 0.866