Manual Orion Delta.
Manual Orion Delta.
Configuration instructions,
ORION controller
www.deltapowersolutions.com
Table of contents
1 About configuration............................................................................................. 6
1.1 Overview of system configuration ............................................................ 6
1.2 User interface ........................................................................................... 7
1.2.1 Web user interface ..................................................................... 7
1.2.2 Local user interface ................................................................... 7
1.2.2.1 Basic gestures ............................................................ 7
1.2.2.2 Top level of the menu ................................................. 7
1.2.2.3 Sub menu ................................................................... 8
1.2.2.4 Password .................................................................... 8
1.2.2.5 Screen saver .............................................................. 8
1.2.3 User interface module UIM Touch ............................................. 8
1.3 Connecting a computer to ORION Touch ................................................ 9
1.3.1 Introduction ................................................................................ 9
1.3.2 Connecting computer to ORION Ethernet port .......................... 9
1.3.2.1 Connecting a computer using automatic mode .......... 9
1.3.3 Connecting computer to ORION via USB-Ethernet adapter ... 10
1.3.4 Connecting a computer or a smart phone to ORION via WLAN
................................................................................................. 10
1.3.4.1 Enabling WLAN AP in ORION.................................. 10
1.3.4.2 Connecting a computer or a smartphone to ORION
over WLAN ............................................................... 11
1.4 Connecting ORION to a LAN ................................................................. 12
1.4.1 Setting the Ipv4 network parameters manually ....................... 12
1.4.2 Setting the Ipv4 network parameters automatically ................. 12
1.4.3 Setting the Ipv6 parameters ..................................................... 13
1.4.4 IP filtering ................................................................................. 14
1.4.5 HTTPS ..................................................................................... 14
1.4.6 VLAN ........................................................................................ 15
1.5 Connecting ORION to a remote server .................................................. 15
1.5.1 Simple Network Management Protocol (SNMP) ..................... 15
1.5.1.1 Installing the software license key ............................ 16
1.5.1.2 Configuring SNMP .................................................... 16
1.5.1.3 Using a loadable MIB ............................................... 19
1.5.2 Modbus slave protocol ............................................................. 19
1.5.2.1 Configuring Modbus Slave TCP ............................... 20
1.5.2.2 Configuring Modbus Slave RTU or ASCII ................ 20
1.5.3 Syslog protocol ........................................................................ 21
1.5.3.1 Configuring syslog .................................................... 21
2 Configuration .................................................................................................... 23
2.1 Configuring ORION controller ................................................................ 23
2.1.1 Active setup ............................................................................. 23
2.1.2 Parameter scope: global and site specific parameters ............ 23
2.1.2.1 Saving the active setup as a setup file to PC ........... 24
2.1.2.2 Restoring the setup file from PC .............................. 24
2.1.2.3 Clearing the active setup .......................................... 24
2.1.2.4 Deleting the active setup .......................................... 24
2.1.3 Configuration management ..................................................... 25
2.1.4 User interface language ........................................................... 26
2.1.5 Meter panel .............................................................................. 26
2.2 Configuring batteries .............................................................................. 28
2.2.1 Supported battery types ........................................................... 28
2.2.2 Battery profiles ......................................................................... 29
2.2.3 Configuring and enabling of battery strings ............................. 30
2.2.4 Float charge ............................................................................. 31
2.2.5 Temperature compensation ..................................................... 31
This document describes the configuration procedures required to enable the ORION
controller to control and monitor a power system and associated components.
The power system is configured when it is installed. The system may also require
reconfiguring during its lifetime, for example, if components are added or removed, or if
the physical configuration of the system is rearranged.
The ORION offers three user interfaces; a web user interface (web browser), a Local
User Interface (UIT) with a touch display and an optional User Interface Module (UIM
Touch). The web user interface allows access to the full range of configuration and
supervision functions. The local interface UIT and UIM Touch allow access to the most
essential functions.
The web user interface is accessed through a web browser on a computer and made
through either a direct connection or over a network.
The local user interface Touch UI is integrated in the front panel of the ORION controller,
while the (optional) user interface module UIM Touch can be located anywhere at the
site, for example at system cabinet door.
Note! The local user has a higher priority than a WEB user. If the Touch UI or
UIM Touch user changes a parameter, the web session is terminated.
All configuration functions are available through the web user interface.
Access the web user interface with a standard browser and navigate with a normal
keyboard and mouse. Most of the displayed measurements and states are updated
automatically.
The local user interface is an easy to use and intuitive touch display which is operated by
simple, smartphone like gestures
There are four pages on the top level, and the user can navigate between them by
swiping left and right.
STATUS
STATUS page shows the main parameters of the system and indicates if there is a
problem.
There is no need to scroll on the STATUS page, but the user can tap an icon to enter to a
sub menu such as RECTIFIER or BATTERY or tap theALARM icon to enter to the
ALARM page.
ALARMS
The active Alarm Events and Issues are listed on this page. Issue list shows functions
that the user should look at. There might be something wrong with the function, but there
is no alarm configured to sindicate it. If the list is long, the user can swipe up/down to see
all items.
METER PANEL
The content of METER PANEL is configurable and the user can scroll the list by swiping
up/down to see all items. METER PANEL can be optionally configured to be the “Home
Page”. The selection can be done through the web page “Options”.
The user can enter to a sub menu by tapping an icon on the HOME or MENU page, and
come back by swiping from left to right. The sub menus contain typically both read-only
information and editable settings. The editable items are distinguished by blue color.
1.2.2.4 Password
To extend the display life, ORION activates a screen saver after a time-out. In case there
are no active alarms, the display is dimmed and shows a slowly moving Delta logo. In
case there is an active alarm, a red bell is shown instead of the Delta logo. To catch
attention, the screen can additionally blink. This can be configured through the web Gui in
the options menu.
UIM Touch is an optional user interface module for ORION Touch. It offers the same
menu structure and touch functionality as the local touch interface UIT, but in bigger size.
(3.5 inch) It is designed to be mounted on a cabinet door, and too support easy system
upgrades it fits into the same opening as the old UIM.
1.3.1 Introduction
ORION can be connected to computer either through the Ethernet port or the USB port
using an USB to Ethernet adapter or a WLAN dongle.
ORION has the possibility to operate with IPv6 addresses and Ipv4 simultaneously. (Dual
stack). In case Ipv6 Mode is disabled only Ipv4 communication are possible.
The Ethernet port of ORION supports two different operating modes: manual and
automatic. In manual mode the network parameters are set manually both in computer
and in ORION. In automatic mode, IP address and Subnet Mask are automatically set
according to RFC 3927 (Zeroconf).
As the most common way is to use automatic mode, the instructions concerning the
manual mode are found in the appendix at the end of this document.
Use this procedure to connect a computer directly to the Ethernet (LAN) interface of the
ORION:
Step 1 Make sure that the DHCP is enabled in the computer. (The network adapter is
configured to obtain the IP address automatically.)
Step 2 Enable the Automatic mode in ORION by using the local user interface.
Touch UI: MENU Network IPv4
UIM: NET CONFIG → ETHERNET → IPv4→ MODE.
Step 4 Wait for a while and let ORION and computer negotiate the network parameters.
This can take up to two minutes because the computer needs some time to
detect that there is no DHCP server in the network and start the address
autoconfiguration process.
Step 6 In the address bar of the internet browser, enter the IP address of ORION which
is shown at:
Touch UI: MENU Network
UIM: NET CONFIG → ETHERNET → IPv4→ IP ADDRESS.
Step 7 When the ORION configuration and supervision tool login page loads, enter the
username and password, and click “Submit”.
Step 8 The web interface is now open and it is possible to change the configuration and
setting if necessary.
If the web server of ORION does not response, please check the following things:
2 Check the proxy server setting in the browser options. A proxy shall not be
used.
3 Check that the IP address and the network mask are correctly defined by
the autoconfiguration process. The IP address of your LAN adapter should
be 169.254.xxx.xxx, where x is any number and the network mask should
be 255.255.0.0. If the address is from a different range, check that your
network adapter is set to obtain the IP address automatically.
4 Deactivate other networks: WLAN, Wireless WAN etc. If there are other
network connections active, it might be that the active routings do not
support communication to the 169.254.. network.
5 Even if all the settings seem to be OK, reboot the computer and try once
more. If this does not help, follow the instructions in the appendix and use
the manual mode with fixed IP addresses.
Step 2 Plug in the USB to Ethernet adapter to the USB port of ORION.
Step 4 Open the web browser in your PC and enter the URL: http://orion.deltaww.com to
login to ORION.
ORION is able to operate as WLAN access point making it possible to use tablets and
smartphones for local access.
Use this procedure to enable WLAN AP in ORION using the web interface:
Step 3 Enable “Default WLAN Operation” by ticking the checkbox or define the “WLAN
SSID”, “WLAN Channel” and “WLAN PSK” manually.
Step 1 Make sure that the DHCP and WLAN is enabled in your device.
Step 2 Plug in the WLAN adapter to the USB port of ORION. The menu for SSID and
PSK is shown on the LCD display of ORION (if it is not visible, it can be found in
the local user interface:
Touch UI: MENU Network WLAN
UIM: NET CONFIG → WIRELESS LAN).
Step 3 Connect your device to the new wireless network that just started.
Step 4 Check the PSK from ORION and enter it to your device.
Step 5 Open the web browser in your device and enter the URL:
http://orion.deltaww.com to login to ORION or use a smartphone app.
Use this procedure to connect the ORION to the local area network, using fixed IP
address.
IPv4 address
IPv4 Subnet mask
IPv4 Gateway address
IPv4 DNS
Step 1 Enable the Manual mode in ORION using the local interface
Touch UI: MENU Network IPv4
UIM: NET CONFIG → ETHERNET → IPv4→ MODE
Step 3 Connect the ORION to the LAN with the appropriate cable.
Step 1 Connect the computer to the LAN with the appropriate cable.
Step 2 Open an internet browser and connect to the defined IP address of the ORION.
Step 3 When the ORION login page loads, enter the username and password, and click
“Submit”.
Step 4 The web interface is now open and it is possible to change the configuration and
setting if necessary.
Use this procedure to connect the ORION to the local area network, using DHCP server
The following parameters are automatically received from the DHCP server
Step 1 Enable the Automatic mode in ORION by using the local user interface.
Touch UI: MENU Network IPv4
UIM: NET CONFIG → ETHERNET → IPv4→ MODE.
Step 2 Enter the host name for this ORION (without domain name). Allowed characters
are “a-z”, “A-Z”, “0-9” and “-“ (hyphen).
Step 1 Connect the computer to the LAN with the appropriate cable.
Step 2 Open an internet browser and connect to the IP address of the ORION. The IP
address is shown at:
Touch UI: MENU Network
UIM: NET CONFIG → ETHERNET → IPv4→ IP ADDRESS.
Alternatively use the host name of ORION.
Step 3 When the ORION responds, enter the username and password, and click
“Submit”.
Step 4 The web interface is now open and it is possible to change the configuration and
setting if necessary.
ORION has the capability to operate with Ipv6 addresses and Ipv4 simultaneously. (Dual
stack). If Ipv6 address is not used, the Ipv6 mode shall be “Disabled”. ORION supports
two different modes for Ipv6:
1 Automatic
To be used when ORION is plugged into an Ipv6 ready network having
a router that supports “Stateless Address Auto configuration” (SLAAC,
RFC 4862) and the RA DNS option (RFC6106) or a DHCPv6 server.
2 Manual
To be used when IPv6 Address, IPv6 Gateway Address and IPv6 DNS
are defined by the user.
IPv6 address
IPv6 Prefix
IPv6 gateway
IPv6 DNS Auto
1.4.4 IP filtering
1 The ICMP communication can be disabled, then the controller will not reply to ping
requests anymore.
2 Allowed networks can be defined. If defined, only communication from those
networks will be accepted. It is possible to define four allowed networks.
Step 4 Define the allowed networks using the CIDR notation. See RFC 4632 for the
details. For Ipv4 it looks like XXX.XXX.XXX.XXX/NN. Where XX.XXX.XXX.XXX is
a standard Ipv4 address notation and NN is a number from 0 to 32 representing
the number of bits to be masked from the IP address, starting from the MSB.
ORION checks the validity of the notation. For Ipv4, XXX.XXX.XXX.0\32 is not
allowed.
1.4.5 HTTPS
ORION supports Hypertext Transfer Protocol Secure (HTTPS) for secure communication.
HTTPS requires a key/certificate. There is a default certificate in ORION, but the user can
load in a customer certificate.
The operating mode can be selected by using the web interface on the page
Configuration → System → Interface Setup → TCP/IP.
If customer certificate is used instead of the default certificate, the Key/Certificate shall be
pasted into the corresponding field as PEM format
1.4.6 VLAN
ORION is able to join into a single VLAN segment. This enables communication over
VLAN in trunk port mode.
The VLAN functionality can be activated and configured on the web page Configuration
→ System → Interface Setup → TCP/IP.
VLAN can be enable/disabled also via Touch UI at MENU > NETWORK.
The ORION controller, as an agent, can send trap messages to the SNMP manager. The
ORION controller is able to send traps to ten IP addresses. For an SNMP manager to
understand a trap sent to it by an agent, the manager must have the Management
Information Base (MIB) for the specific traps loaded. As default ORION supports its own
enterprise MIB and partially MIB-2. As an option the own MIB can be replaced by loading
in a customized MIB Mapping file. Creating the mapping file requires advanced skills, so
this process is not covered by this document. To get a customized MIB, please contact
Delta.
The controller`s SNMP agent supports the SNMP V1, V2c, and V3 protocols. Since V3 is
different from V1 / V2c in terms of security the configuration of the access parameters is
different. The Web SNMP access configuration interface allows selecting between
‘V1/V2c’ or ‘V3’.
SNMP is activated by means of a software license key, which can be obtained from Delta
or authorized representative. Each controller needs an individual license key which is
based on MAC address of the controller. The MAC address can be read through WEB
GUI at Configuration → System → Interface Setup → TCP/IP. It can also be read locally
through the UIT at MENU > NETWORK, or from the product label on the controller.
SNMP can be activated either in the field with a laptop connected to the ORION, or
remotely over a LAN.
Step 3 Enter the license key code and click “Accept Changes”.
Use this procedure to specify the global SNMP parameters when v1/v2c protocol is used.
Default values are: Read community = public Write community = private.
Use this procedure to specify the global SNMP parameters when v3 protocol is used.
Step 4 Enter username, select the authentication and privacy protocols and enter
corresponding passwords.
The fourth type of alarm trap sends all the events which are defined as “alarm events” in
Alarm Setup. This trap is recommended to be used when the new alarm mapping
functionality is used instead of the “S Non Urg Alarm”, “S Urgent Alarm”, and “S Critical
Alarm”.
Step 2 Enter the IP address and Port number for each SNMP manager used. In case of
v3, select the usernames as well.
Each of the four trap types can be enabled separately and additionally it is possible to
enable automatic resend with the defined interval.
To enable the traps and the automatic resend of traps proceed as follows:
Step 2 Tick the “Enable” box for the trap types you want to enable.
Step 3 Tick the “Resend” box for the trap types you want to resend and define the
resend interval.
The ORION has a generic alarm table with up to 16 entries. The user can map any of the
available events into this table. As this table is included in the MIB as a fixed place holder,
the status of the events in this table can be polled by the NMS any time.
Note! SNMP write access is only granted if no other session with write access is
active. So if a user is logged into the WEB interface any SNMP write access
command fails and returns “No Access” as error code.
Step 4 Save the MIB file, provided by Delta, to the SNMP manager MIB file folder.
When SNMP has been enabled the ORION controller sends information about the
system, and three alarms as default: Critical Alarm (CA), Urgent Alarm (UA) and Non-
Urgent Alarm (NUA).
1.5.1.2.6 Thresholds
The user can map up to 20 events that are defined on the page Configuration > Signal
Processing Engine > Event Definitions into this table to make it possible to edit the
thresholds remotely using SNMP.
1.5.1.2.7 Timers
The user can map up to 20 timers that are defined on the page to Configuration > Signal
Processing Engine > Event Processing into this table to make it possible to edit the timer
parameters remotely using SNMP.
1.5.1.2.8 Filters
The user can map up to 20 filter events that are defined on the page to Configuration >
Signal Processing Engine > Event Processing into this table to make it possible to edit
the timer parameters remotely using SNMP.
To use a lodable MIB instead of the default enterprise MIB proceed as follows:
Step 1 Go to to Configuration → System → File Manager to load in the MIB mapping file
Step 2 Select File Type “MIB Mapping” and click “Load File from PC”.
Step 3 Click “Browse” and select the correct file in your PC.
As an option ORION controller can have Modbus slave protocol to support Modbus
communication with master in three different modes:
Please contact Delta in case such upgrade is needed in order to provide the correct
mapping file. Delta needs the setup file of your ORION controller.
Step 11 Select File Type “Modbus Slave Mappinge” and click “Load File from PC”.
Step 12 Click “Browse” and select the mapping file in your PC.
Step 14 Check the default logo to see if there are messages concerning incompatible
mapping entries.
Note! The protocol will be running even in case there are some incompatible
mappings, but some registers might not provide the correct information.
Follow the process below to configure Modbus Slave RTU or ASCII protocol.
Step 22 Select the protocol “Modbus Slave” for any of the available serial ports
Step 23 Change the communication parameters if necessary and click “Accept Changes”
Step 25 Select File Type “Modbus Slave Mapping” and click “Load File from PC”.
Step 26 Click “Choose File” and select the mapping file in your PC.
Syslog is a protocol used to convey event notification messages. See RFC 5424 for more
information.
Parameter Description
Facility This describes the source of the event, see RFC 5424
for more info.
Step 4 Tick the checkbox “System Messages” in case you want to send controller
system messages to Syslog server(s) and set the severity. The same severity
applies to all the system messages.
Step 5 Highlight one or more events in the “Events Selection” list and click one of the
“>>” buttons to move it to a column with an applicable severity class.
Step 6 Repeat step 5 for each event that you want to log into a Syslog server.
In order to deselect an event, select one or more events from a list and click the
“<<” button at the left side of the column. This will send the selected events back
to the “Events Selection” list.
Step 7 After all needed events are moved to applicable columns, click “Accept
Changes” and the “Back”.
Step 8 Enter an URL or an IP address for the server and select the proper server port
and facility. The facility is an information sent to the server to indicate the source
of the generated events, it applies for all events sent from the same controller.
Note! If you use an URL, a DNS server must be configured in the controller in
order to resolve the URL.
Each function of ORION has its own set of parameters which are stored in active setup.
When a parameter is changed it will be automatically saved. After the system has been
configured, the active setup can be stored on a computer as a setup file in xml format.
This file can be used to configure the system for example if the controller has been
replaced. The setup file can also be used where identical systems have been installed,
avoiding manual configuration in each installation. It can only be saved and restored
through the web user interface.
Each configuration parameter has a specific scope. A scope defines if the value for a
parameter should be taken from the loaded setupfile or is unique to the controller and
thus shall not be overwritten. A scope can be either “global” or “site”.
A parameter with scope “global” is a generic parameter that can be overwritten by loading
a new setup, activating a new configuration or restoring a backup. A parameter with the
scope “site” means the parameter is valid for specific site only and shall not be
overwritten by loading a new setup, activating a new configuration or restoring a backup.
Most of the parameters have a fixed scope set to “global”. Some have a fixed scope set
to “site”:
GPS Coordinates
Site Name
And some parameters have a configurable scope, so the user can decide whether the
parameter should get its value from the setup or not. The configurable parameters are:
Note! The scope setting is stored together with the parameter in the setup file.
While loading in a setup or activating a configuration, ORION looks at the scope
setting inside the new setup/configuration file and not the scope setting of the
active configuration.
Step 2 Click “Save to PC” button beside the Setup file. The “Save As” dialogue
appears.
Step 3 Specify the directory, where the file should be stored and, if desired, modify the
file name.
Step 4 In the “Load File from PC” dialogue click “Browse” and choose the desired setup
file.
The controller clears the setup configuration except network settings, user configuration,
calibration values, and license key features.
In addition to the active setup file the controller can have one or more alternative
configuration files (CFG_XYZ.xml) loaded in. This functionality is useful in cases where
the final system configuration is created at the site by combining system building blocks
together. The controller can have several ready-made configuration files in its memory to
support the different physical system variants.
When the user activates any of the configuration files, the active setup is updated by the
content of the chosen configuration file. When done, the state of the chosen configuration
file is “synchronized”. If the user changes any parameter in the system, the active setup is
automatically saved. The state of the activated configuration changes to “not
synchronized” indicating that the active setup is no more the same as the content of the
configuration file that was activated. The user has now the possibility to update the
activated configuration file by the parameters of the active setup, or he can keep the
original configuration file as a backup file. If the user updates the activated configuration
file, ORION creates automatically a backup of the previous file and stores it into the
controller. The name of the backup file is composed of the name of the file being updated
with an additional postfix number.
When the user loads in a Seup file, as described in the chapter “Restoring the setup file
from PC”, ORION does not only activate the setup automatically, but also creates and
activates a new Configuration file called CFG_”setup file name”.xml.
The different use cases and related user interfaces are shown in the table below:
The user interface language can be selected from stored language files. The default
language is English. Three additional language files can be loaded by using the web
interface.
The applicable menu point for different actions are shown in the table below:
The Meter Panel is a customizable page that allows the user to collect important events
and measurements for viewing on a single page. The measurements are also readable at
the UIM/UIL interface as a list.
To view the Meter Panel through the web user interface, go to Status → Meter Panel.
Each meter can be configured to represent almost any event or measurement required.
With optional Hour Meter setting also the active time of the events and with optional
Event Counter the number of transitions from “false” to “True” can be shown on the
Overview page.
When adding an item to the meter panel, the user can select an unique ID which has a
direct connection to the SNMP OID. By Using the meter panel functionality and the
manually selected IDs, the user can standardize the SNMP OIDs across his network also
for manually configured measurements such as “Wind speed” or “Fuel level”.
Limit Values Boolean If the limit values are set, the output
values, which exceed the values set by
“Output 1” and “Output 2” are invalidated.
The available battery functions for different batteries are presented in the following table.
Float Charge
Temperature
Compensation
Battery Test
Equalize
Boost
Separate Charge
Middle Point
Tdiff
Idiff
Block Measurements
Life Prediction
LVD
When the user activates any of the battery profiles, the active setup is updated by the
parameters of the chosen battery profile. When done, the state of the chosen battery
profile is “synchronized”. If the user changes any battery parameter in the system, the
active setup is automatically saved. The state of the activated battery profile to “not
synchronized” indicating that the active setup is no more the same as the activated
battery profile. The user has now the possibility to update the activated battery profile by
the battery parameters of the active setup, or he can keep the original battery profile as a
backup file. If the user updates the activated battery profile, ORION creates automatically
a backup of the previous file and stores it into the controller. The name of the backup file
is composed of the name of the battery profile being updated with an additional postfix
number.
The different use cases and related user interfaces are shown in the table below:
ORION is usually configured to use all the battery shunts that are installed in the system.
However, if all the battery connections are not needed, the unused battery strings can be
disabled to eliminate the non-relevant information on the user interface.
For the correct operation, ORION needs to know what kind of batteries are connected to
each string. For the optimum charging control, ORION needs to know the maximum
allowed charging current for the battery, and to estimate the state of charge, the expected
backup time and the remaining discharge time, ORION needs to know the battery
capacity.
Hour Rating The nominal discharge time for the battery that
corresponds to the nominal capacity.
Enable Battery Charging Checkbox to enable the charging current limit function
Current Limit
After a battery has been fully charged, a slightly lower charge can be constantly applied
to compensate for self-discharge. This is the float charge. The parameters which affect
the usage of the float charge are described in Table 2.
Parameter Explanation
Max Recharge Duration Maximum allowed time for recharge, after which the
voltage returns to Float Charge.
Two types of compensation are available: Linear and Multi-Stage. Additionally ORION
provides functionality for thermal runaway protection.
Parameter Explanation
2.2.5.2 Multi-stage
Type multi-stage is used when different slope is required at low and high temperatures.
Parameter Explanation
High Stop Voltage Minimum level where the temperature compensation can
increase the voltage at high temperature
Runaway Voltage
Parameter Explanation
Runaway Temp The temperature at which the controller will activate the
thermal runaway prevention feature by lowering the
output voltage to the Runaway Voltage parameter
Note! The temperature compensation type can be set only via web interface.
With flooded lead-acid batteries, it is possible to continue charging the batteries after they
are normally considered fully charged. This equalizes the voltages between battery cells
and stirs up the fluids within batteries, extending the battery life. This function is called
Battery Equalize. The parameters and settings which ensure that the procedure is carried
out safely and within certain limitations are described in Table 7.
Caution! Always check the battery specifications and instructions from the
battery manufacturer before setting the parameters.
Parameter Explanation
Use Battery Room Fan To enable lead and lag time, select this checkbox.
Max Battery Temperature To supervise the battery temperature and stop Battery
Equalize if the battery temperature exceeds the following
limit, select this checkbox.
Max Battery Temperature If the battery temperature exceeds this value, the
charging process is stopped.
Alarm Suppression Voltage Deviation from float voltage to stop the alarm
suppression.
Interval (Start Condition) Specifies the time between two battery charging
processes.
Inhibit after Boost (Start Minimum time between boost charge and Battery
Condition) Equalize.
Forbidden Periods During the given time windows, the programmed Battery
Equalize is not executed.
The battery can be boost charged automatically after a mains failure. With this procedure,
the system voltage is increased to a certain level to recharge the batteries faster. The
charging process is either controlled by time, current or energy depending on the
configuration.
Caution! Always check the battery specifications and instructions from the
battery manufacturer before setting the parameters.
SoC below All The boost charge starts only in case the
actual state of charge is equal or below the
entered threshold
Use Battery Room All To delay the battery fan event select this
Fan checkbox.
Alarm Suppression All Deviation from float voltage to stop the alarm
Voltage suppression.
ORION controller is able to communicate with lithium batteries over a digital bus. ORION
Touch supports two different concepts: 1) The lithium batteries are connected to ORION
via gateway module GWM-Battery. This module supports CAN and RS485/Modbus
communication and up to 16 batteries 2) The lithium batteries are connected to RS485
port of ORION Touch. The maximum number of batteries is 32.
Precondition:
1 The gateway module GWM-Battery is connected to the system and configured
properly.
2 The GWM module has a firmware that supports the used battery
3 The communication bus of the battery is connected to the gateway module.
Use the following procedure to add a new lithium-ion battery to the system.
Step 2 In Overview section, select the gateway module from the “Battery Interface”
drop-down list and click “Add”.
Step 4 Optionally edit the battery name and select the fuse fault event to be shown
together with this battery on the Status page.
Step 6 In case the system is equipped with battery shunt(s) for battery current
measurement, go to Configuration → Battery → String Settings and enable the
shunt measurements and enable and set the total battery charging current limit.
It is possible to enable/disable batteries via local interface, but it is not possible to add
new ones.
Step 2 Set the old battery’s address to new battery and connect the bus cable. The
status of the battery should change to “ok”.
Step 3 Press the button on GWM-BATTERY to clear the disconnected battery from the
GWM-BATTERY ID table.
Step 2 Go to Configuration → Battery → Lithium and click “Add” in the “Battery Group”
section, enter the name for the new group, select the interface (serial port) and
select the driver. It is also possible to select “auto detect” to enable automatic
detection of the battery type.
There is also a button on this page to load in the battery drivers.
Step 3 Connect the battery to the RS485 port of ORION. ORION will detect the battery
and set the actual date as installation date.
Step 4 Go to Configuration → Battery → Lithium and confirm the new battery by ticking
the Enable checkbox in the “Overview” section. The status should change from
“New” to “OK”
Step 5 Optionally edit the battery name and select the fuse fault event to be shown
together with this battery on the Status page.
Step 6 In case the system is equipped with a battery shunt for battery current
measurement, go to Configuration → Battery → String Settings and enable the
shunt measurements and enable and set the total battery charging current limit.
Step 1 Disconnect the communication bus cable from the battery to be replaced.
Step 2 Set the old battery’s address to new battery and connect the bus cable. The
status of the battery should change to “ok”.
Step 1 Go to Configuration → Battery → Lithium and set the installation date for the
new battery.
ORION is able to manage the charging of lead acid and lithium batteries in the same
system. However, this requires specific system design with special transfer switches for
the batteries. The configuration of this functionality is not covered by this document.
Please contact Delta in case more information is needed.
The system voltage supervision function monitors the battery voltage and activates
events if the voltage exceeds the given limits.
S Ua high
Ua max
S Us high
Us max
Usys tc
Us min
S Us low
Ua min
S Ua low
Tbatt
Tc_low 20°C Tc_high
Parameter Explanation
* Events already activated remain active until the system voltage exceeds the
corresponding limit, regardless of these settings.
The System voltage supervision can be configured at the following menu points:
For the middle point measurement, the battery is divided into two blocks. The voltage of
the middle point is measured and compared with the calculated middle point value
computed out of the battery voltage value “Ubatt”. If the difference exceeds a given limit,
the battery is considered as faulty. The battery middle point voltage can be measured by
UM or Fuse inputs of ORION or through SENSN devices.
When the voltage difference exceeds the given limit for at least 20s, a log entry is
generated and the events S MP Failure and S BattFail MP are activated. The event
S MP Failure stays active as long as the voltage difference is too high. The event
S BattFail MP remains active until it is manually reset.
Parameter Explanation
The parameter setting and the results of the middle point measurements are available
through the Touch UI/UIM interface as well as the web user interface.
For the block measurement, the battery is divided into equally sized voltage blocks, which
are measured separately. These voltages are compared against the theoretical block
voltage calculated from the system voltage. If the difference exceeds a given limit, the
battery presents a symmetry failure and is considered as faulty.
Parameter Description
The parameter setting and the results of the Block voltage measurements are available
through the Touch UI/UIM interface as well as the web user interface.
Tdiff is the difference between battery temperature and ambient temperature. The
comparison is made continuously. If the two temperatures differ more than a certain value
for more than 2 minutes, a log entry is generated and the events S Tdiff Failure and
S BattFail T are activated. The event S Tdiff Failure remains active as long as the
temperature difference is too high. The event S BattFail T remains active until it is
manually reset.
Parameter Explanation
Failure Event State of the event S BattFail T. The following terms are
possible: ok, active.
The event can be reset manually.
Parameter Explanation
The Current difference (Idiff) measurement calculates the deviation from the calculated
current for each battery string. The calculation assumes that the total battery current is
shared by the strings based on the nominal capacities. A current difference higher than
the given limit can indicate a faulty battery. Idiff is monitored during charge and discharge
of the batteries. The threshold values for charging and discharging are independent of
each other.
If the current difference exceeds the threshold for more than 20 seconds, a log entry is
generated and events S Idiff Failure and S BattFail I are activated. The event S Idiff
Failure remains active, as long as the current difference is too high. The event S BattFail
I remains active until it is manually reset.
Parameter Explanation
Parameter Explanation
Failure Event State of the event S BattFail I. The following terms are
possible: ok, active.
The event can be reset manually.
The Loss of the Backup Time function provides an early warning in event an installed
battery does not provide the expected back-up time. Based on the set value for the
expected backup time and the calculated effective capacity, the ORION calculates a
corresponding maximum discharge current. For li-on batteries the calculation is done
based on nominal capacity. If the average load current during a period, which is equal to
the backup time, exceeds this calculated value the event S Backup Time Lost is
activated. This event remains active until the average load current is within the required
range and the operator has manually reset it.
Parameter Explanation
Parameter Explanation
The low voltage disconnection (LVD) function protects the battery from a deep discharge.
ORION supports two different LVD types:
U and t controlled LVD compares Usys to a voltage threshold. In case the voltage
falls below the threshold, ORION activates an event that drives the relay of the
battery disconnect. The disconnection can be delayed with an adjustable
parameter. The battery is disconnected from the load until the system voltage Usys
rises back to acceptable values.
Event Controlled LVD disconnects the battery based on the status of a control
event which is defined in the Signal Processing Engine.
Low Voltage Disconnection can only be configured through the web user interface and it
is normally configured at the Delta factory.
The parameters for Event controlled LVD depend of the configured logic and can be
adjusted at:
The state of the LVD can be seen and the functionality can be disabled at:
The partial load disconnection function is used to prioritize separate load strings (for
example, difference types of equipment) during mains failure and battery discharge.
The PLD functionality is configured by using the LVD functionality of ORION, so for more
details, please see the previous chapter.
ORION offers different procedures to check the state of the batteries. The user can select
between constant current and real load battery tests, depending on the system size and
the load conditions.
The Constant Current battery test discharges the battery with a constant current during
a certain time period. Load changes are balanced by the rectifiers. For a successful test,
the load current must be greater than the desired battery discharge current.
During the Real Load battery test, the battery is being discharged with the real load
current. To make the testing saf,e the rectifier output voltage is programmed to Usupport
voltage leve,l but the rectifiers remain in operation ready to support the load in case the
battery would fail.
It is possible to configure several tests. One test could be a short check that is done every
month and the second test could be a longer test that is done only oncew or twice a year.
Minimal Duration Both The value represents the minimum battery test
duration in minutes. During that time a battery
test is not stopped if a voltage is below the
support voltage or a current difference is higher
than the specified value.
Voltage Level Both Voltage threshold for the Natural Battery Test
Monitoring Period Both Monitoring period for the Natural Battery Test
Enable Auto Start Both Automatic start of the battery test at specified
intervals.
Voltage within Both To ensure that the battery is fully charged the
Ufloat system voltage must not differ for a certain time
Start Time Between Both Within this time window, a programmed battery
And test can be started.
Inhibit input Both Battery test does not start while this event is
active.
The status and the results of the previous tests can be seen at:
For maintenance of the system, a battery can be separated from the system; then be
discharged with a separate load and finally be recharging with separated rectifiers while
the system is running normally with the remaining battery or batteries.
There are two types of separate charge in the ORION: manual and semi-automatic.
With the manual separate charge and discharge, the separated battery is fully charged
before it is reconnected to the system. The float voltage for the separated battery can be
set to a value different from the system float voltage (=> boost voltage). After the battery
is fully charged, the float voltage is set to the same value as the system float voltage (or
lower). After the voltage of the separated battery has settled to the system voltage, the
battery can be reconnected to the system.
With the semi-automatic separate charge and discharge, the system voltage is reduced to
reconnect voltage “Urecon” during separate charging. After the voltage of the separated
battery has reached the system voltage, the system voltage tracks the separate charging
voltage for a short time and then the battery can be reconnected to the system. The
battery is then charged up to the system float voltage.
During separate charge mode, battery fuse alarms and Idiff measurement are
suppressed.
Parameter Explanation
Touch UI No config
access
The typical lead acid batteries for telecom applications are designed to last 10 years in
optimal environmental conditions. However, if the temperature is higher than the nominal
temperature, typically 20 °C or 25 °C, the life time will be shorter. Also, if the battery is
frequently discharged and recharged, it may limit the battery life.
The battery life prediction function gives information on the expected life time of the
battery in the actual operating conditions and helps in budgeting and planning battery
replacements.
In case the battery prediction time function is activated in a system with an old battery,
the Installation Date must be set according to the real installation date of the battery. As
the real history is not known by ORION, ORION just assumes that the average conditions
in the past were the same as they have been after activating the monitoring functionality.
Parameter Explanation
Some Li-on batteries have built in intelligence to indicate the State of Health with a scale
from zero to 100 %. When available, ORION uses this information to predict the lifetime
instead of external measurements of temperature and discharge cycles.
ORION monitors the battery current continuously and estimates the State of Charge
(SoC). The SoC measurement is shown using a scale from 0 to 100%. SoC can be used
in signal processing and it can be assigned to a data log.
Based on the battery SoC and the actual load current, ORION estimates the Remaining
Backup Time. This measurement tells how long the system could still run on batteries
until they are fully discharged. The Remaining Backup Time measurement is dynamic.
Therefore the measurement will increase and decrease in case the lod current varies.
Note! SoC and Remaining Backup Time are estimates and shall not be
understood as an accurate measurements.
Parameter Explanation
The load strings can be enabled and the parameters can be configured at:
The ORION offers a comprehensive set of functions to control and monitor different
rectifiers, enabling the user to adjust the behaviour of the rectifiers to meet the specific
requirements of the battery and load.
The following instructions describe the main functions from the ORION point of view.
After communication is first established between the rectifiers and the controller, it is
possible to adjust the parameters with the controller. Without initial communication to the
power system controller, Delta’s rectifiers use their own default parameters. With the
controller the user can also adjust the default parameters, after the communication is first
established. The following parameters control the behaviour of the rectifiers when the
power system is not in normal operating mode, such as start-up or low input voltage
mode. The parameters for normal operating mode (float charge mode), and for the whole
power system, are adjusted elsewhere (for example, battery menu).
These parameters can only be viewed or configured through the web user interface.
Parameter Explanation
Parameter Explanation
Table 11. Default parameters (in use when no connection to the ORION)
Parameter Explanation
Input low off Threshold (voltage) for shutting down the rectifiers when
input voltage is too low.
Input low on Threshold (voltage) for switching the rectifiers on, when
input voltage returns from low to acceptable values.
Input high off Threshold (voltage) for shutting down the rectifiers when
input voltage is too high.
Parameter Explanation
Parameter Explanation
Power Up Delay The delay in seconds, after which the first rectifier in the
group/system starts.
Parameter Explanation
Parameter Explanation
Failures for Non-Urgent A threshold for number of failed rectifiers that activates a
Alarm Non-Urgent Alarm for rectifier failure
(internal event: S Non Urg RFA)
Failures for Urgent Alarm A threshold for number of failed rectifiers that activates
an Urgent Alarm for rectifier failure
(internal event: S Urg RFA)
Include Com Fail in RFA When ticked, communication failure is included in the
RFA. If not, then a communication failure activates an
event S RM Com Failure.
Note! If the event “S Urgent RFA” is activated, the “S Non Urg RFA” is
suppressed. During a mains failure both rectifier alarm events “S Urgent RFA”
and “S Non Urg RFA” are suppressed.
After installing new rectifiers, the new number of modules must be manually confirmed for
ORION, unless the checkbox “Acknowledge New Rectifiers Automatically” is ticked.
This dialogue summarizes the status of the whole rectifier system with numbers
for installed, working (ok) and faulty rectifiers.
After Acknowledgment, the “Rectifier installed” field shows the updated number;
“Rectifier new:” must be 0.
Step 3 To avoid unexpected behaviour of the system, verify that none of the rectifiers
show an error. Go to Status → Rectifier. The Rectifier dialogue displays the
status and configuration status of each rectifier.
The “Com”-LED of the related rectifier module blinks for over a minute, to allow
the module to be physically located.
Step 5 To view more details about each rectifier module, click “Details”.
Step 2 Go to “Number of RM” , enter the password and update the number of modules
or
or
Go to “RM NEW”.
After removal of rectifiers, the new number of modules must be confirmed for the ORION.
If this is not done within a certain time a non-urgent alarm arises.
Go to Status → Rectifier.
The Rectifier dialogue displays the status and configuration status of each
rectifier.
Step 2 Go to “Number of RM” , enter the password and update the number of modules
or
or
Go to “RM LOST”.
Rectifiers can communicate with the ORION using advanced communication protocols.
This allows optimising system performance by controlling the rectifiers individually. The
ORION software currently supports an Efficiency Cycling to adapt the power supply to a
momentary load, which reduces power losses and increases the system efficiency. In
addition, with the Forced Rectifier Cycling, it is possible to avoid always using the same
rectifiers to feed power to the system.
The Rectifier Efficiency Cycling allows to run only as many rectifiers as needed for an
optimum overall system performance for a momentary load. Several parameters are
required to specify how many rectifiers are allowed to be turned off and still be able to
react on instantly increasing power demand. The rectifiers that are turned off are cycled
to make sure they are operating correctly, even if ORION has turned them off.
When using the Efficiency Cycling on systems with phase assigned rectifiers (in AC
Measurement Type “Internal – single phase RM” or “Automatic 3-PH slot assignment”),
the load is actively balanced among the phases. With “Internal – single phase RM” mode
all the rectifiers must be manually assigned to phases in order to insure the correct
balance. If the system has unassigned rectifiers then they will be chosen first to be
stopped and last to be started. This condition is indicated by an event S RM Un-assigned.
In case ORION cannot keep the phase loading balanced (= difference is more than one
rectifier module) an event S RM Efficiency Unbalanced is activated.
Parameter Explanation
Limit Switching Times Limits the number of maximum “OFF” commands per
day and per rectifier.
Force Cycling Every To force the efficiency mode at least once per selected
period to change the rectifiers currently switched on and
off. Choose from “never”, “day” or “30 days”.
Minimum Power Reserve This value must be set according to the load
requirements. With batteries, this value is not as critical.
But without batteries, it must be set to a value that the
load change within a period “T” never exceeds the value.
Otherwise the system power cannot be guaranteed.
Parameter Explanation
Touch UI No access
UIM No access
Power Limitation by Event allows the possibility to save costs by using under-
dimensioned generator sets for power supply during mains outages. In this case the
generator supplies only a part of the power needed, while the battery delivers the rest.
The battery is partially discharged but the backup time can be extended. This is achieved
by decreasing the rectifier output power during genset operation.
While the chosen control event is active and the “Fixed” rectifier power limitation is
enabled, the controller limits the total rectifier power to the given threshold Max.
Total Rectifier Power. If the checkbox No Battery Discharge is marked, the
controller prevents discharging of the battery due to this rectifier power limitation
configuration.
While the chosen control event is active and the “Dynamic” rectifier power limitation
is enabled, the controller limits the total rectifier power in a way that the power
taken from the measured source does not exceed the threshold Max. Generator
Power independent if other AC loads are connected to the same source. If the
checkbox No Battery Discharge is marked, the controller prevents discharging of
the battery due to this rectifier power limitation configuration.
Max Total Rectifier Fixed Maximum allowed output power from the
Power rectifier system
Touch UI No access
UIM No access
The controller monitors the power demand and reacts if the system is unable to recharge
the battery within the expected time. This happens, for example, if additional equipment
has been installed but the increase of power requirement has not been realized. If the
Estimated Recharge Time is greater than the Expected Recharge Time, the internal event
S RM Lack of Power is set. Additional rectifiers are required to correct this.
Recharge Power Supervision can only be configured through the web user interface. The
UIM/UIL interface can be used to view the status and the Estimated Recharge Time.
Parameter Explanation
Expected Recharge Input field to enter the maximum allowed recharge time.
Time
The parameters can be configured and the Estimated Recharge Time can be seen at:
The controller measures the load power every minute and compares it to the available
power from the rectifiers and calculates the real number of redundant modules. If the
result falls in two adjacent samples below the given parameter Expected Number of
redundant RM, the internal event S RM Redundancy Lost is set and informs that
additional rectifiers are needed. The reason for lost redundancy could be the same as
mentioned in section 2.5.8 "Recharge Power Supervision".
ORION displays the actual number of redundant modules and also the number of
modules that should be added to reach the expected redundancy.
Parameter Explanation
Required Number Input field to enter the minimum number of redundant modules.
of Redundant RM
The parameters can be configured and the actual number of redundant and lacking
modules can be seen at:
For information about AC Measurements using rectifiers, see section 2.10.3 "Internal AC
measurement".
Each change in the rectifier slot population must be confirmed. The system controller
needs this information for error detection like incorrect cabling or faulty rectifiers. Click
“Acknowledge new” to mark a slot equipped with rectifier as populated. Click
“Acknowledge lost” to mark an empty slot as not populated. Commissioning, extending, or
reducing the system size, but also changing the physical position of a rectifier in the
system requires a confirmation of the slot population. Replacing rectifiers and using the
same slot does not require the confirmation.
The DC/DC converters are configured to ORION by entering the number of DC/DC
modules into ORION.
The following instructions describe the main functions from the ORION point of view, with
step-by-step instructions.
After communication is first established between the DC/DC converters and the
controller, it is possible to adjust the parameters with the controller. Without initial
communication to the power system controller, Delta’s DC/DC converters use their own
default parameters. With the controller the user can also adjust the default parameters,
after the communication is first established.
The following parameters control the behaviour of the DC/DC converters when the power
system is not in normal operating mode, such as start-up or low input voltage mode.
Parameter Explanation
Parameter Explanation
Parameter Explanation
Parameter Explanation
Start Up Delay The delay for starting up after the input voltage is
connected
Parameter Explanation
If a DC/DC converter malfunctions or fails, the ORION raises a DC/DC converter failure
alarm:
The DC/DC converter is considered as fault if at least one of the following criteria is
fulfilled:
Parameter Explanation
Failures for Non-Urgent A threshold for number of failed DC/DC converters that
Alarm activates a Non-Urgent Alarm for rectifier failure
(internal event: S Non Urg DFA). The default value is 1.
Failures for Urgent Alarm A threshold for number of failed rectifiers that activates
an Urgent Alarm for rectifier failure
(internal event: S Urgent DFA). The default value is 2.
Note! If the event “S Urgent DFA” is activated, the “S Non Urg DFA” is
suppressed.
In addition to the above described two alarms ORION can activate the following events:
S DC/DC new DC/DC Indicates that the user has plugged in a new module and
has not yet acknowledged it
S DC/DC Redundancy Lost Please see the chapter 2.6.5 "Redundancy supervision"
S DC/DC Setup Err The controller is not able to send a correct configuration
to the converter
After installing DC/DC converters, the new number of modules must be manually
confirmed for ORION, unless the checkbox “Acknowledge New DC/DC Converters
Automatically” is ticked.
After removal of DC/DC converters, the new number of modules must be confirmed for
ORION. If this is not done within a certain time a non-urgent alarm arises.
This dialogue summarizes the status of the whole DC/DC system with numbers
for installed, working (ok) and faulty DC/DCs.
After Acknowledgment, the “DC/DC installed” field shows the updated number;
“DC/DC new:” must be 0.
Step 3 To avoid unexpected behaviour of the system, verify that none of the DC/DC
converters show an error. Go to Status → DC/DC. The DC/DC Monitor dialogue
displays the status and configuration status of each DC/DC converter.
The “Com”-LED of the related DC/DC converter module blinks for over a minute,
to allow the module to be physically located.
Step 5 To view more details about each DC/DC converter module, click “Details”.
Step 2 Go to “Number of DC/DC” , enter the password and update the number of
modules
or
The controller calculates the number of redundant DC/DCs by requesting the load power
and reserve power from the DC/DCs once a minute and comparing it the total number of
DC/DCs. If the result falls in two adjacent samples below the given parameter Expected
Number of redundant Redundant DC, the internal event S DC Redundancy
Lost is set.
Parameter Explanation
Required Number Input field to enter the minimum number of redundant modules.
of Redundant
DC/DC
The parameters can be configured and the actual number of redundant modules can be
seen at:
The following instructions describe the main functions from the ORION point of view, with
step-by-step instructions
After communication is first established between the PV chargers and the controller, it is
possible to adjust the parameters with the controller. Without initial communication to the
power system controller, Delta’s PV chargers use their own default parameters. With the
controller the user can also adjust the default parameters, after the communication is first
established.
The following parameters control the behaviour of the PV chargers when the power
system is not in normal operating mode, such as start-up or low input voltage mode.
Parameter Explanation
Parameter Explanation
Input Low Off Threshold (voltage) for shutting down the PVCs when
input voltage is too low.
Input Low On Threshold (voltage) for switching the PVCs on, when
input voltage returns from low to acceptable values.
Parameter Explanation
Parameter Explanation
The PV charger is considered as fault if at least one of the following criteria is fulfilled:
Parameter Explanation
S Non Urg PFA Number of faulty PVCs ≥ Failures for Non-Urgent Alarm
Number of working PVCs > Number of configured PVCs
Number of working DC/DCs ≤ Number of configured
DC/DCs – Failures for Non-Urgent Alarm
Note! If the event “S Urgent PFA” is activated, the “S Non Urg PFA” is
suppressed.
In addition to the above described two alarms ORION can activate the following events
which can be mapped to remote alarms:
Event Description
S PVC Setup Err The controller is not able to send a correct configuration
to the converter
S PVC Input Low System event indicating that one of the converter has
been switched off because of input voltage outside the
range or breaker is open.
S PVC Fan Failure System event indicating that at least one of the PVC
reports fan failure.
S PVC Over-Temp System event indicating that at least one of the PVC
Protection reports OTP.
S PVC Over-Voltage System event indicating that at least one of the PVC
Protection reports OVP
After installing new PC chargers, the new number of modules must be confirmed for the
ORION.
This dialogue summarizes the status of the whole PVC system with numbers for
installed, working (ok) and faulty PVCs.
After Acknowledgment, the “PVCs installed” field shows the updated number;
“PVCs new:” must be 0.
Step 3 To avoid unexpected behaviour of the system, verify that none of the PVC show
an error. Go to Status → PVC. The PVC Monitor dialogue displays the status
and configuration status of each PV charger.
The “Com”-LED of the related PV charger module blinks for over a minute, to
allow the module to be physically located.
Step 2 Go to “Number of PVC” , enter the password and update the number of modules
or
2.8.1 Overview
ORION is able to communicate with Delta inverters over the IMBUS. The inverter
modules can be assigned into three phases with up to 32 inverters per phase.
Battery:
In this mode, the inverter power comes from the DC bus / system batteries. This mode
provides the best output waveform regulation.
Bypass:
In this mode, the AC output is directly connected to the AC input, so the power comes
directly from the mains. This mode is the most efficient mode but the waveform quality is
highly dependent on the mains quality.
Online:
This mode is available only if the inverter has PFC function. The waveform regulation is
the same as the Battery mode, but the power comes from the AC input
The system will swithd between different oprtaion modes based on the chosen operating
profile:
Balanced:
In this profile, the 1st priority is Online, 2nd priority is Battery, and Bypass has lowest
priority. This profile provides good waveform / cost ratio. Once the AC is missing, the
source will change to battery and keep providing the power until the energy is exhausted.
Safe:
In this profile, the first priority is Battery, 2nd priority is Online, and Bypass has lowest
priority. This profile provides the best possible waveform but needs more rectifier capacity
because the inverters are normally powered from the DC bus.
Economic:
In this profile, the first priority is Bypass, 2nd priority in Online, and the last one is Battery.
This mode is the most economic one, but has the worst waveform regulation. This profile
is not suitable for regions with bad mains quality.
Parameter Explanation
Parameter Explanation
DC Input Low Off Turn off limit for the inverter Battery mode
AC Input Low Off Turn off limit for the inverter Online mode
AC Input Frequency Low Off Turn off limit for the inverter Online mode
AC Input Frequency Low On Turn on limit for the inverter Online mode
Parameter Explanation
Parameter Explanation
Power Walk-In Slope Defines how quickly the output current can ramp up
Suppress AC Input Alarms If checked, the AC input related alarms are suppressed
The inverter is considered as fault if at least one of the following criteria is fulfilled:
temporary internal off due to OTP, fan failure, short circuit, overload or
configuration changed
internal off (latched, reason still present) due to OTP or fan failure
internal off (latched, reason not present) due to OTP, fan failure, short circuit
or overload
error (hardware defect)
Parameter Explanation
S Non Urg IFA Number of faulty inverters ≥ Failures for Non-Urgent Alarm
Number of working inverters > Number of configured inverters
Number of working inverters ≤ Number of configured inverters
– Failures for Non-Urgent Alarm
In addition to the above described two alarms ORION can activate the following events
which can be mapped to remote alarms:
Event Description
S Inv AC Outside Range One or more inverter indicate the AC input outside range
S Inv Com Failure Communication is lost between ORION and one or more
inverters
S Inv Overload One or more inverter indicate internal latched off due to
overload
S Inv Setup Err The controller is not able to send a correct configuration
to the inverter
After installing new inverters, the new number of modules must be confirmed for the
ORION unless “Acknowledge New Inverters Automatically” is enabled.
This dialogue summarizes the status of the whole inverter system with numbers
for installed, working (ok) and faulty inverter modules.
After Acknowledgment, the “Inverters installed” field shows the updated number;
“Inverters new:” must be 0.
Step 3 To avoid unexpected behaviour of the system, verify that none of the inverters
show an error. Go to Status → Inverter. The Inverter Monitor dialogue displays
the status and configuration status of each Inverter.
The “Com”-LED of the related Inverter module blinks for over a minute, to allow
the module to be physically located.
2.9.1 Overview
The ORION version, ID:E3 with two CAN buses, is able to control and monitor Eltek
rectiverters (RCV) over CAN bus using eNexus protocol. RECTIVERTER™ is a three
ports module with an AC input port, an AC output port, and a bi-directional DC port. It is
capable of charging the 48V battery and simultaneously providing power for the AC and
DC loads. During mains failure AC loads are feed using energy stored in the battery.
Rectiverters can be used in a single phase or three phase systems. Up to 32 rectiverters
can be connected to ORION.
DC in DC in DC in/out
Pure inverter with Delta RMs Inverter with Delta RMs Rectiverter without RMs
Parameter Explanation
Walk-In Time
AC Input Frequency Low On Turn on limit for the inverter Online mode
Parameter Explanation
In addition to the above described two alarms ORION can activate the following events
which can be mapped to remote alarms:
Event Description
S RCV Com Failure Communication is lost between ORION and one or more
rectiverters
This document assumes that the system is prepared and configured for rectiverters. The
user just needs to insert the modules to the shelves and adjust the operating parameters.
Rectiverters get their IDs automatically according to plug-in order. Therefore, insert the
rectiverter modules one by one in the desired ID order. After inserting new rectiverters,
the new number of modules must be confirmed to ORION unless “Acknowledge New
Rectiverters Automatically” is enabled.
If a rectiverter needs to be removed from the system, pull it out from the shelf and wait for
20 second until the controller recognizes that a module has been lost. Confirm the new
number of modules to ORION by acknowledging the lost module.
Check that the number of new and lost rectiverters is zero and acknowledge if necessary:
The rectiverter system can be equipped with a bypass swtich that can be used to isolate
the rectiverters from the load and to transfer the load to the mains. The transfer can be
done without a break when a “make before break” switch is used. To inform ORION about
the position of the swich, an auxiliary contact is connected to ORION input.
Bypass Switch
(make before break)
AC out
DC in
Dig Input ORION
Auxiliary
Contact
AC in DC out
The positioning is based on location information (cabinet, shelf, and slot if applicable)
which is stored on each converter backplane in a dedicated EEPROM or generated by
jumpers and switches on the backplane. ORION supports positioning using the data
which it obtains via the converters.
This type of arrangement is used if the shelf identification is not necessary (for example,
systems with DPR 7200B-48 rectifiers using one rectifier per shelf). With this scheme, up
to 43 cabinets are possible. Each cabinet has up to 16 slots. Although 256 different slot
addresses are possible, the system size is limited to 128 rectifiers. Each cabinet requires
its own RPGA board, or each backplane must be equipped with a memory device in which
the address is stored. The rectifier name consists of cabinet and slot address (for
example, DC 2.9, where DC is the name of the converter located in slot 9 of cabinet 2).
Step 7 In the Converter Positioning Editor dialog, select the Converter Slots that are
available for use in the cabinet.
Change the cabinet name by entering the new name in the Name field.
Shelf Scheme is used for systems with the converters arranged in shelves, for example,
systems with FR 48V-2000W-E, DPR 1200B-48, or DPR 600B-48… rectifiers. With this
scheme, up to 43 shelves are possible. A cabinet can be assigned to each shelf. Each
shelf consists of up to 16 slots. Although 4096 different slot addresses are possible, the
system size is limited to 128 converters. Each cabinet requires its own RPGA board, or
each backplane must be equipped with a memory device in which the address is stored.
The converter name consists of the cabinet address, shelf address and slot address (for
example, RM 1.3.7, where RM is the name of the rectifier located in slot 7 on shelf 3 of
cabinet 1).
RM RM RM RM
1.1.1 1.1.2 1.1.7 1.1.8
Shelf 1
RM RM DC Not
1.2.1 empty 1.2.7 avail.
Shelf 2
DC DC RM RM RM RM RM RM
1.3.1 1.3.2 1.3.7 empty
Shelf 3 x.14.1 x.14.2 x.14.7 1.16.8
x.14.8
Shelf 14
RM RM RM RM
x.15.1 x.15.2 x.15.7 1.16.8
x.15.8
Shelf 15
RM RM RM DC
x.16.1 x.16.2 x.16.7 empty
Shelf 16
Parameter Explanation
Step 5 Select “Shelf ID” from the drop-down list and click “Add Shelf”.
Step 6 In the Converter Positioning Editor dialog, select the converter slots
(checkboxes) that are available for use in the shelf.
Parameter Explanation
Type The name of the module is the same as the name of the
mapping file
Step 2 Select File Type “Modbus Master Mapping” and click “Load File from PC”.
Step 3 Click “Choose File” and select the mapping file that is stored in your PC.
Step 8 Select the “Interface” and “Slave Id” and click “Add. The new module will appear
in the list of Modbus Slaves. Check that the Status of the module is OK
Parameter Explanation
Standby fan speed Defines the speed of the internal fan while the
compressor is off. “Low” or “High”.
Touch UI No access
Touch UI No access
UIM No access
Caution! The FAN-CTRL module and IOM-X1 module are configured in Delta
system factory, so please do not change any settings unless you are absolutely
sure about what you are doing. Wrong settings can result in over temperature of
the equipment.
Available alarm events (visible as horizontal lines) can be connected freely with the
outputs (visible as vertical lines). The outputs are grouped by module and all groups can
be collapsed and expanded. Any available event can be added to the list of alarm events
by clicking the icon.
To be able to map an event to an output using the alarm mapping functionality, it has to
be selected to the list of alarm events. Defining an alarm event adds also additional
functionality and behaviour to it:
The alarm events are internally inverted when used for driving relay outputs.
An active alarm event releases the relay, and therefore, even if the system is
not powered, the active alarm status is still indicated. In other words, when
Only alarm events can be inhibited in the output relays with the function Alarm
Stop. This is useful during maintenance when alarms are expected, but do not
require any actions. The critical alarms are usually driving some relays that
activate external alarming systems. These alarms can be quickly inhibited
with the Alarm Stop function (button “Stop Alarms” at the top of the browser
window or menu “ALARM STOP” in the UIM/UIL interface).
The alarm events are shown on the home page when active.
The status of alarm events is always displayed on the page Alarm → Status.
Step 3 Select an event from the “Non-Alarm Events” list and click “Add”.
The event appears on the “Removable” user alarm events list. It is possible to
select multiple events at same time by using “Shift” and “Ctrl” keys.
Note! The events defined as alarms receive automatically a prefix “A” in front of
the event name. However, on the alarm mapping page this prefix is not shown.
Step 1 Select an event from the “Non-Alarm Events” list and click “Remove”.
Note! The “Non-Removable” list is a list of events that are defined as alarms,
and have been taken into use by some function. Or mapped to an output. These
events cannot be removed from the alarm event list before they are disabled
from the use of the function or functions.
Available alarm events (visible as horizontal lines) can be connected freely with the
outputs (visible as vertical lines). One event can be mapped to several outputs and up to
64 events can be mapped to a single output. The outputs are grouped by module and all
groups can be collapsed and expanded by clicking the minus and plus icon.
Step 3 To disconnect an existing connection click the circle on the crossing of the lines.
Note! Various tooltips are shown when the user leaves the mouse over special
elements:
“Edit Alarm Events” appears on the “edit” icon for the Alarm Events.
“Collapse this group” appears on each “minus” icon in the expanded groups.
“Expand this group” appears on each “plus” icon in the collapsed groups.
“This group has some input/output mapping” appears on the “link” icon for a
collapsed group.
“Clear all connections” appears in the “clear all” icon below a group title.
On each connection a tooltip appears indicating the state of the connection:
“S Urgent Alarm <---> OUT 1” indicates that the connection active.
“S Urgent Alarm <-x-> OUT 1” indicates that the connection is not active.
A tooltip shows the full name of a module, an output and an alarm when the
mouse is over the name (useful in case of truncated name).
For easier identification, it is possible to add a label such as “Urgent alarm” or “Mains
failure” for an output.
Step 2 If the module is not shown, click it in the module list on the right of the page.
It is possible to block an alarm event from triggering a remote alarm. This may be
required during system upgrade, maintenance, or repair situations where events maybe
triggered, but alarms are not required. If an alarm is already active it is frozen in the active
state unless it is reset.
Step 2 For each alarm event, select “frozen”, or click “Stop Alarms” to block all alarm
events having the checkbox Alarm Stop selected.
2.15.2.2 Touch UI
Use this procedure to block all alarm events by activating Alarm Stop.
Caution! When it is no longer necessary to block alarm events, activate the alarms
again by pressing Activate Alarms
In case the Lach functionality of the signal processing engine is used to memorize
alarms, the user has a possibility to map a system event S Alarm Reset to the reset input
of the latches to reset these alarms.
UIM No access
ORION indicates an active alarm by showing a red alarm bell at the right top corner of the
touch UI. In many cases there is also a small red symbol shown together with an icon on
the status page. The red alarm bel is also a link to the Alarm page that shows more
details about the active alarms.
While the screen saver is active, the active alarm is indicated by a red alarm bell that
moves slowly. Additionally the screen can blink if the blinking is enabled on the page
Configuration > Options.
2.16.1 Measurements
All signals that are processed by the ORION controller must be defined as
measurements. Some of them (so-called system measurements) are predefined and
others are generated automatically by defining other system components. There are three
different types of measurements available: Digital, Analogue, and Temperature
measurements.
Digital Measurement
A digital measurement has an adjustable switching level for both directions using the
threshold and hysteresis setting. This can be used for conditioning even noisy signal
sources.
Analogue Measurement
The analogue measurement is used to monitor voltage signals. The measured voltage
may be corrected in a certain range by calibration.
Temperature Measurement
Scaled Measurement
The scaled measurement is used to convert voltage signals into power signals. The
measured voltage can be scaled by a linear conversion, which is defined by two
measurement points. Each measurement point is described by an input value and an
output value.
TIme Measurement
The time measurement measures how long an event has been active. This measurement
can be manually reset in the menu Control → Counter.
From the New Measurement drop-down menu, select the measurement type:
Digital
Analogue
Temperature
Scaled
Time
Step 6 Select the ORION module that the measurement hardware is connected to, for
example, ORION.
Step 7 Select the measurement, created earlier, from the drop-down menu.
Only input measurements with equal units are allowed and the same unit is automatically
selected as well for the output. The output can be used for signal processing in the same
way as any other measurement. The output measurement keeps the properties
(measurement type) of the input measurements, i.e. a Difference Measurement of two
Analogue Measurements has still the properties of the Analogue Measurements.
Step 3 Enter a name for the new measurement and select the processed
measurements.
To use the signal processing engine together with analogue (including temperature)
measurements, they must be digitized first. This is done by defining a threshold and a
hysteresis value for the measurement. Each definition must have a unique name. The
result of this definition is an event. In the ORION some internal system events are created
by default at the Delta factory. The threshold editor within the Event Definition allows
defining both polarities of events. As many different thresholds as needed per
measurement can be defined.
Parameter Explanation
Step 2 Select the required measurement from the New Event(s) on Measurement
drop-down list.
Step 4 In the Threshold Editor dialogue, enter a name or names for the new event(s)
and define the parameters (thresholds and hysteresis).
The setting “UIM Access” defines if the parameters for the defined events can be seen
and/or edited through the Touch UI/UIM interface.
All events, including the system defaults and user-defined events can be processed with
each other. Boolean Logic (AND, OR, Inversion), RS Latching, timer, filter, counter and
time counter functions can be used to process events together or separately. The
maximum number of each function type is 256.
AND event
Parameter Explanation
OR event
The OR event is active, if one or more of the source events are active.
Parameter Explanation
3rd to 8th source event If necessary. Unique source names (event) required.
Inverted event
The Inverted event is active when the source event is not active and vice-versa.
Parameter Explanation
RS latch event
The RS latch combines any two different events to produce an output event state
according to the following truth table:
Function Reset Event input to reset the output Event. If the input Event is still
active, then the active reset Event has no influence. Optional.
If a latch event is defined without input events, it can be mapped to the SNMP Control
Event Table and controlled remotely by SNMP protocol.
Timer event
This function allows creating time controlled events. The Timer event is activated based
on the weekday and the time. The Event is activated on the defined Start Time on every
selected Start Days. It is stopped on the defined End Time on every Selected End Days.
The Start Time and End Time depend on the time settings of ORION. It means that the
times represent the same time zone and daylight savings as the ORION.
Parameter Explanation
Start Day Day of week to set the event to TRUE at Start Time.
End Day Day of week to set the event to FALSE at End Time.
If there are two or more consecutive start or end moments, the current event state is
maintained until a corresponding end or start moment occurs. If a start moment has the
same value as the end moment, the event state is maintained.
Filtered event
The event follows the state of a source event only if/when the time thresholds TRUE and
FALSE are passed. Additionally it is possible to define the state of the output in case the
state of the input event is “indeterminate”.
Parameter Explanation
TRUE for min. When the source event remains active for the specified
time (TRUE) the filtered event is activated.
FALSE for min. When the source event has been deactivated for the
specified time (FALSE) the filtered event is deactivated.
Counter event
A Counter event is counting the false to true transitions of a configured Input event. When
the Counter value matches the counter threshold, the Counter event changes state.
The Counter event has an Enable event. As long as the Enable event is true, the Counter
event counts the false to true transitions of the Input event. If the Enable event is false,
transitions are not counted.
The Counter event has a Reset event. When the Reset event is true, the Counter event
state is set to false, it does not count transitions and the counter value is set to zero. If the
Reset event is false, the Counter event counts normally. The Reset Event has the priority
over the Enable event.
It is at anytime possible to reset the Counter event state and counter value from the Web
interface of the UIM. This kind of reset acts like the Reset event.
There are 2 modes of behaviour for a Counter event, standard and toggle. In standard
mode the Counter event counts until it reaches the threshold, then the Counter event
state is set to true and the counter does not count anymore. In toggle mode the Counter
event counts until it reaches the threshold, then the Counter event state is toggled, the
counter value is reset and the counting goes on.
Parameter Explanation
Threshold When the counter value reach this limit, then the
Counter event state is changed according to the mode
The Time counter event works exactly the same way the Counter event does, except it is
not counting any event transitions, but it is counting seconds. The operating parameters
are also the same except that there is no Input parameter.
Event processing can only be modified through the web user interface.
Step 2 In the Event Processing dialogue, select event type from the Event Type drop-
down menu (AND, OR, Inversion, Filter, RS Latch, Timer, Counter, Time
Counter).
Step 4 In the open dialogue, enter a unique name for the new processed event and
define the parameters.
The thresholds and hysteresis of source events, filter parameters and settings for timers
can be edited in the menu:
The internally defined events can be assigned a relay or an open collector output of
ORION or an add-on module for an external alarming system, and/or a LED integrated to
the UIM/UIL interface. However, in SW versions V6.20 and above, it is recommended to
use the Alarm Mapping functionality for configuring alarms instead of direct mapping of
events on various module specific pages. For more details, please look at the chapter
2.12 "Configuring alarms".
External alarms can be connected to the ORION and to the signal processing engine for
further processing, using the digital input interfaces of the ORION.
Alarm events for I/O cannot be configured through the UIM/UIL interface.
Step 2 Select the signals for Digital Inputs/Temperatures/Middle Point Inputs from the
respective drop-down menu.
Step 3 Select the events for the Digital Outputs/Open Collector Outputs/LVD Outputs
from the respective drop-down menu.
Step 4 Ensure the cabling for external equipment is according to the required
configuration.
Note! It is recommended to use the alarm events differentiated by prefix “A” for
remote alarming. When assigned to relay outputs, the alarm events are
internally inverted. An active alarm event releases the relay, and therefore, even
if the system is not powered, the active alarm status is still indicated.
It is recommended to do the mapping of alarms to LEDs using the Alarm Setup page.
Please see the chapter 2.12 "Configuring alarms". In older SW versions the mapping is
done in the HW module specific configuration pages using the following procedure:
Step 3 If a buzzer is required, (integrated in UIM but not in UIL), select the event that
activates the buzzer from the drop-down menu and untick the checkbox
“Disable”.
Step 4 To create a “Stop Alarms” button at the top of the browser page, select “Display
an Alarm Stop Button”.
Step 5 If required, disable Password for Battery Functions/Alarm Stop by means of the
appropriated checkbox.
Step 6 If required, activate numerical password for UIM / UIL by checking the
“Numerical” checkbox.
Step 2 Select external input events for the correct ORION interfaces in this menu
(Digital Inputs). For the external events to appear in the drop-down menu, they
must be created in the event definition menu.
When the buzzer is active, the user can silence it for 30 minutes by pressing EXIT button.
External
Internal
The rectifier or rectiverter modules measure the input AC voltage and these
measurements are used to show the input AC voltages of the system on web GUI and on
the display of the controller. With single-phase rectifiers, the assignment of modules to
the phases can be manual or automatic depending on the rectifier type and the system
HW. In single phase system or when using three phase rectifiers or rectiverters, no phase
assignment is needed.
HPS
The AC parameters are measured by the HPS ID:A1 module connected via IMBUS to the
controller.
Step 2 Select “external”, “internal - single phase RM”, “internal three phase RM”, “HPS”,
“automatic 3-PH slot assignment”, “internal – single phase system” or
“rectiverter” from drop-down menu.
The ACM1 is a gateway between the ORION and an external 3 phase AC-measurement
device, using RS 485 interface with MODBUS protocol. The commissioning procedure is
possible through the web user interface.
Step 4 Adjust the communication parameters on the AC measurement device. Set the
Hex switch on ACM1 accordingly.
Step 6 In the ACM Devices, enter name of the external AC measurement device.
In case physical addressing is not used in the system, the phase assignment of single-
phase rectifiers needs to be manually according to the following instructions. The purpose
of the assignment is to tell ORION which rectifier modules are connected to phases 1, 2
and 3.
Step 2 Select “internal – single-phase RM” from drop-down menu for “AC Measurement
Type”.
Step 7 For the rectifier connected to the selected phase, click “Config”.
Step 9 Select the next phase and repeat the steps 7 and 8.
The selection of the AC Measurement Type cannot be done via Touch UI, but the phase
assignment is possible.
Step 4 For the rectifier connected to the selected line, press the “Config” button.
The selection of the AC Measurement Type cannot be done via UIM, but the phase
assignment is possible.
Step 5 For the rectifier connected to the selected line, click “Config”.
If the positioning of rectifiers is used and the AC measument type “Automatic 3-PH Slot
Assignment” is selected, the controller reads the three-phase voltages from the rectifiers
using following logic:
L1 is read from the first, fourth, seventh, tenth... rectifier in the rectifier position
table
L2 is read from the second, fifth, eight, eleventh... rectifier
L3 is read from the third, sixth, ninth, twelfth... rectifier
The controller calculates the average voltage from the rectifiers connected to the same
phase. If the measurement is not plausible, it will be not considered in calculation.
Step 2 Select “Automatic 3-PH Slot Assignment” from drop-down menu for “AC
Measurement Type”.
Step 2 Select “Automatic 3-PH Slot Assignment” from drop-down menu for “AC
Measurement Type”.
Note! The logging function can only be configured through the web user
interface.
Step 6 Select the check box “Unix Time” in case you need to have the time stamp also
as Unix time in the log
Step 8 Set the maximum number of log entries in a log file (100 .. 10 000).
Step 9 Select the check box "Excel Compliant" to help Excel to open the log files
containing UTF-8 encoded characters
Event Event state Description seen in the log of UIM & WEB
Step 3 Click “Save to PC” and follow the instructions on the screen.
Step 2 Select “Store Logs” from the list and follow the instructions on the screen
Each login generates a session, which runs until the user logs out or until ORION
terminates it under certain circumstances. ORION supports multiple concurrent sessions,
but only one user can have write access. To track the login/logout activities, a default log
entry is generated every time someone logs in or out of the controller.
The User and Session Management is located in the web user interface
(ORION Configuration and Supervision Tool) menu:
Table 38 describes the default users that are defined in the default user file stored in
ORION. We recommend that at least the passwords are changed after commissioning
the system. Each user can edit his own password. The administrator can edit all
passwords.
With different user profiles, the administrator can optimize the use of the ORION
Configuration and Supervision Tool for different user groups. The different access profiles
define the parameters and measurement displays editable/visible to the user.
Configuration Enables the user to configure the system and edit all the
parameters.
Note! Admin can configure users with any access profile as read-only.
Note! Delta recommends that the default user profiles are only used as access
profiles during commissioning. The administrator should then create new user
profiles according to the organization and delete the default ones. The easiest
way to do this is to load in a new user file.
Step 2 Create new user profiles one by one according to the organization requiring
access to the ORION, or load in the complete set of users as a user file.
Step 4 Distribute the new user profiles to the respective users, and instruct the users
how to log in and change their passwords.
Step 4 Wait until the new user file has been uploaded successfully.
Step 2 In the “User Profiles” section, enter the name of the new user profile and click
“Add User”.
Step 5 Select language for the user (if other than English).
Step 1 Log in to the ORION Configuration and Supervision Tool as the user the
password change concerns.
Step 4 In the Password Editor dialogue, enter the old password and the new password
(twice).
Step 2 Select the checkbox for the user profile you want to delete.
Note! The user file can also be saved by using the file manager Configuration →
System → File Manager.
Note! Only Admin can delete the user file. As soon as the user file is deleted, all
running sessions of other users are terminated and the Admin profile parameters
are set to default values.
4.2 Radius
Remote Authentication Dial-In User Service (RADIUS) is a networking protocol that
provides centralized Authentication, Authorization and Accounting (AAA) management for
users who connect and use a network service. ORION can be configured to work as a
RADIUS client which is able to forward login authorization requests for a Remote Access
Server (RAS) in order to gain access to the ORION WEB GUI.
When RADIUS is enabled, but the authentication fails or the RAS is not reachable,
ORION falls back to the normal local user’s (built-in users) authentication process.
Group Configuration The RAS user role to map on the ORION Configuration role
Group Operation The RAS user role to map on the ORION Operation role
Group Monitor The RAS user role to map on the ORION Monitor role
Language The default language for all the users authenticated via RAS
Fallback Policy In case the “CLASS” (#25) is not available or there was not a
matching entry available the selected policy will be chosen
Step 5 Click “Edit RADIUS Parameters” and set the parameters according your RAS
setup.
Parameter Description
Session Type Indicates from which channel the session was initiated. (Web,
REST-API, HTTP-API)
Session State Each session runs through a set of state between login and
DB Access Indicates what database access this session has. Only one
session can have read-write access at the same time!
Last Access [s] Time in seconds since the last request for an object from the
web server.
The controller manages unsuccessful login attempts in order to prevent misuse of existing
user accounts. For each user account, the controller counts the login attempts with
incorrect password. If too many incorrect passwords are typed in within a given time, the
user account is locked out.
Parameter Description
With Administrator rights, the user can edit the Parameters of Session Manager, shown in
Table 42.
Parameter Description
Max sessions Total number of (WEB) sessions running at the same time.
The local user has higher priority over the remote web users. As soon as the local user
changes the configuration via UIM/UIL, the remote session will be terminated.
The Inventory Report file contains a list of all modules connected to IMBUS. The following
data is saved for each module:
Module type
Part Number
Serial Number
HW Revision (Top Level)
SW Version and Build Number
Part Number
Serial Number
HW Revision (Top Level)
Software Version and Build Number
Step 3 Once the report is ready, click “Save to PC” and follow instructions on screen.
The created file is saved on the ORION controller. A previously created report will always
be overwritten when a new one is created. The Inventory Report file also appears in the
file manager, where it can be deleted or downloaded as well.
The file has a readable text format (ASCII) and all the labels are written in English.
Note! Inventory information is gathered after the system boot from each
connected imbus module. Depending on the system size, collecting the
information can take 2 to 5 minutes. It is recommended to wait at least 5 min
after the system boot to get correct information.
Note! The environmental conditions can be harsh which puts very high
requirements on the SD card to be used. Only high quality SLC memory cards,
developed for industrial applications, can guarantee the required data retention
at elevated operating temperatures. SC cards that are sold for consumer
products do not serve the purpose.
SLC technology
SD and SDHC standards (no SDXC)
512MByte minimum space
Temperature range from -40°C to +85°C.
Read Retry including inbuilt threshold voltage shift to compensate high
temperature differences
Built-in power fail protection
Delta recommends using the SLC 512MB S-450u, an industrial grade micro SD card from
Swissbit (p/n SFSD0512N1BM1TO-I-ME-221-STD; https://www.swissbit.com/). This card
is worldwide available from Digikey (http://www.digikey.com/) and other distributers.
Step 4 When the controller has started, log into the web interface and enable the
automatic backup at: Configuration → System → File Manager.
Step 1 Pull out the old controller from the shelf and remove the microSD card.
Step 2 Insert the microSD card into the card slot of the new controller
Step 4 When the controller starts up, it will ask if the backup from the microSD card
should be used. Please confirm.
When creating the backup, the user can choose whether to include the software file into
the backup or not. The backup withour the software is naturally smaller and thus easier to
distribute to the sites when doing functional upgrade, but the user has the responsibility to
make sure that the backup is compatible with the existing SW in the controller. With the
full backup file, there is no possibility for incompatibility.
When restoring the setup, the user can choose whether to overwrite the communication
settings or not. Keeping the communication settings is useful when upgrading the
controller configuration remotely by loading in a complete backup file. The user can also
choose whether to keep the “System Specific Settings” or not. These settings include
calibration and energy data and log files. This option is useful when upgrading controllers
SW and settings by using a backup file.
Backup/Restore procedure can be triggered either over Web or from USB device in case
a controller version with USB port is used.
Step 2 Click Create Backup “Without Software” or ”With Software”and follow the
instructions on the screen.
Step 2 From the “File Type” drop-down list select “ORION Backup” and click “Load File
from PC”.
Step 4 Optionally select “Preserve Documents if you do not want to overwrite the locally
stored documents
Step 5 Click “Choose File” and choose the ORION Backup file to be transferred, and
select it.
The progress of the restoration will be displayed. If an error occurs, the update procedure
will stop. Upon completion, the ORION will automatically reboot with the settings defined
in the backup file.
Note! Please be aware that all the previous settings will be lost if the options
“Keep Communication Settings” and/or “Keep System Specific Settings” are not
selected . Only the license key for Software features and the LCD contrast
settings will be kept.
Use the following procedure to create a backup file and save it to a USB memory:
Step 2 On the LCD screen, the menu FILE MANAGER appears automatically.
Step 3 Push the command “Create Backup With SW” or “Create Backup Without SW”
and wait until “Backup created” is shown.
Note! If you pull out the USB storage device while creating the backup, the
operation is interrupted and an error is shown.
Step 5 On the LCD screen, the menu 6.11 FILE MANAGER appears automatically.
Step 7 Choose the archive to load the backup from and wait until the controller reboots.
Note! If you pull out the USB storage device while restoring backup, the
operation is interrupted only if it cannot be finished without the USB device (i.e. if
the archive was already copied to the controller, the restore operation
continues).
There is a dedicated menu point “Documents” for document management, but the
documents are accessible also via File Manager.
Use this procedure to set the IP address of the computer manually to enable
communication with ORION.
Step 1 Enable the manual mode in ORION by using the local user interface
Touch UI: MENU Network IPv4
UIM: NET CONFIG → ETHERNET → IPv4→ MODE.
Step 2 Set the IP address of the computer to the same network area as the computer.
Step 4 Connect the computer to the ORION LAN connector with the appropriate cable.
Step 5 Open an internet browser and connect to the IP address of the ORION.
Note! If the IP address contains a zero or zeroes after a period, remove the
zeros, for example, 010.120.177.031 → 10.120.177.31.
Step 6 When the ORION login page loads, enter the username and password, and click
“Submit”.
Step 7 The web interface is now open and it is possible to change the configuration and
setting if necessary.
Note! If the browser cannot connect to the ORION, check the proxy server
setting in the browser options. A proxy must not be used.
Use this procedure in case the user has no privileges to change the IP settings of the
computer and a fixed IP address is used.
Step 1 Enable the manual mode in ORION by using the local user interface
Touch UI: MENU Network IPv4
UIM: NET CONFIG → ETHERNET → IPv4→ MODE
Step 2 Set the IP address of the ORION using the local interface to the same network
area as the computer. Only the numbers in the last section of the IP address can
be different.
Step 4 Connect the computer to the ORION LAN connector with the appropriate cable.
Step 5 Open an internet browser and connect to the defined IP address of the ORION.
Note! If the IP address contains a zero or zeros after a period, remove the
zeros, for example, 010.120.177.031 → 10.120.177.31. When the ORION
configuration and supervision tool login page loads, enter the username and
password, and click “Submit”.
Step 6 The web interface is now open and it is possible to change the configuration and
setting if necessary.
Note! If the browser cannot connect to the ORION, check the proxy server setting
in the browser options. A proxy must not be used.