0% found this document useful (0 votes)
36 views

Modicon M251 Logic Controller System Functions and Variables PLCSystem Library Guide

The document provides a comprehensive guide to the Modicon M251 Logic Controller, detailing its system functions and variables within the PLCSystem library. It emphasizes the importance of proper installation, operation, and maintenance by qualified personnel, and includes safety information and related documentation. The guide is intended for users with a basic understanding of the M251's functionality and programming languages such as FBD, LD, ST, IL, or CFC.

Uploaded by

nbea
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
36 views

Modicon M251 Logic Controller System Functions and Variables PLCSystem Library Guide

The document provides a comprehensive guide to the Modicon M251 Logic Controller, detailing its system functions and variables within the PLCSystem library. It emphasizes the importance of proper installation, operation, and maintenance by qualified personnel, and includes safety information and related documentation. The guide is intended for users with a basic understanding of the M251's functionality and programming languages such as FBD, LD, ST, IL, or CFC.

Uploaded by

nbea
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 104

Modicon M251 Logic Controller

EIO0000001468 04/2014

Modicon M251 Logic


Controller
System Functions and Variables
PLCSystem Library Guide
04/2014
EIO0000001468.00

www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical
characteristics of the performance of the products contained herein. This documentation is not
intended as a substitute for and is not to be used for determining suitability or reliability of these
products for specific user applications. It is the duty of any such user or integrator to perform the
appropriate and complete risk analysis, evaluation and testing of the products with respect to the
relevant specific application or use thereof. Neither Schneider Electric nor any of its affiliates or
subsidiaries shall be responsible or liable for misuse of the information contained herein. If you
have any suggestions for improvements or amendments or have found errors in this publication,
please notify us.
No part of this document may be reproduced in any form or by any means, electronic or
mechanical, including photocopying, without express written permission of Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and
using this product. For reasons of safety and to help ensure compliance with documented system
data, only the manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant
instructions must be followed.
Failure to use Schneider Electric software or approved software with our hardware products may
result in injury, harm, or improper operating results.
Failure to observe this information can result in injury or equipment damage.
© 2014 Schneider Electric. All rights reserved.

2 EIO0000001468 04/2014
Table of Contents

Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
About the Book. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 1 M251 System Variables . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.1 System Variables: Definition and Use . . . . . . . . . . . . . . . . . . . . . . . . . 12
Understanding System Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Using System Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
1.2 PLC_R and PLC_W Structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
PLC_R: Controller Read-Only System Variables . . . . . . . . . . . . . . . . . 18
PLC_W: Controller Read/Write System Variables . . . . . . . . . . . . . . . . 22
1.3 SERIAL_R and SERIAL_W Structures . . . . . . . . . . . . . . . . . . . . . . . . 23
SERIAL_R[0...1]: Serial Line Read-Only System Variables . . . . . 24
SERIAL_W[0...1]: Serial Line Read/Write System Variables . . . . . 25
1.4 ETH_R and ETH_W Structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
ETH_R: Ethernet Port Read-Only System Variables . . . . . . . . . . . . . 27
ETH_W: Ethernet Port Read/Write System Variables. . . . . . . . . . . . . . 32
1.5 TM3_MODULE_R Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
TM3_MODULE_R[0...13]: TM3 Modules Read-Only System
Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
1.6 PROFIBUS_R Structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
PROFIBUS_R: PROFIBUS Read-Only System Variables . . . . . . . . . 34
Chapter 2 M251 System Functions. . . . . . . . . . . . . . . . . . . . . . . . . 35
2.1 M251 Read Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
GetRtc: Get Current RTC Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
IsFirstMastColdCycle: Indicates if Cycle is the First MAST Cold
Start Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
IsFirstMastCycle: Indicates if Cycle is the First MAST Cycle . . . 39
IsFirstMastWarmCycle: Indicates if Cycle is the First MAST Warm
Start Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
2.2 M251 Write Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
SetRTCDrift: Set Compensation Value to the RTC. . . . . . . . . . . . . 42
2.3 M251 User Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
DataFileCopy: Copy File Commands . . . . . . . . . . . . . . . . . . . . . . . 45
ExecuteScript: Script Commands . . . . . . . . . . . . . . . . . . . . . . . . . 48
2.4 TM3 Read Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
TM3_GetModuleBusStatus: Get TM3 Module Bus Status . . . . . . . 51
TM3_GetModuleInternalStatus: Get TM3 Module Internal Status 52
EIO0000001468 04/2014 3
Chapter 3 M251 PLCSystem Library Data Types . . . . . . . . . . . . . 55
3.1 PLC_R/W System Variables Data Types. . . . . . . . . . . . . . . . . . . . . . . 56
PLC_R_APPLICATION_ERROR: Detected Application Error Status
Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
PLC_R_BOOT_PROJECT_STATUS: Boot Project Status Codes . . . 58
PLC_R_IO_STATUS: I/O Status Codes . . . . . . . . . . . . . . . . . . . . . . . 59
PLC_R_SDCARD_STATUS: SD Card Slot Status Codes. . . . . . . . . . 60
PLC_R_STATUS: Controller Status Codes . . . . . . . . . . . . . . . . . . . . . 61
PLC_R_STOP_CAUSE: From RUN State to Other State Transition
Cause Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
PLC_R_TERMINAL_PORT_STATUS: Programming Port Connection
Status Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
PLC_R_TM3_BUS_STATE: TM3 Bus Status Codes . . . . . . . . . . . . . 64
PLC_W_COMMAND: Control Command Codes . . . . . . . . . . . . . . . . . 65
3.2 DataFileCopy System Variables Data Types . . . . . . . . . . . . . . . . . . . . 66
DataFileCopyError: Detected Error Codes. . . . . . . . . . . . . . . . . . . . . . 67
DataFileCopyLocation: Location Codes. . . . . . . . . . . . . . . . . . . . . . . . 68
3.3 ExecScript System Variables Data Types . . . . . . . . . . . . . . . . . . . . . . 69
ExecuteScriptError: Detected Error Codes . . . . . . . . . . . . . . . . . . . . . 69
3.4 ETH_R/W System Variables Data Types. . . . . . . . . . . . . . . . . . . . . . . 70
ETH_R_FRAME_PROTOCOL: Frame Transmission Protocol Codes 71
ETH_R_IP_MODE: IP Address Source Codes . . . . . . . . . . . . . . . . . . 72
ETH_R_PORT_DUPLEX_STATUS: Transmission Mode Codes . . . . 73
ETH_R_PORT_IP_STATUS: Ethernet TCP/IP Port Status Codes . . . 74
ETH_R_PORT_LINK_STATUS: Communication Link Status Codes . 75
ETH_R_PORT_SPEED: Communication Speed of the Ethernet Port
Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
ETH_R_RUN_IDLE: Ethernet/IP Run and Idle States Codes . . . . . . . 77
3.5 TM3_MODULE_R System Variables Data Types . . . . . . . . . . . . . . . . 78
TM3_ERR_CODE: TM3 Expansion Module Detected Error Codes . . 79
TM3_MODULE_R_ARRAY_TYPE: TM3 Expansion Module Read
Array Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
TM3_MODULE_STATE: TM3 Expansion Module State Codes . . . . . 81
3.6 System Function Data Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
RTCSETDRIFT_ERROR: SetRTCDrift Function Detected Error
Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

4 EIO0000001468 04/2014
Appendix A Function and Function Block Representation . . . . . . 85
Differences Between a Function and a Function Block . . . . . . . . . . . . 86
How to Use a Function or a Function Block in IL Language . . . . . . . . 87
How to Use a Function or a Function Block in ST Language . . . . . . . 91
Glossary ......................................... 95
Index ......................................... 103

EIO0000001468 04/2014 5
6 EIO0000001468 04/2014
Safety Information

Important Information

NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device
before trying to install, operate, or maintain it. The following special messages may appear
throughout this documentation or on the equipment to warn of potential hazards or to call attention
to information that clarifies or simplifies a procedure.

EIO0000001468 04/2014 7
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
the use of this material.
A qualified person is one who has skills and knowledge related to the construction and operation
of electrical equipment and its installation, and has received safety training to recognize and avoid
the hazards involved.

8 EIO0000001468 04/2014
About the Book

At a Glance

Document Scope
This document acquaints you with the system functions and variables offered within the Modicon
M251 Logic Controller. The M251 PLCSystem library contains functions and variables to get
information from and send commands to the controller system.
This document describes the data type functions and variables of the M251 PLCSystem library.
The following knowledge is required:
 Basic information on the functionality, structure, and configuration of the M251 Logic Controller
 Programming in the FBD, LD, ST, IL, or CFC language
 System variables (global variables)

Validity Note
This document has been updated with the release of SoMachine V4.1.

Related Documents

Title of Documentation Reference Number


SoMachine Programming Guide EIO0000000067 (ENG);
EIO0000000069 (FRE);
EIO0000000068 (GER);
EIO0000000071 (SPA);
EIO0000000070 (ITA);
EIO0000000072 (CHS)
Modicon M251 Logic Controller Hardware Guide EIO0000001486 (ENG);
EIO0000001487 (FRE);
EIO0000001488 (GER);
EIO0000001489 (SPA);
EIO0000001490 (ITA);
EIO0000001491 (CHS)
Modicon M251 Logic Controller Programming Guide EIO0000001462 (ENG);
EIO0000001463 (FRE);
EIO0000001464 (GER);
EIO0000001465 (SPA);
EIO0000001466 (ITA);
EIO0000001467 (CHS)

EIO0000001468 04/2014 9
You can download these technical publications and other technical information from our website
at www.schneider-electric.com.

Product Related Information

WARNING
LOSS OF CONTROL
 The designer of any control scheme must consider the potential failure modes of control paths
and, for certain critical control functions, provide a means to achieve a safe state during and
after a path failure. Examples of critical control functions are emergency stop and overtravel
stop, power outage and restart.
 Separate or redundant control paths must be provided for critical control functions.
 System control paths may include communication links. Consideration must be given to the
implications of unanticipated transmission delays or failures of the link.
 Observe all accident prevention regulations and local safety guidelines.1
 Each implementation of this equipment must be individually and thoroughly tested for proper
operation before being placed into service.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.

1For additional information, refer to NEMA ICS 1.1 (latest edition), "Safety Guidelines for the
Application, Installation, and Maintenance of Solid State Control" and to NEMA ICS 7.1 (latest
edition), "Safety Standards for Construction and Guide for Selection, Installation and Operation of
Adjustable-Speed Drive Systems" or their equivalent governing your particular location.

WARNING
UNINTENDED EQUIPMENT OPERATION
 Only use software approved by Schneider Electric for use with this equipment.
 Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.

10 EIO0000001468 04/2014
Modicon M251 Logic Controller
M251 System Variables
EIO0000001468 04/2014

Chapter 1
M251 System Variables

M251 System Variables

Overview
This chapter:
 gives an introduction to the system variables (see page 12)
 describes the system variables (see page 18) included with the M251 PLCSystem library

What Is in This Chapter?


This chapter contains the following sections:
Section Topic Page
1.1 System Variables: Definition and Use 12
1.2 PLC_R and PLC_W Structures 17
1.3 SERIAL_R and SERIAL_W Structures 23
1.4 ETH_R and ETH_W Structures 26
1.5 TM3_MODULE_R Structure 33
1.6 PROFIBUS_R Structure 34

EIO0000001468 04/2014 11
M251 System Variables

Section 1.1
System Variables: Definition and Use

System Variables: Definition and Use

Overview
This section defines system variables and how to implement them in the Modicon M251 Logic
Controller.

What Is in This Section?


This section contains the following topics:
Topic Page
Understanding System Variables 13
Using System Variables 15

12 EIO0000001468 04/2014
M251 System Variables

Understanding System Variables

Introduction
This section describes how system variables are implemented. System variables:
 allow you to access general system information, perform system diagnostics, and command
simple actions.
 are structured variables conforming to IEC 61131-3 definitions and naming conventions. You
can access the system variables using the IEC symbolic name PLC_GVL. Some of the PLC_GVL
variables are read-only (for example, PLC_R) and some are read/write (for example, PLC_W).
 are automatically declared as global variables. They have system-wide scope and they can be
accessed by any Program Organization Unit (POU) in any task.

Naming Convention
The system variables are identified by:
 a structure name that represents the category of system variable. For example, PLC_R
represents a structure name of read-only variables used for the controller diagnosis.
 a set of component names that identifies the purpose of the variable. For example,
i_wVendorID represents the controller vendor ID.
You can access the system variables by typing the structure name of the variables followed by the
name of the component.
Here is an example of system variable implementation:
VAR
myCtr_Serial : DWORD;
myCtr_ID : DWORD;
myCtr_FramesRx : UDINT;
END_VAR
myCtr_Serial := PLC_R.i_dwSerialNumber;
myCtr_ID := PLC_R.i_wVendorID;
myCtr_FramesRx := SERIAL_R[0].i_udiFramesReceivedOK;
NOTE: The fully qualified name of the system variable in the example above is
PLC_GVL.PLC_R.i_wVendorID. The PLC_GVL is implicit when declaring a variable using the
Input Assistant, but it may also be entered in full. Good programming practice often dictates the
use of the fully qualified variable name in declarations.

EIO0000001468 04/2014 13
M251 System Variables

System Variables Location


2 kinds of system variables are defined for use when programming the controller:
 located variables
 unlocated variables

The located variables:


 have a fixed location in a static %MW area: %MW60000 to %MW60199 for read-only system
variables.
 are accessible through Modbus TCP, Modbus serial, and EtherNet/IP requests both in
RUNNING and STOPPED states.
 are used in SoMachine programs according to the structure_name.component_name
convention explained previously. %MW addresses from 0 to 59999 can be accessed directly.
Addresses greater than this are considered out of range by SoMachine and can only be
accessed through the structure_name.component_name convention.
The unlocated variables:
 are not physically located in the %MW area.
 are not accessible through any fieldbus or network requests unless you locate them in the
relocation table, and only then these variables can be accessed in RUNNING and STOPPED
states. The relocation table uses the following dynamic %MW areas:
 %MW60200 to %MW61999 for read-only variables
 %MW62200 to %MW63999 for read/write variables

 are used in SoMachine programs according to the structure_name.component_name


convention explained previously. %MW addresses from 0 to 59999 can be accessed directly.
Addresses greater than this are considered out of range by SoMachine and can only be
accessed through the structure_name.component_name convention.

14 EIO0000001468 04/2014
M251 System Variables

Using System Variables

Introduction
This section describes the steps required to program and to use system variables in SoMachine.
System variables are global in scope, and you can use them in all the Program Organization Units
(POUs) of the application.
System variables do not need to be declared in the Global Variable List (GVL). They are
automatically declared from the controller system library.

Using System Variables in a POU


SoMachine has an auto-completion feature. In a POU, start by entering the system variable
structure name (PLC_R, PLC_W...) followed by a dot. The system variables appear in the Input
Assistant. You can select the desired variable or enter the full name manually.

NOTE: In the example above, after you type the structure name PLC_R., SoMachine offers a pop-
up menu of possible component names/variables.

EIO0000001468 04/2014 15
M251 System Variables

Example
The following example shows the use of some system variables:
VAR
myCtr_Serial : DWORD;
myCtr_ID : WORD;
myCtr_FramesRx : UDINT;
END_VAR
myCtr_Serial := PLC_R.i_dwSerialNumber;
myCtr_ID := PLC_R.i_wVendorID;
myCtr_FramesRx := SERIAL_R[0].i_udiFramesReceivedOK;

16 EIO0000001468 04/2014
M251 System Variables

Section 1.2
PLC_R and PLC_W Structures

PLC_R and PLC_W Structures

Overview
This section lists and describes the different system variables included in the PLC_R and PLC_W
structures.

What Is in This Section?


This section contains the following topics:
Topic Page
PLC_R: Controller Read-Only System Variables 18
PLC_W: Controller Read/Write System Variables 22

EIO0000001468 04/2014 17
M251 System Variables

PLC_R: Controller Read-Only System Variables

Variable Structure
This table describes the parameters of the PLC_R system variable (PLC_R_STRUCT type):

Modbus Var Name Type Comment


Address (1)
60000 i_wVendorID WORD Controller Vendor ID.
101A hex = Schneider Electric
60001 i_wProductID WORD Controller Reference ID.
NOTE: Vendor ID and Reference ID
are the components of the Target ID of
the controller displayed in the
communication settings view (Target ID
= 101A XXXX hex).
60002 i_dwSerialNumber DWORD Controller Serial Number
60004 i_byFirmVersion ARRAY[0..3] OF BYTE Controller Firmware Version
[aa.bb.cc.dd]:
 i_byFirmVersion[0] = aa
 ...
 i_byFirmVersion[3] = dd

60006 i_byBootVersion ARRAY[0..3] OF BYTE Controller Boot Version


[aa.bb.cc.dd]:
 i_byBootVersion[0] = aa
 ...
 i_byBootVersion[3] = dd

60008 i_dwHardVersion DWORD Controller Hardware Version.


60010 i_dwChipVersion DWORD Controller Coprocessor Version.
60012 i_wStatus PLC_R_STATUS State of the controller.
(see page 61)
60013 i_wBootProjectStatus PLC_R_BOOT_PROJECT_ Returns information about the boot
STATUS (see page 58) application stored in FLASH memory.
60014 i_wLastStopCause PLC_R_STOP_CAUSE Cause of the last transition from RUN to
(see page 62) another state.
60015 i_wLastApplicationError PLC_R_APPLICATION_ Cause of the last controller exception.
ERROR (see page 57)

18 EIO0000001468 04/2014
M251 System Variables

Modbus Var Name Type Comment


(1)
Address
60016 i_lwSystemFault_1 LWORD Bit field FFFF FFFF FFFF FFFF hex
indicates no detected error.
A bit at low level means that an error
has been detected:
 bit 0 = Reserved
 bit 1 = TM3 detected error
 bit 2 = Ethernet IF1 detected error
 bit 3 = Ethernet IF2 detected error
 bit 4 = Serial 1 in overcurrent
detected error
 bit 5 = Reserved
 bit 6 = CAN 1 detected error
 bit 7 = Reserved
 bit 8 = Reserved
 bit 9 = TM4 detected error
 bit 10 = SD Card detected error
 bit 11 = Firewall detected error

60020 i_lwSystemFault_2 LWORD All bits reserved.


60024 i_wIOStatus1 PLC_R_IO_STATUS Reserved
(see page 59)
60025 i_wIOStatus2 PLC_R_IO_STATUS TM3 I/O status.
(see page 59)
60026 i_wClockBatterystatus WORD Status of the battery of the RTC:
 0 = Battery change needed
 100 = Battery fully charged

Other values (1...99) represents the


percentage of charge. For example, if
the value is 75, it represents that the
battery charge is 75%.
60028 i_dwAppliSignature1 DWORD First DWORD of 4 DWORD signature
(16 bytes total).
The application signature is generated
by the software during build.
60030 i_dwAppliSignature2 DWORD Second DWORD of 4 DWORD
signature (16 bytes total).
The application signature is generated
by the software during build.
60032 i_dwAppliSignature3 DWORD Third DWORD of 4 DWORD signature
(16 bytes total).
The application signature is generated
by the software during build.

EIO0000001468 04/2014 19
M251 System Variables

Modbus Var Name Type Comment


(1)
Address
60034 i_dwAppliSignature4 DWORD Fourth DWORD of 4 DWORD signature
(16 bytes total).
The application signature is generated
by the software during build.
(1)
Not accessible through the application.

n/a i_sVendorName STRING(31) Name of the vendor: “Schneider Electric”.


n/a i_sProductRef STRING(31) Reference of the controller.
n/a i_sNodeName STRING(99) Node name on SoMachine Network.
n/a i_dwLastStopTime DWORD The time of the last detected STOP in seconds
beginning with January 1, 1970 at 00:00.
n/a i_dwLastPowerOffDate DWORD The date and time of the last detected power off
in seconds beginning with January 1, 1970 at
00:00.
NOTE: Convert this value into date and time by
using the function
SysTimeRtcConvertUtcToDate. For more
information about Time and Date conversion,
refer to the Systime Library Guide
(see SoMachine, Getting & Setting Real Time
Clock, SysTime Library Guide).
n/a i_uiEventsCounter UINT Reserved
n/a i_wTerminalPortStatus PLC_R_TERMINAL_ Status of the USB Programming Port (USB Mini-
PORT_STATUS B).
(see page 63)
n/a i_wSdCardStatus PLC_R_SDCARD_ Status of the SD card.
STATUS
(see page 60)
n/a i_wUsrFreeFileHdl WORD Number of available File Handles.
A File Handle is the resource allocated by the
system when you open a file.
n/a i_udiUsrFsTotalBytes UDINT User FileSystem total memory size (in bytes).
It is the size of the flash memory for the directory
"/usr/".
n/a i_udiUsrFsFreeBytes UDINT User FileSystem free memory size (in bytes).

20 EIO0000001468 04/2014
M251 System Variables

n/a i_uiTM3BusState PLC_R_TM3_BUS_ TM3 bus state.


STATE i_uiTM3BusState can have the following
(see page 64) values:
 1: TM3_CONF_ERROR
Configuration mismatch between physical
configuration and SoMachine configuration.
 3: TM3_OK
Physical configuration matches SoMachine
configuration.
 4: TM3_POWER_SUPPLY_ERROR
TM3 bus is not powered (for example when
the Logic Controller is powered by USB).
n/a i_ExpertIO_RunStop_Input BYTE Reserved
n/a i_x10msClk BOOL TimeBase bit of 10 ms.
This variable is toggling On/Off with period =
10 ms. The value toggles when the logic
controller is in Stop and in Run state.
n/a i_x100msClk BOOL TimeBase bit of 100 ms.
This variable is toggling On/Off with period =
100 ms. The value toggles when the logic
controller is in Stop and in Run state.
n/a i_x1sClk BOOL TimeBase bit of 1 s.
This variable is toggling On/Off with period = 1 s.
The value toggles when the logic controller is in
Stop and in Run state.

NOTE: n/a means that there is no pre-defined Modbus address mapping for this system variable.

EIO0000001468 04/2014 21
M251 System Variables

PLC_W: Controller Read/Write System Variables

Variable Structure
This table describes the parameters of the PLC_W system variable (PLC_W_STRUCT type):

%MW Var Name Type Comment


n/a q_wResetCounterEvent WORD Transition from 0 to 1 resets the events
counter (PLC_R.i_uiEventsCounter).
To reset the counter again, it is necessary to
write this register to 0 before another
transition from 0 to 1 can take place.
n/a q_uiOpenPLCControl UINT When Value passes from 0 to 6699, the
command previously written in the following
PLC_W.q_wPLCControl is executed.
n/a q_wPLCControl PLC_W_COMMAND Controller RUN / STOP command executed
(see page 65) when the system variable
PLC_R.q_uiOpenPLCControl value
passes from 0 to 6699.

NOTE: n/a means that there is no pre-defined %MW mapping for this system variable.

22 EIO0000001468 04/2014
M251 System Variables

Section 1.3
SERIAL_R and SERIAL_W Structures

SERIAL_R and SERIAL_W Structures

Overview
This section lists and describes the different system variables included in the SERIAL_R and
SERIAL_W structures.

What Is in This Section?


This section contains the following topics:
Topic Page
SERIAL_R[0...1]: Serial Line Read-Only System Variables 24
SERIAL_W[0...1]: Serial Line Read/Write System Variables 25

EIO0000001468 04/2014 23
M251 System Variables

SERIAL_R[0...1]: Serial Line Read-Only System Variables

Introduction
SERIAL_R is an array of 2 SERIAL_R_STRUCT type. Each element of the array returns diagnostic
system variables for the corresponding serial line.
For the M251 Logic Controller:
 Serial_R[0] refers to serial line
 Serial_R[1] is reserved

Variable Structure
This table describes the parameters of the SERIAL_R[0...1] system variables:

%MW Var Name Type Comment


Serial Line
n/a i_udiFramesTransmittedOK UDINT Number of frames successfully transmitted.
n/a i_udiFramesReceivedOK UDINT Number of frames received without any
detected errors.
n/a i_udiRX_MessagesError UDINT Number of frames received with detected
errors (checksum, parity).
Modbus Specific
n/a i_uiSlaveExceptionCount UINT Number of Modbus exception responses
returned by the logic controller.
n/a i_udiSlaveMsgCount UINT Number of messages received from the Master
and addressed to the logic controller.
n/a i_uiSlaveNoRespCount UINT Number of Modbus broadcast requests
received by the logic controller.
n/a i_uiSlaveNakCount UINT Not used
n/a i_uiSlaveBusyCount UINT Not used
n/a i_uiCharOverrunCount UINT Number of character overruns.

NOTE: n/a means that there is no predefined %MW mapping for this system variable.
NOTE:
The SERIAL_R counters are reset on:
 Download.
 Controller reset.
 SERIAL_W[x].q_wResetCounter command.
 Reset command by Modbus request function code number 8.

24 EIO0000001468 04/2014
M251 System Variables

SERIAL_W[0...1]: Serial Line Read/Write System Variables

Introduction
SERIAL_W is an array of 2 SERIAL_W_STRUCT type. Each element of the array forces the
SERIAL_R system variables for the corresponding serial line to be reset.
For the M251 Logic Controller:
 Serial_W[0] refers to serial line
 Serial_W[1] is reserved

Variable Structure
This table describes the parameters of the SERIAL_W[0...1] system variable:

%MW Var Name Type Comment


n/a q_wResetCounter WORD Transition from 0 to 1 resets all
SERIAL_R[0...1] counters.
To reset the counters again, it is necessary to
write this register to 0 before another transition
from 0 to 1 can take place.

NOTE: n/a means that there is no predefined %MW mapping for this system variable.

EIO0000001468 04/2014 25
M251 System Variables

Section 1.4
ETH_R and ETH_W Structures

ETH_R and ETH_W Structures

Overview
This section lists and describes the different system variables included in the ETH_R and ETH_W
structures.

What Is in This Section?


This section contains the following topics:
Topic Page
ETH_R: Ethernet Port Read-Only System Variables 27
ETH_W: Ethernet Port Read/Write System Variables 32

26 EIO0000001468 04/2014
M251 System Variables

ETH_R: Ethernet Port Read-Only System Variables

Variable Structure
This table describes the parameters of the ETH_R system variable (ETH_R_STRUCT type):

%MW Var Name Type Comment


60050 i_byIPAddress ARRAY[0..3] OF IP address of the Ethernet or
BYTE Ethernet_1 interface
[aaa.bbb.ccc.ddd]:
 i_byIPAddress[0] = aaa
 ...
 i_byIPAddress[3] = ddd

60052 i_bySubNetMask ARRAY[0..3] OF Subnet Mask of the Ethernet or


BYTE Ethernet_1 interface
[aaa.bbb.ccc.ddd]:
 i_bySub-netMask[0] = aaa
 ...
 i_bySub-netMask[3] = ddd

60054 i_byGateway ARRAY[0..3] OF Gateway address of the Ethernet or


BYTE Ethernet_1 interface
[aaa.bbb.ccc.ddd]:
 i_byGateway[0] = aaa
 ...
 i_byGateway[3] = ddd

60056 i_byMACAddress ARRAY[0..5] OF MAC address of the Ethernet or


BYTE Ethernet_1 interface
[aa.bb.cc.dd.ee.ff]:
 i_byMACAddress[0] = aa
 ...
 i_byMACAddress[5] = ff

60059 i_sDeviceName STRING(15) Name used to get IP address from


server.
n/a i_wIpMode ETH_R_IP_MODE Method used to obtain an IP address.
(see page 72)
n/a i_byFDRServerIPAddress ARRAY[0..3] OF The IP address
BYTE [aaa.bbb.ccc.ddd] of the DHCP or
BootP server:
 i_byFDRServerIPAddress[0] = aaa
 ...
 i_byFDRServerIPAddress[3] = ddd

Equals 0.0.0.0 if Stored IP or Default IP


used.
n/a i_udiOpenTcpConnections UDINT Number of open TCP connections.

EIO0000001468 04/2014 27
M251 System Variables

%MW Var Name Type Comment


n/a i_udiFramesTransmittedOK UDINT Number of frames successfully
transmitted. Reset at Power ON or with
reset command
ETH_W.q_wResetCounter.
n/a i_udiFramedReceivedOK UDINT Number of frames successfully
received. Reset at Power ON or with
reset command
ETH_W.q_wResetCounter.
n/a i_udiTransmitBufferErrors UDINT Numbers of frames transmitted with
detected errors. Reset at Power ON or
with reset command
ETH_W.q_wResetCounter.
n/a i_udiReceiveBufferErrors UDINT Numbers of frames received with
detected errors. Reset at Power ON or
with reset command
ETH_W.q_wResetCounter.
n/a i_wFrameSendingProtocol ETH_R_FRAME_ Ethernet protocol configured for
PROTOCOL frames sending (IEEE 802.3 or
(see page 71) Ethernet II).
n/a i_wPortALinkStatus ETH_R_PORT_ Link of the Ethernet Port (0 = No Link,
LINK_STATUS 1 = Link connected to another Ethernet
(see page 75) device).
n/a i_wPortASpeed ETH_R_PORT_ Ethernet Port network speed (10Mb/s
SPEED or 100Mb/s).
(see page 76)
n/a i_wPortADuplexStatus ETH_R_PORT_ Ethernet Port duplex status (0 = Half or
DUPLEX_STATUS 1 = Full duplex).
(see page 73)
n/a i_udiPortACollisions UDINT Number of frames involved in one or
more collisions and subsequently
transmitted successfully. Reset at
Power ON or with reset command
ETH_W.q_wResetCounter.
Modbus TCP/IP Specific
n/a i_udiModbusMessageTransmitted UDINT Number of Modbus messages
transmitted.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.

28 EIO0000001468 04/2014
M251 System Variables

%MW Var Name Type Comment


n/a i_udiModbusMessageReceived UDINT Number of Modbus messages
received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_udiModbusErrorMessage UDINT Modbus detected error messages
transmitted and received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.

EtherNet/IP Specific
n/a i_udiETHIP_IOMessagingTransmitted UDINT EtherNet/IP Class 1 frames
transmitted.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_udiETHIP_IOMessagingReceived UDINT EtherNet/IP Class 1 frames
received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_udiUCMM_Request UDINT EtherNet/IP Unconnected Messages
received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_udiUCMM_Error UDINT EtherNet/IP invalid Unconnected
Messages received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_udiClass3_Request UDINT EtherNet/IP Class 3 requests
received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_udiClass3_Error UDINT EtherNet/IP invalid class 3 requests
received.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.

EIO0000001468 04/2014 29
M251 System Variables

n/a i_uiAssemblyInstanceInput UINT Input Assembly Instance number.


See the appropriate Programming
Guide of your controller for more
information.
n/a i_uiAssemblyInstanceInputSize UINT Input Assembly Instance size. See
the appropriate Programming Guide
of your controller for more
information.
n/a i_uiAssemblyInstanceOutput UINT Output Assembly Instance number.
See the appropriate Programming
Guide of your controller for more
information.
n/a i_uiAssemblyInstanceOutputSize UINT Output Assembly Instance size. See
the appropriate Programming Guide
of your controller for more
information.
n/a i_uiETHIP_ConnectionTimeouts UINT Number of connection timeouts.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_ucEipRunIdle ETH_R_RUN_IDLE Run (value = 1)/Idle(value = 0) flag
(see page 77) for EtherNet/IP class 1 connection.
n/a i_byMasterIpTimeouts BYTE Ethernet Modbus TCP Master
timeout events counter.
Reset at Power ON or with reset
command
ETH_W.q_wResetCounter.
n/a i_byMasterIpLost BYTE Ethernet Modbus TCP Master link
status: 0 = link OK, 1 = link lost.
n/a i_wPortAIpStatus ETH_R_PORT_IP_ Ethernet TCP/IP port stack status.
STATUS
(see page 74)
n/a i_byIPAddress_If2 ARRAY[0..3] OF IP address of the Ethernet or
BYTE Ethernet_2 interface
[aaa.bbb.ccc.ddd]:
 i_byIPAddress[0] = aaa
 ...
 i_byIPAddress[3] = ddd

n/a i_bySubNetMask_If2 ARRAY[0..3] OF Subnet Mask of the Ethernet or


BYTE Ethernet_2 interface
[aaa.bbb.ccc.ddd]:
 i_bySub-netMask[0] = aaa
 ...
 i_bySub-netMask[3] = ddd

30 EIO0000001468 04/2014
M251 System Variables

n/a i_byGateway_If2 ARRAY[0..3] OF Gateway address of the Ethernet or


BYTE Ethernet_2 interface
[aaa.bbb.ccc.ddd]:
 i_byGateway[0] = aaa
 ...
 i_byGateway[3] = ddd

n/a i_byMACAddress_If2 ARRAY[0..5] OF MAC address of the Ethernet or


BYTE Ethernet_2 interface
[aa.bb.cc.dd.ee.ff]:
 i_byMACAddress[0] = aa
 ...
 i_byMACAddress[5] = ff

n/a i_sDeviceName_If2 STRING(15) Name used to get IP address from


server.
n/a i_wIpMode_If2 ETH_R_IP_MODE Method used to obtain an IP
(see page 72) address.
n/a i_wPortALinkStatus_If2 ETH_R_PORT_ Link of the Ethernet Port (0 = No
LINK_STATUS Link, 1 = Link connected to another
(see page 75) Ethernet device).
n/a i_wPortASpeed_If2 ETH_R_PORT_ Ethernet Port network speed
SPEED (10Mb/s or 100Mb/s).
(see page 76)
n/a i_wPortADuplexStatus_If2 ETH_R_PORT_ Ethernet Port duplex status (0 = Half
DUPLEX_STATUS or 1 = Full duplex).
(see page 73)
n/a i_wPortAIpStatus_If2 ETH_R_PORT_IP_ Ethernet TCP/IP port stack status.
STATUS
(see page 74)

NOTE: n/a means that there is no predefined %MW mapping for this system variable.

EIO0000001468 04/2014 31
M251 System Variables

ETH_W: Ethernet Port Read/Write System Variables

Variable Structure
This table describes the parameters of the ETH_W system variable (ETH_W_STRUCT type):

%MW Var Name Type Comment


n/a q_wResetCounter WORD Transition from 0 to 1 resets all ETH_R counters.
To reset again, it is necessary to write this register to 0
before another transition from 0 to 1 can take place.

NOTE: n/a means that there is no predefined %MW mapping for this system variable.

32 EIO0000001468 04/2014
M251 System Variables

Section 1.5
TM3_MODULE_R Structure

TM3_MODULE_R Structure

TM3_MODULE_R[0...13]: TM3 Modules Read-Only System Variables

Introduction
The TM3_MODULE_R is an array of 14 TM3_MODULE_R_STRUCT type. Each element of the array
returns diagnostic system variables for the corresponding TM3 expansion module.
For the Modicon M251 Logic Controller:
 TM3_MODULE_R[0] refers to the TM3 expansion module 0
 ...
 TM3_MODULE_R[13] refers to the TM3 expansion module 13

Variable Structure
The following table describes the parameters of the TM3_MODULE_R[0...13] system variable:

%MW Var Name Type Comment


n/a i_wProductID WORD TM3 expansion module ID.
n/a i_wModuleState TM3_MODULE_STATE Describes the state of the TM3 module.
(see page 81)

NOTE: n/a means that there is no predefined %MW mapping for this system variable.

EIO0000001468 04/2014 33
M251 System Variables

Section 1.6
PROFIBUS_R Structure

PROFIBUS_R Structure

PROFIBUS_R: PROFIBUS Read-Only System Variables

Variable Structure
This table describes the parameters of the PROFIBUS_R system variable (PROFIBUS_R_STRUCT
type):

%MW Var Name Type Comment


n/a i_wPNOIdentifier WORD Slave identification code.
n/a i_wBusAdr UINT PROFIBUS slave address.
n/a i_CommState UDINT Value representing the state of the PROFIBUS module:
 0x00: Unknown
 0x01: Not configured
 0x02: Stop
 0x03: Idle
 0x04: Operate
n/a i_CommError UDINT Communication error code.
n/a i_ErrorCount UDINT Communication error counter.

NOTE: n/a means that there is no predefined %MW mapping for this system variable.

34 EIO0000001468 04/2014
Modicon M251 Logic Controller
M251, System Functions
EIO0000001468 04/2014

Chapter 2
M251 System Functions

M251 System Functions

Overview
This chapter describes the system functions included in the M251 PLCSystem library.

What Is in This Chapter?


This chapter contains the following sections:
Section Topic Page
2.1 M251 Read Functions 36
2.2 M251 Write Functions 42
2.3 M251 User Functions 44
2.4 TM3 Read Functions 50

EIO0000001468 04/2014 35
M251, System Functions

Section 2.1
M251 Read Functions

M251 Read Functions

Overview
This section describes the read functions included in the M251 PLCSystem library.

What Is in This Section?


This section contains the following topics:
Topic Page
GetRtc: Get Current RTC Time 37
IsFirstMastColdCycle: Indicates if Cycle is the First MAST Cold Start Cycle 38
IsFirstMastCycle: Indicates if Cycle is the First MAST Cycle 39
IsFirstMastWarmCycle: Indicates if Cycle is the First MAST Warm Start Cycle 41

36 EIO0000001468 04/2014
M251, System Functions

GetRtc: Get Current RTC Time

Function Description
This function returns current RTC time in seconds in UNIX format.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 85).

I/O Variable Description


The following table describes the I/O variable:

Output Type Comment


GetRtc DINT Current RTC time in seconds in UNIX format.

Example
The following example describes how to get the current RTC time:
VAR
MyRTC : DINT := 0;
END_VAR
MyRTC := GetRtc();

EIO0000001468 04/2014 37
M251, System Functions

IsFirstMastColdCycle: Indicates if Cycle is the First MAST Cold Start Cycle

Function Description
This function returns TRUE during the first MAST cycle after a cold start (first cycle after download
or reset cold).

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 85).

I/O Variable Description


The table describes the output variable:

Output Type Comment


IsFirstMastColdCycle BOOL TRUE during the first MAST task cycle after
a cold start.

Example
Refer to the function IsFirstMastCycle (see page 39).

38 EIO0000001468 04/2014
M251, System Functions

IsFirstMastCycle: Indicates if Cycle is the First MAST Cycle

Function Description
This function returns TRUE during the first MAST cycle after a start.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 85).

I/O Variable Description

Output Type Comment


IsFirstMastCycle BOOL TRUE during the first MAST task cycle after a start.

Example
This example describes the three functions IsFirstMastCycle, IsFirstMastColdCycle and
IsFirstMastWarmCycle used together.
Use this example in MAST task. Otherwise, it may run several times or possibly never (an
additional task might be called several times or not called during 1 MAST task cycle):
VAR
MyIsFirstMastCycle : BOOL;
MyIsFirstMastWarmCycle : BOOL;
MyIsFirstMastColdCycle : BOOL;
END_VAR
MyIsFirstMastWarmCycle := IsFirstMastWarmCycle();
MyIsFirstMastColdCycle := IsFirstMastColdCycle();
MyIsFirstMastCycle := IsFirstMastCycle();
IF (MyIsFirstMastWarmCycle) THEN
(*This is the first Mast Cycle after a Warm Start: all variables are set
to their initialization values except the Retain variables*)
(*=> initialize the needed variables so that your application runs as
expected in this case*)
END_IF;

EIO0000001468 04/2014 39
M251, System Functions

IF (MyIsFirstMastColdCycle) THEN
(*This is the first Mast Cycle after a Cold Start: all variables are set
to their initialization values including the Retain Variables*)
(*=> initialize the needed variables so that your application runs as
expected in this case*)
END_IF;
IF (MyIsFirstMastCycle) THEN
(*This is the first Mast Cycle after a Start, i.e. after a Warm or Cold
Start as well as STOP/RUN commands*)
(*=> initialize the needed variables so that your application runs as
expected in this case*)
END_IF;

40 EIO0000001468 04/2014
M251, System Functions

IsFirstMastWarmCycle: Indicates if Cycle is the First MAST Warm Start Cycle

Function Description
This function returns TRUE during the first MAST cycle after a warm start.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 85).

I/O Variable Description


This table describes the output variable:

Output Type Comment


IsFirstMastWarmCycle BOOL TRUE during the first MAST task cycle after a warm start.

Example
Refer to the function IsFirstMastCycle (see page 39).

EIO0000001468 04/2014 41
M251, System Functions

Section 2.2
M251 Write Functions

M251 Write Functions

SetRTCDrift: Set Compensation Value to the RTC

Function Description
This function accelerates or slows down the frequency of the RTC to give control to the application
for RTC compensation, depending on the operating environment (temperature, …). The
compensation value is given in seconds per week. It can be positive (accelerate) or negative (slow
down).
NOTE: The SetRTCDrift function must be called only once. Each new call replaces the
compensation value by the new one. The value is kept in the logic controller hardware while the
RTC is powered by the main supply or by the battery. If both battery and power supply are
removed, the RTC compensation value is not available.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 85).

42 EIO0000001468 04/2014
M251, System Functions

I/O Variables Description


This table describes the input parameters:

Inputs Type Comment


RtcDrift SINT(-29..29) Correction in seconds per week (-29 ... +29).

NOTE: The parameters Day, Hour, and Minute are used only to ensure backwards compatibility.
NOTE: If the value entered for RtcDrift exceeds the limit value, the logic controller firmware sets
the value to its maximum value.
This table describes the output variable:

Output Type Comment


SetRTCDrift RTCSETDRIFT_ERROR Returns RTC_OK (00 hex) if command is correct
(see page 82) otherwise returns the ID code of the detected error.

Example
In this example, the function is called only once during the first MAST task cycle. It accelerates the
RTC by 4 seconds a week (18 seconds a month).
VAR
MyRTCDrift : SINT (-29..29) := 0;
MyDay : DAY_OF_WEEK;
MyHour : HOUR;
MyMinute : MINUTE;
END_VAR
IF IsFirstMastCycle() THEN
MyRTCDrift := 4;
MyDay := 0;
MyHour := 0;
MyMinute := 0;
SetRTCDrift(MyRTCDrift, MyDay, MyHour, MyMinute);
END_IF

EIO0000001468 04/2014 43
M251, System Functions

Section 2.3
M251 User Functions

M251 User Functions

Overview
This section describes the DataFileCopy and ExecuteScript functions included in the M251
PLCSystem library.

What Is in This Section?


This section contains the following topics:
Topic Page
DataFileCopy: Copy File Commands 45
ExecuteScript: Script Commands 48

44 EIO0000001468 04/2014
M251, System Functions

DataFileCopy: Copy File Commands

Function Description
This function copies memory data to a file and vice versa. The file is located either within the
internal file system or an external file system (SD card).
The DataFileCopy function block can:
 Read data from a formatted file or
 Copy data from memory buffer to a formatted file. For further information, refer to Flash Memory
Organization (see Modicon M251 Logic Controller, Programming Guide).

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 85).

I/O Variable Description


This table describes the input variables:

Input Type Comment


xExecute BOOL On rising edge, starts the function block execution.
On falling edge, resets the outputs of the function block when its execution terminates.
sFileName STRING File name without extension (the extension .DTA is automatically added). Use only a...z,
A...Z, 0...9 alphanumeric characters.
xRead BOOL TRUE: copy from file to memory.
FALSE: copy from memory to file.
xSecure BOOL TRUE: The MAC address is always stored in the file. Only a controller with the same
MAC address can read from the file.
FALSE: Another controller with the same type of memory can read from the file.
iLocation INT 0: the file location is /usr/DTA in internal file system.
1: the file location is /usr/DTA in external file system (SD card).

EIO0000001468 04/2014 45
M251, System Functions

Input Type Comment


uiSize UINT Indicates the size in bytes. Maximum is 65534 bytes.
Only use addresses of variables conforming to IEC 6113-1 (variables, arrays,
structures), for example:
Variable : int;
uiSize := SIZEOF (Variable);
dwAdd DWORD Indicates the address in the memory.
Only use addresses of variables conforming to IEC 6113-1 (variables, arrays,
structures), for example:
Variable : int;
dwAdd := ADR (Variable);

WARNING
UNINTENDED EQUIPMENT OPERATION
Verify that the memory location is of the correct size and the file is of the correct type before
copying the file to memory.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.

This table describes the output variables:

Output Type Comment


xDone BOOL TRUE = indicates that the action is successfully completed.
xBusy BOOL TRUE = indicates that the function block is running.
xError BOOL TRUE = indicates that an error is detected and the function block
aborted the action.
eError DataFileCopyError Indicates the type of the data file copy detected error.
(see page 67)

NOTE: If you write to memory variable within the area of the file write, you generate a CRC
detected error.

46 EIO0000001468 04/2014
M251, System Functions

Example
This example describes how to copy file commands:
VAR
LocalArray : ARRAY [0..29] OF BYTE;
myFileName: STRING := ‘exportfile’;
EXEC_FLAG: BOOL;
DataFileCopy: DataFileCopy;
END_VAR
DataFileCopy(
xExecute:= EXEC_FLAG,
sFileName:= myFileName,
xRead:= FALSE,
xSecure:= FALSE,
iLocation:= DFCL_INTERNAL,
dwSize:= SIZEOF(LocalArray),
dwAdd:= ADR(LocalArray),
xDone=> ,
xBusy=> ,
xError=> ,
eError=> );

EIO0000001468 04/2014 47
M251, System Functions

ExecuteScript: Script Commands

Function Description
This function can run the following SD card script commands:
 Download
 Upload
 SetNodeName
 Delete
 Reboot

Use the same syntax as the USB script to run these commands (case sensitive). Refer to Script
and Files Generation with SD Card Mass Storage (see Modicon M251 Logic Controller,
Programming Guide).

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 85).

I/O Variable Description


This table describes the input variables:

Input Type Comment


xExecute BOOL On rising edge, starts the function block execution.
On falling edge, resets the outputs of the function block when its
execution terminates.
sCmd STRING SD card script command syntax.
Simultaneous command executions are not allowed: if a command is
being executed from another function block or from an SD card script
then the function block queues the command and does not execute it
immediately.
NOTE: An SD card script executed from an SD card is considered as
being executed until the SD card has been removed.

48 EIO0000001468 04/2014
M251, System Functions

This table describes the output variables:

Output Type Comment


xDone BOOL TRUE = indicates that the action is successfully completed.
xBusy BOOL TRUE = the function block is running.
xError BOOL TRUE = indicates error detection and the function block aborts
the action.
eError ExecuteScriptError Indicates the type of the execute script detected error.
(see page 69)

Example
This example describes how to execute a script command:
VAR
EXEC_FLAG: BOOL;
ExecuteScript: ExecuteScript;
END_VAR
ExecuteScript(
xExecute:= EXEC_FLAG,
sCmd:= ‘Upload “/usr/Syslog/*”’,
xDone=> ,
xBusy=> ,
xError=> ,
eError=> );

EIO0000001468 04/2014 49
M251, System Functions

Section 2.4
TM3 Read Functions

TM3 Read Functions

Overview
This section describes the TM3 read functions included in the M251 PLCSystem library.

What Is in This Section?


This section contains the following topics:
Topic Page
TM3_GetModuleBusStatus: Get TM3 Module Bus Status 51
TM3_GetModuleInternalStatus: Get TM3 Module Internal Status 52

50 EIO0000001468 04/2014
M251, System Functions

TM3_GetModuleBusStatus: Get TM3 Module Bus Status

Function Description
This function returns the bus status of the module. The index of the module is given as an input
parameter.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 85).

I/O Variable Description


The following table describes the input variable:

Input Type Comment


ModuleIndex BYTE Index of the module (0 for the first expansion, 1 for the
second, and so on).

The following table describes the output variable:

Output Type Comment


TM3_GetModuleBusStatus TM3_ERR_CODE Returns TM3_OK (00 hex) if command is correct
(see page 79) otherwise returns the ID code of the detected error.

EIO0000001468 04/2014 51
M251, System Functions

TM3_GetModuleInternalStatus: Get TM3 Module Internal Status

Function Description
This function fills the pStatusBuffer with the status table of the module ModuleIndex.

Graphical Representation

IL and ST Representation
To see the general representation in IL or ST language, refer to the chapter Function and Function
Block Representation (see page 85).

I/O Variable Description

WARNING
UNINTENDED EQUIPMENT OPERATION
Be sure that the pStatusBuffer is allocated.
Failure to follow these instructions can result in death, serious injury, or equipment
damage.

The following table describes the input variables:

Input Type Comment


ModuleIndex BYTE Index of the module (0 for the first expansion, 1 for the second, and so on).
StatusOffset BYTE Offset of the first status to be read in the status table.
StatusSize BYTE Number of bytes to be read in the status table.
pStatusBuffer POINTER TO BYTE Buffer containing the read status table.

The following table describes the output variable:

Output Type Comment


TM3_GetModuleInternalStatus TM3_ERR_CODE Returns TM3_OK (00 hex) if command is correct
(see page 79) otherwise returns the ID code of the detected error.

52 EIO0000001468 04/2014
M251, System Functions

Example
The following example describes how to get the module internal status:
VAR
AMM3HT_Channel1_Input_Status: BYTE;
END_VAR
TM3_GetModuleInternalStatus(0, 1, 1, ADR(AMM3HT_Channel1_Input_Status));

EIO0000001468 04/2014 53
M251, System Functions

54 EIO0000001468 04/2014
Modicon M251 Logic Controller
M251 PLC System Library Data Types
EIO0000001468 04/2014

Chapter 3
M251 PLCSystem Library Data Types

M251 PLCSystem Library Data Types

Overview
This chapter describes the data types of the M251 PLCSystem Library.
There are 2 kinds of data types available:
 System variable data types are used by the system variables (see page 11) of the M251
PLCSystem Library (PLC_R, PLC_W,...).
 System function data types are used by the read/write system functions (see page 35) of the
M251 PLCSystem Library.

What Is in This Chapter?


This chapter contains the following sections:
Section Topic Page
3.1 PLC_R/W System Variables Data Types 56
3.2 DataFileCopy System Variables Data Types 66
3.3 ExecScript System Variables Data Types 69
3.4 ETH_R/W System Variables Data Types 70
3.5 TM3_MODULE_R System Variables Data Types 78
3.6 System Function Data Types 82

EIO0000001468 04/2014 55
M251 PLC System Library Data Types

Section 3.1
PLC_R/W System Variables Data Types

PLC_R/W System Variables Data Types

Overview
This section lists and describes the system variable data types included in the PLC_R and PLC_W
structures.

What Is in This Section?


This section contains the following topics:
Topic Page
PLC_R_APPLICATION_ERROR: Detected Application Error Status Codes 57
PLC_R_BOOT_PROJECT_STATUS: Boot Project Status Codes 58
PLC_R_IO_STATUS: I/O Status Codes 59
PLC_R_SDCARD_STATUS: SD Card Slot Status Codes 60
PLC_R_STATUS: Controller Status Codes 61
PLC_R_STOP_CAUSE: From RUN State to Other State Transition Cause Codes 62
PLC_R_TERMINAL_PORT_STATUS: Programming Port Connection Status Codes 63
PLC_R_TM3_BUS_STATE: TM3 Bus Status Codes 64
PLC_W_COMMAND: Control Command Codes 65

56 EIO0000001468 04/2014
M251 PLC System Library Data Types

PLC_R_APPLICATION_ERROR: Detected Application Error Status Codes

Enumerated Type Description


The PLC_R_APPLICATION_ERROR enumeration data type contains the following values:

Enumerator Value Comment


PLC_R_APP_ERR_UNKNOWN FFFF hex Undefined detected error.
PLC_R_APP_ERR_NOEXCEPTION 0000 hex No detected error.
PLC_R_APP_ERR_WATCHDOG 0010 hex Application watchdog of task
expired.
PLC_R_APP_ERR_HARDWAREWATCHDOG 0011 hex Hardware watchdog expired.
PLC_R_APP_ERR_IO_CONFIG_ERROR 0012 hex Incorrect I/O configuration
parameters detected.
PLC_R_APP_ERR_UNRESOLVED_EXTREFS 0018 hex Undefined functions detected.
PLC_R_APP_ERR_IEC_TASK_CONFIG_ERROR 0025 hex Incorrect Task configuration
parameters detected.
PLC_R_APP_ERR_ILLEGAL_INSTRUCTION 0050 hex Undefined instruction detected.
PLC_R_APP_ERR_ACCESS_VIOLATION 0051 hex Attempted access to reserved
memory area.
PLC_R_APP_ERR_DIVIDE_BY_ZERO 0102 hex Integer division by zero detected.
PLC_R_APP_ERR_PROCESSORLOAD_WATCHDOG 0105 hex Processor overloaded by
Application Tasks.
PLC_R_APP_ERR_DIVIDE_REAL_BY_ZERO 0152 hex Real division by zero detected.
PLC_R_APP_ERR_EXPIO_EVENTS_COUNT_EXCEEDED 4E20 hex Too many events on expert I/Os are
detected. Reduce the Event Tasks.
PLC_R_APP_ERR_APPLICATION_VERSION_MISMATCH 4E21 hex Mismatch in the application version
detected.

EIO0000001468 04/2014 57
M251 PLC System Library Data Types

PLC_R_BOOT_PROJECT_STATUS: Boot Project Status Codes

Enumerated Type Description


The PLC_R_BOOT_PROJECT_STATUS enumeration data type contains the following values:

Enumerator Value Comment


PLC_R_NO_BOOT_PROJECT 0000 hex Boot project does not exist in Flash
memory.
PLC_R_BOOT_PROJECT_CREATION_IN_PROGRESS 0001 hex Boot project is being created.
PLC_R_DIFFERENT_BOOT_PROJECT 0002 hex Boot project in Flash is different from the
project loaded in RAM.
PLC_R_VALID_BOOT_PROJECT FFFF hex Boot project in Flash is the same as the
project loaded in RAM.

58 EIO0000001468 04/2014
M251 PLC System Library Data Types

PLC_R_IO_STATUS: I/O Status Codes

Enumerated Type Description


The PLC_R_IO_STATUS enumeration data type contains the following values:

Enumerator Value Comment


PLC_R_IO_OK FFFF hex Inputs/Outputs are operational.
PLC_R_IO_NO_INIT 0001 hex Inputs/Outputs are not initialized.
PLC_R_IO_CONF_FAULT 0002 hex Incorrect I/O configuration parameters
detected.
PLC_R_IO_SHORTCUT_FAULT 0003 hex Inputs/Outputs short-circuit detected.
PLC_R_IO_POWER_SUPPLY_FAULT 0004 hex Inputs/Outputs power supply error
detected.

EIO0000001468 04/2014 59
M251 PLC System Library Data Types

PLC_R_SDCARD_STATUS: SD Card Slot Status Codes

Enumerated Type Description


The PLC_R_SDCARD_STATUS enumeration data type contains the following values:

Enumerator Value Comment


NO_SDCARD 0000 hex No SD card detected in the slot or the slot is not
connected.
SDCARD_READONLY 0001 hex SD card is in read-only mode.
SDCARD_READWRITE 0002 hex SD card is in read/write mode.
SDCARD_ERROR 0003 hex Error detected in the SD card.

60 EIO0000001468 04/2014
M251 PLC System Library Data Types

PLC_R_STATUS: Controller Status Codes

Enumerated Type Description


The PLC_R_STATUS enumeration data type contains the following values:

Enumerator Value Comment


PLC_R_EMPTY 0000 hex Controller does not contain an application.
PLC_R_STOPPED 0001 hex Controller is stopped.
PLC_R_RUNNING 0002 hex Controller is running.
PLC_R_HALT 0004 hex Controller is in a HALT state. (see the controller state
diagram in your controller programming guide).
PLC_R_BREAKPOINT 0008 hex Controller has paused at a breakpoint.

EIO0000001468 04/2014 61
M251 PLC System Library Data Types

PLC_R_STOP_CAUSE: From RUN State to Other State Transition Cause Codes

Enumerated Type Description


The PLC_R_STOP_CAUSE enumeration data type contains the following values:

Enumerator Value Comment


PLC_R_STOP_REASON_UNKNOWN 00 hex Initial value or stop cause is undefined.
PLC_R_STOP_REASON_HW_WATCHDOG 01 hex Stopped after hardware watchdog timeout.
PLC_R_STOP_REASON_RESET 02 hex Stopped after reset.
PLC_R_STOP_REASON_EXCEPTION 03 hex Stopped after exception.
PLC_R_STOP_REASON_USER 04 hex Stopped after a user request.
PLC_R_STOP_REASON_IECPROGRAM 05 hex Stopped after a program command request (for
example: control command with parameter
PLC_W.q_wPLCControl:=PLC_W_COMMAND.PLC_
W_STOP;).
PLC_R_STOP_REASON_DELETE 06 hex Stopped after a remove application command.
PLC_R_STOP_REASON_DEBUGGING 07 hex Stopped after entering debug mode.
PLC_R_STOP_FROM_NETWORK_REQUEST 0A hex Stopped after a request from the network, SD card, or
PLC_W command.
PLC_R_STOP_FROM_INPUT 0B hex Stop required by a controller input.
PLC_R_STOP_FROM_RUN_STOP_SWITCH 0C hex Stop required by the controller switch.
PLC_R_STOP_REASON_RETAIN_MISMATCH 0D hex Stopped after an unsuccessful check context test
during rebooting.
PLC_R_STOP_REASON_BOOT_APPLI_MISMATCH 0E hex Stopped after an unsuccessful compare between the
boot application and the application that was in the
memory before rebooting.
PLC_R_STOP_REASON_POWERFAIL 0F hex Stopped after a power interruption.

For more information on the reasons why the controller has stopped, refer to the Controller State
Description (see Modicon M251 Logic Controller, Programming Guide).

62 EIO0000001468 04/2014
M251 PLC System Library Data Types

PLC_R_TERMINAL_PORT_STATUS: Programming Port Connection Status


Codes

Enumerated Type Description


The PLC_R_TERMINAL_PORT_STATUS enumeration data type contains the following values:

Enumerator Value Comment


TERMINAL_NOT_CONNECTED 00 hex No PC is connected to the programming port.
TERMINAL_CONNECTION_IN_PROGRESS 01 hex Connection is in progress.
TERMINAL_CONNECTED 02 hex PC is connected to the programming port.
TERMINAL_ERROR 0F hex Error detected during connection.

EIO0000001468 04/2014 63
M251 PLC System Library Data Types

PLC_R_TM3_BUS_STATE: TM3 Bus Status Codes

Enumerated Type Description


The PLC_R_TM3_BUS_STATE enumeration data type contains the following values:

Enumerator Value Comment


TM3_CONF_ERROR 01 hex Detected error due to mismatch in the physical
configuration and the configuration in SoMachine.
TM3_OK 03 hex Detected good match in the physical configuration and the
configuration in SoMachine.
TM3_POWER_SUPPLY_ERROR 04 hex Detected error in power supply.

64 EIO0000001468 04/2014
M251 PLC System Library Data Types

PLC_W_COMMAND: Control Command Codes

Enumerated Type Description


The PLC_W_COMMAND enumeration data type contains the following values:

Enumerator Value Comment


PLC_W_STOP 0001 hex Command to stop the controller.
PLC_W_RUN 0002 hex Command to run the controller.
PLC_W_RESET_COLD 0004 hex Command to initiate a Controller cold reset.
PLC_W_RESET_WARM 0008 hex Command to initiate a Controller warm reset.

EIO0000001468 04/2014 65
M251 PLC System Library Data Types

Section 3.2
DataFileCopy System Variables Data Types

DataFileCopy System Variables Data Types

Overview
This section lists and describes the system variable data types included in the DataFileCopy
structures.

What Is in This Section?


This section contains the following topics:
Topic Page
DataFileCopyError: Detected Error Codes 67
DataFileCopyLocation: Location Codes 68

66 EIO0000001468 04/2014
M251 PLC System Library Data Types

DataFileCopyError: Detected Error Codes

Enumerated Type Description


The DataFileCopyError enumeration data type contains the following values:

Enumerator Value Description


ERR_NO_ERR 00 hex No error detected.
ERR_FILE_NOT_FOUND 01 hex The file does not exist.
ERR_FILE_ACCESS_REFUSED 02 hex The file cannot be opened.
ERR_INCORRECT_SIZE 03 hex The request size is not the same as size
read from file.
ERR_CRC_ERR 04 hex The CRC is not correct and the file is
assumed to be corrupted.
ERR_INCORRECT_MAC 05 hex The controller attempting to read from the
file does not have the same MAC address
as that contained in the file.

EIO0000001468 04/2014 67
M251 PLC System Library Data Types

DataFileCopyLocation: Location Codes

Enumerated Type Description


The DataFileCopyLocation enumeration data type contains the following values:

Enumerator Value Description


DFCL_INTERNAL 00 hex Data file with DTA extension is located in /usr/Dta directory.
DFCL_EXTERNAL 01 hex Data file with DTA extension is located in /sd0/usr/Dta directory.
DFCL_TBD 02 hex Not used.

68 EIO0000001468 04/2014
M251 PLC System Library Data Types

Section 3.3
ExecScript System Variables Data Types

ExecScript System Variables Data Types

ExecuteScriptError: Detected Error Codes

Enumerated Type Description


The ExecuteScriptError enumeration data type contains the following values:

Enumerator Value Description


CMD_OK 00 hex No error detected.
ERR_CMD_UNKNOWN 01 hex The command is not recognized.
ERR_SD_CARD_MISSING 02 hex SD card is not present.
ERR_SEE_FWLOG 03 hex There was an error detected during command
execution, see FwLog.txt. For more
information, refer to File Type (see Modicon
M251 Logic Controller, Programming Guide).
ERR_ONLY_ONE_COMMAND_ALLOWED 04 hex An attempt was made to execute several scripts
simultaneously.
CMD_BEING_EXECUTED 05 hex A script is already in progress.

EIO0000001468 04/2014 69
M251 PLC System Library Data Types

Section 3.4
ETH_R/W System Variables Data Types

ETH_R/W System Variables Data Types

Overview
This section lists and describes the system variable data types included in the ETH_R and ETH_W
structures.

What Is in This Section?


This section contains the following topics:
Topic Page
ETH_R_FRAME_PROTOCOL: Frame Transmission Protocol Codes 71
ETH_R_IP_MODE: IP Address Source Codes 72
ETH_R_PORT_DUPLEX_STATUS: Transmission Mode Codes 73
ETH_R_PORT_IP_STATUS: Ethernet TCP/IP Port Status Codes 74
ETH_R_PORT_LINK_STATUS: Communication Link Status Codes 75
ETH_R_PORT_SPEED: Communication Speed of the Ethernet Port Codes 76
ETH_R_RUN_IDLE: Ethernet/IP Run and Idle States Codes 77

70 EIO0000001468 04/2014
M251 PLC System Library Data Types

ETH_R_FRAME_PROTOCOL: Frame Transmission Protocol Codes

Enumerated Type Description


The ETH_R_FRAME_PROTOCOL enumeration data type contains the following values:

Enumerator Value Comment


ETH_R_802_3 00 hex The protocol used for frame transmission is
IEEE 802.3.
ETH_R_ETHERNET_II 01 hex The protocol used for frame transmission is
Ethernet II.

EIO0000001468 04/2014 71
M251 PLC System Library Data Types

ETH_R_IP_MODE: IP Address Source Codes

Enumerated Type Description


The ETH_R_IP_MODE enumeration data type contains the following values:

Enumerator Value Comment


ETH_R_STORED 00 hex Stored IP address is used.
ETH_R_BOOTP 01 hex Bootstrap protocol is used to get an IP address.
ETH_R_DHCP 02 hex DHCP protocol is used to get an IP address.
ETH_DEFAULT_IP FF hex Default IP address is used.

72 EIO0000001468 04/2014
M251 PLC System Library Data Types

ETH_R_PORT_DUPLEX_STATUS: Transmission Mode Codes

Enumerated Type Description


The ETH_R_PORT_DUPLEX_STATUS enumeration data type contains the following values:

Enumerator Value Comment


ETH_R_PORT_HALF_DUPLEX 00 hex Half duplex transmission mode is used.
ETH_R_FULL_DUPLEX 01 hex Full duplex transmission mode is used.
ETH_R_PORT_NA_DUPLEX 03 hex No duplex transmission mode is used.

EIO0000001468 04/2014 73
M251 PLC System Library Data Types

ETH_R_PORT_IP_STATUS: Ethernet TCP/IP Port Status Codes

Enumerated Type Description


The ETH_R_PORT_IP_STATUS enumeration data type contains the following values:

Enumerator Value Comment


WAIT_FOR_PARAMS 00 hex Waiting for parameters.
WAIT_FOR_CONF 01 hex Waiting for configuration.
DATA_EXCHANGE 02 hex Ready for data exchange.
ETH_ERROR 03 hex Ethernet TCP/IP port error detected (cable
disconnected, invalid configuration, and so on).
DUPLICATE_IP 04 hex IP address already used by another equipment.

74 EIO0000001468 04/2014
M251 PLC System Library Data Types

ETH_R_PORT_LINK_STATUS: Communication Link Status Codes

Enumerated Type Description


The ETH_R_PORT_LINK_STATUS enumeration data type contains the following values:

Enumerator Value Comment


ETH_R_LINK_DOWN 00 hex Communication link not available to another device.
ETH_R_LINK_UP 01 hex Communication link available to another device.

EIO0000001468 04/2014 75
M251 PLC System Library Data Types

ETH_R_PORT_SPEED: Communication Speed of the Ethernet Port Codes

Enumerated Type Description


The ETH_R_PORT_SPEED enumeration data type contains the following values:

Enumerator Value Comment


ETH_R_SPEED_NA 0 dec Network speed is 0 megabits per second.
ETH_R_SPEED_10_MB 10 dec Network speed is 10 megabits per second.
ETH_R_100_MB 100 dec Network speed is 100 megabits per second.

76 EIO0000001468 04/2014
M251 PLC System Library Data Types

ETH_R_RUN_IDLE: Ethernet/IP Run and Idle States Codes

Enumerated Type Description


The ETH_R_RUN_IDLE enumeration data type contains the following values:

Enumerator Value Comment


IDLE 00 hex EtherNet/IP connection is idle.
RUN 01 hex EtherNet/IP connection is running.

EIO0000001468 04/2014 77
M251 PLC System Library Data Types

Section 3.5
TM3_MODULE_R System Variables Data Types

TM3_MODULE_R System Variables Data Types

Overview
This section lists and describes the system variable data types included in the TM3_MODULE_R
structure.

What Is in This Section?


This section contains the following topics:
Topic Page
TM3_ERR_CODE: TM3 Expansion Module Detected Error Codes 79
TM3_MODULE_R_ARRAY_TYPE: TM3 Expansion Module Read Array Type 80
TM3_MODULE_STATE: TM3 Expansion Module State Codes 81

78 EIO0000001468 04/2014
M251 PLC System Library Data Types

TM3_ERR_CODE: TM3 Expansion Module Detected Error Codes

Enumerated Type Description


The TM3_ERR_CODE enumeration data type contains the following values:

Enumerator Value Comment


TM3_NO_ERR 00 hex Last bus exchange with the expansion module was
successful.
TM3_ERR_FAILED 01 hex Error detected due to the last bus exchange with the
expansion module was unsuccessful.
TM3_ERR_PARAMETER 02 hex Parameter error detected in the last bus exchange with the
module.
TM3_ERR_COK 03 hex Temporary or permanent hardware error detected on one
of the TM3 expansion modules.
TM3_ERR_BUS 04 hex Bus error detected in the last bus exchange with the
expansion module.

EIO0000001468 04/2014 79
M251 PLC System Library Data Types

TM3_MODULE_R_ARRAY_TYPE: TM3 Expansion Module Read Array Type

Description
The TM3_MODULE_R_ARRAY_TYPE is an array of 0...13 TM3_MODULE_R_STRUCT.

80 EIO0000001468 04/2014
M251 PLC System Library Data Types

TM3_MODULE_STATE: TM3 Expansion Module State Codes

Enumerated Type Description


The TM3_MODULE_STATE enumeration data type contains the following values:

Enumerator Value Comment


TM3_EMPTY 00 hex No module.
TM3_CONF_ERROR 01 hex Physical expansion module does not match with the one
configured in SoMachine.
TM3_BUS_ERROR 02 hex Bus error detected in the last exchange with the module.
TM3_OK 03 hex Last bus exchange with this module was successful.

EIO0000001468 04/2014 81
M251 PLC System Library Data Types

Section 3.6
System Function Data Types

System Function Data Types

RTCSETDRIFT_ERROR: SetRTCDrift Function Detected Error Codes

Enumerated Type Description


The RTCSETDRIFT_ERROR enumeration data type contains the following values:

Enumerator Value Comment


RTC_OK 00 hex RTC drift correctly configured.
RTC_BAD_DAY 01 hex Not used.
RTC_BAD_HOUR 02 hex Not used.
RTC_BAD_MINUTE 03 hex Not used.
RTC_BAD_DRIFT 04 hex RTC Drift parameter out of range.
RTC_INTERNAL_ERROR 05 hex RTC Drift settings rejected on internal detected error.

82 EIO0000001468 04/2014
Modicon M251 Logic Controller

EIO0000001468 04/2014

Appendices

EIO0000001468 04/2014 83
84 EIO0000001468 04/2014
Modicon M251 Logic Controller
Function and Function Block Representation
EIO0000001468 04/2014

Appendix A
Function and Function Block Representation

Function and Function Block Representation

Overview
Each function can be represented in the following languages:
 IL: Instruction List
 ST: Structured Text
 LD: Ladder Diagram
 FBD: Function Block Diagram
 CFC: Continuous Function Chart

This chapter provides functions and function blocks representation examples and explains how to
use them for IL and ST languages.

What Is in This Chapter?


This chapter contains the following topics:
Topic Page
Differences Between a Function and a Function Block 86
How to Use a Function or a Function Block in IL Language 87
How to Use a Function or a Function Block in ST Language 91

EIO0000001468 04/2014 85
Function and Function Block Representation

Differences Between a Function and a Function Block

Function
A function:
 is a POU (Program Organization Unit) that returns one immediate result.
 is directly called with its name (not through an instance).
 has no persistent state from one call to the other.
 can be used as an operand in other expressions.

Examples: boolean operators (AND), calculations, conversion (BYTE_TO_INT)

Function Block
A function block:
 is a POU (Program Organization Unit) that returns one or more outputs.
 needs to be called by an instance (function block copy with dedicated name and variables).
 each instance has a persistent state (outputs and internal variables) from one call to the other
from a function block or a program.
Examples: timers, counters
In the example, Timer_ON is an instance of the function block TON:

86 EIO0000001468 04/2014
Function and Function Block Representation

How to Use a Function or a Function Block in IL Language

General Information
This part explains how to implement a function and a function block in IL language.
Functions IsFirstMastCycle and SetRTCDrift and Function Block TON are used as
examples to show implementations.

Using a Function in IL Language


This procedure describes how to insert a function in IL language:

Step Action
1 Open or create a new POU in Instruction List language.
NOTE: The procedure to create a POU is not detailed here. For more information, refer to Adding
and Calling POUs (see SoMachine, Programming Guide).
2 Create the variables that the function requires.
3 If the function has 1 or more inputs, start loading the first input using LD instruction.
4 Insert a new line below and:
 type the name of the function in the operator column (left field), or
 use the Input Assistant to select the function (select Insert Box in the context menu).

5 If the function has more than 1 input and when Input Assistant is used, the necessary number of lines
is automatically created with ??? in the fields on the right. Replace the ??? with the appropriate
value or variable that corresponds to the order of inputs.
6 Insert a new line to store the result of the function into the appropriate variable: type ST instruction
in the operator column (left field) and the variable name in the field on the right.

To illustrate the procedure, consider the Functions IsFirstMastCycle (without input parameter)
and SetRTCDrift (with input parameters) graphically presented below:

Function Graphical Representation


without input parameter:
IsFirstMastCycle

with input parameters:


SetRTCDrift

EIO0000001468 04/2014 87
Function and Function Block Representation

In IL language, the function name is used directly in the operator column:

Function Representation in SoMachine POU IL Editor


IL example of a function
without input parameter:
IsFirstMastCycle

IL example of a function
with input parameters:
SetRTCDrift

88 EIO0000001468 04/2014
Function and Function Block Representation

Using a Function Block in IL Language


This procedure describes how to insert a function block in IL language:

Step Action
1 Open or create a new POU in Instruction List language.
NOTE: The procedure to create a POU is not detailed here. For more information, refer to Adding and
Calling POUs (see SoMachine, Programming Guide).
2 Create the variables that the function block requires, including the instance name.
3 Function Blocks are called using a CAL instruction:
 Use the Input Assistant to select the FB (right-click and select Insert Box in the context menu).
 Automatically, the CAL instruction and the necessary I/O are created.

Each parameter (I/O) is an instruction:


 Values to inputs are set by ":=".
 Values to outputs are set by "=>".

4 In the CAL right-side field, replace ??? with the instance name.
5 Replace other ??? with an appropriate variable or immediate value.

To illustrate the procedure, consider this example with the TON Function Block graphically
presented below:

Function Block Graphical Representation


TON

EIO0000001468 04/2014 89
Function and Function Block Representation

In IL language, the function block name is used directly in the operator column:

Function Block Representation in SoMachine POU IL Editor


TON

90 EIO0000001468 04/2014
Function and Function Block Representation

How to Use a Function or a Function Block in ST Language

General Information
This part explains how to implement a Function and a Function Block in ST language.
Function SetRTCDrift and Function Block TON are used as examples to show implementations.

Using a Function in ST Language


This procedure describes how to insert a function in ST language:

Step Action
1 Open or create a new POU in Structured Text language.
NOTE: The procedure to create a POU is not detailed here. For more information, refer to Adding
and Calling POUs (see SoMachine, Programming Guide).
2 Create the variables that the function requires.
3 Use the general syntax in the POU ST Editor for the ST language of a function. The general
syntax is:
FunctionResult:= FunctionName(VarInput1, VarInput2,.. VarInputx);

To illustrate the procedure, consider the function SetRTCDrift graphically presented below:

Function Graphical Representation


SetRTCDrift

The ST language of this function is the following:

Function Representation in SoMachine POU ST Editor


SetRTCDrift PROGRAM MyProgram_ST
VAR myDrift: SINT(-29..29) := 5;
myDay: DAY_OF_WEEK := SUNDAY;
myHour: HOUR := 12;
myMinute: MINUTE;
myRTCAdjust: RTCDRIFT_ERROR;
END_VAR
myRTCAdjust:= SetRTCDrift(myDrift, myDay, myHour, myMinute);

EIO0000001468 04/2014 91
Function and Function Block Representation

Using a Function Block in ST Language


This procedure describes how to insert a function block in ST language:

Step Action
1 Open or create a new POU in Structured Text language.
NOTE: The procedure to create a POU is not detailed here. For more information on
adding, declaring and calling POUs, refer to the related documentation
(see SoMachine, Programming Guide).
2 Create the input and output variables and the instance required for the function block:
 Input variables are the input parameters required by the function block
 Output variables receive the value returned by the function block

3 Use the general syntax in the POU ST Editor for the ST language of a Function
Block. The general syntax is:
FunctionBlock_InstanceName(Input1:=VarInput1,
Input2:=VarInput2,... Ouput1=>VarOutput1,
Ouput2=>VarOutput2,...);

To illustrate the procedure, consider this example with the TON function block graphically
presented below:

Function Block Graphical Representation


TON

92 EIO0000001468 04/2014
Function and Function Block Representation

This table shows examples of a function block call in ST language:

Function Block Representation in SoMachine POU ST Editor


TON

EIO0000001468 04/2014 93
Function and Function Block Representation

94 EIO0000001468 04/2014
Modicon M251 Logic Controller
Glossary
EIO0000001468 04/2014

Glossary

0-9
%MW
According to the IEC standard, %MW represents a memory word register (for example, a language
object of type memory word).

A
application
A program including configuration data, symbols, and documentation.
ARRAY
The systematic arrangement of data objects of a single type in the form of a table defined in logic
controller memory. The syntax is as follows: ARRAY [<dimension>] OF <Type>
Example 1: ARRAY [1..2] OF BOOL is a 1-dimensional table with 2 elements of type BOOL.
Example 2: ARRAY [1..10, 1..20] OF INT is a 2-dimensional table with 10 x 20 elements of
type INT.

B
BOOL
(boolean) A basic data type in computing. A BOOL variable can have one of these values: 0
(FALSE), 1 (TRUE). A bit that is extracted from a word is of type BOOL; for example, %MW10.4 is a
fifth bit of memory word number 10.
Boot application
(boot application) The binary file that contains the application. Usually, it is stored in the PLC and
allows PLC to boot on the application that the user has generated.
BOOTP
(bootstrap protocol) A UDP network protocol that can be used by a network client to automatically
obtain an IP address (and possibly other data) from a server. The client identifies itself to the server
using the client MAC address. The server, which maintains a pre-configured table of client device
MAC addresses and associated IP addresses, sends the client its pre-configured IP address.
BOOTP was originally used as a method that enabled diskless hosts to be remotely booted over a
network. The BOOTP process assigns an infinite lease of an IP address. The BOOTP service
utilizes UDP ports 67 and 68.
byte
A type that is encoded in an 8-bit format, ranging from 16#00 to 16#FF in hexadecimal
representation.

EIO0000001468 04/2014 95
Glossary

C
CFC
(continuous function chart) A graphical programming language (an extension of the IEC 61131-3
standard) based on the function block diagram language that works like a flowchart. However, no
networks are used and free positioning of graphic elements is possible, which allows feedback
loops. For each block, the inputs are on the left and the outputs on the right. You can link the block
outputs to the inputs of other blocks to create complex expressions.
configuration
The arrangement and interconnection of hardware components within a system and the hardware
and software parameters that determine the operating characteristics of the system.
controller
Automates industrial processes (also known as programmable logic controller or programmable
controller).
CRC
(cyclical redundancy check) A method used to determine the validity of a communication
transmission. The transmission contains a bit field that constitutes a checksum. The message is
used to calculate the checksum by the transmitter according to the content of the message.
Receiving nodes, then recalculate the field in the same manner. Any discrepancy in the value of
the 2 CRC calculations indicates that the transmitted message and the received message are
different.

D
DHCP
(dynamic host configuration protocol) An advanced extension of BOOTP. DHCP is more
advanced, but both DHCP and BOOTP are common. (DHCP can handle BOOTP client requests.)
DWORD
(double word) Encoded in 32-bit format.

E
element
The short name of the ARRAY element.
equipment
A part of a machine including sub-assemblies such as conveyors, turntables, and so on.
Ethernet
A physical and data link layer technology for LANs, also known as IEE 802.3.

96 EIO0000001468 04/2014
Glossary

EtherNet/IP
(Ethernet industrial protocol) An open communications protocol for manufacturing automation
solutions in industrial systems. EtherNet/IP is in a family of networks that implement the common
industrial protocol at its upper layers. The supporting organization (ODVA) specifies EtherNet/IP
to accomplish global adaptability and media independence.

F
FB
(function block) A convenient programming mechanism that consolidates a group of programming
instructions to perform a specific and normalized action, such as speed control, interval control, or
counting. A function block may comprise configuration data, a set of internal or external operating
parameters and usually 1 or more data inputs and outputs.
firmware
Represents the BIOS, data parameters, and programming instructions that constitute the operating
system on a controller. The firmware is stored in non-volatile memory within the controller.
flash memory
A non-volatile memory that can be overwritten. It is stored on a special EEPROM that can be
erased and reprogrammed.
function
A programming unit that has 1 input and returns 1 immediate result. However, unlike FBs, it is
directly called with its name (as opposed to through an instance), has no persistent state from one
call to the next and can be used as an operand in other programming expressions.
Examples: boolean (AND) operators, calculations, conversions (BYTE_TO_INT)
function block
A programming unit that has 1 or more inputs and returns 1 or more outputs. FBs are called through
an instance (function block copy with dedicated name and variables) and each instance has a
persistent state (outputs and internal variables) from 1 call to the other.
Examples: timers, counters
function block diagram
One of the 5 languages for logic or control supported by the standard IEC 61131-3 for control
systems. Function block diagram is a graphically oriented programming language. It works with a
list of networks where each network contains a graphical structure of boxes and connection lines
representing either a logical or arithmetic expression, the call of a function block, a jump, or a return
instruction.

G
GVL
(global variable list) Manages global variables that can be passed between controllers on an
Ethernet TCP/IP Modbus network.

EIO0000001468 04/2014 97
Glossary

H
hex
(hexadecimal)

I
ID
(identifier/identification)
IEC
(international electrotechnical commission) A non-profit and non-governmental international
standards organization that prepares and publishes international standards for electrical,
electronic, and related technologies.
IEC 61131-3
Part 3 of a 3-part IEC standard for industrial automation equipment. IEC 61131-3 is concerned with
controller programming languages and defines 2 graphical and 2 textual programming language
standards. The graphical programming languages are ladder diagram and function block diagram.
The textual programming languages include structured text and instruction list.
IEEE 802.3
A collection of IEEE standards defining the physical layer, and the media access control sublayer
of the data link layer, of wired Ethernet.
IL
(instruction list) A program written in the language that is composed of a series of text-based
instructions executed sequentially by the controller. Each instruction includes a line number, an
instruction code, and an operand (refer to IEC 61131-3).
INT
(integer) A whole number encoded in 16 bits.
IP
(Internet protocol Part of the TCP/IP protocol family that tracks the Internet addresses of devices,
routes outgoing messages, and recognizes incoming messages.

L
LD
(ladder diagram) A graphical representation of the instructions of a controller program with symbols
for contacts, coils, and blocks in a series of rungs executed sequentially by a controller (refer to
IEC 61131-3).
LWORD
(long word) A data type encoded in a 64-bit format.

98 EIO0000001468 04/2014
Glossary

M
MAC address
(media access control address) A unique 48-bit number associated with a specific piece of
hardware. The MAC address is programmed into each network card or device when it is
manufactured.
MAST
A processor task that is run through its programming software. The MAST task has 2 sections:
 IN: Inputs are copied to the IN section before execution of the MAST task.
 OUT: Outputs are copied to the OUT section after execution of the MAST task.

N
network
A system of interconnected devices that share a common data path and protocol for
communications.

P
PLC
(programmable logic controller) An industrial computer used to automate manufacturing, industrial,
and other electromechanical processes. PLCs are different from common computers in that they
are designed to have multiple input and output arrays and adhere to more robust specifications for
shock, vibration, temperature, and electrical interference among other things.
POU
(program organization unit) A variable declaration in source code and a corresponding instruction
set. POUs facilitate the modular re-use of software programs, functions, and function blocks. Once
declared, POUs are available to one another.
program
The component of an application that consists of compiled source code capable of being installed
in the memory of a logic controller.
protocol
A convention or standard definition that controls or enables the connection, communication, and
data transfer between 2 computing system and devices.

R
run
A command that causes the controller to scan the application program, read the physical inputs,
and write to the physical outputs according to solution of the logic of the program.

EIO0000001468 04/2014 99
Glossary

S
ST
(structured text) A language that includes complex statements and nested instructions (such as
iteration loops, conditional executions, or functions). ST is compliant with IEC 61131-3.
STOP
A command that causes the controller to stop running an application program.
string
A variable that is a series of ASCII characters.
system variable
A variable that provides controller data and diagnostic information and allows sending commands
to the controller.

T
task
A group of sections and subroutines, executed cyclically or periodically for the MAST task or
periodically for the FAST task.
A task possesses a level of priority and is linked to inputs and outputs of the controller. These I/O
are refreshed in relation to the task.
A controller can have several tasks.
TCP
(transmission control protocol) A connection-based transport layer protocol that provides a
simultaneous bi-directional transmission of data. TCP is part of the TCP/IP protocol suite.

U
UDINT
(unsigned double integer) Encoded in 32 bits.
UINT
(unsigned integer) Encoded in 16 bits.
unlocated variable
A variable that does not have an address (refer to located variable).

V
variable
A memory unit that is addressed and modified by a program.

100 EIO0000001468 04/2014


Glossary

W
watchdog
A watchdog is a special timer used to ensure that programs do not overrun their allocated scan
time. The watchdog timer is usually set to a higher value than the scan time and reset to 0 at the
end of each scan cycle. If the watchdog timer reaches the preset value, for example, because the
program is caught in an endless loop, a fault is declared and the program stopped.
WORD
A type encoded in a 16-bit format.

EIO0000001468 04/2014 101


Glossary

102 EIO0000001468 04/2014


Modicon M251 Logic Controller
Index
EIO0000001468 04/2014

Index

D ETH_R_PORT_DUPLEX_STATUS
Data Types, 73
Data Types
ETH_R_PORT_LINK_STATUS
DataFileCopyError, 67
Data Types, 75
DataFileCopyLocation, 68
ETH_R_PORT_SPEED
ETH_R_FRAME_PROTOCOL, 71
Data Types, 76
ETH_R_IP_MODE, 72
ETH_W
ETH_R_PORT_DUPLEX_STATUS, 73
System Variable, 32
ETH_R_PORT_IP_STATUS, 74
ExecuteScript
ETH_R_PORT_LINK_STATUS, 75
Functions, 48
ETH_R_PORT_SPEED, 76
ExecuteScriptError
ETH_R_RUN_IDLE, 77
Data Types, 69
ExecuteScriptError, 69
PLC_R_APPLICATION_ERROR, 57
PLC_R_BOOT_PROJECT_STATUS, 58 F
PLC_R_IO_STATUS, 59
Functions
PLC_R_SDCARD_STATUS, 60
DataFileCopy, 45
PLC_R_STATUS, 61
functions
PLC_R_STOP_CAUSE, 62
differences between a function and a
PLC_R_TERMINAL_PORT_STATUS, 63
function block, 86
PLC_R_TM3_BUS_STATE, 64
Functions
PLC_W_COMMAND, 65
ExecuteScript, 48
RTCSETDRIFT_ERROR, 82
GetRtc, 37
TM3_ERR_CODE, 79
functions
TM3_MODULE_R_ARRAY_TYPE, 80
how to use a function or a function block
TM3_MODULE_STATE, 81
in IL language, 87
DataFileCopy
how to use a function or a function block
Functions, 45
in ST language, 91
DataFileCopyError
Functions
Data Types, 67
IsFirstMastColdCycle, 38
DataFileCopyLocation
IsFirstMastCycle, 39
Data Types, 68
IsFirstMastWarmCycle, 41
SetRTCDrift, 42
E TM3_GetModuleBusStatus, 51
TM3_GetModuleInternalStatus, 52
ETH_R
System Variable, 27
ETH_R_FRAME_PROTOCOL G
Data Types, 71
GetRtc
ETH_R_IP_MODE
Functions, 37
Data Types, 72

EIO0000001468 04/2014 103


Index

I SERIAL_W
System Variable, 25
IsFirstMastColdCycle
SetRTCDrift
Functions, 38
Functions, 42
IsFirstMastCycle
System Variable
Functions, 39
ETH_R, 27
IsFirstMastWarmCycle
ETH_W, 32
Functions, 41
PLC_R, 18
PLC_W, 22
P System variable
PROFIBUS_R, 34
PLC_R System Variable
System Variable, 18 SERIAL_R, 24
PLC_R_APPLICATION_ERROR SERIAL_W, 25
Data Types, 57 TM3_MODULE_R, 33
PLC_R_BOOT_PROJECT_STATUS System Variables
Data Types, 58 Definition, 13
PLC_R_IO_STATUS Using, 15
Data Types, 59
PLC_R_SDCARD_STATUS
Data Types, 60 T
PLC_R_STATUS
TM3_ERR_CODE
Data Types, 61
Data Types, 79
PLC_R_STOP_CAUSE
TM3_GetModuleBusStatus
Data Types, 62
Functions, 51
PLC_R_TERMINAL_PORT_STATUS
TM3_GetModuleInternalStatus
Data Types, 63
Functions, 52
PLC_R_TM3_BUS_STATE
TM3_MODULE_R
Data Types, 64
System Variable, 33
PLC_W
TM3_MODULE_R_ARRAY_TYPE
System Variable, 22
Data Types, 80
PLC_W_COMMAND
TM3_MODULE_STATE
Data Types, 65
Data Types, 81
PROFIBUS_R
System Variable, 34

R
RTCSETDRIFT_ERROR
Data Types, 82

S
SERIAL_R
System Variable, 24

104 EIO0000001468 04/2014

You might also like