Em-Ii Lab
Em-Ii Lab
TECHNOLOGY
(Autonomous)
DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING
LAB MANUAL
SEMESTER : II SEM
REGULATION : R-22
CYCLE-I
CYCLE-II
AIM: (i) To conduct sumpner’s test on two identical single phase transformers.
(ii) To find out the iron loss, copper loss and the efficiency of each transformer.
1-PHASE TRANSFORMER
S.No. NAME RATING
1 Power
2 Voltage
3 Frequency
4 Taps On H.V
APPARATUS REQUIRED:
S.No. NAME TYPE RANGE QUANTITY
1 Voltmeter MI (0-30)V 1
(0-300)V 1
2 Ammeter MI (0-2.5)A 1
(0-20)A 1
3 Variac - (0-20)A 1
SC TEST:
1. Close the DPST switch
2. Switch ON the supply 1-phase,50hz,230v on secondary side of the transformer
3. By slowly varying the 1-phase auto t/f till the rated current is reached
4. Now take the voltage voltmeter(v1&v2),ammeter(A1&A2),W1&W2 respectively
5. Switch OFF the supply
PRECAUTIONS:
(i) Connections must be made tight
(ii) Before making or breaking the circuit, supply must be switched off.
OBSERVATIONS:
O.C TEST
S.NO. Vo (V) Io (A) Wo(W)
S. C TEST:
cos 0 = =
Sin 0 =
R
V00 = Where Iw = I0 cos 0
Iw
X0
V0 = Where Im = I0 sin 0
Im
WSC
R
02 2
I sc
V
Z02 I SC
SC
2 2
X 02 Z 01 R 01 =
X01 K2 V2
X 02
= Where K 1 Transformation ratio.
R K = V1
2
R
01 02 =
CALCULATIONS OF EFFICIENCY AND REGULATION
For example at ½ full load
Cupper losses = Wsc x (1/2)2 watts, where WSC = full – load cupper losses
%
efficiency
Output x 100
Input
Regulation:
V2
EQUIVALENT CIRCUIT:
1. ¼F.L. ¼F.L.
2. ½F.L. ½F.L.
3. ¾F.L. ¾F.L.
4. F.L. F.L.
Lagging Pf Leading Pf
2. 0.4 2. 0.4
3. 0.5 3. 0.5
4. 0.6 4. 0.6
5. 0.7 5. 0.7
6. 0.8 6. 0.8
7. Unity 7. Unity
RESULT:
EXPERIMENT NO -2
NO-LOAD AND BLOCKED ROTOR TEST ON 3-
PHASE INDUCTION MOTOR
CIRCUIT DIAGRAM FOR NO LOAD TEST:
1 Power
2 Voltage
3 Current
4 Phase
5 Frequency
6 Speed
APPARATUS:
S.No. NAME OF THE TYPE RANGE QUANTITY
EQUIPMENT
1 Voltmeter MI 0-150V 1
0-600V 1
2 Ammeter MI 0-5A 1
3 Wattmeter - 600V/5A,LPF 2
150V/10A,UPF 2
4 Tachometer - - 1
PROCEDURE:
NO LOAD TEST:
1. Connect the circuit as per the circuit diagram shown in fig (2).
2. Keeping rheostat in maximum resistance position switch on the 220 V Dc supply.
3. Using volt-ammeter method measure the resistance of the stator winding.
4. After finding the stator resistance, Rdc must be multiplied with 1.6 so as to account
for skin effect i.e. Rac = 1.6 Rdc.
OBSERVATION:
No load test
1. G0=W0/3V 02
2. Y0=I0/V0
3. B0=square root[Y02-G02]
1.Z01=VSC/ISC
2.R01=WSC/3ISC2
3.X01=square root[Z012-R 2] 01
2.ISN=ISC*(V0/VSC)
3.WSN=WSC*(V0/VSC)2
PRECAUTIONS:
RESULT:
QUESTIONS:
2. What is the difference between the transformer equivalent circuit and induction motor
equivalent circuit?
3. What are the reasons in conducting no-load test with rated voltage and blocked-rotor test
with rated current?
4. Why do you choose LPF wattmeter in load test and hpf wattmeter in blocked rotor test?
APPARATUS REQUIRED:
1 Ammeter MC (0-25)A 1
2 Ammeter MI (0-5)A 1
3 Voltmeter MI (0-600)V 1
4 Rheostat - - 1
5 Tachometer Digital - 1
PROCEDURE:
1. Make the connections as per the circuit diagram, start the alternator with the help of prime
mover (DC shunt motor) and adjust speed to the synchronous speed. The speed of the
alternator is to be kept constant throughout the experiment.
2. Excite the field winding alternator keeping armature open .
3. Note down the terminals voltage at different value of field currents.
4. Draw the gram a of armature voltage Vs field current to get open circuit characteristic
(OCC) of the alternator.
5. Close the TPST switch.
6. Excite the field winding of the alternator till the rated current flows through the armature.
7. Note down all meter readings.
8. Draw the graph of the short circuit current Vs field current to get the short
circuit characteristics (SCC)
9. Obtain the synchronous impendence corresponding to the rated voltage ZS = VOC/ISC =IF
constant.
10. Measure the armature resistance per phase by drop method the A.C resistance will be 20%
more than DC resistance Ra=1.2 Ohm DC.
11. Calculate the synchronous reactance XS= SQ Root of Z S2-R ac2
12. Calculate the generated EMF with full load at a power factor.
13. E=[(VcosФ+IRa)2 (VsinФ+IXS)2]1/2
14. Positive sign for lagging power factor and Negative sign for leading power factor
15. Calculate full load regulation at different power factor
16. Draw the graph of regulation Vs power factor
TABULAR FORM:
MODEL GRAPH:
RESULT:
EXPERIMENT NO - 4
V AND INVERTED V CURVES OF 3-PHASE
SYNCHRONOUS MOTOR
V AND INVERTED V CURVES OF 3-PHASE SYNCHRONOUS MOTOR
APPARATUS:
1 Ammeter (0-25)A MI 1
2 Ammeter (0-20A)/3A MI 2
3 Voltmeter (0-600)/300V MI 3
4 Wattmeter (0-300)W MC 1
5 Rheostat (290Ω/12A) - 1
6 Tachometer - Digital 1
PROCEDURE:
PRECAUTIONS:
1. There should not be any load on the motor.
2. Initially the field current should be adjusted to rated value.
3. The direction of the rotation of the rotor should be in proper direction only.
4. If Ia value is increased more than rated value, then it should be brought to rated value by
adjusting the field current.
5. The I/P voltage should be kept constant through out the experiment.
6. After completion of the experiment only 3-phase supply should be disconnected first
and then DC supply.
TABULAR
FORM:
FULL LOAD
(A)
f a (A) POWER(W) Cos(ф)
NO LOAD
(A)
f a(A) POWER(W) Cos(ф)
FORMULA:
COSф1 =W0/√3VaIa
MODEL GRAPH:
RESULT:
EXPERIMENT NO-5
EQUIVALENT OF A SINGLE PHASE INDUCTION MOTOR
CIRCUIT DIAGRAM FOR NO-LOAD TEST:
CIRCUIT DIAGRAM FOR BLOCKED ROTOR TEST:
EQUIVALENT OF A SINGLE PHASE INDUCTION MOTOR
AIM : To conduct OC & SC tests on the given 1-Induction motor and to determine its equivalent
circuit parameters.
.
1 Power
2 Voltage
3 Current
4 Phase
5 Frequency
6 Speed
APPARATUS REQUIRED :
S.NO. NAME TYPE RANGE QUANTITY
1. Voltmeter MI 0-300V 1
2. Ammeter MI 0-10A 1
PROCEDURE :
NO LOAD TEST:
2. Close the DPST & Start the motor with the help of DOL starter without load.
2. Keep the auto transformer at minimum position and blocked the motor.
3. Close the DPST & Apply the rated current by increasing voltage.
CALCULATIONS :
NO LOAD TEST:
2.Cos(φ) = W0/(V0I0)
MOTOR TEST:
PRECAUTIONS :
1) The Dimmerstat should be kept at minimum O/P position initially.
2) In the rotor-blocked test, the rotor should be blocked firmly.
3) In SC test, the Dimmerstat should be varied slowly such that current should not exceed the
rated value.
4) If the wattmeter shows negative deflection, then reverse either pressure coil or current coil &
take that reading as negative.
OBSERVATIONS:
O.C.Test:
V0 I0 W0
S.C. Test:
Vsc Isc Wsc
30 8.18 20X8=160
MODEL CALCULATIONS:
(A) No-load Test:
Sinφ =
Reactive component Ic =Io Cosφ
=
Magnetizing Component Im =Io Sinφ
=
Ro =
X0=
R1e=
Z1e = X1e
=
=
X1 =
=
=
=
EQUIVALENT CIRCUIT:
RESULT:
EXPERIMENT NO - 6
DETERMINATION OF Xd AND Xq OF SALIENT
POLE SYNCHRONOUS MACHINE
DETERMINATION OF Xd AND Xq OF SALIENT POLE
SYNCHRONOUS MACHINE
AIM: To determine Xd and Xq of salient pole type of synchronous machine
NAMEPLATE DETAILS:
1 Capacity
2 Voltage
3 Current
4 Speed
5 Frequency
APPARATUS REQUIRED:
S.No. NAME TYPE RANGE QUANTITY
1 Ammeter MC (0-25)A 1
2 Ammeter MI (0-7.5)A,(0-2.5)A 2
3 Voltmeter - 1
4 Rheostat - - 1
5 Tachometer - - 1
PRECAUTIONS:
1. 1) Check the phase sequence of the machine with that of external supply before closing the
switches.
2. 2) Disconnect the excitation supply of the alternator while giving external supply.
3. 3) Slip should be made as small as possible.
TABULAR FORM:
CALCULATIONS:
RESULT:
EXPERIMENT NO-7
BRAKE TEST ON 3-PHASE INDUCTION MOTOR
CIRCUIT DIAGRAM :
BRAKE TEST ON 3-PHASE INDUCTION MOTOR
AIM: To perform the brake test on 3-phase slip ring induction motor and obtain its
performance characteristics.
APPARATUS REQUIRED:
1. Voltage
2. Rated current
3. Rated power
4. Rated speed
PROCEDURE:
1. Make the connections as per the circuit diagram.
2. Start the 3-phase induction motor on no load by means of 3-phase auto transformer.
4. Apply brake by tightening the best of brake drum and note down the readings of the
meter spring balance and speed.
7. Draw the performance curves of output vs efficiency, torque, speed, Ia ,Power factor on
graph sheet.
OBSERVATION TABULAR FORM:
CALCULATIONS:
2. Torque τ= w x g x r N-m
% = (NS-N)/NS x100
4. Cos Ф = R/ 3 VLIL
PRECAUTIONS:
RESULT:
EXPERIMENT NO-8
AIM : To determine the regulation of a 3-phase alternator by ZPF and ASA method.
1 RATED POWER
2 RATED
VOLTAGE
3 RATED
CURRENT
4 RATED SPEED
APPARATUS REQUIRED:
1 3-Phase alternator - - 1
2 Ammeter MC (0-15)A 1
3 Ammeter MI (0-5)A 1
4 Voltmeter MI (0-600)V 1
5 Tachometer Digital - 1
PRECAUTION:
1. The motor field rheostat should be kept in the minimum resistance position.
2. The Alternator field potential divider should be in the position of minimum potential.
3. Initially all switches are in open position.
RESULT:
EXPERIMENT NO -9
APPARATUS REQUIRED:
3-Phase alternator - - 1
1 Ammeter MC (0-1.5A/3A) 1
3 Voltmeter MC (0-600)V 1
4 Wattmeter - (0-5)A/600V 1
5 Tachometer Digital - 1
PROCEDURE:
2. Ensure that motor field Rheostat is minimum and alternator field rheostat is
maximum
3. Start the motor as with the help of starter and by adjusting motor field rheostat if rated
speed synchronous speed of machine.
4. By smooth variation the field rheostat of the alternator is set at rated V/g(415V)
across any two phases.
5. Apply the different load current upto the rated current of the alternator of each step
each load current. Notedown the readings of Vac ,Idc , Vac, Iac,W1 , W2
7. By applying different loads note down the Vac ,Idc , Vac ,W1 , W2
CALCULATION:
RESULT:
EXPERIMENT-10
AIM:To verify the conversion of 3-phase to 2 1-phase of 90 degrees apart supplies and also verify the
primary current from the 1-phase side.
SCOTT TRANSFORMERS
Transformer rating
Rated Voltage
Taps on HV
APPARATUS REQUIRED:
1 Transformer - 1-phase 2
,50%86.6%
4 Ammeter (0-10)A 5
5 VOltmeter
OBSERVATIONS:
Vin=101V
S.No. LOAD(A) IA IB IC ia ib
MODEL PHASOR DIAGRAMS FOR SCOTT CONNECTION:
PROCEDURE:
RESULT:
EXPERIMENT NO 9
PARALLEL OPERATION OF SINGLE PHSE TRANSFORMERS
PARALLEL OPERATION OF SINGLE PHSE TRANSFORMERS
AIM : To operate the given two 3KVA, 230/110V single phase Transformers in parallel and study
the load sharing between them when supplying resistive load .
NAME PLATE DETAILS :
TWO 1-Φ TRANSFORMERS
1 Power 3KVA
2 No. of phases 1-PHASE
3 Voltage 230V
4 Frequency 50 Hz
5 Taps on HV 100% ,86.6%
50% ,25%
APPARATUS :
S.NO. NAME TYPE RANGE QUANTITY
PROCEDURE :
1. Connect the circuit as per the circuit diagram.
3. Apply the small voltage & measure the voltage on LV & HV side.
FORMULA :
IL = IT1 + IT2
CALCULATIONS:
PRECAUTIONS :
1. The transformers must have same voltage ratio.
RESULT :