Updated Design Criteria (Final Word File)
Updated Design Criteria (Final Word File)
For
Water Supply, Sewerage and Drainage System in
Punjab
February 2023
Table of Contents
ACKNOWLEDGMENT ................................................................................................................................ 5
PREFACE.................................................................................................................................................... 8
EXECUTIVE SUMMARY .............................................................................................................................. 9
Chapter 1: General & Background .......................................................................................................... 10
SECTION I - WATER SUPPLY SYSTEM
Chapter 2: Basic Parameters ................................................................................................................... 13
Chapter 3: Pumping of Water ................................................................................................................. 17
3.1 Tubewells Design Criteria.............................................................................................................. 17
3.2 Skimming Wells ............................................................................................................................. 18
3.3 Infiltration Galleries ...................................................................................................................... 18
3.3.1 Limitations and controlling parameters................................................................................ 18
3.3.2 Estimation for the Length of Screen ..................................................................................... 19
3.3.3 Impermeable Case ................................................................................................................ 19
3.3.4 Permeable Cases ................................................................................................................... 20
Chapter 4: Primary & Secondary Network .............................................................................................. 22
4.1 General Considerations ................................................................................................................. 22
4.2 Recommended Primary Network ................................................................................................. 22
4.3 Secondary Networks ..................................................................................................................... 22
4.4 Tertiary Networks ......................................................................................................................... 22
4.5 Head Loss in Pipes ......................................................................................................................... 22
4.6 Losses in Fittings / Specials ........................................................................................................... 23
4.7 Computer Model for Distribution Network Design ...................................................................... 23
Chapter 5: Pipe Materials ....................................................................................................................... 25
5.1 Cast Iron Pipes............................................................................................................................... 25
5.2 Ductile Iron Pipes .......................................................................................................................... 25
5.3 Steel Pipes (Spiral / Seam Welded) ............................................................................................... 25
5.4 High Density Polyethylene Pipes (HDPE) ...................................................................................... 25
5.5 Galvanized Iron (GI) Pipes ............................................................................................................. 26
Chapter 6: Service Pipes Fittings & Specials ............................................................................................ 30
6.1 House Connection ......................................................................................................................... 30
6.2 Valves ............................................................................................................................................ 30
6.3 Check Valves ................................................................................................................................. 32
Chapter 7: Laying of Water Mains & Distribution System ....................................................................... 33
7.1 Pipe Handling ................................................................................................................................ 33
7.2 Trenching ...................................................................................................................................... 33
7.3 Bedding ......................................................................................................................................... 33
1
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
7.4 Joints ............................................................................................................................................. 34
7.5 Backfilling ...................................................................................................................................... 34
7.6 Hydrostatic Testing ....................................................................................................................... 34
7.7 Thrust Blocks (Horizontal & Vertical) ............................................................................................ 34
Chapter 8: Drinking Water Treatment .................................................................................................... 35
8.1 Slow Sand Filters: .......................................................................................................................... 35
8.2 Modified Slow Sand Filters: .......................................................................................................... 35
8.3 Rapid Sand Filters:......................................................................................................................... 36
8.4 Water Disinfection- Chlorination .................................................................................................. 38
Chapter 9: Filtration Plants ..................................................................................................................... 39
9.1 General .......................................................................................................................................... 39
9.2 Types Generally Used in Punjab.................................................................................................... 39
9.3 Technical Specifications of UF Plants ............................................................................................ 39
9.4 Technical Specification of RO Plants ............................................................................................. 43
9.5 Other Package Plants .................................................................................................................... 47
9.5.1 ACTIVATED ALUMINA (AA) ABSORBENT FOR FLUORIDE REMOVAL ..................................... 47
9.5.2 REMOVAL OF IRON AND MANGANSES ................................................................................. 47
9.5.3 REMOVAL OF NITRATE AND NITRITE .................................................................................... 48
9.5.4 Arsenic Removal .................................................................................................................... 49
Chapter 10: Drinking Water Quality........................................................................................................ 50
Chapter 11: Water Metering ................................................................................................................... 52
SECTION II - SEWERAGE SYSTEM
Chapter 12: General Considerations ....................................................................................................... 57
Chapter 13: Basic Parameters ................................................................................................................. 58
13.1 Design Period ................................................................................................................................ 58
13.2 Design Flow Calculations............................................................................................................... 58
13.3 Peak Factor.................................................................................................................................... 59
13.4 Maximum Dry Weather Flow ........................................................................................................ 59
13.5 Industrial Flow Allowance: ............................................................................................................ 59
13.6 Storm Water Allowance ................................................................................................................ 59
13.7 Steps for Sewer Design ................................................................................................................. 59
13.8 Velocity at Design Flows ............................................................................................................... 60
13.9 Minimum Size of Sewer ................................................................................................................ 60
13.10 Spacing of Manholes ................................................................................................................. 60
13.11 Manholes for Sewers above Subsoil Water Level ..................................................................... 61
13.12 Earth Cover................................................................................................................................ 61
Chapter 14: Sewerage Network .............................................................................................................. 62
14.1 Classification of Sewers................................................................................................................. 62
2
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
14.2 Design Period ................................................................................................................................ 62
14.3 Sewer Pipes ................................................................................................................................... 63
14.4 Design of Sewerage Network ........................................................................................................ 63
14.5 Classification of RCC Pipes ............................................................................................................ 64
14.6 Basis of Acceptance ...................................................................................................................... 64
14.7 Technical Details of RCC Pipes ...................................................................................................... 64
14.8 Other Pipes for Sewerage System................................................................................................. 65
14.9 Sewer Pipes in Saline Soils ............................................................................................................ 65
Chapter 15: Manholes and Sewer Appurtenances .................................................................................. 66
15.1 General Considerations for Manholes: ......................................................................................... 66
15.2 Manhole Spacing and Alignment: ................................................................................................. 66
15.3 Manholes Covers: ......................................................................................................................... 66
15.4 Manhole under Sub Soil Water Level: .......................................................................................... 66
15.5 Benching for Manhole: ................................................................................................................. 66
15.6 Steps in Manhole: ......................................................................................................................... 66
Chapter 16: Laying of Sewers Pipes ........................................................................................................ 67
16.1 Sewer above Subsoil Water Level ................................................................................................. 67
16.2 Sewer Bedding above Subsoil Water Level ................................................................................... 67
16.3 Sewer Bedding under Subsoil Water Level ................................................................................... 67
16.4 Sewer Jointing ............................................................................................................................... 67
16.5 Sewer under Roads ....................................................................................................................... 67
Chapter 17: Protection against Gases ..................................................................................................... 68
17.1 Presence of Gases in Sewer Pipe .................................................................................................. 68
17.2 Ventilating Shafts .......................................................................................................................... 68
17.3 Inert Inner Lining ........................................................................................................................... 68
Chapter 18: Disposal Works .................................................................................................................... 69
18.1 Construction of Pumping Station .................................................................................................. 69
18.2 Land for Disposal Works ............................................................................................................... 69
18.3 Pumping Mains ............................................................................................................................. 69
18.4 Pumping Station Civil Works ......................................................................................................... 69
18.5 Screening Chamber ....................................................................................................................... 69
18.6 Sewage Pumps .............................................................................................................................. 70
18.7 Standby Generators ...................................................................................................................... 70
18.8 Butterfly Valves for the Pumping Station ..................................................................................... 70
18.9 Motor Control Unit ....................................................................................................................... 70
Chapter 19: Treatment of Wastewater in Urban & Rural Communities .................................................. 72
19.1 Mandatory requirements of Septic Tanks .................................................................................... 72
19.2 Treatment of Wastewater in Rural Communities ......................................................................... 72
19.3 Treatment of Wastewater in Towns and Medium Sized Cities .................................................... 73
3
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
19.4 Treatment of Wastewater in Big Cities ......................................................................................... 73
19.5 Car Wash Service Stations............................................................................................................. 73
19.6 Treatment of Wastewater from Hospital ..................................................................................... 74
19.7 Treatment of Wastewater from Industries ................................................................................... 74
SECTION III - DRAINAGE SYSTEM
Chapter 20: Design of Storm Water Drainage System ............................................................................. 76
20.1 Quantum of Storm Water for Small Areas .................................................................................... 76
20.2 Quantum of Storm Water for Larger Areas .................................................................................. 76
20.3 Runoff Coefficient / Impermeability Coefficient........................................................................... 76
20.4 Rainfall intensity............................................................................................................................ 78
20.5 Design of Outfall Works ................................................................................................................ 78
20.6 Open Surface Drains ..................................................................................................................... 78
Chapter 21: Segmental Pavement Design for Laying of Tuff Tiles/Pavers Street Pavement.................... 79
21.1 Flexible Pavement ......................................................................................................................... 79
21.1.1 Subgrade Assessment ........................................................................................................... 79
21.1.2 Design Life ............................................................................................................................. 79
21.1.3 Selection of Pavement Component ...................................................................................... 80
21.1.4 Laying Course ........................................................................................................................ 80
21.1.5 Pavers .................................................................................................................................... 80
21.2 Rigid Pavement (PCC/RCC) ............................................................................................................ 81
21.3 Storm Water/ Domestic Drainage ................................................................................................ 82
4
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
ACKNOWLEDGMENT
I would like to express my sincere gratitude to the team of professionals which was
wholeheartedly involved in revision of Design Criteria. It could not have been possible
without the utmost dedication and diligence of the team, which examined the existing
Design Criteria and brought it in line with needs of the day. Numerous consultative
meetings and exhaustive discussion sessions were carried out by the team of
professionals, which paved the path towards a refined, articulated and consistent piece of
work. I am grateful to Engr. Saleem Raza, Ex. Chief Engineer, PHED and Engr. Abdul
Qadeer, Ex. MD WASA Lahore / WSS Specialist for their devotion and much valuable
contributions stemming from their vast experiences of WASH sector.
I would like to thank Mr. Umar Farooq, Additional Secretary Technical HUD&PHED, Mr.
Raja Shahzad Asghar, Chief Engineer, PHED (North), Mr. Faisal Shoukat, Director Design,
PHED (North), Mr. Syed Soulat Raza, Director Design, PHED (South), Mr. Muhammad
Rafique Saroya, Superintending Engineer, PHED Faisalabad, Mr. Zahoor Ahmad Dogar,
Superintending Engineer, PHED Multan, Mr. Zeshan Bilal, Director WASA Lahore, for
putting in their best efforts, sharing valuable ideas and contributing generously towards
the finalization of this document.
5
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
ACRONYMS
AC Alternating Current
AV Air Valve
API American Petroleum Institute
ASTM American Society for Testing and Materials
AWWA American Water Works Association
AMR Automatic Meter Reading
BS British Standards
CFS Cubic Feet Per Second
CI Cast Iron
CAD Computer Aided Design
CBR California Bearing Ratio
DI Ductile Iron
DIN Deutsches Institut fur Normung
ESAL Equivalent Single Axle Load
EPANET Environmental Protection Agency Network Evaluation Tool
FPS Feet Per Second
FRP Fiber Reinforced Plastic
GSM Global System for Mobile Communication
GPRS General Packet Radio Service
GFH Granular Ferric Hydroxide
GI Galvanized Iron
GPCD Gallons Per Capita Per Day
HMI Human Machine Interface
HDPE High Density Polyethylene
HUD&PHED Housing Urban Development & Public Health Engineering
Department
ISO International Organization for Standardization
IMS Integrated Management System
JWWA Japan Water Works Association
LPD Litres Per Day
LPCD Litres Per Capita Per Day
LPH Liters Per Hour
MS Mild Steel
MSF Modified Sand Filter
MRS Market Rates System
NTU Nephelometric Turbidity Unit
National Sanitation Foundation
NSF
OHR Overhead Resevoir
PDSSP Punjab Devolved Social Services Programme
PPM Parts Per Million
PEQS Punjab Environmental Quality Standards
PSI Pounds Per Square Inch
PLC Programmable Logic Controller
PC Polycarbonate
PES Polyethersulfone
PS Pakistan Standards
PN Pressure Nominal
6
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
PE Polyethylene
PCC Plain Cement Concrete
ROSA Robotic Stereotactic Assistance
RCC Reinforced Cement Concrete
RO Reverse Osmosis
SS Stainless Steel
TDS Total Dissolved Solids
USA United States of America
UPVC Unplasticised Polyvinyl Chloride
UF Ultra Filtration
WASA Water and Sanitation Authority
WASH Water, Sanitation and Hygiene
WHO World Health Organization
WSS Water Supply and Sanitation
7
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
PREFACE
Access to safe water, sanitation and hygiene is the most basic human need for health and
well-being which is also envisaged in Goal 6 of Sustainable Development Goals (SDGs).
Better planning and use of best practices is essential to channelize water as a natural
resource to the human population in an efficient and economical manner. The Government
of Punjab aims at efficient service delivery in social sectors including water supply and
sanitation by adoption of best planning mechanisms and internationally accepted technical
and service delivery standards.
This document mainly consists of Technical and Service Delivery Standards for water
supply and wastewater management (collection and disposal). The provision of these
services to public is the responsibility of TMA’s / City District Governments. However,
execution of WASH projects is the responsibility of Punjab Public Health Engineering
Department which hands over the completed projects to the former for their operation
and service delivery.
As the last up-dation on the Water Supply and Sewerage Design Criteria was carried out
in the year 2007-8, this revision is meant to review the existing Technical and Service
Delivery Standards in the light of practical experiences of various relevant departments
and the inconsistencies observed by them over the time so as to make such improvements
which will enable the planning and execution of future WASH projects in a more efficacious
manner keeping in view the needs and requirements of modern times. To achieve the
aimed objective, Government of Punjab notified a committee comprising experienced
specialists of the WASH sector and experts from all the concerned departments to come
together for consultative discussions aiming at revision of existing Technical and Service
Delivery Standards as per needs of the day. Exhaustive discussions were held, practical
experiences of various concerned departments were shared and impediments faced by
them were pointed out by committee members for deliberation and subsequent necessary
improvements in standards accordingly.
Improvements made in the standards are based on vast experience of WASH sector
departments regarding planning, execution and operation of WSS projects and keen
insight regarding the sector, of WSS experts. It is hoped that these improvements will
cater for the impediments faced previously and will enable concerned departments to meet
with the needs of the day thence improving service delivery to public.
8
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
EXECUTIVE SUMMARY
This document comprises improved and updated version of existing Technical and Service
Delivery Standards in the water supply and sanitation sector. Improvements are made in
the light of shortcomings highlighted by various concerned departments which bog them
down while delivering services to the public. With the passage of time in this developing
world, the standards of service delivery are continuously on an upward trajectory which
necessitate incessant review and improvement in existing practices and standards, in order
to cope up with the needs of modern times. The impediments faced by various concerned
departments of the Government of Punjab are duly deliberated, considered and
incorporated in this document so as to bring improvements in service delivery regarding
water supply and sanitation.
Numerous consultative sessions were held with concerned departments which are
responsible for planning, execution and operation of water supply and sanitation schemes
in rural as well as urban areas of Punjab, which include Punjab Public Health Engineering
Department and Water and Sanitation Agencies throughout Punjab. Feedback from all
relevant stakeholders is incorporated while updating the existing Technical and Service
Delivery Standards.
This report comprises three major sections namely, Water Supply System, Sewerage
System and Drainage System. Each section delineates the technical and service delivery
standards regarding that particular domain which are further subdivided into different
chapters and sub-sections. Water Supply section comprises discussion on design
parameters, materials, laying of water supply networks, water treatment, filtration plants,
water quality and water metering. Similarly, design parameters of sewerage system,
materials, laying of sewerage network and related appurtenances, disposal of wastewater
and treatment of wastewater are discussed in Sewerage System section. Last section on
Drainage System discusses the design of storm water drainage system and design of street
pavements.
9
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Chapter 1
1.1 Background
While more than 70% of the earth’s surface is covered by oceans and seas, 97 percent of
that is salty ocean water and not suitable for drinking. Out of the remaining water, less
than 1 percent of the total available water is fit for human consumption. Water is the
essential component both for the existence of all creatures including human beings and
for a sustainable country’s economic growth.
“Water is not only for life … water is life.” This quote by the United Nations Secretary-
General reflects the critical importance of water as a need that connects all aspects of
human life. United Nations celebrated the International Decade of Action “Water for Life”
from 2005 to 2015. The socio-economic development activities of nations are related to
good quality and ample water availability. People’s well-being and their economic
development are profoundly linked to the availability and usability of water. Too little water
at a time when it is needed most can mean drought and food insecurity.
In extreme emergency conditions there may not be sufficient water available to meet basic
needs and in these cases supplying a minimum level of safe drinking water for survival is
of critical importance. According to WHO:
The history of water availability in Pakistan was good in the past. Pakistan which had
abundance of water resources at the time of independence is now facing the serious water
shortage. The country has crossed the limit of the minimum water security threshold
(1,000 m3 /capita/year) and has been entered into the list of water-scarce countries and
is moving towards an absolute scarcity level of 500 m3 /capita/year. Pakistan is on the
verge of the water crisis. Fresh water is a very limited and vulnerable resource.
In 1977 the position of sweet groundwater in Punjab was good. Major plain areas have
good & sweet quality ground water. The sweet water areas of Punjab were 58% with 74%
resident population. If we add the sweet / non-brackish areas of Pothohar these figures
were 68% (by area) and 82% (with resident population). Sweet water zones in plain areas
are reduced from 58% to 42% of the Province with resident population from 74% to 58%.
Overall position in the Punjab Province is as under:
Barani Area
1 11% 11% 9% 9%
(Pothohar)
Water Scarce
5 5% 5% 0% 0%
Area
11
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
100% 100% 100% 100%
Sweet water zones in plain areas are reduced to 42% of the Province with 58% resident
population.
Water and Sanitation coverage in Punjab is not up to the mark. Drinking Water Coverage
(Safely Managed Water services current level is 43.7% as compared to 100% to be
achieved by the year 2030.
The overall Sanitation Services Level in Punjab is 70.4%, which is not shared and
meeting the SDG’s requirements.
Fresh water is a very limited and vulnerable resource. In recent years, water issues have
been the focus of increasing international concern and debate. Competition among
agriculture, industry and cities for limited water supplies is already constraining
development efforts in many countries including Pakistan. In addition to a decrease in
freshwater resources & deteriorating water quality, advancements in technology also urge
the revision & updating of Design Criteria.
12
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Chapter 2
Basic Parameters
2.1 Design Period
Treatment Works
While calculating the water requirements of a community many factors are required to be
considered. These include water availability, population, socio-economic conditions, living
standards, collection & disposal of wastewater and water metering. With rapidly growing
population, Pakistan is heading towards a situation of water shortage and by corollary, a
threat of food insecurity. With the country’s current water crisis it is not possible to
continue the implementation of 80GPCD (363 LPCD) as per WASA Lahore Design Criteria,
or 50 GPCD (227 LPCD) as per PHED Criteria 1998 or 50-85 GPCD (227-386 LPCD) as
13
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
PDSSP 2007. Therefore, it is recommended that in each locality, while carrying out Water
Supply Design, the following factors may be considered:
Availability of Sweet Water Resources in the Service Area.
Distance between Source of Water & Service Area, if sweet water not available in
the area.
CAPEX & OPEX of Water Supply System.
Affordability of people of the service area.
Per Person Water Supply may be decided to keep in view the above-mentioned factors.
However, as a general guideline the following water supply provisions are proposed:
All water demands, other than domestic are known as non-domestic demands. This
includes water consumed by Industries, educational institutions, hospitals, markets,
dispensaries, schools, colleges, universities and commercial centers, etc.
i. Industrial Water Demand shall be calculated separately as per actual requirements.
ii. For institutions such as hospitals, hostels, schools, etc. an allowance of 10 gallons
per boarder (45 LPCD) for big cities and tourist resorts shall be made.
iii. A provision of 3 gallons per day (13.5 LPCD) shall be made for day scholars and
floaters.
2.4 Fluctuation in Water Demand
The following standards are to be followed for computation of the short term variations:
Maximum Day Demand is to be taken as 1.5 times the Average Day Demand.
14
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Peak Hour Demand to be taken as 1.5 times the Maximum Day Demand. or
Peak Hour Demand is to be taken as 2.25 times the Average Day Demand.
2.5 Terminal Pressure (Minimum)
Minimum earth cover over pipe shall be 3 feet (0.90 Meters). However, in the case of
water supply line laid under road crossings, sand will be filled to provide cover instead of
earth.
2.10 Valves
Sluice Valves: At main control points for purpose of repair & maintenance.
Butterfly Valves: At Water Works.
Air Valves (Air Release/ Air Suction): At the summits and after 2000 meter
intervals in straight reaches to facilitate the escape of trapped air as per design and
topography. Double Acting AV shall be provided as per design.
15
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
2.11 Overhead Reservoirs (OHRs)
Overhead storage reservoirs should be preferably provided in all urban and rural water
supply schemes at strategic locations of the project, except in cases of such hilly / semi-
hilly areas, where appropriately located ground storage reservoirs can be provided.
Capacity of OHRs: The capacity of OHR shall be provided one tenth (1/10th) average day
demand.
16
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Chapter 3
Pumping of Water
For sweet water zones, groundwater is the source of choice. For brackish water zones, in
case a canal or distributary available at a reasonable distance, skimming wells (shallow
Tubewells) will be installed along the bank and pumped to the community through a rising
main after appropriate treatment or disinfection.
Entrance Velocity: The Entrance Velocity 0.05 ft / sec in the strainer is recommended
against the allowable value of 0.1 ft /sec to 0.2 ft / sec to check the entry of fine sand into
the screen.
Opening Area of the Strainer: Opening area normally ranges from 10% to 12%, or as per
bore logging.
Slot Size: Slot size 1”X 1/30” is recommended for the screen.
House Pipe: The diameter of House Pipe will be based on the design discharge of tube
well. Material shall be MS/Fiber Glass.
Sanitary Seal: To control and check the surface and ground contamination at shallow
depths sanitary seal consisting 1:2:4 plain cement concrete is recommended.
Shrouding Material: The shrouding material will be of pea gravels having size 1/8” to 3/8”.
Shrouding Pipes: Shrouding shall be done through 2-3” diameter P.V.C. or equivalent
Delivery Pipes: Length of delivery pipe in pump house should be as per requirements to
have proper installation of measuring instruments like portable Ultrasonic flow meter for
energy audit purpose. Pressure gauge should be installed on the delivery pipe for pressure
head measurements.
Centralizers in the lowering pipe shall be provided to maintain uniformity of the packing
material along strainer in the borehole.
17
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
3.2 Skimming Wells
The daily operating time for tube well pumping machinery should not exceed 8 hours.
Max.Capcity:0.5 cusec.
In the areas where the water table is close to the ground surface and there is a need to
minimize the draw down due to the non-availability of the adequate thickness of the
saturated pervious sediments / aquifer material or the aquifer material is not available,
infiltration galleries are installed in the channel beds or along the periphery of takes to
exploit groundwater. An infiltration gallery consists of one or more horizontality laid
screens which are (preferably) placed perpendicularly to the source of water (river nallah
periphery of the lake, etc.) or the groundwater flow direction.
Because the screens in the galleries are placed in open excavations, the usual practical
depth limitation is about 25 feet. (7.6m), though in general the screens are placed even
at depth of about 5-feet. Water entering the screen is usually collected in a central sump
(or an adjacent percolation well) that can also serve as a storage chamber and into which
the pump intake is placed. The functioning of the infiltration gallery is more or less similar
to the tile drain - normally installed in the water logged-areas to remove excess water
from the sediments. Galleries can be installed in the pervious beds of the perennial
streams, in the beds of the ephemeral streams below the water table or along the
periphery of the lake beds by excavating trenches. The flow to the gallery or its yields will
depend upon the hydraulic head, the flow to the gallery or its yield will depend upon the
hydraulic head, the permeability of the filter material and the width of the gallery. In
general, the discharge of the galleries is much less as compared to the tube wells (with
the same length of screen) as forced pumping or flow is not in action – rather it is free
flow under a particular set of field conditions. Important design criteria and the
precautions during the construction include.
Ensuring the filter pack around the screen is correctly sized.
Screen slot is correctly sized to retain 100% of the filter pack.
18
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
The entrance, velocity through the screen slot opening should be 0.01 feet /
second (0.03 m/sec) or less (as the suction is not going to be in action as in
case of a tubewell).
The axial velocity within the screen should be 3-feet / second (0.9 m/sec) or
even less to reduce the head loss and
Ensuring adequate length of screen (s) to provide the desired quantity of water
in accordance with the water demand.
Infiltration galleries may have to be installed under two types of field condition i.e
i. In the impermeable bed material – in this case artificial gravel pack may have
to be provided to enhance the groundwater flow into the screen, and
ii. In the permeable bed material, where the channel deposits are sand, gravels,
boulders, etc.
Length of screen for the gallery under different conditions is normally be estimated,
keeping in view the desired discharge and the hydraulic parameters of the sediments /
gravel placed around the screen and placement of the screen with respect to the
excavation, as below
Sometimes the infiltration galleries are constructed in the river / lake beds, where the
underlying strata are impermeable as shown in Fig. below.
Length of screen (L) for the gallery placed in “impermeable sediments” may be
determined as:
L = Q*d/K*H*B, where
19
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
K = Hydraulic conductivity (permeability) of gravel shroud used (say in feet /
second)
d = Distance between channel bed and the center of the screen (feet)
Increase with respect to the increase in the design discharge and the distance
between the channel bed and the center of the screen “d” and,
Decrease with increase in the width of the trench, permeable of the fill material
(as the sediments or the filter material with higher permeability will transmit more
water) and the hydraulic head (which will increase the seepage or flow to the
screen).
The field limitations for each of the above parameters have to be given due
consideration as we cannot enormously change these factors. Some allowance in the
length of the screen, estimated as above should be provided (as per field requirement
and financial consideration) to account for the future choking in the screen.
Infiltration Galleries are also constructed in river / lake beds where the underlying strata
are permeable or river bed material is deep enough as shown in Figure below:
20
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
r = Radius of the screen (in feet)
𝜋 = 3.142
Other factors already defined above:
Increase with the increase in desired discharge and the distance (d)
between the stream bed and the centre of the screen, and
Decrease with increase in screen diameter, permeability and head.
21
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Chapter 4
The water supply system to be proposed for any area should be based upon the type and
location of source. Preferably the source should be as near as to the city or town but this
all depends upon the availability of water in qualitative and quantitative terms.
The primary network should be based upon meeting the peak hour demand rate equal to
2.25 times the average day demand rate. On the basis, the primary network water mains
and ground storage reservoirs with booster pumps may be needed in case the source is
away from the city. To establish a primary network sizes for final design, the computer
aided model should be used to arrive at a satisfactory hydraulically balanced system. In
case, low peak factor is used, it will result in reduction of sizes of primary network water
mains, and in the future local storage and booster pumps would be needed at various
locations for satisfying short period demands in excess of the design rate. No house
connection should be provided from the Primary Mains.
Sizes of Secondary Network will be as per design. No house connection will be provided
from secondary network.
Tertiary network sizes are 6 inches and below (150 mm and below) as mentioned above.
Preferably house connections should be given from this network. Maximum pressure in
tertiary network should be 15 meters.
The loss of head in the pipelines shall be calculated by using Hazen & William formula.
V=K.C.D0.63I0.54
Where
V=Velocity of flow (m/sec)
D=Hydraulic Radius (m)
I =Hydraulic gradient (i.e unit head loss in pipe)
22
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
C=Friction factor
K=0.849
Or
V=1.318xCR0.63S0.54
Coefficient of roughness (C) values to cover losses in fittings and valves shall be as
follows:
uPVC / HDPE Pipe 130
DI / MS Pipe 110
S =Hydraulic gradient (i.e. unit head loss in pipe)
R= Hydraulic Radius
Or
Darcy’s Formula
The pressure loss (or major loss) in a pipe, tube or duct can be calculated with the
Darcy-Weisbach equation
× ×
Δp major loss = 𝜆 𝜌𝑓 × =𝜆 (1)
×
where
Δp major_loss = major (friction) pressure loss in fluid flow (Pa (N/m2), psf (lb/ft2))
The major losses in the water supply network will be worked out on the basis of Hazen
William Formula or with the help of Darcy-Wiesbach equation. The 15% of losses in Pipes
will be added for Bends, Tees, Valves and other fittings.
The purpose of the program is to calculate water flows and velocities in pipes and
pressures throughout a water distribution network given the layout of the pipes and other
elements of the network. The various elements, in addition to pipes and nodes (which are
junctions of two or more pipes) are:
i. Source Nodes (where water enters the system) with or without pumps
ii. Booster Pumps
iii. Check Valves
iv. Pressure Reducing Valves
v. Pressure Sustaining Valves
24
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Chapter 5
Pipe Materials
The first known underground water mains were constructed by the ancient Minoan
civilization in approximately 2200 and 1400 BC. The Romans invented concrete and
constructed famous aqueducts using gravity to transport water from the outer reaches of
the city. The invention of Cast Iron Pipe in 15th century was made which brought the first
real revolution in the history of water pipes. The invention of the Ductile Cast Iron Pipe
brought the second revolution in the history of water pipes. The invention of Polyethylene
Pipes knocked out Asbestos Cement Pipes and Plastic Pipes. Pipes preferably be selected
which has a life expectancy of more than a hundred (100) year.
Cast iron pipes and fittings shall comply with BS 78 for spigot and socket vertically cast
pipes, BS 1211 for spigot and socket spun iron pipes and BS 2035 for flanged pipes.
Ductile Iron Pipes or Ductile Cast Iron pipes and fittings shall comply with Pipes: ISO
2531 or EN-545 or AWWA C151/A21.51; AWWA C115/A21.15
Mild Steel Pipes shall comply with API Standard 5L / ASTM with Inner Cement
Mortar/Epoxy Lining with wall thickness as per design. The minimum wall thickness is
6.25mm. The external pipe should have a relevant coating. When pipe is used
underground, anode and cathode protection shall also be used. At welded joints of pipes,
shrink sleeves be provided.
High Density Polyethylene Pipes (HDPE) should be PE-100 and should conform to ISO:
4427 or DIN:8074/8075 or PN as per requirement.
25
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Jointing Method: Butt Fusion and Electro-Fusion
Tests to be performed for pipes shall be Heat Reversion, Short Term Hydrostatic Pressure
Test and Tensile Strength and for P.E. compounds, tests to be performed shall be
Elongation at break, Melt flow rate and Density test. While designing, temperature
correction should be applied as per the manufacturer’s technical manual.
The galvanized iron pipes shall strictly conform to BS 1387-1967 "medium /heavy quality
(flanged/socketed) as per design" Specifications for "Steel Tubes and Tubulars suitable for
screwing to BS 21 pipe threads". All screwed pipes and sockets shall be of wrought iron
conforming to BS 1740. A complete and uniform adherent coating of zinc white will be
provided for galvanized iron pipes and fittings. CI fitting should not be used with GI Pipes.
27
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
High Density ISO: 4427 / DIN:8074/8075,
Polyethylene PE-100
Pipes (HDPE) PN as per requirement (Force Main
Min. PN10 & Distribution System Min.
PN8)
& conforming to all essential tests.
Part-B: Pipes above Ground, open to Sky, River/ Canal / Drains overhead crossing
Preferable Joints are flanged Joints. However, other types of joints may also be used with pipe
support.
28
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Galvanized Iron The galvanized iron pipes shall strictly
conform to BS 1387-1967 "medium
quality" Specifications for "Steel Tubes
and Tubulars suitable for screwing to BS
21 pipe threads". All screwed pipes and
sockets shall be of wrought iron have BS
1740. A complete and uniform adherent
coating of zinc white will be provided for
galvanized iron pipes and fittings.
29
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Chapter 6
6.2 Valves
1. Cast Iron Gate Cast Iron Gate Valves conforming to BS 5150, flanged
Valves ends as per BS 4504. Deals with notional diameters DN
10 to 1000 in notional pressure ratings PN 10,16 & 25.
4 Brass & Cast Iron Valves to be class 125, made of brass with special seal
Globe Valves for PPR hot water connection, inlet: soldered socket,
outlet: union with drain.
30
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Up to and including 50mm size shall be of bronze globe
type with inside screw, stuffing box and screw end
connections.
65mm size and above shall be of cast iron ductile iron
body for PN 16 and PN 25 respectively, with outside
screw and yoker type. Flanged end connections to BS
4504 and EN 1092.
Globe valves shall have re-grinding renewable disc and
seat ring, bronze trimmed non-rising stem.
6. Unit Body Ball Brass chromium plated ball valves, reinforced teflon seat,
Valve and seals, with handle.
31
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
6.3 Check Valves
1. Check Valves Check valve shall comply with the requirements of BSS
(Back Flow 5153: 1974 or BS EN 16767-2020 or equivalent. The
Preventor) valve shall be of swing type and shall be of quick acting
single door type.
Swing check valve conforming to BS 5154 series ’B’
bronze with removable hinge pin and screwed cap,
suitable for operation in either horizontal or vertical
position. Threaded (BS 21) connection for 50mm and
smaller. Flanged (PN 16) connection for valves above
50mm. for valves above 16 bar working pressure. It shall
be of class 300 cast carbon steel swing check valve with
PN 25 flanges.
Back flow Preventor bronze check valve class 125
suitable for vertical or horizontal installation. Seat, Cone
and cone pressure spring of bronze including all
accessories required for connection with piping.
32
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Chapter 7
Most operation in the installation of water distribution mains are the same regardless of
the materials of which the pipe fittings are made. Standards have been issued by the
American Water Works Association (AWWA) and other organizations for the laying of
different types of pipe, and there is no need to discuss them in detail herein. The following
paragraphs are limited to mention of the installation factors which may significantly affect
the performance and life of the water mains.
All pipes and fittings should be inspected for damage when they are being unloaded at
the installation site. Pipes and fittings should not be dropped from the truck. If a derrick
and cable with hooks are used in unloading, the hook should be rubber covered. If a fork
lift is used, care is needed to avoid damaging the exterior coating, or the pipe itself. In
moving pipes and fittings, they should never be pushed by a bulldozer blade or other
mechanical equipment, but should be either rolled by hand or moved by hoist.
7.2 Trenching
Water distribution pipes may be installed with a trench depth that provides cover of 3 feet
over top of the pipe, depending on the pipe size, except at places where it is necessary to
go deeper to get under obstructions. Secondary network pipes (3 to 10-inch size) should
have a cover of 2.5 to 3.5 feet, and primary network pipes (16-inch size or larger) a cover
of 5 feet. The trench width should be kept as narrow as feasible but should be enough to
permit proper installation of the pipe, with room for the workmen to make the joints and
tamp the backfill around the pipe.
All pipes and fittings must be adequately supported by the trench bottom. A continuous
uniform bedding is needed. Stones found in the trench should be removed for a depth of
at least 6 inches below the bottom without special bedding material if the soil is suitable
and the bottom has been leveled properly. For pipe laid in poor soil, wet trench or rock,
special bedding material must be provided for bells or coupling and for making up the
joints.
7.3 Bedding
Preparation and proper compaction of the pipe bedding is very important. The pipe's ability
to support the overlying earth loads is influenced by the degree of support that the pipe
33
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
has under it and at its sides. For FLEXIBLE pipes, the pipe chiefly relies on the support
given by the bedding.
7.4 Joints
The types of joints will depend upon the kind of pipe used, as discussed above under the
heading “Water Main Material”. Jointing procedures should follow the recommendations
of the pipes and fittings.
7.5 Backfilling
Usual practice in backfilling water mains involves partial backfill before tests and completed
backfill after tests. The partial backfill leaves joints exposed or covered only by a shallow
layer of earth. The backfill material should be good soil that does not contain any rocks,
bricks, or hard lumps of clay. For some pipe materials, special precautions are needed
during backfill operations, as recommended by the pipe manufacturer.
The installation specifications should call for pressure tasting of all water mains after they
are installed. The length for one time testing shall be 1000 feet. The test pressure shall
be 1.5 times of the design pressure. The hydrostatic test should be carried out section by
section as completed, usually after the trench has been partially backfilled.
Internal pressure including water hammer creates transverse stress or hoop tension.
Bends / Tees and closures at dead ends or gates produce unbalanced pressure and
longitudinal stress. When pipes are not permitted to change length, variations in
temperature like-wise create longitudinal stress. External loads and foundation reactions
(manners of support) including the weight of the full conduit, and atmospheric pressure
produce flexural stress. Bends and closures at dead ends produce unbalanced pressure
and longitudinal stress in the pipeline. Further when pipes are not permitted to change
length due to variations in temperature, pipes also expand and create longitudinal stress.
Anchorages are necessary to resist the tendency of the pipes to pull apart at bends and
restrain or direct the expansion and contraction of rigidly joined pipes under the influence
of temperature changes.
34
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Chapter 8
A well-designed and properly maintained slow sand filter (SSF) effectively removes
turbidity and pathogenic organisms through various biological, physical and chemical
processes in a single treatment step. The top several inches of the sand has to be removed
regularly--usually by hand--due to the mass of growing material that collects in the filter.
Sand removed is usually washed and returned to the filter. These filters are still in use in
some small plants in rural areas. Slow sand filters are used in water purification for treating
raw water to produce a potable product.
A well-designed and properly maintained Medium Sand Filter or Modified Sand Filters
(MSF) are proposed for effective removal of turbidity and pathogenic organisms through
various biological, physical and chemical processes with the concept to increase the pace
of filtration with no or minimum use of energy. The top several inches of the sand has to
be removed regularly--usually by hand--due to the mass of growing material that collects
35
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
in the filter. Sand removed is usually washed and returned to the filter. Coagulation &
Flocculation processes are included in the process to put less load on sand filters and to
increase the filtration rate as compared to Slow Sand Filters.
The rapid sand filter or rapid gravity filter is a type of filter used in water purification and
is commonly used in municipal drinking water facilities as part of a multiple-stage
treatment system. High filter rate (4000 – 12000 liters per hour per square meter of
surface). Rapid sand filters are typically designed as part of multi-stage treatment systems
used by large municipalities. These systems are complex and expensive to operate and
maintain, and therefore less suitable for small communities and developing nations. The
filtration system requires a relatively small land area in proportion to the population served,
and the design is less sensitive to changes in raw water quality, e.g. turbidity, than slow
sand filters.
ii. Minimum depth of filter Should not be less than 8.5 feet.
iii. Depth of water on the sand Should not be less than 3 feet.
36
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Range Depth
1 – ½ to ¾ inches 3 to 5 inches
¾ to ½ inches 3 to 5 inches
½ to 3”/16 2 to 3 inches
37
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Component Typical Standard
Coagulants Alum & Lime
Disinfection Chlorine
However, Gas chlorine may be used as disinfection in the treatment plants away from the
urbanized areas. In case of town/cities away from the treatment plants and where chlorine
gas cylinders are available, gas chlorination is advisable. For monitoring the concentration
of residual chlorine in the field, the “comparators” or “chlorine kits” may be used.
38
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Chapter 9
Filtration Plants
9.1 General
Filtration Plants are used to remove physical, chemical and biological impurities from
raw/tap water and make it fit for drinking. The application & use of Filtration Plants should
be avoided as far as possible. These may be installed in unavoidable circumstances.
Capacity of Filtration Plants will be designed on the basis of 3 LPCD.
Although Filtration Plants are of many types. The following two types are generally used
in Punjab:
i. Ultra Filtration (UF) Plants: UF Plants will be provided in old water supply
network, where contamination is unavoidable.
ii. Reverse Osmosis (RO) Plants: RO will be provided only in the areas where
Ground Water is brackish and no nearby Surface Water or Ground Water source
is available within economic range.
Sr.
Description Specification
No.
Ultrafiltration Plants 400 LPH/200LPH
1 FEED PUMP (2 No. both for Backwash and one for Normal Operation)
Pump Manufacturer Western Europe, Japan, USA
Pump Type Centrifugal, Multistage
Impeller Material Noryl, Chrome Nickle Steel
Housing Material Stainless Steel
Discharge 4.0 m3/hr - 5.0 m3/hr 2.0 m3/hr - 3.0 m3/hr
Head 40 meter
Pump Efficiency > 60%
Motor Manufacturer Western Europe, Japan, USA
Motor Power Rating (Single Phase), kW ~ 1.5 kW ~0.75 kW
Motor Voltage Rating 1x230V
IP44, IP55 & or IP68 (Depending upon Local
Motor NEMA Insulation Class
Condition)
Motor Temperature Class F
2 PRE-FILTRATION
39
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
2.1 SILICA SAND FILTER (For removal of Suspended Solids from Raw Water)
Filter Vessel FRP Tank (NSF Certified)
Manufactures Type Designation/Origin Top opening, Cylindrical Vessel
2.2 ACTIVATED CARBON FILTER (For Removal of Odour, Colour & Taste from Raw Water)
Filter Vessel FRP Tank (NSF Certified)
Manufactures Type Designation/Origin Top opening, Cylindrical Vessel
40
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Material Fiber Reinforced Plastic (FRP)
Size 24" dia. X 72" Height 16” dia x 52” Height
Thickness 3 - 5 mm
Filter Media
41
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Surface Area of each Membrane Module 6-9 m2
4 CONTROL PANEL (Fully automatic through PLC) for filtration, flushing and Backwashing
PLC and HMI Make Western Europe, Japan, USA
Origin China
Type Rotameter
Quantity 1 no.
Type Analogue
Make/Orign China
Origin China
42
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Flow Range 0 - 4 m3/hr
43
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Motor Temperature Class F
2.2 SILICA SAND FILTER (For removal of Suspended Solids from Raw Water)
Filter Vessel FRP Tank (NSF Certified)
Manufactures Type Designation/Origin Top opening, Cylindrical Vessel
Manufacturer NSF certified Company
Material Fiber Reinforced Plastic (FRP)
Size 30" dia. X 72" Height
Thickness 3 - 5 mm
Filter Media
Silica sand (local - graded) over gravel bed, Acid
Material
Washed Silica Sand
Coefficient of Uniformity <1.4
Size of Media 0.5 - 0.8 mm
Particle removal range Below 100 micron
2.3 ACTIVATED CARBON FILTER (For Removal of Odour, Colour & Taste from Raw Water)
Filter Vessel FRP Tank (NSF Certified)
Manufactures Type Designation/Origin Top opening, Cylindrical Vessel
Manufacturer NSF certified Company
Material Fiber Reinforced Plastic (FRP)
30" dia. X 72" 24" dia. X 72" 16" dia. X 52"
Size
Height Height Height
Thickness 3 - 5 mm
Filter Media
Manufacturer / Origin Asian / European
Material Coconut Shell based Activated Carbon
Effective Size of Media 0.7 to 0.9 mm
Coefficient of Uniformity 1.5 to 1.7
Surface Area 800 - 1050 m2/mg
Bulk Density 0.64 g/cm3
Hardness No. 98 min.
Ash Contents Max. 5%
2.4 ARSENIC REMOVAL FILTER (For Removal of Arsenic from Raw Water upto BDL)
Filter Vessel FRP Tank (NSF Certified)
Manufactures Type Designation/Origin Top opening, Cylindrical Vessel
44
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
30" dia. X 72" 24" dia. X 72" 16" dia. X 52"
Size
Height Height Height
Thickness 3 - 5 mm
Filter Media
Manufacturer/Origin Western Europe, Japan, USA, (NSF Certified)
Media Type Granular Ferric Hydroxide
Active Substance Fe2(OH)3 Minimum 70%
Water Content 10-15%
Grain Size 0.5 - 4 mm
Density of Grains 0.64-0.74 kg/dm3
Specific Surface 270-300m2/gm
Cleaning Process Automatic through PLC Flow Controller
2.5 CARTRIGE FILTER
Quantity 2 set
Flow 2.0 m3/hr - 4.0 m3/hr
Origin NSF certified
Cartridge length 20" jumbo
Housing Material Polypropylene
Porosity 3 micron
2.6 ANTISCALANT DOSING PUMP
Quantity 1
Flow 5L, 7 bar
Origin Western Europe, Japan, USA
3 REVERSE OSMOSIS MEMBRANE (NSF Certified Ultra Low Energy Consumption Membrane)
i. RO design will be based on feed water with total dissolved solids (TDS) for brackish Water with a
maximum of 5000 ppm.
ii. The RO plant shall be designed with minimum of 50% recovery of permeate up to maximum
5000 ppm TDS in Raw Water.
iii. The following membrane manufacture software projections are acceptable.
Simulation softwares are listed below:
a. ROSA/Equivalent
b. IMS Design/Equivalent
No. of RO Membrane 4-8 pcs ultra low pressure 440m2 surface area
45
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Array Installation Vertical / Horizontal 4x(1)
4 CONTROL PANEL (Fully automatic through PLC) for filtration, flushing and Backwashing
PLC Make Western Europe, Japan, USA
PLC Origin Western Europe, Japan, USA
Cable Size 1.0 mm2 ,(1 Core)
Panel (Enclosure Box) Local (Skid Mounted)
5 Miscellaneous
5.1 Pressure gauge
Quantity 2 Nos. (1+1)
Origin China
Manufactures Type Designation Bourden Tube Type - China
Type Analogue
Make/Origin China
Origin China
46
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
5.6 Multipore Valve 3 No., China
Stainless Steel Skid, SS304, Size as per
5.7 1 Set China / Local
proposed Design
6 UV Device
Origin China
Iron and manganese are not dangerous for human consumption, but are influencing the taste of the
potable water, giving it a bitter and metallic taste. Furthermore Iron and Manganese can be oxidized by
chlorine, chlorine dioxide or air in order to form Iron hydroxide and to be filtered off over Gravel. This
last process could be easier when combined with pre-filtration processes.
47
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Oxidants Requirement Continuous process
Chlorine 1 mg /l per mg/l of Fe
0.2 mg /l per mg/l of Fe
KMnO4
2 mg /l per mg/l of Mn
Dosing Equipment for KMnO4 or Cl2
Filtration (Pressure Filters)
If raw water contains nitrate and the total dissolved solids are less than 1000 mg/liter, nitrate shall
be removed through ion-exchange process. For this purpose strong base anionic resins shall be
used, with the following minimum design parameters. Nitrite will also be taken out after oxidation
with Chlorine.
48
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
pH Range 0 – 14
Resin Capacity 0,6 -0.8 eq/l
Turbidity < 5 NTU
TDS < 1000 mg/l
Treated water Quality Increased Chloride level
Post Treatment None
Process Control Digital auto timeer control
The Design criteria for Granular Ferric Hydroxide (GHF) - absorbent iron based for arsenic
removal is as follows:
49
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Chapter 10
The water when it falls as rainfall is H2O in its pure form and free of any salts or
contaminants. However, as it moves on the Earth’s surface it dissolves other elements
both useful and harmful. Therefore, the available drinking water may also contain physical,
chemical bacteriological or radiological contaminants with harmful effects on human
health.
Quality of drinking water plays a pivotal role in the selection, design and implementation
of water supply schemes both for urban and rural areas. In order to determine if the water
is fit for drinking purposes testing, not only, for colour, taste, odour, quantity of total
dissolved solids but also tests for bacterial contamination and pollution are to be carried
out.
The concentration of “total dissolved solids” (TDS) in parts per million (PPM)” is considered
an important factor for determination if the water is fit for drinking. Under WHO guidelines
water with dissolved solids less than 500 PPM is considered safe for human consumption.
However, these limits are relaxed to include up to 1000 PPM and even 1500 PPM
depending upon the local field conditions, the type of solutes (cations and anions) in the
water and the resistance developed by the local inhabitants.
Safe Water or safely managed drinking water: Drinking water from an improved
water source which is located on premises, available when needed and free of fecal and
priority contamination.
Minimum Water Quality Standards are given as per the Schedule given below:
Sr.# Parameters As per WHO As per PEQS Recommended
Value
Physical
50
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
4 Turbidity None <5NTU <5NTU
Biological
Chemical
51
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Chapter 11
Water Metering
For ensuring the sustainability of water supply schemes and for avoiding water wastage,
100% metering will be done. The cost of water meters shall be recovered from the users
in easy installments. Two types of water meters will be used in the system:
i. Mechanical Meters
ii. Meters with Non Moving Parts
Schedule 1: Mechanical Meters
1. Technology:
3. General Features
(a) Visual Meter Reading
(b) Tamper proof.
(c) Provided with non-return valve
(d) Un- affected by grit and particulates
(e) Provided with wire and lead seal
(f) Not effected by Magnetic field
52
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
4. Conforming to:
53
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
I. Technology:
Static Smart Water Meters
Ultrasonic technology,
Electromagnetic,
Fluidic oscillation.
3. General Features
(a) No Moving Parts
(b) Visual Meter Reading
(c) Tamper proof.
(d) Provided with non-return valve
(e) Un- affected by grit and particulates
(f) Provided with wire and lead seal
(g) No Reverse Flow Measurements
(h) As per class 2 of OIML/ ISO specifications (Current)
4. Conforming to:
54
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Japan Water Works Association (JWWA)
6. Equipment Used for Testing (Quality Assurance)
Equipment used for testing shall comply with clause 4.6 of BS 5750: Part 3:
1987(5)
55
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Sewerage System
56
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Chapter 12
General Considerations
In light of the resolution of the United Nations General Assembly provision of Sanitation
facilities is also among the basic human right like water. This is re-confirmed under
Sustainable Development Goals.
Wastewater is the water that has been used in a home, in a business, or as part of an
industrial process. It is the water that has been contaminated by human use. Wastewater
is also defined as "used water from any combination of domestic, industrial, commercial
or agricultural activities, surface runoff or storm water, and any sewer inflow or sewer
infiltration".
As per Multiple Indicator Cluster Survey 2017-18 (MICS 2017-18) the coverage of basic
Sanitation Facilities is 70.4% against the target level of 100% to be achieved by 2030.
Open Defecation still exists in 13% areas of Punjab, which is required to be zero.
Wastewater Treatment is also one of the neglected sectors in Punjab. Only 5% of Domestic
Wastewater is being treated. Rest is disposed of in water bodies without any treatment.
The technical standards for sewerage & Drainage systems include the prescribed
directions, requirements, explanations, terms and provisions pertaining to the various
features of the work to be done, or manner and method of performance.
57
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Chapter 13
Basic Parameters
The technical standards for sewerage system include the prescribed directions,
requirements, explanations, terms and provisions pertaining to the various features of the
work to be done, or manner and method of performance.
58
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Commercial Flow: As per Actual
Infiltration Rate: Sewers above sub-soil water level. 350 gpd/inches/dia/miles.
Sewers below sub-soil water level. 700 gpd/inches/dia/miles.
13.3 Peak Factor
Peak flows are the cumulative results of combinations of factors such as daily and
seasonal flow variations of flow components characteristic responses of inflow and base
flows to the storm events. Peak flows can be determined by multiplying the average dry
weather flow (DWF) by the peaking factor (PF).
The maximum design flow is determined using Average Daily Flow (ADF) and the
Harmon Peaking Factor (HPF):
14
𝑀 = 1+
4 + √𝑃
Where,
M = the Harmon Peaking Factor
P = population (in thousands)
The maximum design flow shall be the average daily flow times the peaking factor M.
13.4 Maximum Dry Weather Flow
Maximum Dry Weather Flow: Average Daily Flow x Peak Factor
13.5 Industrial Flow Allowance:
Addition of Industrial Flow: Add allowance for industrial wastewater as per actual
assessment of the treated industrial wastewater
according to National Environmental Quality Standards
(NEQS).
13.6 Storm Water Allowance
Storm Water Allowance Rural Areas: 33% of Peak Flows
Storm Water Allowance for Urban Areas of North Punjab: 50% of Peak Flows
Storm Water Allowance for Urban Areas of South Punjab: 33% of Peak Flows
13.7 Steps for Sewer Design
(a) Calculate the ultimate tributary population of the area served by the sewer, using
the anticipated ultimate population.
(b) Multiply the population obtained by the per capita sewage volume (GPCD) to obtain
the average daily flow, and convert to an average daily rate in cubic feet per second
(Cfs).
(c) Select peak factor from the Harmon Formula.
59
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
(d) Multiply average daily rate by the peak factor to obtain maximum flow rate.
(e) Calculate the allowance for industrial sewage as per actual assessment of treated
industrial effluent according to NEQS.
(f) Calculate infiltration allowance after tentatively determining the sewer size.
(g) Calculate sub-total of flow.
(h) Add storm water allowance.
The total design flow for the sewer (estimated peak design flow) is the sum of items from
(a) to (h).
13.8 Velocity at Design Flows
It is proposed that minimum gradient to be adopted are such that to maintain a self-
cleansing velocity of 2.5 ft/sec at design peak flow in new sanitary sewer under the
ultimate scenario subject to minimum velocity of 2 ft/sec for peak flows under critical
conditions. Hence, while designing the sewers, it is proposed to maintain a desirable
velocity under flowing full condition is to be adopted as 2.5 ft. /sec.
9–12 in 50 feet
15-18 in 100 feet
21-24 in 150 feet
27-42 in 250 feet
48 – 60 in dia 300 feet
Above 60 in dia 400 feet
60
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
b) Manhole should invariably be provided at every change of alignment, change in size
of sewer or at junctions.
From 15 ft to 20 ft,
45–54 8–20 7½’ dia Depth, 18 to 13-½
inches
60 8–20 8’ dia
66 8–20 8’ dia
72 8–20 9’ dia
e) For manholes under sub soil water, core-wall and floor will be designed as
per actual depth of water encountered.
f) For depth more than 10 ft, RCC slab will be placed at 7 ft from invert and
then 4 ft dia masonry will be constructed up to surface.
61
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Chapter 14
Sewerage Network
Terms which are used to describe sanitary sewers include the following; laterals,
secondary sewers, primary collectors, interceptors and force mains. These are explained
as follows;
a) Laterals- These are sewers that discharge into a secondary or other sewer and
have no other sanitary sewer as a tributary; they are usually of the smallest size
permitted in the wastewater collection system or 9-inch diameter.
b) Secondary Sewers- These are also known as branch or sub-main sewers, into
which two or more laterals discharge, and which carry the wastewater flows to
the primary collectors or interceptors; they may be considered to vary in size from
9 to 15-inch diameter.
c) Primary Sewers- These are also known as main or trunk sewers, into which the
laterals or secondary sewers discharge, and which discharge to interceptors or
pump stations; they may be considered to be of relatively large sizes, 18-inch
diameter or larger.
d) Interceptors- These are sewers that receive wastewater flows from a number of
transverse or tributary sewers, and conduct such flows to a point for pumping,
treatment, or disposal; they usually are of a similar range of sizes to the primary
sewers
The design period for civil works and sewers should be 25 years. There are a number of
considerations for selecting design period of sewers and allied civil work, which includes
expansion trends, economies of scale and financial position of the sponsoring / client
institutions. It has however been observed that sewers laid in various cities of the province
for the last more than 30 years are still functioning well. In view of the present economic
condition of the country it is advisable to use 25 years as design period for sewers and
allied civil works.
62
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
14.3 Sewer Pipes
Circular sewers are adopted when the flow of the sewers is nearly uniform, as these are
stronger, cheaper and structurally more stable than others. Oval or egg shaped sewers
are adopted best for situations where there is an intermittent flow of sewerage- that is,
when the flow varies considerably at different times. The reason for this is, at time when
there is, but a small quantity of sewage passing, the flow occupies the narrow bottom of
the egg-shaped sewer at a greater depth than it would be in a circular sewer of the same
area of section. This increase depth of the sewage causes it to flow with greater velocity,
and thus renders the sewer high hydraulic efficiency. However, they have become obsolete
due to problems in laying, instability at bottom and high precision required during laying.
Horizontal elliptical pipe is used with equivalent circular sizes with tongue and groove
cement mortar or mastic compound joint. The horizontal elliptical pipe is installed with the
major axis horizontal and is used for minimum cover situations or other conditions where
vertical clearance problems are encountered. It offers the hydraulic advantage of greater
capacity for the same depth of flow than other shapes of equivalent sectional area. Load
under similar cover conditions are similar to that of circular pipe with the same span. Thus
they are mostly used under conditions of insufficient covers for laying of pipes. In order
to ensure a smooth flow for carrying peak discharge by a hydraulically efficient system
and less prone to blockage, it is proposed to have circular pipes for the sewerage collection
network.
. / /
𝑉= ×𝑅 𝑆
63
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Sewer Material Manning Coefficient
UPVC 0.009
PE 0.008-0.011
HDPE 0.012
All of the sewers are assumed to involve the use of reinforced concrete pipes pre-cast in
the factory in accordance with the requirements of the latest revision of standard
specification ASTM C-76-20, pipes, as amended by PHED. Selection of Class will be
carried out as per Design & Site conditions.
Class-II: Providing and laying R.C.C. pipe sewers, molded with cement concrete
1:1½:3 conforming to ASTM Specification C-76-20, Class II, wall B.
Class-III: Providing and laying R.C.C. pipe sewers, molded with cement concrete
1:1½:3 conforming to ASTM Specification C-76-20, Class III, wall B.
Class-IV: Providing and laying R.C.C. pipe sewers, molded with cement concrete
1:1½:3 conforming to ASTM Specification C-76-20, Class IV, wall B.
Acceptance of reinforced cement concrete pipes will be on the basis of three edge
bearing and material tests as per ASTM Designation C-76-20 (latest revision) and
inspection of manufactured pipes for defects and imperfections.
The internal diameters and wall thicknesses of reinforced concrete pipes shall be as set
forth in ASTM Designation C-76-20. Rubber gasket joints shall be used for either tongue
and groove or bell and spigot pipes. The rubber gasket joints shall conform to all applicable
requirements of the latest revision of ASTM Designation C443, entitled "Joints for Circular
Concrete Sewer and Culvert pipe, using Flexible Watertight Rubber Type Gaskets" except
64
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
that the test pressure needs not exceed 10 feet of head at which the complete sewers
shall meet the infiltration or ex-filtration limits set forth hereinafter.
The groove end of tongue and groove of pipes shall have at least one line of wire
reinforcement of 8 gauge size placed in the center of the groove. Rubber gasket joints
shall be made using specially designed rubber gaskets, made to fit the applicable tongue
and groove or bell and spigot pipes and adequately tested under operating conditions. The
rubber gasket joints shall conform to all applicable requirements of the latest revision of
ASTM Designation C443, entitled "Joints for Circular Concrete Sewer and Culvert pipe,
using Flexible Watertight Rubber Type Gaskets" except that the test pressure need not
exceed 10 feet of head at which the complete sewers shall meet the infiltration or ex-
filtration limits set forth hereinafter.
The following pipes may also be used for sewerage network as per design and site
conditions:
High Density Polyethylene Pipes (HDPE).
Spiral Pipes.
uPVC
The Sulphate Resistant Cement shall be used for sewer pipes where the land consists of
Saline soils.
65
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Chapter 15
In case of construction of manholes for laterals, branches and sometimes even on the
intermediate sections, minimum velocity for the design flow is likely to be less that the
self-cleaning velocity. But manholes and sewers will be flushed out during peak flow period
carrying forward silt, which may get deposited during minimum flow period, especially
during night hours. Adopting lower values of velocities through lesser gradients will be
helpful in avoiding deep excavations. However, at certain sections, where undercrossing
of deeper sub drains and main drains as physical constraints, smaller sections of the sewer
may be sloped at a steeper gradient to minimize the number and height of the drops
required invert levels. While developing sewers, this point shall be given due consideration
prior to the design of the sewers. In case, where the above velocity criteria are not met,
prescribes slope for different flows shall be adopted.
For manholes under sub soil water, core-wall and floor will be designed as per actual depth
of water encountered.
The PCC 1:1.5:3 benching in the Manhole to be provided as per the approved drawing of
PHED.
66
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Chapter 16
Sewer above Sub-soil water level shall be constructed as per following design criteria
Size of Sewer
Depth (Feet) Manhole (Feet) Remarks
(Inches)
The following bedding will be used for Sewers above Water Table
For Sewers having dia 9-12”, sand will be used. However, in special conditions (like
mega cities, where WASAs have their own Design criterias) brick or stone ballast can be
used.
For sewers 15 in. dia and above Crushed stone (1/4 in -1 in size)
16.3 Sewer Bedding under Subsoil Water Level
For manholes under sub-soil water, core-wall and floor will be designed as per actual
depth of water encountered.
Sewer gas is a complex, generally obnoxious smelling mixture of toxic and nontoxic gases
produced and collected in sewage systems by the decomposition of organic household
or industrial wastes.
Sewer gases may include hydrogen sulfide, ammonia, methane, esters, carbon
monoxide, sulfur dioxide and nitrogen oxides.
Gases present in sewerage can strongly impact material durability due to the action of
microorganisms. The most deleterious one is associated to hydrogen sulfide which can
result in biogenic sulfide corrosion or microbial corrosion. In worst cases, it may lead to
the collapse of the RCC Pipes with significant cost for its rehabilitation. To protect the
sewerage system, the following precaution shall be carried out.
1) Ventilating shafts may be installed to release the gases from the sewerage
system/ Pipe.
2) Spacing of ventilating shafts: 1000ft
3) Height of Vent Pipe: 30 feet
4) Material: Cast Iron, Asbestos Cement in RCC casing, RCC Pipe, PVC pipe in RCC
casing, UV Resistant PVC Pipe in RCC casing as decided by the Engineer in charge
68
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Chapter 18
Disposal Works
The work shall consist of furnishing, installing, commissioning and testing of sewage pumps
and appurtenances involving all mechanical and electrical works and construction of pumping
station in accordance with these specifications and in reasonably close conformity with the
lines, grades, and dimensions shown on the plans and or established by the Engineer.
Building for the pumping station shall be constructed in accordance with the relevant
specifications and Drawings and as directed by the Engineer. The installation, testing and
commissioning of sewage pumps shall be strictly in accordance with the instructions of the
manufacturer of such machinery
Land for Disposal Station should be acquired with a planning horizon of 40 years.
Pumping mains can be designed with a lifespan of at least 30 years. However, it is not
possible for pumping mains to work for 30 years without preventive and operational
maintenance. Repair or replacement of the pumping sets might be necessary after 10
years of operation. The machinery needs continuous upkeep and maintenance, if properly
maintained, it can last for 20 years. For replacement purposes 15 years period is
recommended. For the Pumping Main 25 years period is proposed.
Coarse screens with 2 inch c/c mesh should be installed on the screening chamber.
Materials: SS 316
Bar Thickness: Coarse screens with 2 inch
69
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Bar Size: 10mm x 50mm
Bar spacing should be 25mm (clear spacing)
Screen may be Mechanical or Manual.
Angle of Slope of Bar Screen shall be 60 degree.
Desirable velocity through screening chamber should be 2 fps.
Pen Stock Gate should be made of SS 304.
All such pumps will be designed for passing solids of 2-3 inches size. These will be
powered by AC electric connections/ standby Generator/Solar System.
70
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Designation Labels: Engraved traffolyte white letter-in on a
black background.
Current transformers: As per B.S. 3938 or Equivalent
Voltmeter & Ammeters: As per B.S. 89 or Equivalent
Moulded case circuit As per B.S. 4752: Part I or
breakers: Equivalent.
71
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Chapter 19
a. Where there is a public sewer or drain, all sewer laid in the building shall be
connected thereto.
b. Septic Tanks shall be provided in all the residential and commercial buildings. All
the sullage water of the buildings shall be connected to the septic tank and then to
the public sewer.
c. The minimum sizes of septic tanks for residential plots will be as follows:
The Septic System contains a collection of living organisms that digest and treat
household waste. Pouring toxins down to drain can kill these organisms and harm the
septic system. Therefore, at the kitchen sink, bathtub, or utility sink:
Avoid chemical drain openers for a clogged drain. Instead, use boiling water or a
pressure system.
Never pour oil-based paints, solvents, or large volumes of toxic cleaners down the
drain. Even latex paint waste should be minimized.
Eliminate or limit the use of garbage disposal. This will significantly reduce the
amount of fats, grease, and solids that enter the septic tank and ultimately clog its
drain field.
72
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
4. All wastewater of Rural Communities should be treated through Wetlands and
Oxidation Ponds.
1. Each Car Wash Service Station should have the Water Recycling Facility.
3. No wastewater from the Car Wash Service Station will be discharged into Sewerage
or drainage system. All wastewater discharged into Sewerage/drainage shall be
through Septic Tank of appropriate size depending upon the capacity of the Car
Wash Service station.
73
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
19.6 Treatment of Wastewater from Hospital
No wastewater from any hospital will be allowed to dispose into any sewer or drain without
treatment. It shall be allowed only after meeting the NEQS requirements.
No wastewater from any industry shall be allowed to dispose into any sewer or drain
without treatment. It shall be allowed only after meeting the NEQS requirements.
74
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Drainage System
75
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Chapter 20
Q = CIA
Where:
Q = Discharge in cusecs
C = Run Off Co-efficient
I = Rain fall intensity
𝑆
𝑄 = 𝐴𝑅𝐶 ×
𝐴
a) Type Surface
Type of Surface Run off coefficient
76
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Same with un-cemented joints 0.70-0.80
2% slope 0.05-0.10
2-7% slope 0.10-0.15
2% slope 0.13-0.17
Light 0.50-0.70
Heavy 0.50-0.80
77
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Parks, cemeteries 0.60-0.90
Playgrounds 0.10-0.25
Railroad yards 0.20-0.35
Unimproved areas 0.20-0.40
Heavy 0.50-0.80
78
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
Chapter 21
i. Brick Pavement
Particular care should be exercised with soils having CBR of 3% or less. It should be
recognized that BS 1377-9 requires that CBRs are quoted to the nearest whole figure so
that for very low CBRs the recorded value will be an approximation. Detailed preparations
of the subgrade should be in accordance with the recommendations in BS 7533-3.
79
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
(cv/d), or the number of standard axles. A twenty five (25) years design life should
generally be applicable unless access for possible maintenance of the road is likely to be
difficult or expensive. Where the pavement serves a finite area, zero growth in traffic is
likely to be applicable, otherwise, 2% growth is recommended. If calculated growth figures
are available these should be used to ascertain the number of standard axles.
21.1.5 Pavers
Generally, the Pavers thickness should be 50 mm, 60 mm or 80 mm.
Design of Pavers
Assumptions:
Sub-grade CBR Design value = ≥5% - <10%
Design:
Assumption:
Sub-grade CBR design value = ≥5% - <10%
Design Traffic ESAL range = 4-8 msa (million standards axles)
Design:
Cement concrete plain including placing, compacting, finishing and curing complete
(including screening and washing of stone aggregate)
Thickness as per width of street and loading.
ii. Sub Base of PCC 1:7:20 having thickness as per width of street and loading.
81
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab
RCC Pavement:
RCC Pavement should be provided as per traffic load in the main streets.
82
Updated Design Criteria for Water Supply, Sewerage and Drainage System in Punjab