3134 32-Channel Relay Output Card: Technical Manual

The 3134 32-Channel Relay Output Card provides control for 32 field signals, supporting voltages up to 250 VAC or 30 VDC at 0.5 Amperes. It features diagnostics, watchdog timers, and an onboard temperature sensor, ensuring reliable operation and fault detection. The card is not suitable for safety-critical functions but can be used for non-safety related applications, with detailed specifications and configuration instructions provided in the manual.

Uploaded by

Prakash Babu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
6 views18 pages

3134 32-Channel Relay Output Card: Technical Manual

The 3134 32-Channel Relay Output Card provides control for 32 field signals, supporting voltages up to 250 VAC or 30 VDC at 0.5 Amperes. It features diagnostics, watchdog timers, and an onboard temperature sensor, ensuring reliable operation and fault detection. The card is not suitable for safety-critical functions but can be used for non-safety related applications, with detailed specifications and configuration instructions provided in the manual.

Uploaded by

Prakash Babu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 18

Technical Manual

3134
32-Channel
Relay Output Card
© 2002 - 2018 RTP Corporation
Specifications, information and graphics are subject to change without notice. Contact
RTP’s corporate office for specifics regarding any changes.
Not for reproduction in any printed or electronic media without express written consent
from RTP Corp.
All information, data, graphics and statements in this document are proprietary
intellectual property of RTP Corp. unless otherwise indicated and are to be considered
RTP Corp. confidential. This intellectual property is made available solely for the direct
use of potential or licensed RTP Corp. customers in their application of RTP Corp.
products, and any other use or distribution is expressly prohibited. If you have received
this publication in error, immediately delete, discard or return all copies to RTP Corp.

RTP Corporation
2832 Center Port Circle
Pompano Beach, FL 33064
Phone: (954) 597-5333
Internet: http://www.rtpcorp.com

Last Updated: 4/4/2018

2
TABLE OF CONTENTS

INTRODUCTION ........................................................................................ 4
SPECIFICATIONS ..................................................................................... 5
FAILURE RATES IN ACCORDANCE TO IEC 61508 ............................... 6
CABLING ................................................................................................... 6
SOFTWARE CONFIGURATION ............................................................... 9
PLD Upgrade ................................................................................................. 9
NetArrays Configuration ............................................................................... 11
Watchdog Timer ..................................................................................... 12
Integer Error Detection ........................................................................... 12
Float Temperature Input ......................................................................... 13
Integer Card Revision............................................................................. 13
Integer Readback (0-15) Status ............................................................. 13
Integer Readback (16-32) Status ........................................................... 13
Channel ................................................................................................. 14
I/O Tag ................................................................................................... 14
Default (3100/Non safety system only) .................................................. 14
COMPLIANCE WITH CE MARK ............................................................. 15
ENVIRONMENTAL CONDITIONS .......................................................... 17
REFERENCED COMPANIES .................................................................. 18
DEFINITIONS .......................................................................................... 18

3
Introduction

The 3134 32-Channel Relay Output Card provides sourcing switching control of 32 field signals.
The card can switch signals up to 250 VAC or 30 VDC at 0.5 Amperes. You can read back the
command to the output channels using the output readback feature of the card.
I/O bus checking diagnostics, card address tests, and configuration tests are performed each
time the controller accesses the card. All data and control transfers are performed twice, once
using the actual data and then using the data inverted. Both versions of the data are compared
to verify that all I/O bus data bits are functioning properly. The configuration code from the card is
compared to the I/O configuration to check that the correct card is installed in the rack. I/O Bus
slot address and control signal contention tests also are performed. Any fault detected sets
status bits in an error detection variable returned to the user application program.
Watchdog timers on the card can open all of the output channels in the event backplane
communication errors persist.
The card also includes an onboard temperature sensor which can be used to verify the air flow
around the cards.
The thirty-two LEDs on the 3099/40-100 and 3099/41-100 termination modules indicate the state
of each output. An LED, located near the top of the front panel of the card, indicates the overall
health status of the card. If this LED is on, the card is functioning normally; if it is off, the card has
detected an error or is offline.

4
Specifications
Module Safety Integrity: Non-Interfering with Safety Functions
Card Address: Determined by the slot of the controller backplane
Number of channels: 32
Isolation: 500 VAC/DC Channel to RTP System
Type of protection: Isolated by relays and fuse protected on termination
modules
Maximum permanent allowed
voltage (no damage): 30 VDC or 250 VAC maximum
Maximum Closed Circuit Current: 0.5 A per channel, fuse protected to 1 A slow acting
Maximum Inrush current: 5 A per channel
Total Output Current per Card: 16 A
Minimum Load: 10 mA @ 5 VDC
Common Points between Channels: All channels share a common external voltage and return
Output Configuration: Each channel has a Form A (SPST normally open) non-
latching contact
Output ratings for other loads
such as incandescent lamps: Supported with same ratings
Maximum Power per Channel: 15 Watts, 125 VA
Contact Resistance: 0.2  maximum
Contact Bounce: 2 ms maximum
Backplane to Card Output Delay Time:
10 ms maximum (ON to OFF or OFF to ON)
Maximum relay cycle speed 1,200 operations per hour at full load
Relay Life Expectancy: 300,000 cycles at full load
Suppressor networks for
inductive kickback: Diode protected on 3099/40-100 and snubber protected on
3099/41-100 termination modules.
Output behavior: During interruptions of MPU control, voltage dips and
interruptions and power up/down sequences, all channels
will be de-energized to the OFF state.
Watchdog Timers:
Programmable 150 ms (RTP3000), 250 ms (RTP3100)
Fixed 1.6 s maximum
Power Requirements: +5 VDC @ 1.1 A

Field Power to Termination: +5 VDC to +30 VDC at 16 A maximum


24 VAC to 250 VAC at 16 A maximum
Termination Module Connectors: 37 pin D-Sub connector for use with the 3055/00 Power
Digital Cables. These cables have a diameter of 0.5 inches
(1.27 centimeters) with a minimum bend radius of 4.6 inches
(11.69 centimeters).

5
Termination Modules:
5 - 24 VDC 3099/40-100 Single Termination Module
120 VAC 3099/41-100 Single Termination Module
240 VAC 3099/41-110 Single Termination Module
User Replaceable Fuses: Littelfuse type 0665 002.HXSL or
Wickmann type 3741200041
Termination Module Dimensions: All Termination Modules are 4.38 inches (11.1 centimeters)
in height and have 3.75 inches (9.5 centimeters) of depth.
The width is 12.64 inches (32.11 centimeters) for each
termination module. Maximum field wiring is 12 AWG.
Minimum field wiring is 30 AWG
Module dimension values are ± 0.05 inches or ± 0.127
centimeters.

Failure Rates in Accordance to IEC 61508


The 3134 32-Channel Relay Output card cannot be used for safety-critical functions. However,
the module is non-interfering with other safety-critical modules and therefore can be used for non-
safety related functions.

Cabling
Adhere to the specified insulation strip length of 0.26 inches (6.5 mm) when you connect field
wiring to the terminal modules; excessive insulation strip lengths causes an electrical hazard. Do
not exceed the specified torque when you secure the wires into the terminal module; maximum
torque is 2.2 inch-pounds (0.25 N-m).

Standard cables to termination modules are minimum 5 feet in length.

You must disable (offline) an I/O card before you can hot-swap it. After you replace an I/O card,
you must enable it to return it to operation. While NetArrays is operating in Debug mode, use the
I/O Configuration Form to disable or enable I/O cards. To hot swap an I/O card, first display the
card’s icon in the I/O Configuration Form. If the I/O card’s icon is red, you can remove it. If the
I/O card’s icon is yellow or green, select the icon and disable it before you remove the card. After
you replace the I/O card, select the card’s icon and re-enable it. The color of the icon changes to
yellow or green to indicate the card is online.

Warning! Dangerous high voltages may be present at the cards’ terminal blocks during
normal operation. When you service these cards, avoid contact with exposed voltages
on the card while you connect the field cabling. The field cabling terminal block
connectors also may have high voltages when disconnected from the card.

Warning! Never remove the card from the chassis with the termination cables
connected and the field power applied. Always disconnect the field power and cables
before removing the card from the chassis. Always insert the card into the chassis with
the cables and field power disconnected.

6
Pin Signal
TB 1 Pin 1 Channel 0+
TB 1 Pin 2 Channel 0-
TB 1 Pin 3 Channel 1+
TB 1 Pin 4 Channel 1-
TB 1 Pin 5 Channel 2+
TB 1 Pin 6 Channel 2-
TB 1 Pin 7 Channel 3+
TB 1 Pin 8 Channel 3-
TB 1 Pin 9 Channel 4+
TB 1 Pin 10 Channel 4-
TB 1 Pin 11 Channel 5+
TB 1 Pin 12 Channel 5-
TB 1 Pin 13 Channel 6+
TB 1 Pin 14 Channel 6-
TB 1 Pin 15 Channel 7+
TB 1 Pin 16 Channel 7-
TB 1 Pin 17 No Connection
TB 1 Pin 18 No Connection
TB 2 Pin 1 Channel 8+
TB 2 Pin 2 Channel 8-
TB 2 Pin 3 Channel 9+
TB 2 Pin 4 Channel 9-
TB 2 Pin 5 Channel 10+
TB 2 Pin 6 Channel 10-
TB 2 Pin 7 Channel 11+
TB 2 Pin 8 Channel 11-
TB 2 Pin 9 Channel 12+
TB 2 Pin 10 Channel 12-
TB 2 Pin 11 Channel 13+
TB 2 Pin 12 Channel 13-
TB 2 Pin 13 Channel 14+
TB 2 Pin 14 Channel 14-
TB 2 Pin 15 Channel 15+
TB 2 Pin 16 Channel 15-
TB 2 Pin 17 No Connection
TB 2 Pin 18 No Connection
TB 3 Pin 1 Channel 16+
TB 3 Pin 2 Channel 16-
Load TB 3 Pin 3 Channel 17+
TB 3 Pin 4 Channel 17-
TB 3 Pin 5 Channel 18+
TB 3 Pin 6 Channel 18-
TB 3 Pin 7 Channel 19+
TB 3 Pin 8 Channel 19-
TB 3 Pin 9 Channel 20+
TB 3 Pin 10 Channel 20-

7
TB 3 Pin 11 Channel 21+
TB 3 Pin 12 Channel 21-
TB 3 Pin 13 Channel 22+
TB 3 Pin 14 Channel 22-
TB 3 Pin 15 Channel 23+
TB 3 Pin 16 Channel 23-
TB 3 Pin 17 No Connection
TB 3 Pin 18 No Connection
TB 4 Pin 1 Channel 24+
TB 4 Pin 2 Channel 24-
TB 4 Pin 3 Channel 25+
TB 4 Pin 4 Channel 25-
TB 4 Pin 5 Channel 26+
TB 4 Pin 6 Channel 26-
TB 4 Pin 7 Channel 27+
TB 4 Pin 8 Channel 27-
TB 4 Pin 9 Channel 28+
TB 4 Pin 10 Channel 28-
TB 4 Pin 11 Channel 29+
TB 4 Pin 12 Channel 29-
TB 4 Pin 13 Channel 30+
TB 4 Pin 14 Channel 30-
3099/40-X00: 5 - 30 VDC TB 4 Pin 15 Channel 31+
TB 4 Pin 16 Channel 31-
16 A max
TB 4 Pin 17 No Connection
3099/41-X00: 24 - 250 VAC
TB 4 Pin 18 No Connection
16 A max
- +
VS TB 5 Pin 1 Field Power +
TB 5 Pin 2 Field Power -

Figure 1: Field wiring example using 3099/40-100 or 3099/41-100 Termination


Modules.

8
Software Configuration
PLD Upgrade
To update card’s PLD firmware follow this procedure:
1. Turn the power ON at all chassis within the target node.
2. From Windows StartPrograms menu, launch the RTP Netsuite/RTPNC utility.
3. Select the Node with the I/O cards to be updated.
4. Select FILE/Download File and navigate to the Program pldprog.pgm. Use the FILE
TYPE/pgm option. CLICK/OPEN button to initiate downloading the file. When prompted
for PASSWORD enter “rtp” (or the correct node password).
5. Select FILE/Download File and Select CID_0085.PLD. Use the FILE TYPE/pld option.
CLICK/OPEN button to initiate downloading the file. When prompted for PASSWORD
enter “rtp” (or the correct node password).
6. In RTP NetArrays Select Status for the Node, and observe that the pldprog.pgm file
and the CID_0085.PLD file were received as shown in Status Window 1.
7. Turn the power OFF and then back ON at all chassis within the target node.
8. The program pldprog.pgm downloaded will start and automatically update all of the
applicable cards’ PLDs. All non-distributed I/O cards should have their status LEDs ON.
9. In NetArrays Select Status for the Node, observe that the update has started as shown
in Status Window 1.
10. The Status Window will show all cards marked to be updated. Ensure that all applicable
cards in the Node are identified for updating.
11. Depending on the speed of the node, it will take several minutes for the process to
complete. When finished, the Status Window will show as shown in Status Window 2.
12. The cards being updated are processed at different times. Ensure that all cards identified
for updating have been processed before proceeding.
13. It is possible that cards of a type not being updated will report an error. This is of no
concern.
14. After the PLD update process is complete, all applicable cards in the Node will have their
PLDs updated.
15. Turn the power OFF and then back ON at all chassis within the target node. After the
power cycle, the 2 files downloaded will automatically be deleted, and the normal node
program will be active. The cards’ Integer Card Revision variables will show the revision
of the PLD downloaded.

9
Status Window 1

Status Window 2

10
NetArrays Configuration

11
Each output point is controlled by a Bool Variable object with the corresponding Tag. Two integer
readback status inputs can be read to determine the states of the card’s relay drive signals for the
32 outputs. NetArrays also returns an error detection status word for the card. This card includes
a Watchdog Timer, which can disable the outputs if the processor fails to access the card within
the allotted time.

Card Properties
Watchdog Timer
When enabled, the Watchdog Timer will disable the outputs if the card is not accessed by the
controller within 150 ms. When disabled, the Watchdog Timer has no effect on the card's
operation.

Integer Error Detection


The Error Detection input is an Int Variable that can be used to detect an I/O card failure.
NetArrays assigns a default Tag to this variable when the card is added to the I/O configuration.

A Card Timeout Error (Bit 0) will set the Error Latch bit (Bit14), which will remain set until this bit is
cleared to zero by an operator. While the Error Latch is set, the card will be offline and the target
node will not attempt to communicate with it. Note that most cards do not use all the status bits
shown. Any unused bits will always equal zero.

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
ERR DATA DATA CARD TIME
LTCH ERR INV ID OUT

Bit 14 Card Error Latch


This status bit indicates that a Card Timeout Error occurred on the I/O card, and that it
has been taken offline. The card will not be initialized or placed online until this bit is
cleared in the project program or operator intervention.
If this bit is set, it must be cleared to return the card to operation. The correct way to
clear this bit is to select the card’s icon in the I/O configuration Form while NetArrays is
operating in Debug mode and answer “Yes” to the Enable prompt. See I/O Card Status
and Control. (It is also possible to change the value of this variable by forcing an Integer
Bit Variable object, with Bit 14 selected in the object's properties, to zero. Do not clear
the entire Error Detection Integer Variable to zero.)
Bit 9 Backplane Bus Data Error
This status bit indicates that a data error was detected in a data or command transfer to
or from an I/O card.
Bit 8 Data Invalid
This status bit indicates that the I/O card is not ready to send valid data.
Bit 7 Card ID Does Not Match I/O Configuration
This bit indicates that the ID code read from the I/O card does not match the card type
specified in the NetArrays I/O configuration.
Bit 0 Card Timeout Error
This bit indicates that there was no response from the I/O card. The card is not returning
a ready test signal, is offline, or has been removed from the chassis. This bit sets the
Card Error Latch (Bit 14).

12
Float Temperature Input
The Board Temp is a floating-point value, which equals to the operating temperature in Degrees
Celsius as measured by an on-board sensor. User applications can implement customized limits
for alarms and annunciations by examining the value of this variable. NetArrays assigns a default
Tag to this variable when the card is added to the I/O configuration. Reassign this Tag as
required to access this board temperature in the project program.

Integer Card Revision


The card revision is an integer value, which equals to the revision number of the PLD code.
NetArrays assigns a default Tag to this variable when the card is added to the I/O configuration.
Reassign this Tag as required to access this card revision in the project program.

Integer Readback (0-15) Status


The bits of this Int input represent the states of the card’s drive signals to the relay coils for
channels 0 through 15. A 1 indicates that the contacts are driven to be closed (set); a 0 indicates
that the contacts are driven to be open (reset). NetArrays assigns a Tag to this input when the
card is added to the I/O configuration. Reconfigure the Tag as required to match the Module
Form Int Variable object that is used to monitor the card’s Readback (0-15) Status input.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Chan Chan Chan Chan Chan Chan Chan Chan Chan Chan Chan Chan Chan Chan Chan Chan
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Integer Readback (16-32) Status


The bits of this Int input represent the states of the card’s drive signals to the relay coils for
channels 16 through 32. A 1 indicates that the contacts are driven to be closed (set); a 0
indicates that the contacts are driven to be open (reset). NetArrays assigns a Tag to this input
when the card is added to the I/O configuration. Reconfigure the Tag as required to match the
Module Form Int Variable object that is used to monitor the card’s Readback (16-32) Status input.

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Chan Chan Chan Chan Chan Chan Chan Chan Chan Chan Chan Chan Chan Chan Chan Chan
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16

13
I/O Channel Properties
Channel
Each output channel can be enabled (Bool), or disabled (Disabled). You can disable any unused
channel to avoid scanning unconnected outputs and to free up the assigned Tag.

I/O Tag
A True output from a Bool Variable object will close (set) the relay’s contacts. A False output
from the Bool Variable object will open (reset) the relay’s contacts. NetArrays assigns a default
Tag to this variable when the card is added to the I/O configuration.
Note! All unused un-terminated I/O points must be disabled in IO Configuration.

Default (3100/Non safety system only)


Note! This property is available only if output card is used in non safety 3100 Node.
Specifies channel behavior when chassis to node communication is lost:
On – channel will be On
Off - channel will be Off
Freeze - channel value will be frozen at last value

14
Compliance with CE Mark
This section describes how to install and operate RTP equipment for use in the European Union
(EU) to comply with the requirements of the CE Mark and its referenced standards. The
procedures in this section apply also to other environments where provisions of the EU’s EMC
and Low Voltage Directives are either required or desirable.
RTP Corporation has successfully tested and reviewed its products to the stringent requirements
of the European Union’s EMC Directives (2004/108/EC) and Low Voltage Directive (2006/95/EC).
In order for the equipment to meet the requirements of these directives, the equipment
must be installed and operated in accordance with these instructions.
These tests and reviews are in accordance to EN 61131-2:2007 as listed in the next section.
Information on the tests performed and the standards involved is available from RTP Corporation.
To comply with the requirements of the CE Mark and its referenced standards, the system
integrator, installer, and end user must store, integrate, install, and operate this equipment in
accordance with the following guidelines.
1. Compliance with all product specific instructions (including but not limited to storage
instructions, installation instructions, operating instructions, maintenance instructions,
disposal instructions, and specifications) is required.
2. RTP equipment is rated for use in Installation Category (Overvoltage Category) II and
Pollution Degree 2 environments in accordance with standard IEC 664.
3. To assure that an Operator is not exposed to electrical hazards, all equipment capable of
electrical hazards must be housed in a grounded enclosure (equipment cabinet/rack) that
limits access to the equipment only to Service Personnel. Limited access may include
enclosure doors and side panels, which are locked or require a tool to open. To assure
compliance with the EMC requirements, the equipment must be housed in an enclosure
(equipment cabinet/rack) that provides EMC shielding. Compliance testing was
performed in a shielded equipment rack provided by Hoffman Concept® Wall Mounted
Enclosure model number CSD242420. To assure compliance, the equipment must be
installed in this style cabinet, or one with similar or greater RF attenuation characteristics.
The cabinet should be outfitted with continuous copper finger gasketing and copper foil
along all seams and joints.
4. The Service Personnel must be trained to operate the equipment and must be aware of
the potential of electrical hazards of the equipment and of the field I/O signals connected
to the equipment.
5. Hazardous voltage warning labels must be applied to the enclosure doors adjacent to the
locking mechanisms to warn the Service Personnel that hazardous voltages are
contained within the enclosure, if modules carrying 120 V and above are used.
6. Hazardous voltage warning labels also must be applied to the termination modules
(which carry 120 V and above), adjacent to the external connectors, to warn the Service
Personnel that hazardous voltages are present at the module's terminal blocks.
7. To assure compliance with the EMC requirements, the equipment must have all
communications, power, and field signal cabling exiting the enclosure enclosed in metal
conduits or shielded wireways. These conduits must provide EMI/RFI shielding and must
be terminated at the enclosure shell. There must be no uncovered openings in the
cabinet. Connections between the cabinet and conduit must be made with conduit
connectors making good (low impedance) electrical contact to the enclosure. Input
mains power to the enclosure and mains power fed to switching digital output I/O cards
and modules must be filtered by AC mains filters with attenuation characteristics of

15
Corcom VR series filters or with similar filters with equal or greater attenuation
characteristics.
8. DC input mains power to the enclosure and mains power must be filtered by a DC mains
filters with attenuation characteristics of Corcom 6EH1 series filters or with similar filters
with equal or greater attenuation characteristics.
9. Insulation strip length of 0.26 inches (6.5 mm) is required on all field wirings to the I/O
card termination modules.
10. The disposal of any electronic products must be in accordance with local regulations (e.g.
Directive 2002/96/EC of the European Parliament and of the Council on waste electrical
and electronic equipment). Some RTP Corporation products contain materials that may
be detrimental to the environment. These materials may include, but are not limited to
lead (in solder) and lithium (in batteries).
11. Prior to storage or shipping, the equipment must be packaged in accordance with the
following guidelines:
● Inventory all items and inspect all components for damage.
● Verify that all fasteners are properly tightened and that the chassis I/O module
retaining bar is properly installed.
● Wrap the chassis assembly in plastic bubble wrap.
● Select a suitable shipping box that provides at least 1½ inches of space between the
equipment and all sides of the box. This space shall be tightly packed with packing
peanuts or bubble wrap to protect the equipment during storage or shipping.
● Close and secure the box with suitable packing tape.
● Do not stack boxes more than three high. Store the boxes in a protected, dry
environment. Do not expose the boxes to rain or environmental conditions beyond
the ranges specified for the equipment in this document.

16
Environmental Conditions
The modules are rated for the following environmental conditions:

Specification Type Recommended Range Test Specification


IEC 60068-2-30, Db
Operating Temperature -20 ºC to 60 ºC
RTP Type Testing
Operating Temperature Change 10 ºC/minute IEC 60068-2-14 Test Nb
Operating Humidity 10% to 95% non-condensing IEC 60068-2-30, Db
IEC 60068-2-1 Tests Ab, Ad
Storage Temperature -40 ºC to 85 ºC IEC 60068-2-2 Tests Bb, Bd
RTP Type Testing
Storage Temperature Change 10 ºC/minute IEC 60068-2-14 Test Na
Storage Humidity 0% to 100% condensing IEC 60068-2-30, Db
Vibration 9 Hz to 150 Hz at 1 g IEC 60068-2-6, Fc
Mechanical Shock 15 g for 11 milliseconds IEC 60068-2-27, Ea
Electrostatic Discharge Immunity ±6 kV contact IEC 61000-4-2
80 MHz to 1 GHz at 20 V/m
1 GHz to 2.1 GHz at 10 V/m
Radiated E-Field Immunity IEC 61000-4-3
2.1 GHz to 2.5 GHz at 5 V/m
2.5 GHz to 2.7 GHz at 1 V/m
Ethernet Line Burst Immunity ±2 kV IEC 61000-4-4
Ethernet Line Surge Immunity ±2 kV IEC 61000-4-5
Ethernet Line Conducted RF
150 kHz to 80 MHz at 10 V IEC 61000-4-6
Immunity
Pulsed Magnetic Field 300 A/m IEC 61000-4-9

Modules can be ordered with optional HumiSeal© conformal coating. In this case, the modules
can be installed in G3 harsh environmental conditions as defined in standard ISA–S71.04–1985.

This equipment has been tested and found to comply with the limits for a Class A digital device,
pursuant to Part 15 of FCC Rules. These limits are designed to provide reasonable protection
against harmful interference when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if not installed and used
in accordance with the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to cause interference
in which case the user will be required to correct the interference at his own expense.

This Class A digital apparatus complies with Canadian ICES-003.


Cet appareil numérique de la Classe A est conforme à la norme NMB-003 du Canada.

17
Referenced Companies
Corcom Inc.; Libertyville, Illinois, USA; 708-680-7400
Hoffman; Anoka, Minnesota, USA; 763-422-2178

Definitions
OPERATOR is any personnel other than SERVICE PERSONNEL. Requirements
assume that the OPERATOR is oblivious to electrical hazards, but does not act
intentionally in creating a hazard.
SERVICE PERSONNEL are assumed reasonably careful in dealing with obvious
hazards.
CE Conformité Européenne
EMC Electro-Magnetic Compatibility
EMI Electro-Magnetic Interference
EC European Community
EN European Norm
ESD Electro-Static Discharge
EU European Union
IEC International Electrotechnical Commission
MPU Main Processing Unit
RF Radio Frequency
RFI Radio Frequency Interference