0% found this document useful (0 votes)
0 views1 page

BANTAYAN%20ISLAND-E1%20(2)

Download as pdf or txt
Download as pdf or txt
Download as pdf or txt
You are on page 1/ 1

GENERAL NOTES LOAD SCHEDULE PB- PANEL BOARD

1. ALL ELECTRICAL WORKS, HEREIN SHALL BE DONE IN ACCORDANCE WITH THE


REQUIREMENTS OF THE NATIONAL BUILDING CODE, THE PHILIPPINE ELECTRICAL CODE, CKT. N0. LOAD DESCRIPTION WATTS VOLTAGE AMPS ACB WIRE SIZE & TYPE CONDUIT SIZE & TYPE
THE RULES AND REGULATION OF THE LOCAL GOVERNMENT, AND THE REQUIREMENT (CURRENT)
OF THE LOCAL ELECTRIC UTILITY.
2.
3.
ALL MATERIALS TO BE USED SHALL BE NEW AND OF GOOD QUALITY.
LIGHTING BRANCH CIRCUIT SHALL BE 3.5 sq.mm THHN STRANDED WIRE IN 20mmØ PVC 1 LIGHTING OUTLET 155 230 0.67 15A 2 - 2.0 mm² THHN 1/2" Ø PVC
PIPE.
4. CONVENIENCE OUTLET CIRCUIT SHALL BE 5.5 sq.mm THHN STRANDED WIRE IN 20mmØ
PVC PIPE.
2 POWER OUTLET 1,620 230 7.04 20A 2 - 3.5 mm² THHN 3/4" Ø PVC
5. AIRCON OUTLET CIRCUIT SHALL BE 8.0 sq.mm THHN STRANDED WIRE IN 20mmØ PVC

6.
PIPE
MOUNTING HEIGHT OF DEVICE SHALL BE AS FOLLOWS UNLESS NOTED OTHERWISE
3 LIGHTING OUTLET 180 230 0.78 15A 2 - 2.0 mm² THHN 1/2" Ø PVC
PANEL BOARD 1500mm ABOVE FINISHED FLOOR 4 1 HP FUEL DISPENSER OUTLET 750 230 3.41 30A 2 - 5.5 mm² THHN 1" Ø PVC
LOCAL SWITCHES 1400mm ABOVE FINISHED FLOOR
CONVENIENCE OUTLET 300mm ABOVE FINISHED FLOOR
170mm ABOVE COUNTERS 5 1 HP FUEL DISPENSER OUTLET 750 230 3.41 30A 2 - 5.5 mm² THHN 1" Ø PVC
AIRCON OUTLET 2000mm ABOVE FINISHED FLOOR
EMERGENCY LIGHT 300mm BELOW FINISHED CEILING
6 SPLIT TYPE ACU, 2.0 hp 1,500 230 6.52 30A 2 - 5.5 mm² THHN 1" Ø PVC
7. ALL LOCAL SWITCHES TO BE CONNECTED SHALL BE RATED 15 AMPERES
8. ALL ELECTRICAL INSTALLATIONS SHALL BE UNDER THE SUPERVISION OF A DULY
LICENSED ELECTRICAL ENGINEER OR REGISTERED MASTER ELECTRICIAN 7 SPLIT TYPE ACU, 2.0 hp 1,500 230 6.52 30A 2 - 5.5 mm² THHN 1" Ø PVC
8 SPARE 1,500 2 - 8.0 mm² THHN
9 SPARE 1,500
LEGEND
MAIN TOTAL 9,455 230 41.10 60A 1 - 5.5mm² THHN(GROUND) 1"Ø PVC PIPE
SYMBOL DESCRIPTION
CIRCUIT RUN
7W LED PINLIGHT
Sa 1 GANG SWITCH
EM
EMERGENCY LIGHT

S ab 2 GANG SWITCH
CO
CONVENIENCE OUTLET

S abc 3 GANG SWITCH


ACU
AIRCON OUTLET
FROM POWER SOURCE
30W LED FLOODLIGHT
PB PANEL BOARD SERVICE ENTRANCE
FIRE EXTINGUISHER
FEEDER LINE FE (1.40 M)

LINE NOT CONNECTED


M KWHR METER

2 -14mm² THW IN 32mm RSC PIPE


1-5.5mm² THHN(GROUND)

60A MAIN ACB


a b
c
15w 15w 15w
C2 TO
MDP

C6 a b c C7 TO
Sab PB
TO 15w 15w 15w MDP PANEL BOARD
MDP Scde
C1
e e C1 MAIN 60A 15 A
TO
15w 15w MDP
THIS SITE C2
20 A 15 A
C3

C4 C5
30 A 30 A

C6 C7
30 A 30 A

C6 C7
SPARE SPARE

CONVENIENCE STORE AND 1- #8 TW (GREEN)

OFFICE LAYOUT 5/8


SCALE 1:75 M

VICINITY MAP
SCALE NTS
SINGLE LINE DIAGRAM
SCALE NTS

SEAL PROFESSIONAL ELECTRICAL ENGINEER PROJECT TITLE : PROJECT OWNER : SHEET NUMBER
DESIGNED:

BENJENITO R. CEMINI DRAFTED : E-1


REG. NO. : 0003212 VALIDITY : 07/09/2025
PROPOSED ONE-STOREY BUILDING WITH ROOFDECK DATE : PROJECT NUMBER

PTR. NO. : 0916920 DATE : JAN. 02, 2025 JANUARY 2025


TIN NO. : 922-009-352 PLACE: TANJAY CITY LOCATION: MOJON-MARICABAN ROAD, MARICABAN, SANTA FE, CEBU ADDRESS: VALLEYVIEW VILL, MOHON, TALISAY CITY, CEBU