Ps-Ii Notes
Ps-Ii Notes
UNIT –I
Per-Unit representation of Power system elements - Per-Unit equivalent reactance network of a three
phase Power System - Graph Theory: Definitions, Bus Incidence Matrix, YBus formation by Direct
and Singular Transformation Methods, Numerical Problems.
UNIT -II
Formation of Zbus
Formation of ZBus: Partial network, Algorithm for the Modification of ZBus Matrix for addition
element for the following cases: Addition of element from a new bus to reference, Addition of element
from a new bus to an old bus, Addition of element between an old bus to reference and Addition of
element between two old busses - Modification of ZBus for the changes in network ( Problems )
.
UNIT –III
Power flow Analysis
Static load flow equations – Load flow solutions using Gauss Seidel Method: Algorithm and
Flowchart. Acceleration Factor, Load flow Solution for Simple Power Systems (Max. 3-Buses):
Newton Raphson Method in Polar Co-Ordinates Form: Load Flow Solution- Jacobian Elements,
Algorithm and Flowchart. Decoupled and Fast Decoupled Methods.- Comparison of Different Methods
UNIT – IV
Short Circuit Analysis
Symmetrical fault Analysis: Short Circuit Current and MVA Calculations, Fault levels, Application of
Series Reactors. Symmetrical Component Theory:, Positive, Negative and Zero sequence components:
Positive, Negative and Zero sequence Networks. Unsymmetrical Fault Analysis: LG, LL, LLG and
LLLG faults with and without fault impedance, Numerical Problems.
UNIT –V
Stability Analysis
191 Page
Elementary concepts of Steady State, Dynamic and Transient Stabilities. Derivation of Swing
Equation, Power Angle Curve and Determination of Steady State Stability. Determination of Transient
Stability by Equal Area Criterion, Application of Equal Area Criterion, Critical Clearing Angle
Calculation. Numerical methods for solution of swing equation - Methods to improve Stability -
Application of Auto Reclosing and Fast Operating Circuit Breakers.
Course Outcomes:
After completing the course, the student should be able to do the following:
Remember and understand the concepts of per unit values, Y Bus and Z bus formation, load flow
studies, symmetrical and unsymmetrical fault calculations.
Apply the concepts of good algorithm for the given power system network and obtain the converged
load flow solution and experiment some of these methods using modern tools and examine the results.
Analyse the symmetrical faults and unsymmetrical faults and done the fault calculations, analyse the
stability of the system and improve the stability. Demonstrate the use of these techniques through good
communication skills.
Develop accurate algorithms for different networks and determine load flow studies and zero,
positive and negative sequence impedances to find fault calculations.
Design and select efficient Circuit Breakers to improve system stability. Implement them in
resolving various day-to-day issues ina Power System.
TEXT BOOKS:
1. G.W.Stagg and A.H.El “Computer Methods in Power System Analysis”, Abiad, Mc Graw-Hill,
2006.
2. I.J.Nagrath & D.P.Kothari, “Modern Power system Analysis”, 4th Edition, Tata McGraw-Hill
Publishing Company, 2011.
REFERENCE BOOKS:
1. Grainger and Stevenson, “Power System Analysis”, McGraw Hill, 1994.
2. Hadi Saadat, “Power System Analysis”, McGraw Hill, 1998.
3. B.R.Gupta, “Power System Analysis and Design”, S. Chand & Company, 2005.
POWER SYSTEM ANALYSIS
To maintain the voltage at various buses real and reactive power flow between buses
To design the circuit breakers
To plan the future expansion of existing system
To analyze the system under different fault conditions (three phase fault, L-G, L-L, L-L-G
faults)
To study the ability of the system for large disturbance (Sudden application of the large
load)
To study the ability of the system for small disturbance
Natural Sources
Coal
Water flow
Uranium & Thorium
Fossil Fuel
Wind
Tidal
Solar
Bio-Gas
security
Power system planning and operational analysis covers the maintenance of generation,
transmission and distribution facilities
Monitoring
Implementation Comparing plans
Planning of plans with result
Corrective
action
Steps:
Planning of power system
Implementation of the plans
Monitoring system
Compare plans with the results
If no undesirable deviation occurs, then directly go to planning of system
If undesirable deviation occurs then take corrective action and then go to planning Of the system
Planning and operation of power system
Planning and operation of power system the following analysis are very important
(a). Load flow analysis
(b). Short circuit analysis
(c). Transient analysis
Load flow study is done during the planning of a new system or the extension of an existing one
Short circuit studies
To determine the magnitude of the current flowing through out the power system at various time
intervals after fault
The objective of short circuit analysis - To determine the current and voltages at different
location of the system corresponding to different types of faults
(a). Three phase to ground fault
(b). Line to ground fault
(c). Line to line fault
(d). Double line to ground fault
(e). Open conductor fault
Transient stability analysis
The ability of the power system consisting of two (or) more generators to continue to operate
after change occur on the system is a measure of the stability
In power system the stability depends on the power flow pattern generator characteristics system
loading level and the line parameters
I
Φ = 90
C Load P=0 Q<0
(Leads)
Generator models
Generators:
The thevenins equivalent circuit of the generator i.e. The voltage source in series with the
thevenins equivalent impedance. Z = R + jX
.
Fig 1.4 Norton Equaivalent circuit
Transformer model
The Π model
Fig 1.8 Pi model
Vs A B Vr
Is C D Ir
X = Lω
Y/2 = Cω/2
A = 1+ZY/2
B=Z
C=Y(1+ZY/4)
D=1+ZY/4
Shunt Elements:
The shunt capacitor is connected to bus i. If S is MVAR rating of shunt capacitor. So is base
MVA admittance P.u. Y P.u. = 0+jS/S0
Load representation
Load:
Load is represented by a constant power representation. Both MW (P) & MVAR (Q) -
constant
In general electrical power systems are represented by a one line diagram (or) single line
diagram
A single line diagram of a power system shows the main connections & arrangements of
components in a simplified manner
Pictorial representation of the entire power system from generating end to the consumer
premises is known as single line diagram
Standard symbols
2 Bus
8 Transmission lines
9 Static load
10 Circuit Breaker
12 Disconnect
13 Fuse
14 Capacitor
15 Current transformer
16 Potential transformer
17 Lighting arrester
(iii). Transformer
IMPEDANCE DIAGRAM
The impedance diagram on single-phase basis for use under balanced conditions can be easily
drawn from the SLD. The following assumptions are made in obtaining the impedance diagrams.
Assumptions:
1. The single phase transformer equivalents are shown as ideals with impedance on appropriate
side (LV/HV),
2. The magnetizing reactance of transformers are negligible,
3. The generators are represented as constant voltage sources with series resistance or
reactance,
4. The transmission lines are approximated by their equivalent -Models,
5. The loads are assumed to be passive and are represented by a series branch of
resistance or reactance and
6. Since the balanced conditions are assumed, the neutral grounding impedance do not
appear in the impedance diagram.
Example system
As per the list of assumptions as above and with reference to the system of figure 2, the impedance
diagram can be obtained as shown in figure
REACTANCE DIAGRAM
With some more additional and simplifying assumptions, the impedance diagram can be
simplified further to obtain the corresponding reactance diagram. The following are the
assumptions made.
Additional assumptions:
The resistance is often omitted during the fault analysis. This causes a very negligible error since,
resistances are negligible
Loads are Omitted
Transmission line capacitances are ineffective &
Magnetizing currents of transformers are neglected.
Example system
as per the assumptions given above and with reference to the system of figure 2 and
Figure, the reactance diagram can be obtained as shown in figure
Definition: Per Unit value of a given quantity is the ratio of the actual value in any given unit to
the base value in the same unit. The percent value is 100 times the pu value. Both the pu and
percentage methods are simpler than the use of actual values. Further, the main advantage in using
the pu system of computations is that the result that comes out of the sum, product, quotient, etc. of
two or more pu values is expressed in per unit itself.
In an electrical power system, the parameters of interest include the current, voltage, complex
power (VA), impedance and the phase angle. Of these, the phase angle is dimensionless and the
other four quantities can be described by knowing any two of them. Thus clearly, an arbitrary
choice of any two base values will evidently fix the other base values.
Normally the nominal voltage of lines and equipment is known along with the complex power
rating in MVA. Hence, in practice, the base values are chosen for complex power (MVA) and line
voltage (KV). The chosen base MVA is the same for all the parts of the system. However, the base
voltage is chosen with reference to a particular section of the system and the other base voltages
(with reference to the other sections of the systems, these sections caused by the presence of the
transformers) are then related to the chosen one by the turns-ratio of the connecting transformer.
If Ib is the base current in kilo amperes and Vb, the base voltage in kilo volts, then the base MVA
is, Sb = (VbIb). Then the base values of current & impedance are given by
Base current (kA), Ib = MVAb/KVb
= Sb/Vb
Base impedance, Zb = (Vb/Ib)
= (KVb2 / MVAb)
Hence the per unit impedance is given by
Zpu = Zohms/Zb
= Zohms (MVAb/KVb2)
In 3-phase systems, KVb is the line-to-line value & MVAb is the 3-phase MVA. [1-phase
MVA = (1/3) 3-phase MVA].
CHANGE OF BASE.
It is observed from equation (3) that the pu value of impedance is proportional directly to the base
MVA and inversely to the square of the base KV. If Zpunew is the pu impedance required to be
calculated on a new set of base values: MVAbnew & KVbnew from the already given per unit
impedance Zpuold, specified on the old set of base values, MVAbold & KVbold , then we have
Demerits:
If proper bases are not chosen, then the resulting pu values may be highly absurd (such as 5.8 pu,
-18.9 pu, etc.). This may cause confusion to the user. However, this problem can be avoided by
selecting the base MVA near the high-rated equipment and a convenient base KV in any section of
the system.
Bus Frame of Reference: There are b independent equations (b = no. of buses) relating the bus
vectors of currents and voltages through the bus impedance matrix and bus admittance matrix:
EBUS = ZBUS IBUS
IBUS = YBUS EBUS
Branch Frame of Reference: There are b independent equations (b = no. of branches of a selected
Tree sub-graph of the system Graph) relating the branch vectors of currents and voltages through
the branch impedance matrix and branch admittance matrix:
EBR = ZBR IBR
IBR = YBR EBR
Loop Frame of Reference: There are b independent equations (b = no. of branches of a selected
Tree sub-graph of the system Graph) relating the branch vectors of currents and voltages through
the branch impedance matrix and branch admittance matrix:
ELOOP = ZLOOP ILOOP
ILOOP = YLOOP ELOOP
Of the various network matrices refered above, the bus admittance matrix (YBUS) and the bus
impedance matrix (ZBUS) are determined for a given power system by the rule of inspection as
explained next.
Rule of Inspection
Consider the 3-node admittance network as shown in figure5. Using the basic branch relation: I
= (YV), for all the elemental currents and applying Kirchhoff’s Current Law principle at the
nodal points, we get the relations as under:
At node 1: I1 =Y1V1 + Y3 (V1-V3) + Y6 (V1 – V2)
At node 2: I2 =Y2V2 + Y5 (V2-V3) + Y6 (V2 – V1)
At node 3: 0 = Y3 (V3-V1) + Y4V3 + Y5 (V3 – V2)
i.
These are the performance equations of the given network in admittance form and they can be
represented in matrix form as:
In other words, the relation of equation (9) can be represented in the form IBUS = YBUS EBUS
Where, YBUS is the bus admittance matrix, IBUS & EBUS are the bus current and bus voltage
vectors respectively.
By observing the elements of the bus admittance matrix, YBUS of equation (9), it is observed
that the matrix elements can as well be obtained by a simple inspection of the given system
diagram:
Diagonal elements: A diagonal element (Yii) of the bus admittance matrix, YBUS, is equal to the
sum total of the admittance values of all the elements incident at the bus/node i,
Off Diagonal elements: An off-diagonal element (Yij) of the bus admittance matrix, YBUS, is
equal to the negative of the admittance value of the connecting element present between the
buses I and j, if any.
This is the principle of the rule of inspection. Thus the algorithmic equations for the rule of
inspection are obtained as:
Note: It is to be noted that the rule of inspection can be applied only to those power systems that
do not have any mutually coupled elements.
Problem #2: Obtain YBUS and ZBUS matrices for the impedance network shown aside by the
rule of inspection. Also, determine YBUS for the reduced network after eliminating the eligible
unwanted node. Draw the resulting reduced system diagram.
The operating voltage of motors is 12.5 KV. Assuming the base quantities as 50 MVA, 13.8 KV,
draw the per unit reactance diagram. The percentage reactance for generators is 15% and that for
motors is 20%.
Solution:
The one line diagram with the data is obtained as shown in figure
Solution:
The one line diagram with the data is obtained as shown in figure P1
Problem #2:
Draw the per unit reactance diagram for the system shown in figure below. Choose a base of 11
KV, 100 MVA in the generator circuit.
Solution:
The one line diagram with the data is considered as shown in figure.
Selection of base quantities:
100 MVA, 11 KV in the generator circuit(Given); the voltage bases in other sections are: 11
(115/11.5) = 110 KV in the transmission line circuit and 110 (6.6/11.5) = 6.31 KV in the motor
circuit.
Calculation of pu values:
XG = j 0.1 pu, Xm = j 0.2 (100/90) (6.6/6.31)2 = j 0.243 pu.
Xt1 =Xt2 = j 0.1 (100/50) (11.5/11)2 = j 0.2185 pu.
Xt3 =Xt4 = j 0.1 (100/50) (6.6/6.31)2 = j 0.219 pu.
Xlines = j 20 (100/1102) = j 0.1652 pu.
Problem #3:
A 30 MVA, 13.8 KV, 3-phase generator has a sub transient reactance of 15%. The generator
supplies 2 motors through a step-up transformer - transmission line – step down transformer
arrangement. The motors have rated inputs of 20 MVA and 10 MVA at 12.8 KV with 20% sub
transient reactance each. The 3-phase transformers are rated at 35 MVA, 13.2 KV- -Y
with 10 % leakage reactance. The line reactance is 80 ohms. Draw the equivalent per unit
reactance diagram by selecting the generator ratings as base values in the generator circuit.
Solution:
The one line diagram with the data is obtained as shown in figure P3
Calculation of pu values:
XG = j 0.15 pu.
Xm1 = j 0.2 (30/20) (12.8/13.8)2 = j 0.516 pu.
Xm2 = j 0.2 (30/10) (12.8/13.8)2 = j 0.2581 pu.
Xt1 =Xt2 = j 0.1 (30/35) (13.2/13.8)2 = j 0.0784 pu.
Xline = j 80 (30/120.232) = j 0.17 pu.
Eg =
Problem #4:
A 33 MVA, 13.8 KV, 3-phase generator has a sub transient reactance of 0.5%. The generator
supplies a motor through a step-up transformer - transmission line – step-down transformer
arrangement. The motor has rated input of 25 MVA at 6.6 KV with 25% sub transient reactance.
base values in the motor circuit, given the transformer and transmission line data as under:
pu.
Zt1 = 0.005 + j 0.077 (25/30) (13.2/12.09)2 = 0.005 + j 0.0765 pu. (ref. to LV side)
Zt2 = 0.008 + j 0.08 (25/25) (110/105.316)2 = 0.0087 + j 0.0873 pu. (ref. to HV side)
Zline = 75 (0.2+j 0.8) (25/ 105.3162) = 0.0338 + j 0.1351 pu.
Problems
1. Determine the reactances of the three generators rated as follows on a common base of 200
MVA, 35 KV: Generator 1: 100 MVA, 33 KV, sub transient reactance of 10%; Generator 2: 150
MVA, 32 KV, sub transient reactance of 8% and Generator 3: 110 MVA, 30 KV, sub transient
reactance of 12%.
[Answers: XG1 = j 0.1778, Xg2 = j 0.089, Xg3 = j 0.16 all in per unit]
2. A 100 MVA, 33 KV, 3-phase generator has a sub transient reactance of 15%. The generator
supplies 3 motors through a step-up transformer - transmission line – step down transformer
arrangement. The motors have rated inputs of 30 MVA, 20 MVA and 50 MVA, at 30 KV with
20% sub transient reactance each. The 3-phase transformers are rated at 100 MVA, 32
KV- -Y with 8 % leakage reactance. The line has a reactance of 50 ohms. By
selecting the generator ratings as base values in the generator circuit, determine the base values
in all the other parts of the system. Hence evaluate the corresponding pu values and draw the
equivalent per unit reactance diagram.
[Answers: XG = j 0.15, Xm1 = j 0.551, Xm2 = j 0.826
3. A 80 MVA, 10 KV, 3-phase generator has a sub transient reactance of 10%. The generator
supplies a motor through a step-up transformer - transmission line – step-down transformer
arrangement. The motor has rated input of 95 MVA, 6.3 KV with 15% sub transient reactance.
The step-up 3-phase transformer is rated at 90 MVA, 11 KV-Y /110 KV-Y with 10% leakage
reactance. The 3-phase step-down transformer consists of three single phase Y-
transformers, each rated at 33.33 MVA, 68/6.6 KV with 10% leakage reactance. The line has a
reactance of 20 ohms. By selecting the 11 KV, 100 MVA as base values in the generator circuit,
determine the base values in all the other parts of the system. Hence evaluate the corresponding
pu values and draw the equivalent per unit reactance diagram.
[Answers
j0.114 and Xline = j 0.17 all in per unit]
4. For the three-phase system shown below, draw an impedance diagram expressing all
impedances in per unit on a common base of 20 MVA, 2600 V on the HV side of the transformer.
Using this impedance diagram, find the HV and LV currents.
[Answers
Zcable = 0.136 +j 0.204 and Zload = 5.66 + j 2.26, I = 0.158 all in per unit, I
(hv)= 0.7 A and I (lv) = 7.5 A]
CLASSIFICATION OF BUSES
Bus
The meeting point of various components in a power system is called a bus. The bus is a conductor
made of copper or aluminum having negligible resistance .At some of the buses power is being
injected into the network, whereas at other buses it is being tapped by the system lods.
.
ITERATIVE SOLUTION USING NEWTON-RAPHSON METHOD – ALGORITHM
Step 1: Assume a suitable solution for all buses except the slack bus. Let Vp = a+j0 for P
= 2,3,……n V1 = a+j0
Step 7 : Check if the bus is the question is a PV bus. If yes compare Q PK with the limits.
If it exceeds the limit fix the Q value to the corresponding limit and treat the bus
as PQ for that iteration and go to next step (or) if the lower limit is not violated
evaluate │ΔVP│2 = │ Vspec│2 - │VPK│2 and go to step 9
Step 9 : Advance bus count P = P+1 and check if all buses taken in to account if not go to
step 5
Step 12: Evaluate the element of Jacobin matrices J1, J2, J3, J4, J5 and J6
Step 16: Evaluate bus and line power and print the result
Step 6: Compute the real and reactive power mismatches ΔPK and ΔQK. If the mismatches
Are with in desirable tolerance the iteration end
Step 7: Normalize the mismatches by dividing each entry by its respective bus voltage
magnitude ΔPK =ΔP 2K / V 2K
ΔP 3K / V 3K
.
.
ΔP nK / V nK
ΔQK =ΔQ 2K / V 2K
ΔQ 3K / V 3K
.
.
ΔQ nK / V nK
Step 8: Solve for the voltage magnitude and the correction factors ΔVK and ΔδK by using the
constant matrices B’ and B” which are extracted from the bus admittance matrix Y Bus
[B’] ΔδK = ΔPK
[B”]ΔQK = ΔQK
Step 10: Check if all the buses are taken into account if yes go to next step otherwise go
to next step. Otherwise go to step 4
Step 11: Advance iteration count K = K+1 go to step 3
Step 12: Evaluate bus and load powers and print the results
Advantages: Calculations are simple and so the programming task is lessees. The memory
requirement is less. Useful for small systems;
Disadvantages: Requires large no. of iterations to reach converge .Not suitable for large
systems. Convergence time increases with size of the system
Advantages: Faster, more reliable and results are accurate, require less number of iterations;
Disadvantages: Program is more complex, memory is more complex.
Y matrix of the sample power system as shown in fig. Data for this system is given in table.
. .
(vii). The negative sequence impedances of alternators are assumed to be the same as their positive
sequence impedance Z+ = Z-
Need for short circuit studies or fault analysis
Short circuit studies are essential in order to design or develop the protective schemes for various
parts of the system .To estimate the magnitude of fault current for the proper choice of circuit breaker
and protective relays.
Doubling effect
If a symmetrical fault occurs when the voltage wave is going through zero then the maximum
momentary short circuit current will be double the value of maximum symmetrical short circuit
current. This effect is called doubling effect.
SYMMETRICAL FAULT
In symmetrical faults all the three phases are short circuited to each other and to earth also. Such
faults are balanced and symmetrical in the sense that the voltage and current of the system
remains balanced even after the fault and it is enough if we consider any one phase
(OR)
Transient reactance
The synchronous reactance is the ratio of induced emf on no load and the transient symmetrical rms
current.
Fault current in fig., if the Pre-fault voltage at the fault point is 0.97 p.u.
Thevenin’s theorem:
(i). Fault current = Eth / (Zth+Zf)
(ii). Determine current contributed by the two generators IG1 = If * (Z2/(Z1+Z2))
IG2 = If * (Z1 / (Z1+Z2))
(iii). Determine Post fault voltage Vif = Vi°+ΔV = V°+(-Zi2*IGi)
(iv). Determine post fault voltage line flows Iij = (Vi –Vj) / Zij series
(v). Short circuit capacity If = │Eth│2 / Xth
Two generators G1 and G2 are rated 15MVA, 11KV and 10MVA, 11KV respectively. The
generators are connected to a transformer as shown in fig. Calculate the sub transient current in each
generator when a three phase fault occurs on the high voltage side of the transformer.
A radial power system network is shown in fig. a three phase balanced fault occurs at F.
Determine the fault current and the line voltage at 11.8 KV bus under fault condition.
Problem : 2
A 100MVA,11KV generator with X’’=0.20 p.u is connected through a transformer and line to a bus
bar that supplies three identical motor as shown in fig. and each motor has X’’=0.20 p.u and X’=0.25
p.u on a base of 20MVA,33KV.the bus voltage at the motors is 33KV when a three phase balanced
fault occurs at the point F. Calculate
(a) subtransient current in the fault
(b) subtransient current in the circuit breaker B
(c) Momentary current in the circuit breaker B
(d) The current to be interrupted by CB B in (i) 2 cycles (ii) 3 cycles (iii) 5 cycles (iv) 8 cycles
UNIT- IV
Sequence operator
In unbalanced problem, to find the relationship between phase voltages and phase currents, we use
sequence operator ‘a’.
a = 1∠120˚ == - 0.5+j0.866
A balanced delta connected load is connected to a three phase system and supplied to it is a current of
15 amps. If the fuse is one of the lines melts, compute the symmetrical components of line currents.
Draw zero sequence network of the power system as shown in fig. Data are given below.
A 50MVA, 11KV, synchronous generator has a sub transient reactance of 20%.The generator supplies
two motors over a transmission line with transformers at both ends as shown in fig. The motors have
rated inputs of 30 and 15 MVA, both 10KV, with 25% sub transient reactance. The three phase
transformers are both rated 60MVA, 10.8/121KV, with leakage reactance of 10% each. Assume zero
sequence reactance for the generator and motors of 6% each. Current limiting reactors of 2.5 ohms
each are connected in the neutral of the generator and motor number 2. The zero sequence reactance
of the transmission line is 300 ohms. The series reactance of the line is 100 ohms. Draw the positive,
negative and zero sequence networks.
A 30 MVA, 13.2KV synchronous generator has a solidly grounded neutral. Its positive, negative and
zero sequence impedances are 0.30, 0.40 and 0.05 p.u respectively. Determine the following:
a) What value of reactance must be placed in the generator neutral so that the fault current for a line
to ground fault of zero fault impedance shall not exceed the rated line current?
b) What value of resistance in the neutral will serve the same purpose?
c) What value of reactance must be placed in the neutral of the generator to restrict the fault current
to ground to rated line current for a double line to ground fault?
d) What will be the magnitudes of the line currents when the ground current is restricted as above?
e) As the reactance in the neutral is indefinitely increased, what are the limiting values of the line
currents?
Two alternators are operating in parallel and supplying a synchronous motor which is receiving
60MW power at 0.8 power factor lagging at 6.0 KV. Single line diagram for this system is given in
fig. Data are given below. Compute the fault current when a single line to ground fault occurs at the
middle of the line through a fault resistance of 4.033 ohm.
Transient stability
Transient stability is defined as the ability of the power system to bring it to a stable condition or
remain in synchronism after a large disturbance.
Dynamic stability
It is the ability of a power system to remain in synchronism after the initial swing (transient stability
period) until the system has settled down to the new steady state equilibrium condition
Voltage stability
It is the ability of a power system to maintain steady acceptable voltages at all buses in the system
under normal operating conditions and after being subjected to a disturbance.
Swing equation for a SMIB (Single machine connected to an infinite bus bar) system.
3 machine system having ratings G1, G2 and G3 and inertia constants M1, M2 and M3.What is
the inertia constants M and H of the equivalent system.
This is possible if the positive (accelerating) area under P – δ curve is equal to the negative
(decelerating) area under P – δ curve for a finite change in δ. hence stability criterion is called equal
area criterion.
A 400 MVA synchronous machine has H1=4.6 MJ/MVA and a 1200 MVA machines H2=3.0
MJ/MVA. Two machines operate in parallel in a power plant. Find out Heq relative to a 100MVA
base.
A 100 MVA, two pole, 50Hz generator has moment of inertia 40 x 103 kg-m2.what is the energy
stored in the rotor at the rated speed? What is the corresponding angular momentum? Determine the
inertia constant h.
The sending end and receiving end voltages of a three phase transmission line at a 200MW load are
equal at 230KV.The per phase line impedance is j14 ohm. Calculate the maximum steady state power
that can be transmitted over the line.
A single line diagram of a system is shown in fig. All the values are in per unit on a common base.
The power delivered into bus 2 is 1.0 p.u at 0.80 power factor lagging. Obtain the power angle
equation and the swing equation for the system. Neglect all losses.
1. What are the main divisions of power system. OR What are the functions of modern power system
Nov/Dec-2014, Nov/Dec-2013
There are three main divisions in power system
a) Generation System
b) Transmission system
c) Distribution system
2. What is single line diagram? Or What is the meaning of one line diagram of a power system?
April / May 2010, November / December 2011, May / June 2012, Nov / Dec 2007
A single line diagram is a diagrammatic representation of power system in which the components are
represented by their symbols and the interconnection between them are shown by a single straight line.
3. What are the components of a power system? Or List the different components of power system. April /
May 2008,May / June 2012
The components of a power system are Generators, Power transformers, Transmission lines, Substation
transformers, Distribution transformers and Loads.
4. Define per unit value. Or Define per unit value of an electrical quantity. Write equation for base impedance
with respect to 3-phase system. May / June 2009
The per unit value of any quantity is defined as the ratio of actual value of the quantity to base value of the
quantity.
Per unit = Actual value
Base value
5. What is the need for base value? Or what is the need of per unit value. Nov/Dec-2014
The components or various sections of power system may operate at different voltage and power
levels. It will be convenient for analysis of power system if the voltage, power, current and impedance
ratings of components of power system are expressed with a common value called base value. Hence for
analysis purpose a base value is chosen for voltage, power, current and impedance.
6. What is the need for system analysis in planning and operation of power system? May / June
2007, Nov / Dec 2008
Planning the operation of a power system requires load studies, fault calculations,the design of means for
protecting the system against lightning and switching surges and against short circuits, and studies of the
stability of the system
7. What are the quantities whose base values are required to represent the power system by reactance
diagram? Or .
How are the base values chose in per unit representation of a power system? Nov / Dec 2008
The base value of voltage, current, power and impedance are required to represent
the power system by reactance diagram. Selection of base values for any two of them
determines the base values of the remaining two. Usually the base values of voltage and power are chosen
in kilovolt and kVA or mVA respectively. The base values of current and impedance are calculated
using the chosen bases.
8. Write the equation for converting the p.u. impedance expressed in one base to another. April / May 2010
Zp.u,new = Zp.u,old * (kVb,old / kVb,new) * (MVAb,new / MVAb,old)
9. What are the advantages of per unit computations? Or What are the advantages of per unit system?
May / June 2007, April / May 2008, April / May 2011
a) Manufacturers usually specify the impedance of a device or machine in per unit on the basis of the name
plate details.
b) The p.u. values of widely different rating machines lie within a narrow range even though the ohmic values
has a very large range.
c) The p.u. impedance of circuit element connected by a transformer expressed on a proper base will be same
if it is referred to either side of a transformer.
d) The p.u. impedance of a 3-phase transformer is independent of the type winding connection.
12. How are the loads represented in reactance or impedance diagram? Nov / Dec- 2011
The loads represented in reactance or impedance diagram which is the combination of resistance and inductive
reactance in series.
13. Give the equations for transforming base kV on LV side to HV side and viceversa. Or Write the equation
for converting the p.u. impedance expressed in one base to another base. April / May 2010
The state of the system in the first second following a system fault or large
disturbance is called the transient state of the power system.
18. If the reactance in ohms is 15 ohms, find the p.u value for a base of 15 KVA and 10 KV. May / June 2012
21. Explain bus incidence matrix. Or Define bus incidence matrix. Nov / Dec 2008, May / June 2012
For the specific system, we can obtain the following relation (relation between element voltage
and bus voltage).
V = A VBUS
where A is the bus incidence matrix, which is a rectangular and singular matrix. Its
elements are found as per the following rules.
th th
aik = 1, if i element is incident to and oriented away from the k node (bus).
= -1, if i element is incident to but oriented towards the kth node.
th
22. Define primitive network. Or Describe primitive network. Give an example. April / May 2010
Primitive network is a set of unconnected elements which provides information
regarding the characteristics of individual elements only. The performance equations
of primitive network are given below.
V + E = ZI (In Impedance form)
I + J = YV (In Admittance form)
where V and I are the element voltage and current vectors respectively.
J and E are source vectors.
Z and Y are the primitive Impedance and Admittance matrices respectively.
24. What is Jacobian matrix? How the elements of Jacobian matrix are computed? April / May 2011
The matrix formed from the derivates of load flow equations is called Jacobian
matrix and it is denoted by J. The elements of Jacobian matrix will change in every iteration. In
each iteration, the elements of the Jacobian matrix are obtained by partially differentiating the load
flow equations with respect o unknown variable and then evaluating the first derivates
usingthe solution of previous iteration.
25. Name the diagonal and off-diagonal elements of bus admittance matrix.Nov/Dec-2013
The diagonal elements of bus admittance matrix are called self admittances of the matrix and off-diagonal
elements are called mutual admittances of the buses.
26. Write the equation to find the elements of new bus admittance matrix after eliminating nth row and column
in a n*n matrix.
Yjk = Yjk-(YjnYnk / Ynn)
28. Name the diagonal and off-diagonal elements of bus impedance matrix. Nov/Dec-2013
The diagonal elements of bus impedance matrix are called driving point impedances of the buses and
off-diagonal elements are called transfer impedances of the buses.
29. What are the methods available for forming bus impedances matrix?
a) Form the bus admittances matrix and then take its inverse to get bus impedance matrix.
b) Directly from the bus impedance matrix from the reactance diagram. This method utilizes the techniques of
modification of existing bus impedance matrix due to addition of new bus.
30. Write the four ways of adding an impedance to an existing system so as to modify bus impedance matrix.
a) Case 1:Adding a branch impedance Zb from a new bus P to the reference bus.
b) Case 2:Adding a branch impedance Z b from a new bus P to the existing bus q.
c) Case 3:Adding a branch impedance Zb from a existing bus q to the reference bus.
d) Case 4:Adding a branch impedance Zb between two existing bus h and q.
32. Draw a simple per-phase model for a cylindrical rotor synchronous machine? April / May 2011
2. What are the informations that are obtained from a load flow study?
The information obtained from a load flow study are magnitude and phase of bus voltages, real and reactive
power flowing in each line and the line losses. The load flow solution also gives the initial conditions of the
system when the transient behaviour of the system is to be studied.
5. What are the quantities that are associated with each bus in a system?
Each bus in a system are associated with four quantities and they are real power,reactive power, magnitude of
voltage and phase angle of voltage.
8. What is PQ bus?
A bus is called PQ are load bus when real and reactive components of power are specified for the bus. In a load
bus the voltage is allowed to vary within the permissible value.
10. What is the need for slack bus? (APR/MAY 2004),(NOV/DEC 2004),Nov/Dec-2013
The slack bus is needed to account for transmission line losses. In a power system, the total power
generated will be equal to sum of power consumed by loads and losses. In a power system, only the generated
power and load power are specified for the buses. The slack bus is assumed to generate the power
required for losses. Since the losses are unknown, the real and reactive power are not specified for slack bus.
They are estimated through the solution of line flow equations.
13. List the quantities specified and the quantities to be determined from load flow
study for various types of buses. (MAY/JUNE 2006)
The following table shows the quantities specified and the quantities to be
obtained for various types of buses.
14. What are the iterative methods used for solution of load flow problems?
Guass-Seidal (GS) method and Newton Raphson(NR) method.
21. Write the most important mode of operation of power system and mention the
PSA Page 94 of 106 DEPARTMENT OF EEE
POWER SYSTEM ANALYSIS
major problems encountered with it.
Symmetrical steady state is the most important mode of operation of power
system. Three major problems are encountered in this mode of operation. They are,
a) Load flow problem
b) Optimal load scheduling problem
c) Systems control problem
23. Compare G-S method and N-R methods of load flow solutions.
G-S method N-R method
1. The variables are expressed in 1. Variables are expressed in polar co-
rectangular co-ordinates. ordinates.
2. Computation time per iteration is 2. Computation time per iteration is
less. more
3. It has linear convergence 3. It has quadratic convergence
characteristics.
characteristics.
4. The number of iterations required for 4.The number of iterations are
independent
convergence increase with size of of the size of the system.
the
system.
5.The choice of slack bus is critical. 5. The choice of slack bus is arbitrary.
24. Write the equation for power flow in the transmission line.
The equation for power low in the transmission line (say p-q) at bus ‘p’ is given by,
S = P -jQ
pq pq pq
= E *-Eipq]Y p
.(Y
= E * p q pq + E * ’/2)
p [E p Ep pq
S = P -jQ
qp qp qp
= E * iqp q
-E ]Y
= E *[Eq q p pq + E *Eq .(Ypq’/2)
q
25. Discuss the effect of acceleration factor in the load flow solution algorithm.
(APR/MAY 2004) ,Nov/Dec-2012
In load flow solution by iterative methods, the number of iterations can be
reduced if the correction voltage at each bus is multiplied by some constant. The
multiplication of the constant will increase the amount of correction to bring the voltage closer to
the value it is approaching. The multipliers that accomplish this improved converged
are called acceleration factors. An acceleration factor of 1.6 is normally used in load flow problems.
26. Why do Ybus used in load flow study instead of Zbus? Nov/Dec-2013
27. When will the generator bus to be treated as load bus ? Nov/Dec-2013
If the iterative power of a generator bus violates the specified limits then the generator bus is treated
as load bus.
What ARE THE DATA RE
28. why power flow analysis is made? or what are the datas required power flow studies ? Nov/Dec-2012
Power flow analysis is performed to calculate the magnitude and phase angle of
voltages at the buses and also the active power and reactive voltamperes flow for
the given terminal or bus conditions. The variables associated with each bus or node are,
a. Magnitude of voltage |V|
b. Phase angle of voltage δ
c. Active power, P
d. Reactive voltamperes, Q
1. The one line diagram of a power system is shown in figure. The three phase power and line
2. Draw the reactance diagram for the power system shown in figure. Neglect resistance and
use a base of 100 MVA, 220 kV in 50Ω line. The ratings of the generator, motor and
transformer are given below.
(May/June 2012)
Generator : 50 MVA, 11 kV, X’’ =30%
Synchronous motor : 40 MVA, 33/220 kV, X=15%
Y-Y Transformer : 30 MVA, 11/220 kV, X =15%
Y-Δ Transformer
: 40 MVA, 25 kV, X’’ =20%