It Air Conditionner

The document details the specifications and features of the Datatech BTD UEDA 32.1 HH air conditioning unit designed for IT applications, emphasizing efficiency, reliability, and flexibility in air delivery. It outlines the components including fans, filters, refrigerant circuits, compressors, and control systems, along with their operational capabilities and configurations. Additionally, it discusses the testing, packaging, and shipment procedures for the units, ensuring quality and safety standards are met.

Uploaded by

Mustapha Lafria
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
30 views12 pages

It Air Conditionner

The document details the specifications and features of the Datatech BTD UEDA 32.1 HH air conditioning unit designed for IT applications, emphasizing efficiency, reliability, and flexibility in air delivery. It outlines the components including fans, filters, refrigerant circuits, compressors, and control systems, along with their operational capabilities and configurations. Additionally, it discusses the testing, packaging, and shipment procedures for the units, ensuring quality and safety standards are met.

Uploaded by

Mustapha Lafria
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

24/01/2025

CHDesign - v2.9

Model: Datatech BTD UEDA 32.1 HH

GENERAL

Air conditioners specifically designed for IT applications: maximisation of sensible capacity, efficiency,
reliability, availability and redundancy. They additionally provide for utmost flexibility in terms of direction
of the air delivery and return lines for better adaptation to the different site
layouts.

CONFIGURATIONS

EDA: Direct expansion, air-condensed conditioning units

STRUCTURE BTD

For enhanced thermal and acoustic insulation the units consist of a load-bearing frame made of a 22 mm
thick sandwich sheet metal, with internal insulating glass wool material, 30 kg/m³ density. The fire reaction
class of the panelling is A1 (in accordance with EN13501). Air tightness is achieved with adhesive sealing
strips placed allaround the edges of the panels. The internal sheet metal parts are hot galvanised and have
variable thickness (from 2.5 mm for the base to 1 mm for removable panels), whereas visible parts are
painted with an oven-baked epoxy polyester powder coating RAL7016 and have a textured surface finish.
The frame is secured with structural rivets. The front and rear panels are fixed with ¼ turn fasteners or
they are screwed to the top part, respectively, and they are supplied with tabs for installation in dedicated
slots on the base. The front panel opposite the electric switch is hingedand supplied with a handle for
opening. Access to all the main components of the unit is gained from th front, so no clearance spaces
must be left at the sides and back of the unit for both routine and non-routine maintenance. All the
materials making up the unit are CFC-free. All electrical, cooling and hydraulic connections are normally
made from the bottom of the unit. Solutions for lateral connections are also available upon request.

pag. 1/12
24/01/2025
CHDesign - v2.9

FANS

Units are equipped with 1, 2, 3 and/or 4 radial fans with backward-curved blades, without scroll. Fans are
balanced, as required by standard ISO DIN 1940. The average air capacity value is 82 l/s per kW of sensible
cooling capacity. Fans featuring brushless, electronically commutated (EC) motors offer a number of
advantages:
• greater efficiency at full load if compared with the corresponding AC model;
• Cosfi value close to 1;
• built-in soft starter;
• user-friendly adjustment - the 0-10V control signal enables monitoring the motor speed electronically
with continuous regulation via the microprocessor onboard the unit so as to implement various control
strategies (constant flow, constant pressure, based on thermal load, etc.).
• The motors are provided with integrated electronic protection against overtemperature, overcurrent,
over or under-voltage with absence of one or more phases.
The strategic advantage of EC fans is the cubic ratio between speed and absorption. In other words, the
consumption of a fan running at 70% is 50%, it is 18% when running at 50%, etc. This brings about a
potential saving that is exponential to partial loads. Hence, the need exists to modulate the fan efficiently
and continuously using the correct algorithm required by the application. Air flow is constantly monitored
by a differential pressure switch, which signals an alarm condition when there is no flow or the flow is poor.

AIR FILTERS

The filters are pleated and in a rigid galvanized steel frame, filtration class ISO Coarse 75% (ISO 16890-
3; G4 - EN779), and designed to minimize head losses and to have a high degree of filtration. The thickness
of the filters can be 50 or 100 mm depending on the sizes or the setups. The filters are always removed
from the front of the unit. Higher efficiency and low head loss filters ISO ePM10 (M5), ISO ePM10 75%
(M6), ISO ePM1 50% (F7) may be supplied upon request (refer to the corresponding options for further
details). If the specific option (CF) is ordered, the condition of the filters is constantly monitored by a
differential pressure switch that signals when they are excessively fouled.

REFRIGERANT CIRCUIT (direct expansion unit ED)

The refrigerant circuit comprises:


• Compressor;
• direct expansion evaporator coil;
• liquid receiver (excluding water-condensed sizes 6.1 and 8.1);
• thermostatic expansion valve, complete with external equalizer (the solution with an electronic
expansion valve - TEV - is available as option);
• solenoid valve for shutting off the refrigerant liquid (only in versions with a remote condenser or with
electronic valve option);
• refrigerant liquid transit gauge with humidity indicator;
• solid cartridge freon filter;
• safety valve; (excluding water-condensed sizes 6.1 and 8.1);
• high pressure safety pressure switch with manual reset;
• low pressure switch with automatic reset (with electronic expansion valve option replaced by a
transducer);
• on-off valves for external connections (air-condensed versions);
• copper refrigerant pipes with anti-condensation insulation on the suction line;

pag. 2/12
24/01/2025
CHDesign - v2.9

• 5/16” service pressure outlets on high and low pressure sides;


• 5/16” service pressure outlet on liquid side.

COMPRESSORS (direct expansion unit ED)

Compressors are either rotary or scroll type (depending on size): they operate with refrigerant R410A and
have a power supply of 400V/3~/50Hz. Models with an up to 8kW nominal capacity require a power supply
to the compressor of 230V/1~/50Hz (optionally, 400V three phase power).
All compressors are provided with the following:
• internal thermal overload protection which automatically cuts out the power supply in the event of a
thermal overload and internal bypass valve between high and low pressure;
• pre-filled oil and heater for crankcase pre-heating;
• internal mechanical non-return valve on gas delivery line

EVAPORATOR COIL (direct expansion unit ED)

Evaporator coils consist of a finned pack, copper tubes and aluminium fins with a corrugated profile and
hydrophilic surface treatment. The sensible heat ratio is close to 1. All direct expansion coils are specifically
designed and sized for use with refrigerant R410A, and they are guaranteed for pressure values up to 45
bar. A stainless steel condensation collection basin is installed at the base of the coil, complete with fitting
for drain and siphon.

VERSIONS

The version in all models indicates the operating mode required to preserve the thermo-hygrometric
conditions in the relevant environment. HH versions are fitted with cooling, heating and
humidificationdevices. In addition to the temperature probe fitted on he air return line, these units are
provided with a humidity probe that is used to control the humidity parameter as well. More specifically,
when the relative humidity drops below the desired value, the humidifier outputs vapour into the
environment. The HH ersion may be supplied without heaters upon request. Versions CO/CH (where fitted
with an additional humidity probe) and HH are also used for de-humidification of the environment whenever
the humidity value exceeds the desired threshold. Please keep in ind that the unitshave limited
dehumidification properties for the intended type of application. For more efficient de-humidification, the
units can modulate their components to increase their latent heat removal capabilities via software where
these operations re programmed. When de-humidification is required, the units can reduce the fan speed
and increase their de-humidification capability.

ELECTRIC HEATERS BY VERSION CH-HH

The heating elements are made of AISI304 steel and have low surface temperature, spiral AISI304 steel
fins featuring a safety bimetal thermostat. The heating elementsare grouped in banks that are made of
galvanised sheet metal with a locked electric box or they are installed in circle configuration around the
fan (“XS” sizes). The electric heaters are controlled according to power steps (either one or two depending
on the unit size).
• Frames SXS,XS,S: 1 power step.
• All other frames: 2 power steps.

pag. 3/12
24/01/2025
CHDesign - v2.9

HUMIDIFIER FOR VERSION HH

When the necessary option is fitted, the unit can be equipped with an immersed electrode humidifier to
wet the air in cases where the air humidity is below the setpoint stored. The operating principle of the
humidifier is as follows. A container featuring lectrodes is filled with water until the electrodes are slightly
covered, as water serves as the conducting medium between the electrodes. The Joule effect causes the
running current to heat the water which evaporates as soon as it reaches the boilingpoint. The utput
vapour is transferred to the environment. The solution with immersed electrodes is fully safe from a health
standpoint and it is designed for proportional adjustment of vapour generation.

ELECTRICAL CONTROL PANEL

The electrical panel located in a dedicated compartment and separately from the air flow is made in
accordance with IEC standards. It includes:
• a main power switch;
• automatic switches for the power circuit and the auxiliary circuit;
• contactors for power loads;
• phase sequence relays (on direct expansion, three-phase units);
• a transformer to separate the power lines of the power circuits and the control circuits;
• a microprocessor electronic controller;
• an auxiliary terminal board for the electrical connection of loads and external signals/ok signals.
The electrical control panel is always accessible from the front part of the unit. The main power switch is
supplied with a door lock handle that prevents opening of the electrical control panel door if the power
supply is enabled. The electrical control panel is structured in such way that it meets protection level IP42.
The microprocessor controller inside the electrical control panel is provided with the following
functions/features:
• display showing the return air temperature;
• humidity (versions HH or featuring the relevant option);
• display showing the temperature in the delivery line;
• display showing the fan speed;
• two-level alarm message(s) (serious alarm and minor alarm);
• log recording of the last 100 alarms;
• operating hour meter;
• display showing the status of the controlled devices;
• display showing the status of inputs and outputs of the microprocessor.
Power supply [V/ph/Hz]: 230/1~/50 ±5% for sizes 6.1, 8.1; 400/3~/50 ±5% for the other models. The
following potential-free contacts are supplied in the terminal board as standard:
• remote ON/OFF;
• serious alarm;
• minor alarm (message).

BLUE THINK DATA

The Blue Think Data software fully incorporates the knowhow and expertise of Swegon-Blue Box in Data
Cooling applications. Blue Think Data is developed and constantly updated in-house through a continual
improvement process. Blue Think Data was conceived for the best functionality of the various units and
systems installed in multiple machines, and at the same time it guarantees the highest safety level for
both the components and application. The graphic interface was designed for immediate feedback on the

pag. 4/12
24/01/2025
CHDesign - v2.9

operating condition as well as for easy and efficient access to the various functionalities. Blue Think Data
incorporates the following key functions:
• control of return temperature;
• Outlet temperature water control(only for motocondenser with inverter);
• delivery temperature restriction;
• control of either relative or absolute humidity in the return line (only applies to units with the necessary
sensor and/or humidifier);
• multiple solutions for ventilation control (with modulating fans and their options);
• integrated condensation control (where the relevant options have been selected);
• advanced alarm management: recording of 100 alarms in the memory, division of alarms into two
categories (minor and serious alarms), smart automatic reset;
• auto restart after a voltage failure;
• function for absorption limitation, which is implemented either via the setting of a limit absorption value
or via an external digital request signal (only if the relevant options have been selected);
• integrated clock for timer-controlled switch-on/off and setpoint variation according to time bands;
• password-protected levels of access to parameter setup pages, protection against undesired tampering
or tampering by unauthorised/non qualified staff;
• multi language interface, which the operator can select in real time;
• management of multiple locally networked units (up to 32) for integrated and optimised operation (if the
corresponding option has been selected).
Specific functionalities (e.g. Local Network, Air free cooling, Ventilation) and set-up solutions are illustrated
in more in-depth details in the relevant sections.
HARDWARE
input/output boards including a 32-bit, 100 MHz microprocessor, with a 128-Mbyte non-volatile (FLASH)
memory, 90Mbyte of which are available as file storage, and a 16 Mbyte data memory (RAM). Three
different board sizes are used to optimise the number of nputs and outputs with respect to the application;
a humidifier-specific I/O board (which is therefore only fitted if this option is selected) communicating with
the master board in serial mode;a driver for the electronic expansion valve (where this option is elected)
to pilot the electronic valve and integrate its data and functions in the machine. Communicationwith the
master board is in serial mode. The graphic terminal is a 4.3” touch screen panel. The electronic technology
featured and the 65.000 colour display help manage high quality images and advanced functions. The
touch screen panel is also designed for easier man-machine interaction as it makes screen browsing much
more user-friendly. The display is also supplied with a LED bar featuring different message- ssociated
colours. The machine status can be viewed at any time without having to go close to the display. Another
innovative feature is the front position of the USB outlet for easier access without the use of specific tools.

TESTING

All units are leak tested for possible leaks. Units are filled with a mix of nitrogen and helium (30 bar for
direct expansion systems). The circuit is pressurised and left in such condition for a predefined period of
time (which varies according to the mix used), after which the pressure level is tested. The entire circuit
is also checked for micro leaks with a sniffer. The units are then subjected to a functional test which
includes the following, among others:
• inspection that the correct options are fitted and the necessary documentation is available;
• software uploading in the unit controller and parameter setup, based on the unit and the featured options;
• inspection that the probes can read correctly and probe calibration, where necessary;
• functional dry run testing.
The units are finally delivered as follows:

pag. 5/12
24/01/2025
CHDesign - v2.9

• chilled water or direct expansion unit versions without compressor - with a nitrogen-filled
hydraulic/refrigerant circuit.

PACKAGING AND SHIPMENT

All Datatech units are anchored to a pallet at the time of shipment, with corners protected by polyethylene
angular pieces and wrapped in stretch film.

Selected accessories:

UNDE - Downward air ejection

VEC - EC fans
-

CRM - Provision for remote condenser (with speed regulator)


This option is mandatory if an air-condensed, direct expansion unit (EDA) is combined with a remote
condenser supplied by our company, type Standard, Plus, Low Noise, with AC fans. This set-up consists in
an automatic switch and in the regulation of the fan speed in the remote condenser. Speed is regulated by
a phase-cutting speed regulator that is directly commanded by the microprocessor fitted on board the unit.
These components are always installed inside the unit.

GRLD - "Datalink" local network management


-

A43N - 400/3+N/50 power supply


400/3+N/50 power supply

GABB - Packaging in wooden crate


The unit is protected by a made-to-measure wooden crate. The accessory is mandatory if shipping by
container is required

AC PLUS - LMC3N1541 - CONDENSER


Unit with remote condenser
Remote condensers with axial fans (230/1~/50 power supply) are included in air-condensed units (supplied
as option) in the standard, low noise, oversize, low noise oversize and high temperature (HT) versions.
The fan motors are AC or, ptionally, EC brushless (not for HT). The protective devices and the speed
regulator are included in the internal unit in this case (this does not apply to some HT models).

pag. 6/12
24/01/2025
CHDesign - v2.9

Model: Datatech BTD UEDA 32.1 HH


Option: UNDE-VEC-CRM-GRLD-A43N-GABB
Remote Model: AC PLUS - LMC3N1541
Remote Option: -

.............................................................................................................................................................

COOLING

Performance data Indoor air


Cooling capacity (A2) kW 29.6 Dry bulb temp. °C 24.0
Cooling capacity (sensible) kW 26.5 Relative humidity % 50.0%
(A2)
Latent capacity (Dehum.) kW 3.06 Specific humidity g/kg 9.3
(A2)
Total input power (A2) kW 9.52 Extract flow rate m³/h 7754
Compressor input power kW 8.44 Supply air
Input current (E0) A 16.6 Dry bulb temp. °C 13.7
Power factor (E0) - 0.83 Relative humidity % 90.4%
Heat rejection capacity kW 39.7 Specific humidity g/kg 8.8
EER W/W 3.11 Supply flow rate m³/h 7754
SEER W/W 2.78 Fan speed rpm 1380
SHR - 0.897 Fan input power kW 1.07
Gross performance Fan input current A 2.00
Cooling capacity (A2) kW 30.7 Fans available static pressure Pa 0
Cooling capacity (sensible) kW 27.6 Max fans available static Pa 377
(A2)
EER W/W 3.22 pressure
Reheating operation data (Full Load)
SEER W/W 2.90 Supply air temp. °C 17.1
Source Electric heaters - Punctual operat. data
Altitude m 0.0 State Off
Dry bulb outdoor air °C 35.0 Total input power (A2) kW 0.00
Outdoor air Relative humidity % 49.3 Reheating operation data (Full Load)
Air flow rate m³/h 10163 Total input power (A2) kW 9.00
Fan input power kW 0.53
Fan input current A 3.18
Fans available static pressure Pa 0

pag. 7/12
24/01/2025
CHDesign - v2.9

DESIGN AND SIZING DATA

GENERAL DATA
Compressor type Scroll ELECTRICAL DATA
Number of compressors 1 Nominal voltage supply Ph/V/Hz 3/400/50+N
Number of circuits 1 Maximum voltage supply V 440
Capacity steps 1 Minimum voltage supply V 360
Minimum capacity step % 100.0 Maximum input power (P1) kW 24.4
Refrigerant type R410A Maximum input current (E0) A 42.7
GWP 2088 Maximum peak current (E0) A 22.2
Total refrigerant charge (R1) kg 3.30 Input power in stand-by mode kW 0.0100
CO2 equivalent charge kg 6889 Power factor (E0) 0.83

DIMENSIONS Sound data (C2)


Length mm 1102 Calculated sound power dB(A) 69
Width mm 850 Sound pressure(C0) [2.0 m] dB(A) 49
Height mm 1990
Shipping weight kg 443
Net weight kg 404

AIR CIRCUIT COMPONENTS

Supply fan Humidifier data


Fan type Plug fan Number 1
Fan motor EC Nominal flow rate kg/h 5.00
Number of fans 1 Maximum input power (P1) kW 3.75
Maximum input power (P1) kW 2.27 Maximum input current (E0) A 5.40
Maximum input current (E0) A 3.80

Electric heaters data


Air filter Number 1
Extract filter Maximum input power (P1) kW 9.00
Number 1 Maximum input current (E0) A 13.0
Class Coarse

pag. 8/12
24/01/2025
CHDesign - v2.9

REMOTE HEAT EXCHANGER

GENERAL DATA DIMENSIONS


Number 1 Length mm 2982
AC PLUS - Width mm 480
Model
LMC3N1541 Height mm 510
Fan type Axial Shipping weight kg 139
Fan motor AC Net weight kg 88.0
Number of fans 4
Total refrigerant charge (R1) kg 1.90 Sound data (C2)
CO2 equivalent charge kg 3966 Calculated sound power dB(A) 77
Sound pressure(C0) [2.0 m] dB(A) 57
ELECTRICAL DATA
Nominal voltage supply Ph/V/Hz 1/230/50+N
Maximum voltage supply V 253
Minimum voltage supply V 207
Maximum input power (P1) kW 0.74
Maximum input current (E0) A 3.32
Maximum peak current (E0) A 0.830
Input power in stand-by mode kW 0.0100
Power factor (E0) 0.75

(A0) Technical data shown are not binding. The Company shall have the right to introduce at any time whatever modifications necessary to the improvement of the product.
(A2) According to standard: EN 14511-2022
(C0) Noise pressure is calculated according to the following sound propagation method: Hemispherical ISO EN 3744 source

(C2) Calculated sound power cooling mode: unit operating at nominal operating capacity, without any accesories. Calculated sound power is the only binding value.

The acoustic data relates to the standard conditions described above, in referable and reproducible operating modes.
All data except Calculated sound are given for the mere purpose of example and can not be used for predictive purposes or for the verification of enforced limits.
With specific reference to the acoustic emissions, the Manufacturer commits to their conformity limited to the declared "Calculated sound power" value.
Any liability of the Manufacturer is excluded concerning the impact of such emissions with reference to the location of the plant and to other conditions related to the installation
of the unit.
The environment and the installation’s characteristics, besides the operating modes, may alter the acoustic emissions.
The overall acoustic evaluation, with regard to site conditions, remains the responsibility of the installer.
(E0) Electrical data may change without notice. It is therefore necessary to always refer to the electrical diagram.

pag. 9/12
24/01/2025
CHDesign - v2.9

Category Code Description Q.ty

Datatech BTD UEDA 32.1


Close control - 2
HH

FAN SECTION ACCESSORIES UNDE Downward air ejection 2

FAN SECTION ACCESSORIES VEC EC fans 2

Provision for remote condenser (with speed


ELECTRICAL ACCESSORIES CRM 2
regulator)

ELECTRICAL ACCESSORIES GRLD "Datalink" local network management 2

ELECTRICAL ACCESSORIES A43N 400/3+N/50 power supply 2

VARIOUS ACCESSORIES GABB Packaging in wooden crate 2

pag. 10/12
24/01/2025
CHDesign - v2.9

REMOTE CONDENSER / DRY


AC PLUS - LMC3N1541 CONDENSER 2
COOLER

pag. 11/12
24/01/2025
CHDesign - v2.9

pag. 12/12