0% found this document useful (0 votes)
5 views

Project Report

This document outlines a lighting project created with DIALux, including planning notes, a detailed table of contents, and descriptions of various sites and buildings involved. It includes luminaire lists, dimming values, and calculation objects for different rooms and light scenes. The document serves as a comprehensive guide for the project's lighting design and specifications.

Uploaded by

AJITH KANNAN
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
5 views

Project Report

This document outlines a lighting project created with DIALux, including planning notes, a detailed table of contents, and descriptions of various sites and buildings involved. It includes luminaire lists, dimming values, and calculation objects for different rooms and light scenes. The document serves as a comprehensive guide for the project's lighting design and specifications.

Uploaded by

AJITH KANNAN
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 160

Date 08-02-2025

Project

Created with DIALux


Project

Preface

Notes on planning:

The energy consumption quantities do not take into account light


scenes and their dimming levels.
Project

Table of Contents

Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dimming values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9. . . . . . . . . . . . . . . . . . . . . . . . . . . .

Product data sheets


Luceco PLC - Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 . . . . . . . . . . . . . . . . . . . . . . . 10
..............................
STD (1x LED)

Site 1
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
..............................

Site 1

Building 1
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
..............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
.............................

Site 1 - Building 1

Storey 1
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
..............................
Room list / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21 .............................
Control groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24 .............................

Site 1 - Building 1 - Storey 1

Room 1
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
..............................
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29 .............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32 .............................
Working plane (Room 1) / Light scene 1 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34 .............................
Project

Table of Contents

Control groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35


.............................

Site 1 - Building 1 - Storey 1

Room 2
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 ..............................
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38 .............................
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
40
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
42
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43.............................
Working plane (Room 2) / Light scene 1 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
Control groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
46

Site 1 - Building 1 - Storey 1

Room 3
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 ..............................
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
49
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51.............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
54.............................
Working plane (Room 3) / Light scene 1 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
Control groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57.............................

Site 1 - Building 1 - Storey 1

Room 4
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 ..............................
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
60
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62.............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
65.............................
Working plane (Room 4) / Light scene 1 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
Control groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68.............................

Site 1 - Building 1 - Storey 1

Room 5
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 ..............................
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
71
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73.............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
76.............................
Project

Table of Contents

Working plane (Room 5) / Light scene 1 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78 .............................


Control groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.

Site 1 - Building 1 - Storey 1

Room 6
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81 ..............................
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
82
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84.............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .87.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
88.............................
Working plane (Room 6) / Light scene 1 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90. . . . . . . . . . . . . . . . . . . . . . . . . . . .
.
Control groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91.............................

Site 1 - Building 1 - Storey 1

Room 7
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 ..............................
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .............................
94
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96.............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .98.............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
99.............................
Working plane (Room 7) / Light scene 1 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
101. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. .
Control groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
102

Site 1 - Building 1 - Storey 1

Room 8
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104 ...............................
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
105
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
107
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
109..............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
110..............................
Working plane (Room 8) / Light scene 1 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
112. .............................
Control groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .113. . . . . . . . . . . . . . . . . . . . . . . . . . . .
. .

Site 1 - Building 1 - Storey 1

Room 9
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115 ...............................
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
116
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
118
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
120
Project

Table of Contents

Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121 ...............................


Working plane (Room 9) / Light scene 1 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
123..............................
Control groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
124 .............................

Site 1 - Building 1 - Storey 1

Room 10
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126 ...............................
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
127
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .129..............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
131 ..............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
132 ..............................
Working plane (Room 10) / Light scene 1 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
134 ..............................
Control groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .135. .............................

Site 1 - Building 1 - Storey 1

Room 11
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137 ...............................
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
138
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
140..............................
Working plane (Room 11) / Light scene 1 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
142..............................

Site 1 - Building 1 - Storey 1

Room 12
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143 ...............................
Summary / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..............................
144
Luminaire layout plan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .146..............................
Luminaire list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
148 ..............................
Calculation objects / Light scene 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
149 ..............................
Working plane (Room 12) / Light scene 1 / Perpendicular illuminance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
151 ..............................
Control groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .152. .............................

Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .154
..............................
Project

Description

7
Project

Luminaire list

Φtotal Ptotal Luminous efficacy


600000 lm 5000.0 W 120.0 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

100 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 4000K IP65 STD

8
Project

Dimming values

Control group CG 1

Light scene 1 100

Dimming values [%]

9
Project

Product data sheet

Luceco PLC - Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD

Article No. LCL15O70ULS40-DW

P 50.0 W

ΦLamp –

ΦLuminaire 6000 lm

η –
Polar LDC
Luminous efficacy 120.0 lm/W

CCT 4000 K

CRI 80

RUG diagram (SHR: 0.25)

10
Project

Site 1
Description

11
Project

Building 1
Description

12
Project

Building 1
Luminaire list

Φtotal Ptotal Luminous efficacy


600000 lm 5000.0 W 120.0 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

100 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 4000K IP65 STD

13
Project

Building 1 · Storey 1
Description

14
Project

Building 1 · Storey 1 (Light scene 1)


Room list

15
Project

Building 1 · Storey 1 (Light scene 1)


Room list

Room 1

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


300.0 W 16.12 m² 18.61 W/m² = 2.74 W/m²/100 lx (Space) 678 lx
33.30 W/m² = 4.91 W/m²/100 lx (Working plane)

pcs. Manufacturer Article No. Article name P ΦLuminaire

6 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD 50.0 W 6000 lm
ULS40-DW

Room 2

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


300.0 W 17.16 m² 17.48 W/m² = 2.86 W/m²/100 lx (Space) 611 lx
28.78 W/m² = 4.71 W/m²/100 lx (Working plane)

pcs. Manufacturer Article No. Article name P ΦLuminaire

6 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD 50.0 W 6000 lm
ULS40-DW

Room 3

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


350.0 W 33.17 m² 10.55 W/m² = 2.10 W/m²/100 lx (Space) 502 lx
12.68 W/m² = 2.53 W/m²/100 lx (Working plane)

pcs. Manufacturer Article No. Article name P ΦLuminaire

7 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD 50.0 W 6000 lm
ULS40-DW

16
Project

Building 1 · Storey 1 (Light scene 1)


Room list

Room 4

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


400.0 W 30.38 m² 13.17 W/m² = 2.09 W/m²/100 lx (Space) 631 lx
19.96 W/m² = 3.16 W/m²/100 lx (Working plane)

pcs. Manufacturer Article No. Article name P ΦLuminaire

8 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD 50.0 W 6000 lm
ULS40-DW

Room 5

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


450.0 W 44.98 m² 10.01 W/m² = 1.79 W/m²/100 lx (Space) 560 lx
13.83 W/m² = 2.47 W/m²/100 lx (Working plane)

pcs. Manufacturer Article No. Article name P ΦLuminaire

9 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD 50.0 W 6000 lm
ULS40-DW

Room 6

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


1000.0 W 113.86 m² 8.78 W/m² = 1.42 W/m²/100 lx (Space) 617 lx
10.69 W/m² = 1.73 W/m²/100 lx (Working plane)

pcs. Manufacturer Article No. Article name P ΦLuminaire

20 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD 50.0 W 6000 lm
ULS40-DW

17
Project

Building 1 · Storey 1 (Light scene 1)


Room list

Room 7

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


200.0 W 11.20 m² 17.86 W/m² = 3.29 W/m²/100 lx (Space) 543 lx
35.15 W/m² = 6.47 W/m²/100 lx (Working plane)

pcs. Manufacturer Article No. Article name P ΦLuminaire

4 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD 50.0 W 6000 lm
ULS40-DW

Room 8

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


400.0 W 29.98 m² 13.34 W/m² = 2.15 W/m²/100 lx (Space) 621 lx
20.59 W/m² = 3.32 W/m²/100 lx (Working plane)

pcs. Manufacturer Article No. Article name P ΦLuminaire

8 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD 50.0 W 6000 lm
ULS40-DW

Room 9

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


600.0 W 132.83 m² 4.52 W/m² = 1.48 W/m²/100 lx (Space) 305 lx

pcs. Manufacturer Article No. Article name P ΦLuminaire

12 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD 50.0 W 6000 lm
ULS40-DW

18
Project

Building 1 · Storey 1 (Light scene 1)


Room list

Room 10

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


450.0 W 41.95 m² 10.73 W/m² = 2.00 W/m²/100 lx (Space) 537 lx
11.83 W/m² = 2.20 W/m²/100 lx (Working plane)

pcs. Manufacturer Article No. Article name P ΦLuminaire

9 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD 50.0 W 6000 lm
ULS40-DW

Room 12

Ptotal ARoom Lighting power density Ēperpendicular (Working plane)


550.0 W 93.00 m² 5.91 W/m² = 2.78 W/m²/100 lx (Space) 213 lx
6.59 W/m² = 3.10 W/m²/100 lx (Working plane)

pcs. Manufacturer Article No. Article name P ΦLuminaire

11 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD 50.0 W 6000 lm
ULS40-DW

19
Project

Building 1 · Storey 1
Luminaire list

Φtotal Ptotal Luminous efficacy


600000 lm 5000.0 W 120.0 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

100 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 4000K IP65 STD

20
Project

Building 1 · Storey 1 (Light scene 1)


Calculation objects

21
Project

Building 1 · Storey 1 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 12) 213 lx 37.2 lx 400 lx 0.17 0.093 WP1
Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.098 m

Working plane (Room 11) 0.00 lx 0.00 lx 0.00 lx - - WP2


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.413 m

Working plane (Room 10) 537 lx 407 lx 649 lx 0.76 0.63 WP3
Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.150 m

Working plane (Room 9) 305 lx 131 lx 400 lx 0.43 0.33 WP4


Perpendicular illuminance (≥ 200 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

Working plane (Room 8) 621 lx 517 lx 702 lx 0.83 0.74 WP5


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.500 m

Working plane (Room 7) 543 lx 503 lx 572 lx 0.93 0.88 WP6


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.480 m

Working plane (Room 6) 617 lx 454 lx 724 lx 0.74 0.63 WP7


Perpendicular illuminance (≥ 200 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.500 m

Working plane (Room 5) 560 lx 445 lx 650 lx 0.79 0.68 WP8


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.500 m

Working plane (Room 4) 631 lx 537 lx 695 lx 0.85 0.77 WP9


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.500 m

Working plane (Room 3) 502 lx 386 lx 601 lx 0.77 0.64 WP10


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.234 m

Working plane (Room 2) 611 lx 522 lx 682 lx 0.85 0.77 WP11


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.413 m

22
Project

Building 1 · Storey 1 (Light scene 1)


Calculation objects

Working plane (Room 1) 678 lx 622 lx 726 lx 0.92 0.86 WP12


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.500 m

23
Project

Building 1 · Storey 1
Control group CG 1

24
Project

Building 1 · Storey 1
Control groups

Control group CG 1

Light scene 1 100

Dimming values [%]

pcs. Manufacturer Article No. Article name P Index

100 Luceco PLC LCL15O70ULS40- Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K 50.0 W 1
DW IP65 STD

25
Project

Building 1 · Storey 1 · Room 1


Description

26
Project

Building 1 · Storey 1 · Room 1 (Light scene 1)


Summary

Ground area 16.12 m² Clearance height 7

Reflection factors Ceiling: 70.0 %, Mounting height 4.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.500 m

27
Project

Building 1 · Storey 1 · Room 1 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 678 lx ≥ 500 lx WP12

Uo (g1 ) 0.92 ≥ 0.60 WP12

Lighting power density 33.30 W/m² –

4.91 W/m²/100 lx –

Glare valuation(1) RUG, max 22 ≤ 19

Energy estimation(2) Consumption 743 kWh/a max. 600 kWh/a

Space Lighting power density 18.61 W/m² –

2.74 W/m²/100 lx –

(1) Based on a rectangular space of 3.489 m x 4.620 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (34.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

6 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 22 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 6000LM 4000K IP65 STD

28
Project

Building 1 · Storey 1 · Room 1


Luminaire layout plan

29
Project

Building 1 · Storey 1 · Room 1


Luminaire layout plan

Manufacturer Luceco PLC P 50.0 W

Article No. LCL15O70ULS40-DW ΦLuminaire 6000 lm

Article name Climate PRO


weatherproof PC-
PMMA 50W 6000LM
4000K IP65 STD

Fitting 1x LED

6 x Luceco PLC Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.770 m / 0.872 m /
4.500 m 0.770 m 2.616 m 4.500 m 1

X-direction 3 pcs., Centre - 2.310 m 2.616 m 4.500 m 2


centre, 1.540 m
3.850 m 2.616 m 4.500 m 3
Y-direction 2 pcs., Centre -
centre, 1.744 m 0.770 m 0.872 m 4.500 m 4

Arrangement A1 2.310 m 0.872 m 4.500 m 5

3.850 m 0.872 m 4.500 m 6

30
Project

Building 1 · Storey 1 · Room 1


Luminaire list

Φtotal Ptotal Luminous efficacy


36000 lm 300.0 W 120.0 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

6 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 4000K IP65 STD

31
Project

Building 1 · Storey 1 · Room 1 (Light scene 1)


Calculation objects

32
Project

Building 1 · Storey 1 · Room 1 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 1) 678 lx 622 lx 726 lx 0.92 0.86 WP12


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.500 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

33
Project

Building 1 · Storey 1 · Room 1 (Light scene 1)


Working plane (Room 1)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 1) 678 lx 622 lx 726 lx 0.92 0.86 WP12


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.500 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

34
Project

Building 1 · Storey 1 · Room 1


Control group CG 1

35
Project

Building 1 · Storey 1 · Room 1


Control groups

Control group CG 1

Light scene 1 100

Dimming values [%]

pcs. Manufacturer Article No. Article name P Index

6 Luceco PLC LCL15O70ULS40- Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K 50.0 W 1
DW IP65 STD

36
Project

Building 1 · Storey 1 · Room 2


Description

37
Project

Building 1 · Storey 1 · Room 2 (Light scene 1)


Summary

Ground area 17.16 m² Clearance height 4.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 4.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.413 m

38
Project

Building 1 · Storey 1 · Room 2 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 611 lx ≥ 500 lx WP11

Uo (g1 ) 0.85 ≥ 0.60 WP11

Lighting power density 28.78 W/m² –

4.71 W/m²/100 lx –

Glare valuation(1) RUG, max 22 ≤ 19

Energy estimation(2) Consumption 743 kWh/a max. 650 kWh/a

Space Lighting power density 17.48 W/m² –

2.86 W/m²/100 lx –

(1) Based on a rectangular space of 6.240 m x 2.750 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (34.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

6 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 22 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 6000LM 4000K IP65 STD

39
Project

Building 1 · Storey 1 · Room 2


Luminaire layout plan

40
Project

Building 1 · Storey 1 · Room 2


Luminaire layout plan

Manufacturer Luceco PLC P 50.0 W

Article No. LCL15O70ULS40-DW ΦLuminaire 6000 lm

Article name Climate PRO


weatherproof PC-
PMMA 50W 6000LM
4000K IP65 STD

Fitting 1x LED

6 x Luceco PLC Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.040 m / 0.688 m /
4.500 m 1.040 m 2.063 m 4.500 m 1

X-direction 3 pcs., Centre - 3.120 m 2.063 m 4.500 m 2


centre, 2.080 m
5.200 m 2.063 m 4.500 m 3
Y-direction 2 pcs., Centre -
centre, 1.375 m 1.040 m 0.688 m 4.500 m 4

Arrangement A1 3.120 m 0.688 m 4.500 m 5

5.200 m 0.688 m 4.500 m 6

41
Project

Building 1 · Storey 1 · Room 2


Luminaire list

Φtotal Ptotal Luminous efficacy


36000 lm 300.0 W 120.0 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

6 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 4000K IP65 STD

42
Project

Building 1 · Storey 1 · Room 2 (Light scene 1)


Calculation objects

43
Project

Building 1 · Storey 1 · Room 2 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 2) 611 lx 522 lx 682 lx 0.85 0.77 WP11


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.413 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

44
Project

Building 1 · Storey 1 · Room 2 (Light scene 1)


Working plane (Room 2)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 2) 611 lx 522 lx 682 lx 0.85 0.77 WP11


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.413 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

45
Project

Building 1 · Storey 1 · Room 2


Control group CG 1

46
Project

Building 1 · Storey 1 · Room 2


Control groups

Control group CG 1

Light scene 1 100

Dimming values [%]

pcs. Manufacturer Article No. Article name P Index

6 Luceco PLC LCL15O70ULS40- Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K 50.0 W 1
DW IP65 STD

47
Project

Building 1 · Storey 1 · Room 3


Description

48
Project

Building 1 · Storey 1 · Room 3 (Light scene 1)


Summary

Ground area 33.17 m² Clearance height 4.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 4.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.234 m

49
Project

Building 1 · Storey 1 · Room 3 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 502 lx ≥ 500 lx WP10

Uo (g1 ) 0.77 ≥ 0.60 WP10

Lighting power density 12.68 W/m² –

2.53 W/m²/100 lx –

Glare valuation(1) RUG, max 22 ≤ 19

Energy estimation(2) Consumption 866 kWh/a max. 1200 kWh/a

Space Lighting power density 10.55 W/m² –

2.10 W/m²/100 lx –

(1) Based on a rectangular space of 6.280 m x 6.077 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (34.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

7 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 22 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 6000LM 4000K IP65 STD

50
Project

Building 1 · Storey 1 · Room 3


Luminaire layout plan

51
Project

Building 1 · Storey 1 · Room 3


Luminaire layout plan

Manufacturer Luceco PLC P 50.0 W

Article No. LCL15O70ULS40-DW ΦLuminaire 6000 lm

Article name Climate PRO


weatherproof PC-
PMMA 50W 6000LM
4000K IP65 STD

Fitting 1x LED

7 x Luceco PLC Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.785 m / 1.519 m /
4.500 m 2.355 m 4.557 m 4.500 m 1

X-direction 4 pcs., Centre - 3.925 m 4.557 m 4.500 m 2


centre, 1.570 m
5.495 m 4.557 m 4.500 m 3
Y-direction 2 pcs., Centre -
centre, 3.038 m 0.785 m 1.519 m 4.500 m 4

Arrangement A1 2.355 m 1.519 m 4.500 m 5

3.925 m 1.519 m 4.500 m 6

5.495 m 1.519 m 4.500 m 7

52
Project

Building 1 · Storey 1 · Room 3


Luminaire list

Φtotal Ptotal Luminous efficacy


42000 lm 350.0 W 120.0 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

7 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 4000K IP65 STD

53
Project

Building 1 · Storey 1 · Room 3 (Light scene 1)


Calculation objects

54
Project

Building 1 · Storey 1 · Room 3 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 3) 502 lx 386 lx 601 lx 0.77 0.64 WP10


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.234 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

55
Project

Building 1 · Storey 1 · Room 3 (Light scene 1)


Working plane (Room 3)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 3) 502 lx 386 lx 601 lx 0.77 0.64 WP10


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.234 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

56
Project

Building 1 · Storey 1 · Room 3


Control group CG 1

57
Project

Building 1 · Storey 1 · Room 3


Control groups

Control group CG 1

Light scene 1 100

Dimming values [%]

pcs. Manufacturer Article No. Article name P Index

7 Luceco PLC LCL15O70ULS40- Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K 50.0 W 1
DW IP65 STD

58
Project

Building 1 · Storey 1 · Room 4


Description

59
Project

Building 1 · Storey 1 · Room 4 (Light scene 1)


Summary

Ground area 30.38 m² Clearance height 4.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 4.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.500 m

60
Project

Building 1 · Storey 1 · Room 4 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 631 lx ≥ 500 lx WP9

Uo (g1 ) 0.85 ≥ 0.60 WP9

Lighting power density 19.96 W/m² –

3.16 W/m²/100 lx –

Glare valuation(1) RUG, max 22 ≤ 19

Energy estimation(2) Consumption 990 kWh/a max. 1100 kWh/a

Space Lighting power density 13.17 W/m² –

2.09 W/m²/100 lx –

(1) Based on a rectangular space of 4.340 m x 7.000 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (34.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

8 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 22 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 6000LM 4000K IP65 STD

61
Project

Building 1 · Storey 1 · Room 4


Luminaire layout plan

62
Project

Building 1 · Storey 1 · Room 4


Luminaire layout plan

Manufacturer Luceco PLC P 50.0 W

Article No. LCL15O70ULS40-DW ΦLuminaire 6000 lm

Article name Climate PRO


weatherproof PC-
PMMA 50W 6000LM
4000K IP65 STD

Fitting 1x LED

8 x Luceco PLC Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.542 m / 1.750 m /
4.500 m 0.542 m 5.250 m 4.500 m 1

X-direction 4 pcs., Centre - 1.627 m 5.250 m 4.500 m 2


centre, 1.085 m
2.712 m 5.250 m 4.500 m 3
Y-direction 2 pcs., Centre -
centre, 3.500 m 3.797 m 5.250 m 4.500 m 4

Arrangement A1 0.542 m 1.750 m 4.500 m 5

1.627 m 1.750 m 4.500 m 6

2.712 m 1.750 m 4.500 m 7

3.797 m 1.750 m 4.500 m 8

63
Project

Building 1 · Storey 1 · Room 4


Luminaire list

Φtotal Ptotal Luminous efficacy


48000 lm 400.0 W 120.0 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

8 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 4000K IP65 STD

64
Project

Building 1 · Storey 1 · Room 4 (Light scene 1)


Calculation objects

65
Project

Building 1 · Storey 1 · Room 4 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 4) 631 lx 537 lx 695 lx 0.85 0.77 WP9


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.500 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

66
Project

Building 1 · Storey 1 · Room 4 (Light scene 1)


Working plane (Room 4)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 4) 631 lx 537 lx 695 lx 0.85 0.77 WP9


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.500 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

67
Project

Building 1 · Storey 1 · Room 4


Control group CG 1

68
Project

Building 1 · Storey 1 · Room 4


Control groups

Control group CG 1

Light scene 1 100

Dimming values [%]

pcs. Manufacturer Article No. Article name P Index

8 Luceco PLC LCL15O70ULS40- Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K 50.0 W 1
DW IP65 STD

69
Project

Building 1 · Storey 1 · Room 5


Description

70
Project

Building 1 · Storey 1 · Room 5 (Light scene 1)


Summary

Ground area 44.98 m² Clearance height 4.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 4.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.500 m

71
Project

Building 1 · Storey 1 · Room 5 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 560 lx ≥ 500 lx WP8

Uo (g1 ) 0.79 ≥ 0.60 WP8

Lighting power density 13.83 W/m² –

2.47 W/m²/100 lx –

Glare valuation(1) RUG, max 22 ≤ 19

Energy estimation(2) Consumption 1114 kWh/a max. 1600 kWh/a

Space Lighting power density 10.01 W/m² –

1.79 W/m²/100 lx –

(1) Based on a rectangular space of 7.000 m x 6.490 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (34.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

9 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 22 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 6000LM 4000K IP65 STD

72
Project

Building 1 · Storey 1 · Room 5


Luminaire layout plan

73
Project

Building 1 · Storey 1 · Room 5


Luminaire layout plan

Manufacturer Luceco PLC P 50.0 W

Article No. LCL15O70ULS40-DW ΦLuminaire 6000 lm

Article name Climate PRO


weatherproof PC-
PMMA 50W 6000LM
4000K IP65 STD

Fitting 1x LED

9 x Luceco PLC Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.082 m / 1.167 m /
4.500 m 1.082 m 5.833 m 4.500 m 1

X-direction 3 pcs., Centre - 3.245 m 5.833 m 4.500 m 2


centre, 2.163 m
5.408 m 5.833 m 4.500 m 3
Y-direction 3 pcs., Centre -
centre, 2.333 m 3.245 m 3.500 m 4.500 m 4

Arrangement A1 1.082 m 3.500 m 4.500 m 5

5.408 m 3.500 m 4.500 m 6

1.082 m 1.167 m 4.500 m 7

3.245 m 1.167 m 4.500 m 8

5.408 m 1.167 m 4.500 m 9

74
Project

Building 1 · Storey 1 · Room 5


Luminaire list

Φtotal Ptotal Luminous efficacy


54000 lm 450.0 W 120.0 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

9 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 4000K IP65 STD

75
Project

Building 1 · Storey 1 · Room 5 (Light scene 1)


Calculation objects

76
Project

Building 1 · Storey 1 · Room 5 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 5) 560 lx 445 lx 650 lx 0.79 0.68 WP8


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.500 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

77
Project

Building 1 · Storey 1 · Room 5 (Light scene 1)


Working plane (Room 5)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 5) 560 lx 445 lx 650 lx 0.79 0.68 WP8


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.500 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

78
Project

Building 1 · Storey 1 · Room 5


Control group CG 1

79
Project

Building 1 · Storey 1 · Room 5


Control groups

Control group CG 1

Light scene 1 100

Dimming values [%]

pcs. Manufacturer Article No. Article name P Index

9 Luceco PLC LCL15O70ULS40- Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K 50.0 W 1
DW IP65 STD

80
Project

Building 1 · Storey 1 · Room 6


Description

81
Project

Building 1 · Storey 1 · Room 6 (Light scene 1)


Summary

Ground area 113.86 m² Clearance height 4.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 4.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.500 m

82
Project

Building 1 · Storey 1 · Room 6 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 617 lx ≥ 200 lx WP7

Uo (g1 ) 0.74 ≥ 0.40 WP7

Lighting power density 10.69 W/m² –

1.73 W/m²/100 lx –

Glare valuation(1) RUG, max 24 ≤ 25

Energy estimation(2) Consumption 165 kWh/a max. 4000 kWh/a

Space Lighting power density 8.78 W/m² –

1.42 W/m²/100 lx –

(1) Based on a rectangular space of 10.980 m x 10.370 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

20 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 24 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 6000LM 4000K IP65 STD

83
Project

Building 1 · Storey 1 · Room 6


Luminaire layout plan

84
Project

Building 1 · Storey 1 · Room 6


Luminaire layout plan

Manufacturer Luceco PLC P 50.0 W

Article No. LCL15O70ULS40-DW ΦLuminaire 6000 lm

Article name Climate PRO


weatherproof PC-
PMMA 50W 6000LM
4000K IP65 STD

Fitting 1x LED

20 x Luceco PLC Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.098 m / 1.296 m /
4.500 m 1.098 m 9.074 m 4.500 m 1

X-direction 5 pcs., Centre - 3.294 m 9.074 m 4.500 m 2


centre, 2.196 m
5.490 m 9.074 m 4.500 m 3
Y-direction 4 pcs., Centre -
centre, 2.593 m 7.686 m 9.074 m 4.500 m 4

Arrangement A1 9.882 m 9.074 m 4.500 m 5

1.098 m 6.481 m 4.500 m 6

3.294 m 6.481 m 4.500 m 7

5.490 m 6.481 m 4.500 m 8

7.686 m 6.481 m 4.500 m 9

9.882 m 6.481 m 4.500 m 10

1.098 m 3.889 m 4.500 m 11

3.294 m 3.889 m 4.500 m 12

85
Project

Building 1 · Storey 1 · Room 6


Luminaire layout plan

X Y Mounting Luminaire
height

5.490 m 3.889 m 4.500 m 13

7.686 m 3.889 m 4.500 m 14

9.882 m 3.889 m 4.500 m 15

1.098 m 1.296 m 4.500 m 16

3.294 m 1.296 m 4.500 m 17

5.490 m 1.296 m 4.500 m 18

7.686 m 1.296 m 4.500 m 19

9.882 m 1.296 m 4.500 m 20

86
Project

Building 1 · Storey 1 · Room 6


Luminaire list

Φtotal Ptotal Luminous efficacy


120000 lm 1000.0 W 120.0 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

20 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 4000K IP65 STD

87
Project

Building 1 · Storey 1 · Room 6 (Light scene 1)


Calculation objects

88
Project

Building 1 · Storey 1 · Room 6 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 6) 617 lx 454 lx 724 lx 0.74 0.63 WP7


Perpendicular illuminance (≥ 200 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.500 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

89
Project

Building 1 · Storey 1 · Room 6 (Light scene 1)


Working plane (Room 6)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 6) 617 lx 454 lx 724 lx 0.74 0.63 WP7


Perpendicular illuminance (≥ 200 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.500 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

90
Project

Building 1 · Storey 1 · Room 6


Control group CG 1

91
Project

Building 1 · Storey 1 · Room 6


Control groups

Control group CG 1

Light scene 1 100

Dimming values [%]

pcs. Manufacturer Article No. Article name P Index

20 Luceco PLC LCL15O70ULS40- Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K 50.0 W 1
DW IP65 STD

92
Project

Building 1 · Storey 1 · Room 7


Description

93
Project

Building 1 · Storey 1 · Room 7 (Light scene 1)


Summary

Ground area 11.20 m² Clearance height 4.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 4.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.480 m

94
Project

Building 1 · Storey 1 · Room 7 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 543 lx ≥ 500 lx WP6

Uo (g1 ) 0.93 ≥ 0.60 WP6

Lighting power density 35.15 W/m² –

6.47 W/m²/100 lx –

Glare valuation(1) RUG, max 22 ≤ 19

Energy estimation(2) Consumption 495 kWh/a max. 400 kWh/a

Space Lighting power density 17.86 W/m² –

3.29 W/m²/100 lx –

(1) Based on a rectangular space of 3.200 m x 3.500 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (34.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

4 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 22 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 6000LM 4000K IP65 STD

95
Project

Building 1 · Storey 1 · Room 7


Luminaire layout plan

96
Project

Building 1 · Storey 1 · Room 7


Luminaire layout plan

Manufacturer Luceco PLC P 50.0 W

Article No. LCL15O70ULS40-DW ΦLuminaire 6000 lm

Article name Climate PRO


weatherproof PC-
PMMA 50W 6000LM
4000K IP65 STD

Fitting 1x LED

4 x Luceco PLC Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.800 m / 0.875 m /
4.500 m 0.800 m 2.625 m 4.500 m 1

X-direction 2 pcs., Centre - 2.400 m 2.625 m 4.500 m 2


centre, 1.600 m
0.800 m 0.875 m 4.500 m 3
Y-direction 2 pcs., Centre -
centre, 1.750 m 2.400 m 0.875 m 4.500 m 4

Arrangement A1

97
Project

Building 1 · Storey 1 · Room 7


Luminaire list

Φtotal Ptotal Luminous efficacy


24000 lm 200.0 W 120.0 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

4 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 4000K IP65 STD

98
Project

Building 1 · Storey 1 · Room 7 (Light scene 1)


Calculation objects

99
Project

Building 1 · Storey 1 · Room 7 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 7) 543 lx 503 lx 572 lx 0.93 0.88 WP6


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.480 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

100
Project

Building 1 · Storey 1 · Room 7 (Light scene 1)


Working plane (Room 7)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 7) 543 lx 503 lx 572 lx 0.93 0.88 WP6


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.480 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

101
Project

Building 1 · Storey 1 · Room 7


Control group CG 1

102
Project

Building 1 · Storey 1 · Room 7


Control groups

Control group CG 1

Light scene 1 100

Dimming values [%]

pcs. Manufacturer Article No. Article name P Index

4 Luceco PLC LCL15O70ULS40- Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K 50.0 W 1
DW IP65 STD

103
Project

Building 1 · Storey 1 · Room 8


Description

104
Project

Building 1 · Storey 1 · Room 8 (Light scene 1)


Summary

Ground area 29.98 m² Clearance height 4.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 4.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.500 m

105
Project

Building 1 · Storey 1 · Room 8 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 621 lx ≥ 500 lx WP5

Uo (g1 ) 0.83 ≥ 0.60 WP5

Lighting power density 20.59 W/m² –

3.32 W/m²/100 lx –

Glare valuation(1) RUG, max 22 ≤ 19

Energy estimation(2) Consumption 990 kWh/a max. 1100 kWh/a

Space Lighting power density 13.34 W/m² –

2.15 W/m²/100 lx –

(1) Based on a rectangular space of 7.630 m x 3.930 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (34.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

8 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 22 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 6000LM 4000K IP65 STD

106
Project

Building 1 · Storey 1 · Room 8


Luminaire layout plan

107
Project

Building 1 · Storey 1 · Room 8


Luminaire layout plan

Manufacturer Luceco PLC P 50.0 W

Article No. LCL15O70ULS40-DW ΦLuminaire 6000 lm

Article name Climate PRO


weatherproof PC-
PMMA 50W 6000LM
4000K IP65 STD

Fitting 1x LED

8 x Luceco PLC Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 0.954 m / 0.983 m /
4.500 m 0.954 m 2.947 m 4.500 m 1

X-direction 4 pcs., Centre - 2.861 m 2.947 m 4.500 m 2


centre, 1.908 m
4.769 m 2.947 m 4.500 m 3
Y-direction 2 pcs., Centre -
centre, 1.965 m 6.676 m 2.947 m 4.500 m 4

Arrangement A1 0.954 m 0.983 m 4.500 m 5

2.861 m 0.983 m 4.500 m 6

4.769 m 0.983 m 4.500 m 7

6.676 m 0.983 m 4.500 m 8

108
Project

Building 1 · Storey 1 · Room 8


Luminaire list

Φtotal Ptotal Luminous efficacy


48000 lm 400.0 W 120.0 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

8 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 4000K IP65 STD

109
Project

Building 1 · Storey 1 · Room 8 (Light scene 1)


Calculation objects

110
Project

Building 1 · Storey 1 · Room 8 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 8) 621 lx 517 lx 702 lx 0.83 0.74 WP5


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.500 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

111
Project

Building 1 · Storey 1 · Room 8 (Light scene 1)


Working plane (Room 8)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 8) 621 lx 517 lx 702 lx 0.83 0.74 WP5


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.500 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

112
Project

Building 1 · Storey 1 · Room 8


Control group CG 1

113
Project

Building 1 · Storey 1 · Room 8


Control groups

Control group CG 1

Light scene 1 100

Dimming values [%]

pcs. Manufacturer Article No. Article name P Index

8 Luceco PLC LCL15O70ULS40- Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K 50.0 W 1
DW IP65 STD

114
Project

Building 1 · Storey 1 · Room 9


Description

115
Project

Building 1 · Storey 1 · Room 9 (Light scene 1)


Summary

Ground area 132.83 m² Clearance height 4.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 4.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.000 m

116
Project

Building 1 · Storey 1 · Room 9 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 305 lx ≥ 200 lx WP4

Uo (g1 ) 0.43 ≥ 0.40 WP4

Glare valuation(1) RUG, max 26 ≤ 25

Energy estimation(2) Consumption 99.0 kWh/a max. 4700 kWh/a

Space Lighting power density 4.52 W/m² –

1.48 W/m²/100 lx –

(1) Based on a rectangular space of 10.980 m x 14.600 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

12 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 26 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 6000LM 4000K IP65 STD

117
Project

Building 1 · Storey 1 · Room 9


Luminaire layout plan

118
Project

Building 1 · Storey 1 · Room 9


Luminaire layout plan

Manufacturer Luceco PLC P 50.0 W

Article No. LCL15O70ULS40-DW ΦLuminaire 6000 lm

Article name Climate PRO


weatherproof PC-
PMMA 50W 6000LM
4000K IP65 STD

Fitting 1x LED

12 x Luceco PLC Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.098 m / 2.433 m /
4.500 m 5.490 m 12.167 m 4.500 m 1

X-direction 5 pcs., Centre - 7.686 m 12.167 m 4.500 m 2


centre, 2.196 m
9.882 m 12.167 m 4.500 m 3
Y-direction 3 pcs., Centre -
centre, 4.867 m 1.098 m 7.300 m 4.500 m 4

Arrangement A1 3.294 m 7.300 m 4.500 m 5

5.490 m 7.300 m 4.500 m 6

7.686 m 7.300 m 4.500 m 7

9.882 m 7.300 m 4.500 m 8

1.098 m 2.433 m 4.500 m 9

3.294 m 2.433 m 4.500 m 10

5.490 m 2.433 m 4.500 m 11

7.686 m 2.433 m 4.500 m 12

119
Project

Building 1 · Storey 1 · Room 9


Luminaire list

Φtotal Ptotal Luminous efficacy


72000 lm 600.0 W 120.0 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

12 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 4000K IP65 STD

120
Project

Building 1 · Storey 1 · Room 9 (Light scene 1)


Calculation objects

121
Project

Building 1 · Storey 1 · Room 9 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 9) 305 lx 131 lx 400 lx 0.43 0.33 WP4


Perpendicular illuminance (≥ 200 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

122
Project

Building 1 · Storey 1 · Room 9 (Light scene 1)


Working plane (Room 9)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 9) 305 lx 131 lx 400 lx 0.43 0.33 WP4


Perpendicular illuminance (≥ 200 lx) (≥ 0.40)
Height: 0.800 m, Wall zone: 0.000 m

Utilisation profile: General areas inside buildings - Control rooms (11.1 Plant rooms, switchgear rooms)

123
Project

Building 1 · Storey 1 · Room 9


Control group CG 1

124
Project

Building 1 · Storey 1 · Room 9


Control groups

Control group CG 1

Light scene 1 100

Dimming values [%]

pcs. Manufacturer Article No. Article name P Index

12 Luceco PLC LCL15O70ULS40- Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K 50.0 W 1
DW IP65 STD

125
Project

Building 1 · Storey 1 · Room 10


Description

126
Project

Building 1 · Storey 1 · Room 10 (Light scene 1)


Summary

Ground area 41.95 m² Clearance height 4.500 m

Reflection factors Ceiling: 70.0 %, Mounting height 4.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.150 m

127
Project

Building 1 · Storey 1 · Room 10 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 537 lx ≥ 500 lx WP3

Uo (g1 ) 0.76 ≥ 0.60 WP3

Lighting power density 11.83 W/m² –

2.20 W/m²/100 lx –

Glare valuation(1) RUG, max 22 ≤ 19

Energy estimation(2) Consumption 1114 kWh/a max. 1500 kWh/a

Space Lighting power density 10.73 W/m² –

2.00 W/m²/100 lx –

(1) Based on a rectangular space of 7.351 m x 5.990 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (34.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

9 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 22 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 6000LM 4000K IP65 STD

128
Project

Building 1 · Storey 1 · Room 10


Luminaire layout plan

129
Project

Building 1 · Storey 1 · Room 10


Luminaire layout plan

Manufacturer Luceco PLC P 50.0 W

Article No. LCL15O70ULS40-DW ΦLuminaire 6000 lm

Article name Climate PRO


weatherproof PC-
PMMA 50W 6000LM
4000K IP65 STD

Fitting 1x LED

9 x Luceco PLC Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.225 m / 0.998 m /
4.500 m 1.225 m 4.992 m 4.500 m 1

X-direction 3 pcs., Centre - 3.676 m 4.992 m 4.500 m 2


centre, 2.450 m
6.126 m 4.992 m 4.500 m 3
Y-direction 3 pcs., Centre -
centre, 1.997 m 1.225 m 2.995 m 4.500 m 4

Arrangement A1 3.676 m 2.995 m 4.500 m 5

6.126 m 2.995 m 4.500 m 6

1.225 m 0.998 m 4.500 m 7

3.676 m 0.998 m 4.500 m 8

6.126 m 0.998 m 4.500 m 9

130
Project

Building 1 · Storey 1 · Room 10


Luminaire list

Φtotal Ptotal Luminous efficacy


54000 lm 450.0 W 120.0 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

9 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 4000K IP65 STD

131
Project

Building 1 · Storey 1 · Room 10 (Light scene 1)


Calculation objects

132
Project

Building 1 · Storey 1 · Room 10 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 10) 537 lx 407 lx 649 lx 0.76 0.63 WP3
Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.150 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

133
Project

Building 1 · Storey 1 · Room 10 (Light scene 1)


Working plane (Room 10)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 10) 537 lx 407 lx 649 lx 0.76 0.63 WP3
Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.150 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

134
Project

Building 1 · Storey 1 · Room 10


Control group CG 1

135
Project

Building 1 · Storey 1 · Room 10


Control groups

Control group CG 1

Light scene 1 100

Dimming values [%]

pcs. Manufacturer Article No. Article name P Index

9 Luceco PLC LCL15O70ULS40- Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K 50.0 W 1
DW IP65 STD

136
Project

Building 1 · Storey 1 · Room 11


Description

137
Project

Building 1 · Storey 1 · Room 11 (Light scene 1)


Summary

Ground area 17.02 m²

Reflection factors Ceiling: 70.0 %, Clearance height 4.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.413 m

138
Project

Building 1 · Storey 1 · Room 11 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 0.00 lx ≥ 500 lx WP2

Uo (g1 ) - ≥ 0.60 WP2

Lighting power density 0.00 W/m² –

Energy estimation(2) Consumption 0.00 kWh/a max. 600 kWh/a

Space Lighting power density 0.00 W/m² –

(1) Based on a rectangular space of 6.190 m x 2.750 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (34.2 Standard (office))

139
Project

Building 1 · Storey 1 · Room 11 (Light scene 1)


Calculation objects

140
Project

Building 1 · Storey 1 · Room 11 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 11) 0.00 lx 0.00 lx 0.00 lx - - WP2


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.413 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

141
Project

Building 1 · Storey 1 · Room 11 (Light scene 1)


Working plane (Room 11)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 11) 0.00 lx 0.00 lx 0.00 lx - - WP2


Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.413 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

142
Project

Building 1 · Storey 1 · Room 12


Description

143
Project

Building 1 · Storey 1 · Room 12 (Light scene 1)


Summary

Ground area 93.00 m² Clearance height 2.8

Reflection factors Ceiling: 70.0 %, Mounting height 4.500 m


Walls: 50.0 %,
Floor: 20.0 % Height Working plane 0.800 m

Maintenance factor 0.80 (fixed) Wall zone Working plane 0.098 m

144
Project

Building 1 · Storey 1 · Room 12 (Light scene 1)


Summary

Results

Symbol Calculated Target Check Index

Working plane Ēperpendicular 213 lx ≥ 500 lx WP1

Uo (g1 ) 0.17 ≥ 0.60 WP1

Lighting power density 6.59 W/m² –

3.10 W/m²/100 lx –

Glare valuation(1) RUG, max 27 ≤ 19

Energy estimation(2) Consumption 1361 kWh/a max. 3300 kWh/a

Space Lighting power density 5.91 W/m² –

2.78 W/m²/100 lx –

(1) Based on a rectangular space of 8.713 m x 36.583 m and SHR of 0.25.


(2) Calculated using DIN:18599-4.

Utilisation profile: DIALux presetting (34.2 Standard (office))

Luminaire list

pcs. Manufacturer Article No. Article name RUG P Φ Luminous efficacy

11 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 27 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 6000LM 4000K IP65 STD

145
Project

Building 1 · Storey 1 · Room 12


Luminaire layout plan

146
Project

Building 1 · Storey 1 · Room 12


Luminaire layout plan

Manufacturer Luceco PLC P 50.0 W

Article No. LCL15O70ULS40-DW ΦLuminaire 6000 lm

Article name Climate PRO


weatherproof PC-
PMMA 50W 6000LM
4000K IP65 STD

Fitting 1x LED

11 x Luceco PLC Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K IP65 STD

Type Field Arrangement X Y Mounting Luminaire


height
1st luminaire (X/Y/Z) 1.770 m / 0.789 m /
4.500 m 1.770 m 35.752 m 4.500 m 1

X-direction 6 pcs., Centre - 1.770 m 30.757 m 4.500 m 2


centre, 1.770 m
1.770 m 25.762 m 4.500 m 3
Y-direction 8 pcs., Centre -
centre, 4.995 m 1.770 m 20.767 m 4.500 m 4

Arrangement A1 1.770 m 15.773 m 4.500 m 5

1.770 m 10.778 m 4.500 m 6

1.770 m 5.783 m 4.500 m 7

1.770 m 0.789 m 4.500 m 8

3.540 m 0.789 m 4.500 m 9

5.310 m 0.789 m 4.500 m 10

7.080 m 0.789 m 4.500 m 11

147
Project

Building 1 · Storey 1 · Room 12


Luminaire list

Φtotal Ptotal Luminous efficacy


66000 lm 550.0 W 120.0 lm/W

pcs. Manufacturer Article No. Article name P Φ Luminous efficacy

11 Luceco PLC LCL15O70 Climate PRO weatherproof PC-PMMA 50W 6000LM 50.0 W 6000 lm 120.0 lm/W
ULS40-DW 4000K IP65 STD

148
Project

Building 1 · Storey 1 · Room 12 (Light scene 1)


Calculation objects

149
Project

Building 1 · Storey 1 · Room 12 (Light scene 1)


Calculation objects

Working planes

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 12) 213 lx 37.2 lx 400 lx 0.17 0.093 WP1
Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.098 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

150
Project

Building 1 · Storey 1 · Room 12 (Light scene 1)


Working plane (Room 12)

Properties Ē Emin Emax Uo (g1 ) g2 Index


(Target) (Target)

Working plane (Room 12) 213 lx 37.2 lx 400 lx 0.17 0.093 WP1
Perpendicular illuminance (≥ 500 lx) (≥ 0.60)
Height: 0.800 m, Wall zone: 0.098 m

Utilisation profile: DIALux presetting (34.2 Standard (office))

151
Project

Building 1 · Storey 1 · Room 12


Control group CG 1

152
Project

Building 1 · Storey 1 · Room 12


Control groups

Control group CG 1

Light scene 1 100

Dimming values [%]

pcs. Manufacturer Article No. Article name P Index

11 Luceco PLC LCL15O70ULS40- Climate PRO weatherproof PC-PMMA 50W 6000LM 4000K 50.0 W 1
DW IP65 STD

153
Project

Glossary

A Formula symbol for a surface in the geometry

Background area The background area borders the direct ambient area according to DIN EN 12464-1 and
reaches up to the borders of the room. In larger rooms, the background area is at least
3 m wide. It is located horizontally at floor level.

CCT (Engl. correlated colour temperature)


Body temperature of a thermal radiator which serves to describe its light colour. Unit:
Kelvin [K]. The lesser the numerical value the redder; the greater the numerical value the
bluer the light colour. The colour temperature of gas-discharge lamps and semi-
conductors are termed "correlated colour temperature" in contrast to the colour
temperature of thermal radiators.

Allocation of the light colours to the colour temperature ranges acc. to EN 12464-1:

Light colour - colour temperature [K]


warm white (ww) < 3, 300 K
neutral white (nw) ≥ 3, 300 – 5,300 K
daylight white (dw) > 5,300 K

Clearance height The designation for the distance between upper edge of the floor and bottom edge of
the ceiling (in the completely furnished status of room).

Control group A group of luminaires that are dimmed and controlled together. For each lighting scene,
a control group provides its own dimming value. All luminaires within a control group
share this dimming value. The control groups with their luminaires are automatically
determined by DIALux on the basis of the created light scenes and their luminaire
groups.

CRI (Engl. colour rendering index)


Designation for the colour rendering index of a luminaire or a lamp acc. to DIN 6169:
1976 or CIE 13. 3: 1995.

The general colour rendering index Ra (or CRI) is a dimensionless figure that describes
the quality of a white light source in regards to its similarity with the remission spectra of
defined 8 test colours (see DIN 6169 or CIE 1974) to a reference light source.

154
Project

Glossary

Daylight autonomy Describes what percentage of the daily working time the required illuminance is met by
daylight. The nominal illuminance is used from the room profile, unlike described in EN
17037. The calculation is not done in the centre of the room but at the placed sensor
measuring point. A room is considered sufficiently supplied with daylight if it achieves at
least 50% daylight autonomy.

Daylight factor Ratio of the illuminance achieved solely by daylight incidence at a point in the inside to
the horizontal illuminance in the outer area under an unobstructed sky.

Formula symbol: D (Engl. daylight factor)


Unit: %

Daylight quotient effective area A calculation surface within which the daylight quotient is calculated.

Energy evaluation Based on an hourly calculation procedure for daylight in indoor spaces, considering the
project geometry and any existing daylight control systems. Orientation and location of
the project are also considered. The calculation uses the specified system power of the
luminaires to determine the energy demand. A linear relationship between power and
luminous flux in the dimmed state is assumed for daylight-controlled luminaires. Times
of use and nominal illuminance are determined from the usage profiles of the spaces.
Switched-on luminaires that are explicitly excluded from control also consider the
specified times-of-use. The daylight control systems use a simplified control logic that
closes them at an outdoor horizontal illuminance of 27,500lx.

The calendar year 2022 is used as a reference only. It is not a simulation of this year. The
reference year is only used to assign the days of the week to the calculated results. The
changeover to summer time is not considered. The reference sky type used is the
average sky described in CIE 110 without direct sunlight.

The method was developed together with the Fraunhofer Institute for Building Physics
and is available for review by the Joint Working Group 1 ISO TC 274 as an extension of
the previous annual regression-based method.

Environmental zones The assessment of intrusive light and light immission depends on the environment of
the lighting installation. Depending on the standard, 4- 6 different zones are defined,
ranging from highly protected areas in natural settings to urban areas, commercial
zones, and industrial zones.

Eta (η) (light output ratio)


The light output ratio describes what percentage of the luminous flux of a free radiating
lamp (or LED module) is emitted by the luminaire when installed.

Unit: %

155
Project

Glossary

g1 Often also Uo (Engl. overall uniformity)


Designates the overall uniformity of the illuminance on a surface. It is the quotient from
Emin to Ē and is required, for instance, in standards for illumination of workstations.

g2 Actually it designates the "non-uniformity" of the illuminance on a surface. It is the


quotient of Emin to Emax and is generally only relevant for certifying the emergency
lighting acc. to EN 1838.

Illuminance Describes the ratio of the luminous flux that strikes a certain surface to the size of this
surface (lm/m² = lx). The illuminance is not tied to an object surface. It can be determined
anywhere in space (inside or outside). The illuminance is not a product feature because it
is a recipient value. Luxometers are used for measuring.

Unit: Lux
Abbreviation: lx
Formula symbol: E

Illuminance, adaptive For the determining of the middle adaptive illuminance on a surface, this is rastered
"adaptively". In the area of large illuminance differences within the surface, the raster is
subdivided finer; within lesser differences, a rougher classification is made.

Illuminance, horizontal Illuminance that is calculated or measured on a horizontal (level) surface (this can be for
example a table top or the floor). The horizontal illuminance is usually identified by the
formula letter Eh.

Illuminance, perpendicular Illuminance that is calculated or measured plumb-vertical to a surface. This needs to be
taken into account for tilted surfaces. If the surface is horizontal or vertical, then there is
no difference between the perpendicular and the horizontal or vertical illuminance.

Illuminance, vertical Illuminance that is calculated or measured on a vertical surface (this can be for example
the front of some shelves). The vertical illuminance is usually identified by the formula
letter Ev.

kS The glare effect of a light source can be described by the glare metric kS. It relates the
solid angle of the glaring light source as seen from the point of immission, the ambient
luminance, and the maximum allowable luminance.

156
Project

Glossary

LENI (Engl. lighting energy numeric indicator)


Lighting energy numeric indicator acc. to EN 15193

Unit: kWh/(m² * a)

LLMF (Engl. lamp lumen maintenance factor)/acc. to CIE 97: 2005


Lamp flux maintenance factor that takes the luminous flux reduction into account of a
luminaire or an LED module in the course of the operating time. The lamp flux
maintenance factor is specified as a decimal digit and can have a maximum value of 1
(no luminous flux reduction existing).

LMF (Engl. luminaire maintenance factor)/acc. to CIE 97: 2005


Luminaire maintenance factor that takes the soiling into account of the luminaire in the
course of the operating time. The luminaire maintenance factor is specified as a decimal
digit and can have a maximum value of 1 (no soiling existing).

LSF (Engl. lamp survival factor)/acc. to CIE 97: 2005


Lamp survival factor that takes the total failure into account of a luminaire in the course
of the operating time. The lamp survival factor is specified as a decimal digit and can
have a maximum value of 1 (no failures existing within the time concerned or prompt
replacement after the failure).

Luminance Dimension for the "brightness impression" that the human eye has of a surface. The
surface itself can emit light thereby or light striking it can be reflected (emitter value). It is
the only photometric value that the human eye can perceive.

Unit: Candela per square metre


Abbreviation: cd/m²
Formula symbol: L

Luminous efficacy Ratio of the emitted luminous flux Φ [ lm] to the absorbed electrical power P [W] Unit:
lm/W.

This ratio can be formed for the lamp or LED module (lamp or module light output), the
lamp or module with control gear (system light output) and the complete luminaire
(luminaire light output).

Luminous flux Dimension for the total light output that is emitted from one light source in all directions.
It is thus an "emitter value" that specifies the entire emitting output. The luminous flux of
a light source can only be determined in a laboratory. A difference is made between the
lamp or LED module luminous flux and the luminaire luminous flux.

Unit: Lumen
Abbreviation: lm
Formula symbol: Φ

157
Project

Glossary

Luminous intensity Describes the intensity of the light in a certain direction (emitter value). The luminous
intensity is a matter of the luminous flux Φ that is emitted in a certain spherical angle Ω.
The radiation characteristics of a light source are presented graphically in a light
distribution curve (LDC). The luminous intensity is an SI base unit.

Unit: Candela
Abbreviation: cd
Formula symbol: I

Maintenance factor See MF

MF (Engl. maintenance factor)/acc. to CIE 97: 2005


Maintenance factor as decimal number between 0 and 1 that describes the ratio of the
new value of a photometric planning parameter (e.g. of the illuminance) to a
maintenance value after a certain time. The maintenance factor takes into account the
soiling of luminaires and rooms as well as the luminous flux reduction and the failure of
light sources.
The maintenance factor is taken into account either overall or determined in detail acc.
to CIE 97: 2005 by the formula RMF x LMF x LLMF x LSF.

Obtrusive light/Light immission To protect the nocturnal environment and minimize problems for humans, flora, and
fauna, it is necessary to limit obtrusive light (also known as light pollution), which can
cause serious physiological and ecological issues for individuals and the environment.
Light immission refers to the disturbing influence of emitted light from artificial light
sources.

Operating times The assessment of obtrusive light and light immission depends on the operating times
of the lighting installation. Depending on the standard, 1-3 different operating times are
specified. In the absence of specific details, an operating time between 06:00 and 22:00
can be assumed.

P (Engl. power)
Electric power consumption

Unit: watt
Abbreviation: W

158
Project

Glossary

R(UG) max Measure of the psychological glare in indoor spaces.


In addition to the luminance of luminaires, the level of the R(UG) value also depends on
the observer position, the viewing direction and the ambient luminance. The calculation
is made according to the table method, see CIE 117. Among other things, EN 12464-
1: 2021 specifies maximum permissible R(UG) - values R( UGL) for various indoor workplaces.

RDLO The ratio of the luminous flux emitted below the horizontal plane to the total lamp
luminous flux of a luminaire or lighting installation in its operational position.

RG The glare directly caused by luminaires of an outdoor lighting installation is determined


using the CIE Glare Rating (RG) method. To calculate this, the equivalent veiling
luminance of the surroundings is needed. There are four options for determining this:
• An exact calculation according to CIE 112, based on the scene area.
• A simplified method according to EN 12464-2, based on the scene area.
• Using a custom calculation area to determine the equivalent veiling luminance.
• Specifying a fixed value for easy comparability.

RUF upward flux ratio


The ratio of the luminous flux emitted directly or reflected above the horizontal plane to
the luminous flux that cannot be avoided under ideal conditions to achieve the
illuminance level on a deliberately illuminated area.

RUL upward light ratio


The ratio of the luminous flux emitted above the horizontal plane to the luminous flux of
a luminaire or lighting installation in its operational position. The luminaire efficiency is
considered in this calculation.

RULO upward light output ratio


The ratio of the luminous flux emitted above the horizontal plane to the total lamp
luminous flux of a luminaire or lighting installation in its operational position.

Reflection factor The reflection factor of a surface describes how much of the striking light is reflected
back. The reflection factor is defined by the colour of the surface.

RMF (Engl. room maintenance factor)/acc. to CIE 97: 2005


Room maintenance factor that takes the soiling into account of the space encompassing
surfaces in the course of the operating time. The room maintenance factor is specified
as a decimal digit and can have a maximum value of 1 (no soiling existing).

RUG (max) (unified glare rating)


Measure for the psychological glare effect in interiors.
In addition to luminaire luminance, the RUG value also depends on the position of the
observer, the viewing direction and the ambient luminance. Among other things, EN
12464-1 specifies maximum permissible RUG values for various indoor workplaces.

159
Project

Glossary

RUG observer Calculation point in the room, for the DIALux the RUG value is determined. The location
and height of the calculation point should correspond to the typical observer position
(position and eye level of the user).

Surrounding area The ambient area directly borders the area of the visual task and should be planned with
a width of at least 0.5 m according to DIN EN 12464-1. It is at the same height as the
area of the visual task.

Visual task area The area that is needed for carrying out the visual task in accordance with DIN EN 12464
-1. The height corresponds with the height at which the visual task is executed.

Wall zone Circumferential area between working plane and walls which is not taken into account
for the calculation.

Working plane Virtual measuring or calculation surface at the height of the visual task that generally
follows the room geometry. The working plane may also feature a wall zone.