PROPERTIES
Technical İnformation
RS485 MODBUS
COMMUNICATION
4 Byte Format For ex: 1234567 define MSB LSB MSB LSB
as float
MSB LSB MSB LSB Low = 46136 = 0xB438 0xB4 0x38 0x49 0x96
High = 18838 = 0x4996
{
{
{
** Cable connection
** Other information
2 Byte Format
MOD-BUS MASTER
MSB LSB
For ex: 0x01 value
Low = 0x01
High = 0x00
MOD-BUS TERMİNAL
MSB LSB
0x00 0x01
BILL
THE USING FORMAT OF 06 AND 16 COMMANDS
Command Response
Field name ASCII Field name ASCII
Starting : Starting :
Modbus Address 0 1 Modbus Adress 0 1
Function 1 0 Function 1 0
Starting Address MSB 0 0 Starting Address MSB 0 0
Starting Address LSB 0 2 Starting Address LSB 0 2
Register No MSB 0 0 Register No MSB 0 0
Register No LSB 0 2 Register No LSB 0 2
Byte count 0 4 LRC E B
Data High 2 3 CR-LF
Data Low F 0
Data High 4 9
Data Low 7 4
LRC 1 7
CR-LF
NOTE = The parts which are outside of consumption should be written in integer format.
For ex : While changing slave id at address 4005.
Slave Id = 56 = 0x38
High = 0 = 0x00
Low = 56 = 0x38
while writing to 4005, at first 0x00 and then 0x38 shoul be sent.
Command Response
Field name ASCII Field name ASCII
Starting : Starting :
Modbus Address 0 1 Modbus Address 0 1
Function 0 6 Function 0 6
Register No MSB 0 0 Register No MSB 0 0
Register No LSB 0 4 Register No LSB 0 4
Data High 0 0 Data High 0 0
Data Low 3 8 Data Low 3 8
LRC LRC
CR-LF CR-LF
NOTE: Maximum number of registers that can be read is 16. The properties defined above may
vary according to the mechanical structure/type of the water meter.