DSC PowerSeries PC1616 PC1832 PC1864 Panel Programming Guide
DSC PowerSeries PC1616 PC1832 PC1864 Panel Programming Guide
6 NA
Installation Guide
WARNING: This manual contains information on limitations regarding product use and function and information on
the limitations as to liability the manufacturer. The entire manual should be read carefully.
Table of Contents
Guidelines for Locating Smoke Detectors and CO Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii
Chapter 1 Installation & Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.1 Keybus Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Zone Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3 Zone Expanders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4 Bell Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.5 AUX Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.6 PGM Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.7 Carbon Monoxide Detector Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.8 Telephone Line Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.9 Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.10 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.11 AC Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.12 RFK5500 and RFK5564 Easy Wireless Enrollment Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Chapter 2 User Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1 Away Arming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Stay Arming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3 Disarming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.4 [✱] Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.5 Function Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Chapter 3 Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.1 Template Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.2 DLS Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.3 Advanced Keypad Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 4 Programming Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Chapter 5 Programming Worksheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.1 Index to Programming Worksheets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Appendix A: Reporting Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Appendix B: UL Listed Commercial and Residential Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Appendix C: SIA False Alarm Reduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Appendix D: Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Appendix E: Template Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Appendix F: Communicator Format Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
SAFETY INSTRUCTIONS FOR SERVICE PERSONNEL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
FCC COMPLIANCE STATEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
i
PowerSeries - PC1616/PC1832/PC1864
Figure 3
Figure 1 Figure 2
Figure 3a Figure 4
CO Detectors
Carbon monoxide gas moves freely in the air. The human body is most vulnerable to the effects of CO gas
during sleeping hours. For maximum protection, a CO alarm should be located outside primary sleeping BEDROOM
areas or on each level of your home. Figure 5 indicates the suggested locations in the home. The elec-
tronic sensor detects carbon monoxide, measures the concentration and sounds a loud alarm before a BEDROOM BEDROOM
potentially harmful level is reached. GARAGE
GROUND KITCHEN
Do NOT place the CO alarm in the following areas: FLOOR
• Where the temperature may drop below -10ºC or exceed 40 ºC.
BASEMENT
• Near paint thinner fumes.
• Within 5 feet (1.5 meters) of open flame appliances such as furnaces, stoves and fireplaces. CARBON MONOXIDE DETECTOR
• In exhaust streams from gas engines, vents, flues or chimneys. Figure 5
• In close proximity to an automobile exhaust pipe; this will damage the detector.
ii
Chapter 1 Installation & Wiring
All necessary information required to meet UL Listing requirements is included in this document.
Technical Summary
FEATURES PC1616 PC1832 PC1864
OUT Of THE BOX On-board Zones 6 8 8
Partitions 2 4 8
COMPATIBLE DEVICES
INSTALLATION
Begin the installation by mounting additional modules in the cabinet using the stand-offs provided, then mount the cabinet in a dry, protected
area with access to unswitched AC power. Install hardware in the sequence indicated in the following pages. Do NOT apply power until instal-
lation is complete.
All wiring entry points are designated by arrows. All circuits are classified UL power limited except for the battery leads. Minimum 1/4”
(6.4mm) separation must be maintained at all points between power limited and non-power limited wiring and connections.
1
PowerSeries - PC1616/PC1832/PC1864
220
DSCPTD 1640U
Class II Transformer
WARNING:
NOTE: Do not connect High Voltage. Disconnect AC Power
transformer to receptacle and telephone lines before servicing
controlled by a switch
PC1864 PC1864
Only PC1832
Only
CON1
BAT+BAT-
TB-2
AUX+ BELL+ PGM1 PGM3 RING R-1
AC AC AUX- BELL- RED BLK YEL GRN PGM2 PGM4 Z1 COM Z2 Z3 COM Z4 Z5 COM Z6 Z7 COM Z8 EGND TIP T-1
Battery
StandbyTime:
24Hrs min.
FUSE
b)The connection to the mains supply must be made as per the local
authorities rules and regulations.
An appropriate disconnect device must be provided as par t of the
building installation. Where it is not possible to rely on identification of
PC-LINK
the neutral in the AC Mains supply the disconnecting device must
disconnect both poles simultaneously (line and neutral). The device
shall disconnect the supply during servicing.
AUX+ and Keybus (Red) are Internally Connected
Total current draw from Keypads, PGM Outputs and 10
c)The equipment enclosure must be secured to the building structure Aux circuits must not exceed 700mA
before operation.
Internally Connected
e)Internal wiring must be routed in a manner that prevents:
- Excessive strain on wire and on terminal connections;
- Loosening of terminal; connections;
- Damage of conductor insulation PC1864 PC1864
Only PC1832
Only
f) Disposal of the used batteries shall be made according to the waste CON1
TB-2
recovery and recycling regulations applicable to the intended market. BAT+BAT-
AC AC + AUX - + BELL - RED BLK YEL GRN 1 PGM 2 3 PGM 4 Z1 COM Z2 Z3 COM Z4 Z5 COM Z6 Z7 COM Z8 EGND RING TIP R-1 T-1
WARNING:
High Voltage. Disconnect AC Power
and telephone lines before servicing
2
Chapter 1 Installation & Wiring
3
PowerSeries - PC1616/PC1832/PC1864
2200 Ohm
END-OF-LINE ALARM
RESISTOR INITIATING
EOLR-3 LOOP
RESISTANCE
100 Ohm
EOLR-2
END-OF-LINE
RESISTOR
5600 Ohm, 0.5W
RESISTOR
COM Z
ALARM
(SEOL TYPE 41) wireless receiver model RF5132-433 v5.1 (and higher) or DSC
INITIATING
RM-1/RM-2
LOOP keypad receiver models RFK55XX-433 (xx= 00/01/08/16/64)
RESISTANCE v1.2 (and higher) are required when installing wireless CO
POWER LOOP 100 ohm
SUPERVISORY detectors. For more details on either the WS4913 CO detector
RELAY or the receivers, please refer to their respective installation
(12VDC, 35mA) manuals.
4
Chapter 1 Installation & Wiring
1.9 Ground
Ground Installation
Tighten nut to break paint and make
good connection to the cabinet
1.10 Battery
Standby Battery Guide A sealed, rechargeable, lead acid battery or gel type battery is required to
Battery Charging Current: 400 mA meet UL requirements for power standby times.
Battery Standby NOTE: UL Residential/Commercial Burglary installations require 4Hrs
Size 4Hr 24Hr of standby battery time.
--------------------------------------------------------- NOTE: UL/ULC Residential Fire & Health Care installations require 24
4Ahr 700mA ---- Hrs of standby battery time. ULC Commercial Burglary and Fire moni-
7Ahr 700mA 180mA toring installations require 24Hrs of standby battery time plus 5 minutes
14Ahr 700mA 470mA of alarm condition.
NOTE: Battery capacity will deterio-
rate with age and the number of
charge/discharge cycles. Replace
every 3-5 years.
1.11 AC Wiring
AC Wiring (UL Listed Installations)
Primary: 120VAC/60Hz./0.33A
Secondary: 16.5VAC/40VA DSC PTD1640U, DSC PTC1640U,
DSC PTD1640U-CC Plug-in, Class 2 Transformer.
NOTE: Use DSC PTD1640 for Canadian installations.
5
PowerSeries - PC1616/PC1832/PC1864
Press the [#] key to reset the keypad if an error has been made entering user codes or keypad commands.
2.3 Disarming
The user must enter through a door programmed as Delay. Upon entering, the keypad will emit a steady tone (and emit a pulsing tone during
the last 10 seconds of entry delay) to prompt the user to disarm the system. Enter a valid user code to disarm the system. If an alarm occurred
while the panel was armed, the Memory light and the zones that went into alarm will be flashing (LED keypad) or the keypad will display
‘Alarm in Memory’ (LCD keypad). Press the [#] key to return the keypad to the Ready state.
Re-activate Stay/Away Zones: Press [✱][1] when the system is armed in the Stay mode to change the armed status to Away mode. The
system will add the Stay/Away zones back into the system after the exit delay time expires.
6
Chapter 2 User Commands
7
PowerSeries - PC1616/PC1832/PC1864
If using LCD keypads, scroll to the desired option then press [✱].
8
Chapter 3 Programming
Chapter 3 Programming
This chapter provides the information necessary to program all the features required for a basic system, as well as common applications.
You cannot enter Installer Programming while the system or any partition is armed or in alarm.
9
PowerSeries - PC1616/PC1832/PC1864
In addition to the standard digits 0-9, HEX digits and special dialer functions can also be programmed.
. .4 iewing Programming
LED and LCD5501Z Keypads
Any programming section can be viewed from an LED or LCD5501Z
keypad. When a programming section is entered, the keypad will immedi-
ately display the first digit of information programmed in that section.
The keypad displays the information using a binary format, according to
the following chart:
Press any of the Emergency keys (Fire, Auxiliary or Panic) to advance to
the next digit.
When all the digits in a section have been viewed, the panel will exit the section. The Ready light will turn OFF, and the Armed light
will turn ON. The system is now waiting for the next 3-digit programming section number to be entered. Press the [#] key to exit the
section.
LCD Keypad
The keypad will immediately display all the information programmed when a programming section is entered. Use the arrow keys (< >) to
scroll through the data being displayed. Scroll past the end of the data displayed or press the [#] key to exit the section.
10
Chapter 4 Programming Descriptions
11
PowerSeries - PC1616/PC1832/PC1864
[30] Fire Supervisory: Instant alarm, system will activate keypad buzzer. A valid user code is required to silence keypad buzzer
[31] Day Zone: Instant alarm when system is armed, keypad buzzer (no alarm) when system is disarmed
[32] Instant Stay/Away: Similar to ‘Instant’ except panel will auto-bypass the zone if Armed in the Stay mode
[35] 24-Hr Bell/Buzzer: Instant alarm when violated, system will activate bell output if armed, keypad buzzer if disarmed
[36] 24-Hr Non-Latching Tamper Zone: Instant tamper condition when violated. Active in both the armed and disarmed state
[37] Night Zone: Functions like Interior Stay/Away but will remain bypassed if the user presses [✱][1] to re-activate Stay/Away zones
when armed in the Stay mode
[41] 24 Hr. Carbon Monoxide: This zone type is used with a hardwired CO detector. This zone definition has a distinct bell cadence in the
event of an alarm. The cadence of this alarm is 4 cycles of 100ms on/off pulses, followed by a 5-second pause, and then repeated.
After 4 minutes, the 5-second pause is extended to 60 seconds in duration. The bell is silenced when an access code is entered or the
bell times out (see your Carbon Monoxide instruction sheet for more details).
[81] 24 Hr. Carbon Monoxide (Wireless): This zone type is used with a wireless CO detector. This zone definition has a distinct bell
cadence in the event of an alarm. The cadence of this alarm is 4 cycles of 100ms on/off pulses, followed by a 5-second pause, and then
repeated. After 4 minutes, the 5-second pause is extended to 60 seconds in duration. The bell is silenced when an access code is
entered or the bell times out.
[87] Delayed 24-Hour Fire (Wireless/Addressable): Same as Delayed 24-Hour Fire (Hardwire) but must be used for wireless or address-
able smoke detectors
[88] Standard 24-Hour Fire (Wireless/Addressable): Same as Standard 24-Hour Fire (Hardwire) but must be used for wireless or
addressable smoke detectors
12
Chapter 4 Programming Descriptions
[11] System Tamper: Output will activate when any tamper condition is present
[12] TLM and Alarm: Output will activate if a telephone line trouble is present and then an alarm occurs
[13] Kissoff: Output will activate for 2 seconds when a valid kissoff is received from the central station
[14] Ground Start: Output will activate for 2 seconds when the panel attempts to seize the phone line (additional dial tone search must
be programmed in the central station phone number – HEX [D])
[15] Remote Operation: Output can be activated/deactivated via the DLS software
[16] For Future Use
[17] Away Armed Status: Activates when all of the selected partitions are armed in Away mode
[18] Stay Armed Status: Activates when all of the selected partitions are armed in Stay mode
[19] Command Output 1: Activates when a [✱][7][1] command is entered on the selected partition – Command can be programmed to require
a valid access code and output can be programmed to activate for the time programmed in Section [170] or programmed to latch.
[20] Command Output 2: Activates when a [✱][7][2] command is entered on the selected partition – Command can be programmed to require
a valid access code and output can be programmed to activate for the time programmed in Section [170] or programmed to latch.
[21] Command Output 3: Activates when a [✱][7][3] command is entered on the selected partition – Command can be programmed to require
a valid access code and output can be programmed to activate for the time programmed in Section [170] or programmed to latch.
[22] Command Output 4: Activates when a [✱][7][4] command is entered on the selected partition – Command can be programmed to require
a valid access code and output can be programmed to activate for the time programmed in Section [170] or programmed to latch.
[23] Silent 24-Hour Input: Changes PGM to a 24-hr Silent zone (PGM2 only)
[24] Audible 24-Hour Input: Changes PGM to a 24-hr Audible zone (PGM2 only)
[25] Delayed Fire and Burglary: Functions as a Fire and Burglary output but does not activate until the TX Delay time expires
[26] Battery Test Output: Output activates for 10 seconds at midnight each day.
[27] For Future Use
[28] Holdup Output: Activates when a Holdup Alarm occurs on any assigned partition. Remains active until all assigned partitions have
been armed or disarmed. Will not activate if a Holdup Zone goes into a fault or tamper condition.
[29] Zone Follower (Zones 1-8): Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
[30] Partition Status Alarm Memory: Activates if the selected partition is armed. Output will pulse “one second ON / one second OFF
if an alarm occurs
[31] Alternate Communicator: Activates when selected system event occurs. If active in the armed state, it remains active until the sys-
tem is disarmed. If activated in the disarmed state, it remains active until a valid access code is entered within the bell cut-off time, or
when the system is armed after the bell cut-off time has expired.
[32] For Future Use
[33] For Future Use
[34] Away Armed with no Zone Bypassed Status: Activates when armed with stay/away zones active and no zones bypassed.
[35] Zone Follower (Zones 9-16): Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
[36] Zone Follower (Zones 17-24): Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
[37] Zone Follower (Zones 25-32): Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
[38] Zone Follower (Zones 33-40): Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
[39] Zone Follower (Zones 41-48): Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
[40] Zone Follower (Zones 49-56): Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
[41] Zone Follower (Zones 57-64): Active when any of the selected zones are active and deactivates when all of the selected zones are restored.
* See Section [501]-[514] Programmable Output Attributes, PGM Output Option [29] and [35]-[41] Option 8 on 24.
13
PowerSeries - PC1616/PC1832/PC1864
14
Chapter 4 Programming Descriptions
15
PowerSeries - PC1616/PC1832/PC1864
16
Chapter 4 Programming Descriptions
[5] ON: the user cannot switch from Away Arm mode to Stay Arm mode using the function keys.
OFF: the user can switch arming modes.
[6] ON: the system disconnects a listen in/two-way session if a new event occurs.
OFF: the system does NOT disconnect. New events are transmitted only after the session is terminated.
[7] ON: the system does NOT activate the keypad buzzer for any trouble condition (excluding Fire Troubles).
OFF: the system announces troubles via the keypad buzzer (two beeps every 10 seconds).
[8] ON: Keyswitches will always arm in Away mode.
OFF: Keyswitches will arm in Away mode if an entry/exit zone is violated during exit delay.
17
PowerSeries - PC1616/PC1832/PC1864
Do not program the Hour outside of the valid range or the time will not change. Do not program the value of the Increment to be greater
then the number of hours remaining in the current day.
1 1 to 1 Auto-arm Sc edules
Program the amount of time to auto-arm ([181] for partition 1, [182] for partition 2, etc.) for each day of the week. Each option has seven, 4-digit
entries: two digits for the hour, two digits for the minute, Sunday through Saturday. Program using the twenty-four-hour system (for example, to
auto-arm at 8:00 pm, program data [20][00]). Valid entries are [00][00] to [23][59]. Program [99][99] to disable auto-arming.
1
C apter 4 Programming Descriptions
Telephone Communications
All telephone number sections are 32 digits in length. Hexadecimal digits may be programmed in the telephone number to perform addi-
tional functions as follows:
Enter [✱][2][✱] – HEX B to dial “✱”
• Enter [✱][3][✱] – HEX C to dial “#”
• Enter [✱][4][✱] – HEX D for an additional dial tone search, as is required for PBX telephone systems
• Enter [✱][5][✱] – HEX E to insert a 2-second pause in the telephone number.
There is an automatic 2-second pause before additional dial tone searches are initiated.
1
PowerSeries - PC1616/PC1832/PC1864
20
Chapter 4 Programming Descriptions
21
PowerSeries - PC1616/PC1832/PC1864
These settings do not affect the 6-hour DLS downloading window on power-up.
[2] ON: the user can enable downloading for the DLS Window using the [✱][6] command.
OFF: the user cannot enable downloading.
[3] ON: the system will hang up after a successful DLS connection and call the computer back using the DLS Phone Number ([402]).
OFF: the system stays connected to the computer.
[4] ON: the user can initiate a downloading session using the [✱][6] command.
OFF: the user cannot initiate a downloading session.
[5] ON: the system attempts to call the downloading computer after transmitting an Event Buffer 75% Full event to the central station.
OFF: the system does NOT call the downloading computer after transmitting this event.
[6] ON: panel communicates with DLS at 300 Baud. OFF: panel communicates with DLS at 110 Baud.
[7]-[8] For Future Use
22
Chapter 4 Programming Descriptions
23
PowerSeries - PC1616/PC1832/PC1864
24
Chapter 4 Programming Descriptions
25
PowerSeries - PC1616/PC1832/PC1864
26
Chapter 4 Programming Descriptions
1. Enter the section number of the label to be pro- [<] Display Left (Previous character position)
grammed. e.g., [*][8][Installer Code][*][001]. [>] Display Right (Next character position)
[✽ ] [SELECT]
2. Scroll to the desired character’s location using the <> [#] [ESCAPE]
Keys. [0] [SPACE]
3. Enter the number of the corresponding character [1] [A], [B], [C], [1]
group until the desired character is displayed. [2] [D], [E], [F], [2]
[3] [G], [H], [I], [3]
Example: [4] [J], [K], [L], [4]
Press the “2” key 3 times to enter the letter “F.” [5] [M], [N], [O], [5]
Press the “2” key 4 times to enter the number [6] [P], [Q], [R], [6]
“2.” [7] [S], [T], [U], [7]
4. Press [ ✱ ] to access the “Select Option” menu. [8] [V], [W], [X], [8]
Scroll to “Save” then press [ ✱ ] to save the label. [9] [Y], [Z], [9], [0]
WORDS - This option provides access to the Label Library, a collection of words commonly used when programming
labels.
ASCII ENTRY - This option is for entering uncommon characters, or as a primary method for programming labels. 255
character entries are available, although some entries are duplicated. Use the [<] [>] keys to scroll through the characters or
enter a 3-digit number from 000-255. Press the [✱] key to enter a character in the label.
CHANGE CASE - This option toggles the letter entry between upper case letters (A, B, C) and lower case letters (a, b, c).
CLEAR TO END - This option clears the display from the character where the cursor is located to the end of the display.
CLEAR DISPLAY - This option sets all characters in a label to “space” or cleared.
SAVE - Saves the new label. If save is not selected before leaving the label programming section, the changes are lost.
Label Library
The Label Library is a database of words commonly used when programming labels. Individual words can be combined as needed. e.g., Front +
Door. Each line of the display supports a maximum of 14 characters. If a word will not fit on a line, scroll right until the cursor appears at the first
character of the second line then add the word.
To program a custom label using the Label Library:
1. Enter keypad programming and select the label to change. e.g., [*][8][Installer Code][*][001] (to program the label for zone 01).
2. Press [*] to open the “Select Options” menu.
3. Press [*] again to select the “Words” option.
4. Enter the 3-digit number corresponding to a word (see Words table below) or use the scroll keys [<][>] to view words in the library.
5. Press [*] to select the word.
6. To add another word, repeat the above procedure from step 2.
7. To add a space, press the right scroll key [>].
8. To clear characters, select “Clear to End” or “Clear Display” from the “Select Options” menu.
9. To save the current label, press [*] to access the “Select Options” menu, scroll left [<] to “Save” then press [*] again.
27
PowerSeries - PC1616/PC1832/PC1864
Words Table
Item Text Item Text Item Text Item Text Item Text Item Text
# # # # # #
001 Aborted 042 Control 083 Garage 124 Motion 165 Shop 206 E
002 AC 043 Date 084 Gas 125 No 166 Side 207 F
003 Access 044 Daughter’s 085 Glass 126 North 167 Siren 208 G
004 Active 045 Degrees 086 Goodbye 127 Not 168 Sliding 209 H
005 Activity 046 Delay 087 Gym 128 Now 169 Smoke 210 I
006 Alarm 047 Den 088 Hallway 129 Number 170 Son’s 211 J
007 All 048 Desk 089 Heat 130 Off 171 Sound 212 K
008 AM 049 Detector 090 Hello 131 Office 172 South 213 L
009 Area 050 Dining 091 Help 132 OK 173 Special 214 M
010 Arm 051 Disarmed 092 High 133 On 174 Stairs 215 N
011 Armed 052 Door 093 Home 134 Open 175 Stay 216 O
012 Arming 053 Down 094 House 135 Opening 176 Sun 217 P
013 Attic 054 Download 095 In 136 Panic 177 Supervisory 218 Q
014 Auxiliary 055 Downstairs 096 Install 137 Partition 178 System 219 R
015 Away 056 Drawer 097 Interior 138 Patio 179 Tamper 220 S
016 Baby 057 Driveway 098 Intrusion 139 Pet 180 Temperature 221 T
017 Back 058 Duct 099 Invalid 140 Phone 181 Test 222 U
018 Bar 059 Duress 100 Is 141 Please 182 Time 223 V
019 Basement 060 East 101 Key 142 PM 183 To 224 W
020 Bathroom 061 Energy Saver 102 Kids 143 Police 184 Touchpad 225 X
021 Battery 062 Enter 103 Kitchen 144 Pool 185 Trouble 226 Y
022 Bedroom 063 Entry 104 Latchkey 145 Porch 186 Unbypass 227 Z
023 Bonus 064 Error 105 Laundry 146 Power 187 Unit 228 (Space)
024 Bottom 065 Exercise 106 Left 147 Press 188 Up 229 ’ (Apostrophe)
025 Breezeway 066 Exit 107 Level 148 Program 189 West 230 - (Dash)
026 Building 067 Exterior 108 Library 149 Progress 190 Window 231 _ (Underscore)
027 Bus 068 Factory 109 Light 150 Quiet 191 Zone 232 *
028 Bypass 069 Failure 110 Lights 151 Rear 192 0 233 #
029 Bypassed 070 Family 111 Living 152 Receiver 193 1 234 :
030 Cabinet 071 Father’s 112 Load 153 Report 194 2 235 /
031 Cancelled 072 Feature 113 Loading 154 RF 195 3 236 ?
032 Car 073 Fence 114 Low 155 Right 196 4
033 Carbon 074 Fire 115 Lower 156 Room 197 5
034 Central 075 First 116 Main 157 Safe 198 6
035 Chime 076 Floor 117 Master 158 Schedule 199 7
036 Closed 077 Force 118 Mat 159 Screen 200 8
037 Closet 078 Foyer 119 Medical 160 Second 201 9
038 Closing 079 Freeze 120 Memory 161 Sensor 202 A
039 Code 080 Front 121 Menu 162 Service 203 B
040 Communicator 081 Furnace 122 Monoxide 163 Shed 204 C
041 Computer 082 Gallery 123 Mother’s 164 Shock 205 D
28
Chapter 5 Programming Worksheets
[000] Keypad Enrollment .......................................................................30 [348] Test Transmission Reporting Codes .................................................44
[001]-[004] Zone Definitions..................................................................30 [349] PC5700 Maintenance Reporting Codes ...........................................44
[005] System Times ................................................................................31 [350] Communicator Format Options .......................................................44
[006] Installer Code ................................................................................31 [351]-[358] Alarm/Restore Communicator Call Directions.......................44
[007] Master Code ..................................................................................31 [359]-[366] Tamper/Restore Communicator Call Directions.....................44
[008] Maintenance Code.........................................................................31 [367]-[374] Opening/Closing Communicator Call Directions ...................45
[009] PGM 1&2 Output Programming (Main Panel) .............................32 [375] System Maintenance Communicator Call Directions ......................45
[010] PGM 3-10 Output Programming (Main Panel/PC5208)...............32 [376] System Test Transmissions Communicator Call Directions .............45
[011] PGM 11-14 Output Programming (PC5204) ................................32 [377] Communication Variables .................................................................45
[012] Keypad Lockout Options .............................................................32 [378] Test Transmission Time of Day .......................................................45
[013] 1st System Options........................................................................33 [379] Periodic DLS Time of Day ...............................................................45
[014] 2nd System Options ......................................................................33 [380] 1st Communicator Options ...............................................................46
[015] 3rd System Options .......................................................................33 [381] 2nd Communicator Options ..............................................................46
[016] 4th System Options .......................................................................33 [382] 3rd Communicator Options...............................................................46
[017] 5th System Options .......................................................................34 [383] 4th Communicator Options...............................................................46
[018] 6th System Options .......................................................................34 [389] TL/GS Module Fault Check Timer ..................................................46
[019] 7th System Options .......................................................................34 [401] DLS Downloading Option Codes .....................................................47
[020] Keypad Zone Assignments ...........................................................34 [402] DLS Downloading Telephone Number (32 Digits) ..........................47
[021] 8th System Options .......................................................................35 [403]-[404] DLS Downloading Access Code / Panel ID Code .................47
[022] 9th System Options .......................................................................35 [405] Answering Machine Double Call Timer ...........................................47
[023] 10th System Options .....................................................................35 [406] Number of Rings to Answer On .......................................................47
[030] Zone Loop Response (Zones 1-8) .................................................35 [499] Initiate PC-Link Downloading..........................................................47
[101] - [164] Zone Attributes..................................................................36 [501]-[502] PGM 1&2 Output Attributes (Main Panel).............................48
[165] Maximum Dialing Attempts to Each Telephone Number.............38 [503]-[504] PGM 3&4 Output Attributes (Main Panel / PC5208).............48
[166] Post Dial Wait for Handshake (All Formats) ...............................38 [505]-[510] PGM 5-10 Output Attributes (5208).......................................48
[167] TL/GS Module Wait for Acknowledgement .................................38 [511]-[514] PGM 11-14 Output Attributes (5204) .....................................48
[168] Set Clock Forward (Daylight Saving Time)..................................39 [551]-[552] PGM 1&2 Output Partition Assignment (Main Panel)...........49
[169] Set Clock Back (Standard Time)...................................................39 [553]-[554] PGM 3&4 Output Partition Assignment
[170] PGM Output Timer .......................................................................39 (Main Panel/PC5208) .................................................................................49
[171] Tamper PGM Output Timer ..........................................................39 [555]-[560] PGM 5-10 Output Partition Assignment (5208) .....................49
[175] Auto-Arm Postpone Timer............................................................39 [561]-[564] PGM 11-14 Output Partition Assignment (5204) ...................49
[176] Cross Zone/Police Code Timer ....................................................39 [601]-[604] Closing (Arming) Reporting Codes, Access Codes 33-95........49
[181]-[188] Automatic Arming Schedule...............................................39 [605]-[608] Opening (Disarming) Reporting Codes, Access Codes 33-95.......50
[190] No Activity Arming Pre-Alert Time .............................................39 [681]-[688] Automatic Disarming Schedule ..............................................50
[191]-[198] No Activity Arming Timers ................................................39 [691]-[698] Auto-Disarm Holiday Schedule ..............................................50
[199] Auto-Arming Pre-Alert Timer ......................................................39 [700] Automatic Clock Adjust ...................................................................51
[201] Partition Selection Mask ...............................................................40 [701] 1st International Options...................................................................51
[202]-[265] Partition 1-8 Zone Assignment ...........................................40 [702] 2nd International Options..................................................................51
[301] 1st Telephone Number (32 Digits) ................................................40 [703] Delay between Dialing Attempts ......................................................51
[302] 2nd Telephone Number (32 Digits)...............................................40 [801] PC5400 Printer Module Programming .............................................52
[303] 3rd Telephone Number (32 Digits) ...............................................40 [802] PC59xx VOX Programming .............................................................52
[304] Call Waiting Cancel String (6 Digits) ...........................................40 [804] Wireless Expansion Programming ....................................................52
[310] System Account Code ...................................................................41 [805] PC5100 Programming.......................................................................52
[311]-[318] Partition 1-8 Account Numbers...........................................41 [851] TL/GS Programming.........................................................................52
[320]-[323] Alarm Reporting Codes, Zones 01-64.................................41 [898] Wireless Enrollment..........................................................................52
[324]-[327] Alarm Restoral Reporting Codes, Zones 01-64 ..................41 [899] Template Programming.....................................................................52
[328] Miscellaneous Alarm Reporting Codes.........................................42 [900] Panel Version Displayed ...................................................................52
[329] Priority Alarm and Restoral .........................................................42 [901] Installer Walk Test Mode Enable/Disable ........................................52
[330]-[333] Tamper Reporting Codes, Zones 01-64...............................42 [902] Module Supervision Reset ...............................................................52
[334]-[337] Tamper Restoral Reporting Codes, Zones 01-64 ................42 [903] Module Supervision Field ................................................................52
[338] Miscellaneous Tamper Reporting Codes ......................................43 [904] Wireless Module Placement Test .....................................................52
[339]-[340] Closing (Arming) Reporting Codes, [989] Default Master Code .........................................................................52
Access Codes 1-32.................................................................................43 [990] Installer Lockout Enable ...................................................................52
[341] Miscellaneous Closing (Arming) Reporting Codes ......................43 [991] Installer Lockout Disable ..................................................................52
[342]-[343] Opening (Disarming) Reporting Codes, [993] Restore Alternate Communicator to Default Programming .............52
Access Codes 1-32.................................................................................43 [995] Restore Escort5580 to Default Programming ...................................52
[344] Miscellaneous Opening (Disarming) Reporting Codes ................43 [996] Restore RF5132 to Default Programming ........................................52
[345] Maintenance Alarm Reporting Codes ...........................................43 [997] Restore PC5400 to Default Programming ........................................52
[346] Maintenance Restoral Reporting Codes .......................................43 [998] Restore PC59xx to Default Programming ........................................52
[347] Miscellaneous Maintenance Reporting Codes ..............................44 [999] Restore Control Panel to Default Programming ...............................52
29
PowerSeries - PC1616/PC1832/PC1864
Programming Worksheets
Shaded programming sections indicate minimum programming requirements
The defaults for SIA FAR CP-01 are indicated in gray text.
[20] Zone
Partition/Slot Key 1 Key 2 Key 3 Key 4 Key 5
Assigned
ICON / LED Defaults 11 00 03 04 06 14 16
KEYPAD 1 00
KEYPAD 2 00
KEYPAD 3 00
KEYPAD 4 00
KEYPAD 5 00
KEYPAD 6 00
KEYPAD 7 00
KEYPAD 8 00
[001]-[004] Zone Definitions (enter the values below in the table immediately following):
00 Null Zone (Not Used) 13 24-hr Gas* 26 24-hr Non-alarm*
01 Delay 1* 14 24-hr Heating* 29 Auto-Verified Fire
02 Delay 2* 15 24-hr Auxiliary (Medical)* 30 Fire Supervisory
03 Instant* 16 24-hr Panic* 31 Day Zone*
04 Interior* 17 24-hr Emergency* 32 Instant Stay/Away*
05 Interior, Stay/Away* 18 24-hr Sprinkler* 35 24-hr Bell/Buzzer
06 Delay, Stay/Away* 19 24-hr Water* 36 24-hr Non-Latching Tamper Zone
07 Delayed 24-hr Fire (Hardwired)** 20 24-hr Freeze* 37 Night Zone
08 Standard 24-hr Fire (Hardwired) 21 24-hr Latching Tamper* 39 For Future Use
09 24-hr Supervisory 22 Momentary Keyswitch Arm* 41 24-hr Carbon Monoxide (hardwired)
10 24-hr Supervisory Buzzer* 23 Maintained Keyswitch Arm* 81 24-hr Wireless Carbon Monoxide
11 24-hr Burglary* 24 For Future Use 87 Delay 24-hr Fire (Wireless/Addressable)**
12 24-hr Holdup* 25 Interior/Delay* 88 Standard 24-hr Fire (Wireless/Addressable)**
*For burglary applications only ** For residential fire applications only
30
Chapter 5 Programming Worksheets
Section Zone Def. Section Zone Def. Section Zone Def. Section Zone Def.
[001] 01 01 I_____I_____I [002] 17 00 I_____I_____I [003] 33 00 I_____I_____I [004] 49 00 I_____I_____I
02 03 I_____I_____I 18 00 I_____I_____I 34 00 I_____I_____I 50 00 I_____I_____I
03 03 I_____I_____I 19 00 I_____I_____I 35 00 I_____I_____I 51 00 I_____I_____I
04 03 I_____I_____I 20 00 I_____I_____I 36 00 I_____I_____I 52 00 I_____I_____I
05 04 I_____I_____I 21 00 I_____I_____I 37 00 I_____I_____I 53 00 I_____I_____I
06 04 I_____I_____I 22 00 I_____I_____I 38 00 I_____I_____I 54 00 I_____I_____I
07 04 I_____I_____I 23 00 I_____I_____I 39 00 I_____I_____I 55 00 I_____I_____I
08 04 I_____I_____I 24 00 I_____I_____I 40 00 I_____I_____I 56 00 I_____I_____I
09 00 I_____I_____I 25 00 I_____I_____I 41 00 I_____I_____I 57 00 I_____I_____I
10 00 I_____I_____I 26 00 I_____I_____I 42 00 I_____I_____I 58 00 I_____I_____I
11 00 I_____I_____I 27 00 I_____I_____I 43 00 I_____I_____I 59 00 I_____I_____I
12 00 I_____I_____I 28 00 I_____I_____I 44 00 I_____I_____I 60 00 I_____I_____I
13 00 I_____I_____I 29 00 I_____I_____I 45 00 I_____I_____I 61 00 I_____I_____I
14 00 I_____I_____I 30 00 I_____I_____I 46 00 I_____I_____I 62 00 I_____I_____I
15 00 I_____I_____I 31 00 I_____I_____I 47 00 I_____I_____I 63 00 I_____I_____I
16 00 I_____I_____I 32 00 I_____I_____I 48 00 I_____I_____I 64 00 I_____I_____I
For SIA CP-01 compliant installations, the Exit Delay must be within the range of 045-255 seconds (Default 60 seconds). If the Exit
Delay is silent (Section 14, Option 6 or Stay Function Key Arming), the exit delay must be twice the programmed value. It cannot, however,
exceed 255 seconds (i.e., 090-255 seconds).
For UL Installations, the Entry Delay plus the Communications Delay must not exceed 60 seconds.
Exit Time Restart shall be disabled when the panel is used in combination with T-Link TL250/TL300.
31
PowerSeries - PC1616 PC1 2 PC1 64
PC1616 and PC1832 have 2 onboard PGMs (PGM 1 and 2). PC1864 has 4 on-board PGMs (PGM 1-4).
Default Default
19 I_______I_______I PGM 1 10 I_______I_______I PGM 2
t er System ptions
012 eypad Lockout ptions
If Keypad Lockout is active, the panel cannot be disarmed with a keyswitch.
Default
000 I_______I_______I_______I umber o In alid Codes Be ore Lockout 001-255 codes 000 to disable
000 I_______I_______I_______I Lockout Duration 000-255 minutes
32
Chapter 5 Programming Worksheets
1 ❏ Arm /Disarm Bell Squawk Enabled ❏ Arm /Disarm Bell Squawk Disabled
3 ❏ Quick Exit Enabled (ON for SIA CP-01) ❏ Quick Exit Disabled
4 ❏ Quick Arming Enabled (No Code Required) ❏ Quick Arming Disabled (Code Required)
8 ❏ TLM Audible (Bell) when Armed ❏ TLM Trouble Beeps when Armed
2 ❏ Trouble Light Flashes if AC Fails ❏ Trouble Light does NOT follow AC Status
7 ❏ Bypass Status Displayed While Armed ❏ Bypass Status Not Displayed While Armed
33
PowerSeries - PC1616/PC1832/PC1864
1 ❏ WLS Key Does Not use Access Codes ❏ WLS Key Uses Access Codes
7 ❏ Exit Delay Restart Enabled (Enabled for SIA CP-01) ❏ Exit Delay Restart Disabled
34
Chapter 5 Programming Worksheets
1 ❏ Access Code Entry Blocked During Entry Delay ❏ Access Code Entry Not Blocked During Entry Delay
5 ❏ Switching from AWAY to STAY disabled ❏ AWAY to STAY toggle Option Permitted
6 ❏ 2-way Audio will Not Disconnect for a New Event ❏ 2-way Audio will Disconnect for a New Event
35
PowerSeries - PC1616/PC1832/PC1864
Zone Type:
00 Null Zone N N N N N N N N N
01 Delay 1 Y Y Y Y N Y N N N
02 Delay 2 Y Y Y Y N Y N N N
03 Instant Y Y Y Y N Y N N N
04 Interior Y Y N Y N Y N N N
05 Int. Stay/Away Y Y N Y Y Y N N N
06 Dly. Stay/Away Y Y N Y Y Y N N N
07 Dly. 24hr Fire (Hardw.) Y N N N N N N N N
08 Stand. 24hr Fire (Hardw.) Y N N N N N N N N
09 24hr Superv. N Y N N Y N N N N
10 24hr Superv. Buzzer N Y N Y N N N N N
11 24hr Burglary Y Y N Y N N N N N
12 24hr Holdup N Y N N N N N N N
13 24hr Gas Y N N N N N N N N
14 24hr Heating Y N N N N N N N N
15 24hr Auxiliary (Medical) Y Y N N N N N N N
16 24hr Panic Y Y N N N N N N N
17 24hr Emergency Y Y N N N N N N N
18 24hr Sprinkler Y Y N N N N N N N
19 24hr Water Y Y N N N N N N N
20 24hr Freeze Y Y N N N N N N N
21 24hr Latching Tamper Y Y N N N N N N N
22 Momentary Keyswitch N N N N Y N N N N
23 Maintained Keyswitch N N N N Y N N N N
25 Interior/Delay Y Y N Y N Y N N N
26 24hr Non-alarm N N N N Y N N N N
29 Auto Verified Fire Y N N N N N N N N
30 Fire Supervisory N N N N N N N N N
31 Day Zone Y Y N Y Y Y Y N N
32 Instant Stay/Away Y Y N Y N N N N N
35 24 hr Bell/Buzzer Y Y N Y N Y N N N
36 24hr Non Latching Tamper N Y N N N Y N N N
37 Night Zone Y Y N Y Y Y N N N
41 24hr Carbon Monoxide Y N N N N N N N N
81 24hr Carbon Monoxide (WLS) Y N N N N N N Y N
87 Dly. 24hr Fire (Wireless) Y N N N N N N Y N
88 Stand. 24hr Fire (Wireless) Y N N N N N N Y N
* For UL installations, do not change attribute 5 (Force Arming) from the default setting.
Attribute: 10 11 12 13 14 15 16
ON Zone Attributes 10-13 For Future Use NC Loops SEOL DEOL
Zone Type:
00 Null Zone N N N N N N N
01 Delay 1 N N N N N N N
02 Delay 2 N N N N N N N
03 Instant N N N N N N N
04 Interior N N N N N N N
05 Int. Stay/Away N N N N N N N
06 Dly. Stay/Away N N N N N N N
07 Dly. 24hr Fire (Hardw.) N N N N N Y N
08 Stand. 24hr Fire (Hardw.) N N N N N Y N
09 24hr Superv. N N N N N N N
10 24hr Superv. Buzzer N N N N N N N
11 24hr Burglary N N N N N N N
12 24hr Holdup N N N N N N N
13 24hr Gas N N N N N N N
14 24hr Heating N N N N N N N
15 24hr Medical N N N N N N N
16 24hr Panic N N N N N N N
17 24hr Emergency N N N N N N N
18 24hr Sprinkler N N N N N N N
36
Chapter 5 Programming Worksheets
Attribute: 10 11 12 13 14 15 16
ON Zone Attributes 10-13 For Future Use NC Loops SEOL DEOL
19 24hr Water N N N N N N N
20 24hr Freeze N N N N N N N
21 24hr Latching Tamper N N N N N N N
22 Momentary Keyswitch N N N N N N N
23 Maintained Keyswitch N N N N N N N
25 Interior Delay N N N N N N N
26 24hr Non-alarm N N N N N N N
29 Auto Verified Fire N N N N N N N
30 Fire Supervisory N N N N N N N
31 Day Zone N N N N N N N
32 Instant Stay/Away N N N N N N N
35 24hr Bell/Buzzer N N N N N N N
36 24hr Non Latching Tamper N N N N N N N
37 Night Zone N N N N N N N
41 24hr Carbon Monoxide N N N N N Y N
81 24hr Carbon Monoxide (Wireless) N N N N N N N
87 Dly. 24hr Fire (Wireless) N N N N N N N
88 Stand. 24hr Fire (Wireless) N N N N N N N
Section Zone # Zone Audible/ Steady/ Chime Bypass Force* Swing Tx. Delay Wireless Cross Zn
Type** Silent Pulsed No No No No No No No
1 2 3 4 5 6 7 8 9
[101] 01 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[102] 02 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[103] 03 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[104] 04 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[105] 05 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[106] 06 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[107] 07 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[108] 08 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[109] 09 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[110] 10 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[111] 11 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[112] 12 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[113] 13 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[114] 14 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[115] 15 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[116] 16 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[117] 17 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[118] 18 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[119] 19 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[120] 20 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[121] 21 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[122] 22 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[123] 23 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[124] 24 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[125] 25 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[126] 26 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[127] 27 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[128] 28 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[129] 29 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[130] 30 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[131] 31 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[132] 32 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[133] 33 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[134] 34 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
37
PowerSeries - PC1616/PC1832/PC1864
Section Zone # Zone Audible/ Steady/ Chime Bypass Force* Swing Tx. Delay Wireless Cross Zn
Type** Silent Pulsed No No No No No No No
1 2 3 4 5 6 7 8 9
[135] 35 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[136] 36 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[137] 37 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[138] 38 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[139] 39 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[140] 40 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[141] 41 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[142] 42 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[143] 43 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[144] 44 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[145] 45 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[146] 46 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[147] 47 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[148] 48 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[149] 49 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[150] 50 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[151] 51 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[152] 52 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[153] 53 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[154] 54 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[155] 55 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[156] 56 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[157] 57 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[158] 58 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[159] 59 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[160] 60 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[161] 61 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[162] 62 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[163] 63 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
[164] 64 ( ) I________I I________| I________| I________| I________| I________| I________| I________I I________I
Section Zone # Zone For Future For Future For Future For Future NC Loops SEOL DEOL
Type** Use Use Use Use Config. Config. Config.
10 11 12 13 14 15 16
[101] 01 ( ) I________I I________| I________| I________| I________| I________| I________|
System Timers
[165] Maximum Dialing Attempts to Each Telephone Number
Default 005 I_______I_______I_______I Valid entries are 001-005 attempts
For UL Listed Installations, 5 dialing attempts are required.
[166] Post Dial Wait for Handshake (All Formats)
Default 040 I_______I_______I_______I Valid entries are 001-255 seconds
[167] TL/GS Module Wait for Acknowledgement
Default 060 I_______I_______I_______I Valid entries are 060-255 seconds
38
Chapter 5 Programming Worksheets
39
PowerSeries - PC1616/PC1832/PC1864
Partition Programming
[201] Partition Selection Mask
Opt Def ON OFF
1 ❏ Partition 1 is enabled ❏ Cannot be disabled
For the PC1864 and PC1832, the default setting is partition 1, zones 1-16 ON. For the PC1616, the default setting is par-
tition 1, zones 1-6 ON.
Partition 1 Zone Assignment Partition 2 Zone Assignment Partition 3 Zone Assignment Partition 4 Zone Assignment
[202] 1-8 ❏❏❏❏❏❏❏❏ [210] 1-8 ❏❏❏❏❏❏❏❏ [218] 1-8 ❏❏❏❏❏❏❏❏ [226] 1-8 ❏❏❏❏❏❏❏❏
[203] 9-16 ❏❏❏❏❏❏❏❏ [211] 9-16 ❏❏❏❏❏❏❏❏ [219] 9-16 ❏❏❏❏❏❏❏❏ [227] 9-16 ❏❏❏❏❏❏❏❏
[204] 17-24 ❏❏❏❏❏❏❏❏ [212] 17-24 ❏❏❏❏❏❏❏❏ [220] 17-24 ❏❏❏❏❏❏❏❏ [228] 17-24 ❏❏❏❏❏❏❏❏
[205] 25-32 ❏❏❏❏❏❏❏❏ [213] 25-32 ❏❏❏❏❏❏❏❏ [221] 25-32 ❏❏❏❏❏❏❏❏ [229] 25-32 ❏❏❏❏❏❏❏❏
[206] 33-40 ❏❏❏❏❏❏❏❏ [214] 33-40 ❏❏❏❏❏❏❏❏ [222] 33-40 ❏❏❏❏❏❏❏❏ [230] 33-40 ❏❏❏❏❏❏❏❏
[207] 41-48 ❏❏❏❏❏❏❏❏ [215] 41-48 ❏❏❏❏❏❏❏❏ [223] 41-48 ❏❏❏❏❏❏❏❏ [231] 41-48 ❏❏❏❏❏❏❏❏
[208] 49-56 ❏❏❏❏❏❏❏❏ [216] 49-56 ❏❏❏❏❏❏❏❏ [224] 49-56 ❏❏❏❏❏❏❏❏ [232] 49-56 ❏❏❏❏❏❏❏❏
[209] 57-64 ❏❏❏❏❏❏❏❏ [217] 57-64 ❏❏❏❏❏❏❏❏ [225] 57-64 ❏❏❏❏❏❏❏❏ [233] 57-64 ❏❏❏❏❏❏❏❏
Partition 5 Zone Assignment Partition 6 Zone Assignment Partition 7 Zone Assignment Partition 8 Zone Assignment
[234] 1-8 ❏❏❏❏❏❏❏❏ [242] 1-8 ❏❏❏❏❏❏❏❏ [250] 1-8 ❏❏❏❏❏❏❏❏ [258] 1-8 ❏❏❏❏❏❏❏❏
[235] 9-16 ❏❏❏❏❏❏❏❏ [243] 9-16 ❏❏❏❏❏❏❏❏ [251] 9-16 ❏❏❏❏❏❏❏❏ [259] 9-16 ❏❏❏❏❏❏❏❏
[236] 17-24 ❏❏❏❏❏❏❏❏ [244] 17-24 ❏❏❏❏❏❏❏❏ [252] 17-24 ❏❏❏❏❏❏❏❏ [260] 17-24 ❏❏❏❏❏❏❏❏
[237] 25-32 ❏❏❏❏❏❏❏❏ [245] 25-32 ❏❏❏❏❏❏❏❏ [253] 25-32 ❏❏❏❏❏❏❏❏ [261] 25-32 ❏❏❏❏❏❏❏❏
[238] 33-40 ❏❏❏❏❏❏❏❏ [246] 33-40 ❏❏❏❏❏❏❏❏ [254] 33-40 ❏❏❏❏❏❏❏❏ [262] 33-40 ❏❏❏❏❏❏❏❏
[239] 41-48 ❏❏❏❏❏❏❏❏ [247] 41-48 ❏❏❏❏❏❏❏❏ [255] 41-48 ❏❏❏❏❏❏❏❏ [263] 41-48 ❏❏❏❏❏❏❏❏
[240] 49-56 ❏❏❏❏❏❏❏❏ [248] 49-56 ❏❏❏❏❏❏❏❏ [256] 49-56 ❏❏❏❏❏❏❏❏ [264] 49-56 ❏❏❏❏❏❏❏❏
[241] 57-64 ❏❏❏❏❏❏❏❏ [249] 57-64 ❏❏❏❏❏❏❏❏ [257] 57-64 ❏❏❏❏❏❏❏❏ [265] 57-64 ❏❏❏❏❏❏❏❏
Communications
[301] First Telephone Number (32 Digits)
I__D__I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I
[304] Call Waiting Cancel String (6 Digits) - This feature is activated in [382] Option 4
I_______I_______I_______I_______I_______I_______I Default = DB70EF Program unused digits with Hex F
All six digits must be entered for changes to be saved. Fill unused digit spaces with ‘F’.
40
Chapter 5 Programming Worksheets
Account Codes
Enter a 6-digit account number for the system account code. SIA will use this account code for all eight partitions. Only SIA supports
6-digit account codes. If the last two digits of the account code are FF, the panel will only use the first four digits.
Reporting Codes
[320]-[323] Alarm Reporting Codes, Zones 01-64
All Reporting Codes defaulted to FF unless otherwise indicated.
Section
[320] Zone 01 Zone 02 Zone 03 Zone 04 Zone 05 Zone 06 Zone 07 Zone 08
I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I
Zone 09 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zone 16
I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I
41
PowerSeries - PC1616/PC1832/PC1864
42
Chapter 5 Programming Worksheets
[345] Maintenance Alarm Reporting Codes [346] Maintenance Restoral Reporting Codes
I_______I_______I Battery Trouble Alarm I_______I_______I Battery Trouble Restoral
I_______I_______I AC Failure Trouble Alarm I_______I_______I AC Failure Trouble Restoral
I_______I_______I Bell Circuit Trouble Alarm I_______I_______I Bell Circuit Trouble Restoral
I_______I_______I Fire Trouble Alarm I_______I_______I Fire Trouble Restoral
I_______I_______I Auxiliary Power Supply Trouble Alarm I_______I_______I Auxiliary Power Supply Trouble Restoral
I_______I_______I TLM Trouble Code I_______I_______I TLM Restoral
I_______I_______I General System Trouble I_______I_______I General System Trouble Restoral
I_______I_______I General System Supervisory I_______I_______I General System Supervisory Restoral
I_______I_______I For Future Use I_______I_______I Cold Start
43
PowerSeries - PC1616/PC1832/PC1864
[347] Miscellaneous Maintenance Reporting Codes [348] Test Transmission Reporting Codes
I_______I_______I Telephone Number 1 FTC Restore I_______I_______I Walk Test End
I_______I_______I Telephone Number 2 FTC Restore I_______I_______I Walk Begin
I_______I_______I Event Buffer 75% Full Since Last Upload I_______I_______I Periodic Test Transmission with Trouble
I___0___I___0__I DLS Lead IN I_______I_______I Periodic Test Transmission
I___0___I___0__I DLS Lead OUT I_______I_______I System Test
I_______I_______I Zone Fault Alarm I_______I_______I For Future Use
I_______I_______I Zone Fault Restore
I_______I_______I Delinquency Code
I_______I_______I General Zone Low Battery Alarm
I_______I_______I General Zone Low Battery Restoral
I___0___I___0__I Installer Lead Out
I___0___I___0__I Installer Lead In
44
Chapter 5 Programming Worksheets
* For UL installations, the Entry Delay plus Communication Delay time must not exceed 60 seconds.
**Dependent on programming in [382], Option [6].
***Dependent on programming in [702], Option [3].
****Dependent on programming in [380], Option [8].
[378] Test Transmission Time of Day
Default
9999 I_______I_______I_______I_______I Valid entries are 0000-2359 (9999 to disable)
45
PowerSeries - PC1616/PC1832/PC1864
4 ❏ Switch to Pulse Dialing on 5th Attempt ❏ DTMF Dial For All Attempts
6 ❏ Alternate Dial (1st & 3rd) ❏ Call 1st Number, Back up to 3rd
2 ❏ Open After Alarm Bell Ringback Enabled ❏ Open After Alarm Bell Ringback Disabled
3 ❏ SIA Sends Programmed Reporting Codes ❏ SIA Sends Automatic Reporting Codes
7 ❏ Contact ID Uses Programmed Reporting Codes ❏ Contact ID Uses Automatic Reporting Codes
46
Chapter 5 Programming Worksheets
DLS Downloading
[401] Downloading Option Codes
Opt Def ON OFF
1 ❏ Answering Machine/Double Call enabled ❏ Answering Machine/Double Call disabled
2 ❏ User Can Enable DLS Window ❏ User Cannot Enable DLS Window
5 ❏ Auto Event Buffer Upload enabled ❏ Auto Event Buffer Upload disabled
[403]-[404] DLS Downloading Access Code / Panel ID Code (Enter 6 Hexadecimal Digits)
Panel Default [403] Downloading Access Code [404] Panel ID Code
[405] Answering Machine Double Call Timer [406] Number of Rings to Answer On
Default 060 I_______I_______I_______I (001-255 seconds) Default 000 I_______I_______I_______I (000-255 rings)
[499] Initiate PC-Link Downloading
Enter [499][Installer Code][499]
47
PowerSeries - PC1616/PC1832/PC1864
Attribute:
1 2 3 4 5 6 7 8
PGM Option
ON Serv. req. AC Fail TLM Fault FTC Zone Fault Zone Tmp. Zn. Low Loss of
Bat. Clock
OFF Disabled Disabled Disabled Disabled Disabled Disabled Disabled Disabled
[09] System Trouble Y Y Y Y Y Y Y Y
ON Burg. Evnt. Fire Evnt. Panic Evnt. Med. Evnt. Supv. Evnt. Priority Holdup Follows
Evnt. Evnt. Timer*
OFF Disabled Disabled Disabled Disabled Disabled Disabled Disabled Latched
[10] System Event Y Y Y Y Y Y Y N
ON Fire Alarm Panic Alarm Burglary Open/ Zone Auto Medical Police Active When
Alarm Close Bypass Alarm Code true
OFF Disabled Disabled Disabled Disabled Disabled Disabled Disabled Latched
[31] Alternate N N N N N N N N
Communicator
ON Future Use Future Use True Output Future Use Future Use Future Use Future Use AND Logic
OFF Inverted OR Logic
[29], [35]-[41] Zone Follower N N Y N N N N N
Section PGM Output 1 2 3 4 5 6 7 8
# Type*
Main Board
[501] 1 ( ) I________I I________| I________| I________| I________| I________| I________| I________I
PC5204
[511] 11 ( ) I________I I________| I________| I________| I________| I________| I________| I________I
48
Chapter 5 Programming Worksheets
PC5208
[555] 5 I________I I________| I________| I________| I________| I________| I________| I________I
PC5204
[561] 11 I________I I________| I________| I________| I________| I________| I________| I________I
[29] Zone Follower (1-8) Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8
[35] Zone Follower (9-16) Zone 9 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zone 16
[36] Zone Follower (17-24) Zone 17 Zone 18 Zone 19 Zone 20 Zone 21 Zone 22 Zone 23 Zone 24
[37] Zone Follower (25-32) Zone 25 Zone 26 Zone 27 Zone 28 Zone 29 Zone 30 Zone 31 Zone 32
[38] Zone Follower (33-40) Zone 33 Zone 34 Zone 35 Zone 36 Zone 37 Zone 38 Zone 39 Zone 40
[39] Zone Follower (41-48) Zone 41 Zone 42 Zone 43 Zone 44 Zone 45 Zone 46 Zone 47 Zone 48
[40] Zone Follower (49-56) Zone 49 Zone 50 Zone 51 Zone 52 Zone 53 Zone 54 Zone 55 Zone 56
[41] Zone Follower (57-64) Zone 57 Zone 58 Zone 59 Zone 60 Zone 61 Zone 62 Zone 63 Zone 64
49
PowerSeries - PC1616/PC1832/PC1864
50
Chapter 5 Programming Worksheets
INTERNATIONAL PROGRAMMING
[700] Automatic Clock Adjust
Default = 60 |________|_________| Valid Entries 00-99 Seconds
[701] First International Options
Opt Def ON OFF
1 ❏ 50 Hz AC ❏ 60 Hz AC
4 ❏ All System Tampers Require Installer Reset ❏ All System Tampers Follow Restore
3 ❏ Land Line Test Transmission in Minutes ❏ Land Line Test Transmission in Days
7 ❏ One-Time 1-hr User Enabled DLS Window ❏ Full 6-hr User Enabled DLS Window
51
PowerSeries - PC1616/PC1832/PC1864
Module Programming
[801] PC5400 Printer Module Programming
Refer to the PC5400 Installation Manual for installation and programming instructions.
[802] PC59xx VOX Module Programming
Refer to the PC59xx Installation Manual for installation and programming instructions.
[804] Wireless Expansion Programming
Refer to the RF5132/RFK55xx Installation Manual for programming locations and instructions.
[805] PC5100 Programming
Refer to the PC5100 Installation Manual for programming locations and instructions.
[851] TL/GS Module Programming
Refer to the TL/GS Installation Manual for programming locations and instructions.
Special Installer Functions
[898] Wireless Enrollment
52
Chapter 5 Programming Worksheets
Address: ____________________________________________________________________________________________________________
53
PowerSeries - PC1616/PC1832/PC1864
54
Appendix A: Reporting Codes
55
PowerSeries - PC1616/PC1832/PC1864
Automatic
Dialer SIA Auto
Section # Reporting Code Code Sent When... Contact ID
Direction* Rep Codes**
Codes
[345]-[346] TLM Failure/Restore Telephone line monitoring trouble/Telephone line restored MA/R E(3)51-000/ LT-01/LR-01
R(3)51-000
[345]-[346] Gen System Trouble/Rest. “Service Required” trouble (view troubles using [*][2])/trouble MA/R E(3)AA-000/ YX-00/YZ-00
restored R(3)AA-000
[345]-[346] Gen System Supervisory Control panel loses/restores communications with module(s) MA/R E(3)3A-000/ ET-00/ER-00
Trouble/Rest. connected to the Keybus R(3)3A-000
[346] Cold Start (System Reset) The system has been restarted after a total power loss. The reporting MA/R R(3)A5-000 RR-00
code is sent after a 2 minute start-up delay
[347] Phone# 1 or 2 FTC Restoral Control panel has restored communications to central station on MA/R R(3)54-000 YK-00
Phone# 1 or 2 (after FTC)
[347] Event Buffer is 75% Full Event buffer is almost full since last upload MA/R E(6)22-000 JL-00
[347] DLS Lead In Downloading session start MA/R E(4)11-000 RB-00
[347] DLS Lead Out Downloading session complete MA/R E(4)12-000 RS-00
[347] Zone Fault/Rest. One or more zones have faults/restored MA/R E(3)8A-ZZZ/ UT-ZZ/UJ-ZZ
R(3)8A-ZZZ
[347] Delinquency Programmed amount of time (days or hours) for delinquency has MA/R E(6)54-000*** CD-00
expired without zone activity, or without system being armed
[347] Wireless Device Low Battery Wireless zones, panic pendants, handheld keypads, wireless keys MA/R E(3)84-000/ XT-00/XR-00
Trouble/Rest. have low battery/all low batteries restored R(3)84-000 XT-ZZ/XR-ZZ****
[347] Installer Lead In/Lead Out Installer’s mode has been entered/exited MA/R E(6)27-000/ LB-00/LS-00
E(6)28-000
[348] Walk Test End/Begin End of test/Beginning of test T R(6)A7-UUU/ TE-00/TS-00
E(6)A7-UUU
[348] Periodic Test with Trouble Periodic system test transmission with trouble T E(6)A8-000 RY-00
[348] Periodic Test Periodic system test transmission T E(6)A2-000 RP-00
[348] System Test [*][6] bell/communications test T E(6)A1-000 RX-00
[349] PC5700 Ground Fault Trouble/ Ground/Fault/Trouble occurs on the PC5700 MA/R E(3)1A-000 US-00/UR-00
Rest
[349] PC5700 TLM Line 1 Trouble/Rest. TLM Trouble /Restore occurs on the PC5700 MA/R E(3)51-000/ LT-01/LR-01
R(3)51-000
[349] PC5700 TLM Line 2 Trouble/Rest. TLM Trouble /Restore occurs on the PC5700 MA/R E(3)52-000/ LT-02/LR-02
R(3)52-000
[601]-[604] Closings System armed (user 33-95 indicated) O/C R(4)A1-UUU CL-UU
[605]-[608] Openings System disarmed (user 33-95 indicated) O/C E(4)A1-UUU OP-UU
* A/R = alarms/restorals; T/R = tampers/restorals; O/C = openings/closings; MA/R = miscellaneous alarms/restorals; T = test transmissions
** UU = user number (User 01-95); ZZ = zone number (01-64)
*** Use the “Fail to close” event code [(4)54] to report closing or activity delinquency. Ensure the central station is aware that this code is used.
**** Zones are identified, panic pendants, wireless keys, and handheld keypads are not.
Table 2: Contact ID Programmed Zone Alarm/Restoral Event Codes Table 3: Automatic Zone Alarm/Restoral Codes
(as per SIA DCS: ‘Contact ID’ 01-1999): Program any of these codes for zone
alarms/restorals when using the standard (non-automatic) Contact ID reporting Zone Definition SIA Auto Rep Contact ID Contact ID
format. Codes* Alarm Auto Rest. Auto
Rep Codes* Rep Codes
Medical Alarms (1)34 Entry / Exit Delay 1 BA-ZZ/BH-ZZ E(1)3A-ZZZ R(1)3A-ZZZ
(1)AA Medical (1)35 Day / Night Delay 2 BA-ZZ/BH-ZZ E(1)3A-ZZZ R(1)3A-ZZZ
(1)A1 Pendant Transmitter (1)36 Outdoor Instant BA-ZZ/BH-ZZ E(1)3A-ZZZ R(1)3A-ZZZ
Interior BA-ZZ/BH-ZZ E(1)3A-ZZZ R(1)3A-ZZZ
(1)A2 Fail to Report In (1)37 Tamper
Interior Stay/Away BA-ZZ/BH-ZZ E(1)3A-ZZZ R(1)3A-ZZZ
Fire Alarms (1)38 Near Alarm Delay Stay/Away BA-ZZ/BH-ZZ E(1)3A-ZZZ R(1)3A-ZZZ
Delayed 24-Hr Fire FA-ZZ/FH-ZZ E(1)1A-ZZZ R(1)1A-ZZZ
(1)1A Fire Alarm General Alarms Standard 24-Hr Fire FA-ZZ/FH-ZZ E(1)1A-ZZZ R(1)1A-ZZZ
(1)11 Smoke (1)4A General Alarm 24-Hr Supervisory US-ZZ/UR-ZZ E(1)5A-ZZZ R(1)5A-ZZZ
(1)12 Combustion (1)43 Exp. module failure 24-Hr Supervisory Buzzer UA-ZZ/UH-ZZ E(1)5A-ZZZ R(1)5A-ZZZ
(1)13 Water Flow (1)44 Sensor tamper 24-Hr Burglary BA-ZZ/BH-ZZ E(1)3A-ZZZ R(1)3A-ZZZ
24-Hr Holdup HA-ZZ/HH-ZZ E(1)22-ZZZ R(1)22-ZZZ
(1)14 Heat (1)45 Module Tamper
24-Hr Gas GA-ZZ/GH-ZZ E(1)51-ZZZ R(1)51-ZZZ
(1)15 Pull Station (1)4A Cross Zone Police Code 24-Hr Heat KA-ZZ/KH-ZZ E(1)58-ZZZ R(1)58-ZZZ
(1)16 Duct 24 Hour Non-Burglary 24-Hr Auxiliary (Medical) MA-ZZ/MH-ZZ E(1)AA-ZZZ R(1)AA-ZZZ
24-Hr Panic PA-ZZ/PH-ZZ E(1)2A-ZZZ R(1)2A-ZZZ
(1)17 Flame (1)5A 24 Hour non-Burg
24-Hr Emerg. (non-medical) QA-ZZ/QH-ZZ E(1)A1-ZZZ R(1)A1-ZZZ
(1)18 Near Alarm (1)51 Gas detected
24-Hr Sprinkler SA-ZZ/SH-ZZ E(1)13-ZZZ R(1)13-ZZZ
Panic Alarms (1)52 Refrigeration 24-Hr Water WA-ZZ/WH-ZZ E(1)54-ZZZ R(1)54-ZZZ
24-Hr Freeze ZA-ZZ/ZH-ZZ E(1)59-ZZZ R(1)59-ZZZ
(1)2A Panic (1)53 Loss of Heat
24-Hr Latching UA-ZZ/UH-ZZ E(1)4A-ZZZ R(1)4A-ZZZ
(1)21 Duress (1)54 Water Leakage Interior Delay BA-ZZ/BH-ZZ E(1)3A-ZZZ R(1)3A-ZZZ
(1)22 Silent (1)55 Foil Break Auto Verified Fire FA-ZZ/FH-ZZ E(1)1A-ZZZ R(1)1A-ZZZ
(1)23 Audible (1)56 Day Trouble 24-Hr Fire Supervisory FS-ZZ/FV-ZZ E(2)AA-ZZZ R(2)AA-ZZZ
Burglar Alarms (1)57 Low bottled Gas level Day Zone BA-ZZ/BH-ZZ E(1)3A-ZZZ R(1)3A-ZZZ
Instant Stay/Away BA-ZZ/BH-ZZ E(1)3A-ZZZ R(1)3A-ZZZ
(1)3A Burglary (1)58 High Temp 24-Hr Bell/Buzzer UA-ZZ/UH-ZZ E(1)5A-ZZZ R(1)5A-ZZZ
(1)31 Perimeter (1)59 Low Temp 24-Hr Non-latching Tamper UA-ZZ/UH-ZZ E(1)4A-ZZZ R(1)4A-ZZZ
(1)32 Interior (1)61 Loss of Air Flow Night Zone BA-ZZ/BH-ZZ E(1)3A-ZZZ R(1)3A-ZZZ
(1)33 24 Hour Delayed 24-Hr Fire (Wireless) FA-ZZ/FH-ZZ E(1)1A-ZZZ R(1)1A-ZZZ
Standard 24-Hr Fire(Wireless) FA-ZZ/FH-ZZ E(1)1A-ZZZ R(1)1A-ZZZ
24-Hr CO Alarm GA-ZZ/GH-ZZ E(1)62-ZZZ R(1)62-ZZZ
* ZZ or ZZZ= zones 01-64
56
Appendix B: UL Listed Commercial and Residential Installations
57
PowerSeries - PC1616/PC1832/PC1864
Exit Time - [005], 3rd entry Access to Entry and Exit delays for each partition and Bell Time Out for the system For Full or auto arming: Required
Range: 45-255 seconds (programmable)
Default: 60 sec.
Progress Annunciation/ Enables audible exit beeps from the keypad for the duration of exit delay Individual keypads Allowed
Disable - for Silent Exit - may be disabled
[014], Option 6 ON Default: All Enabled
Exit Time Restart - Enables the exit delay restart feature Default: Enabled Required
[018], Option 7 ON
Auto Stay Arm on Unvacated Function Key: Stay Arming. All Stay/Away type zones (05, 06) will be automatically If no exit after full arm Required
Premises - [001]-[004] Zone bypassed Default: Enabled
type 05, 06
Exit Time and Progress System Times and Audible Exit beeps can be disabled when using the Key fob to Default: Enabled Allowed
Annunciation/Disable arm away the system
or Remote Arming -
[005] and [014] bit 6
Entry Delay(s) - [005], 1st and Access to Entry and Exit delays for each partition and Bell Time Out for the system. Range: 30 sec. to 4 min. Required
2nd entry NOTE: Combined Entry delay and Communications Delay (Abort Window) shall not Default: 30 sec. (programmable)
exceed 60s
Abort Window for Non-Fire Access to zone attributes, i.e, swinger shutdown, transmission delay and cross May be disabled Required
zones - [101]-[164] bit 7 ON zone. Individual zones attribute bit 7 (Transmission delay) is by default ON by zone or zone type
Default: Enabled
Abort Window - for Non-Fire Access to the programmable delay before communicating alarms. NOTE: Com- Range: 15 - 45 sec. Required
zones - [377], 4th entry bined Entry delay and Communications Delay (Abort Window) shall not exceed 60s Default: 30 sec. (programmable)
Abort Annunciation - [382], Enables the “Communication Cancelled” message display on all keypads Annunciate that no Required
Option 3 ON alarm was transmitted
Default: Enabled
Cancel Annunciation - [328], Access to the reporting code for Alarm Cancelled Annunciate that a Required
8th entry Cancel was transmitted
Default: Enabled
Duress Feature - [✱][5] Master Do not derive code from an existing Master/User code (e.g., Master code is 1234, No 1+/- derivative of another Allowed
Code - [99] Option 2 ON the duress code should not be 1233 or 1235) user code. No duplicates with
other user codes
Default: disabled
Cross Zoning - [018] This option enables Cross Zoning for entire system. Individual zones can be ena- Programming required Required
Option 6 ON bled for Cross zoning via Zone attribute bit 9 in sections [101] - [164] Default: Disabled
[101]-[164] bit 9 OFF
Cross Zone Timer - [176] Access to the programmable Cross Zone timer May program Allowed
Range: 001-255 sec.
Default: 60 secs
Swinger Shutdown for Alarms Access to the swinger shutdown limit for zone alarms For all non-fire zones Required
[377] 1st entry shut down at 1 or 2 trips (programmable)
Default: 1 Trip
Swinger Shutdown Disable - Access to zone attributes, i.e., swinger shutdown, transmission delay and cross For non-police Allowed
[101] - [164] bit 6 ON zone. Individual zones attribute bit 6 (Swinger shutdown enabled) is by default ON response zones
Default: Enabled
Fire Alarm Verification - Auto Verified Fire, use only with 4 wire type detectors that can be reset by the panel 70 seconds reset and Required
Zone Type [29] 4-wire smoke detector powered from AUX + and PGM1 - PGM4 (type 03, Sensor confirmation time
reset) Default: disabled
Call Waiting Cancel Dial String - Access to the dialing sequence used to disable call waiting Dependant on user phone line Required
[304], [382], Opt. 4 OFF Default: disabled
Testing
System Test: [✱][6] Master The system activates all keypad sounders, bells or sirens for 2 seconds and all keypad lights turn on.
Code, Option 4 Refer to the User Manual (part no. 29008261).
Installer Walk Test Mode: [901] This mode is used to test each zone on the system for proper functionality.
Alarm Communications Enables Communication of zone alarms while installer Walk Test is active.
During Walk Test [382] Opt. 2
Walk Test End and Begin Access to the reporting codes for Walk Test Begin and Walk Test End.
Reporting Codes [348], 1st and
2nd Entries
58
Appendix D: Troubleshooting Guide
• Power up system
• Program options as required (See Programming Section)
• Violate, then restore zones
• Verify correct Reporting Codes are sent to the Central Station
Troubleshooting:
NOTE: When additional information is available for a specific trouble condition a [✱] will appear on the display.
Press the [✱] key to view the additional information
LED Keypads, LCD Fixed Message Keypads
• Press [✱][2] to view a trouble condition.
• The trouble light will flash.
• Refer to the Trouble Summary chart below to determine the trouble condition(s) present.
Trouble Summary:
Light [7][✱] Wireless Device Low Battery - Press [7] for more information
59
PowerSeries - PC1616/PC1832/PC1864
[2] Bell Circuit Bell Bell-... pen Circuit Disconnect Bell- Bell wire leads measure resistance o wire
leads.
- pen circuit indicates break in wiring or de ecti e siren bell
umper Bell Bell- wit 1 resistor Brown Black ed
- eri y trouble clears
[3] General System PC5204 utput 1 pen Circuit I utput 1 is unused: nsure t at terminals 1 AUX are
Trouble umpered wit 1 resistor Brown Black ed
I utput 1 is used: Disconnect wire leads rom 1 AUX
terminals measure t e resistance o t e wire leads
- pen circuit indicates a break in t e wiring
PC5204 AUX eri y oltage measured across AC input terminals is 16-1 AC.
Disconnect all connections to PC5204 AUX terminal.
- eri y AUX oltage is 1 .70 - 1 . 0 DC.
Printer connected to PC5400 o line eri y printer operation out o paper paper am etc.
[4] General System amper input on module s open circuit S ort tamper terminal to C M terminal on unused modules connected
Tamper to BUS PC5100 PC510 PC5200 PC5204 PC520 PC5 20
PC5400 PC5700 .
[5] Module Panel does not communicate wit Modules are immediately enrolled and super ised w en detected on
Supervision module s on BUS t e BUS. I a module as been remo ed or i t e slot assignment
o a keypad as been c anged module super ision must be reset.
eypad assigned to incorrect slot. iew t e e ent bu er ia DLS or LCD5500 keypad to identi y t e
speci ic module s in trouble
o reset module super ision:
- nter Program Section 02 .
- Press wait 1 minute or panel to scan BUS .
nter Program Section 0 to identi y modules connected to t e
BUS.
[6] RF Jam Detected Wireless ecei er - excessi e noise C eck or external 4 M signal sources
detected. o disable F am: enable ption 7 in program section 04
subsection 0 .
[7] PC5204 Low PC5204 battery less t an 11.5 DC See 1 Low Battery abo e
Battery
NOTE: This trouble condition will not
clear until the battery voltage is
12.5VDC min., under load.
[8] PC5204 AC Failure o AC at PC5204 AC inputs eri y oltage measured across AC terminals is 16-1 AC.
eplace trans ormer i re uired.
60
Appendix D: roubles ooting Guide
rouble 2 AC Failure
o AC at panel AC input eri y oltage measured across AC terminals is 16-1 AC. eplace
terminals trans ormer i re uired.
rouble 5 one Fault Press 5 to determine speci ic ones wit a ault trouble
pen circuit is present on one or more nsure ire ones a e a 5.6 resistor Green Blue ed
ire ones on t e main panel or one connected.
expander
emo e t e wire leads rom and C M terminals and measure t e
resistance o t e wire leads.
- An open circuit indicates a break in t e wiring or resistor not
connected.
Connect a 5.6 resistor Green Blue ed across t e and C M
terminals. eri y t e trouble condition clears.
An open circuit is present on PGM2 being nsure t e correct 2.2 end-o -line resistor is connected ed
used as a 2-wire smoke detector input ed ed .
emo e t e wire leads rom PGM2 and AUX terminals and
measure t e resistance o t e wire leads.
- An open circuit indicates a break in t e wiring or no resistor
connected.
Connect a 2.2 resistor ed ed ed across t e PGM2 and
AUX terminals. eri y t e trouble condition clears.
ne or more wireless de ices a e not I t e trouble occurs immediately a con lict wit a ard wired one
c ecked in wit in t e programmed time exists:
- e one being used is already assigned to a PC510 one
expander
- e one being used is assigned as a keypad one
Per orm a Module Placement est Program Section 04 and
eri y t e wireless de ice is in a good location.
- I bad test results occur test t e wireless de ice in anot er location
- I t e wireless de ice now tests good t e original mounting
location is bad
- I t e wireless de ice continues to gi e bad test results replace t e
wireless de ice
A s ort circuit is present on one or more emo e t e wire leads rom and C M terminals and measure t e
ones wit double end-o -line resistors resistance o t e wire leads.
enabled - A s ort circuit indicates a s ort in t e wiring.
Connect a 5.6 resistor Green Blue ed across t e and C M
terminals.
- eri y t e trouble condition clears.
61
PowerSeries - PC1616/PC1832/PC1864
rouble 6 one amper Press 6 to determine speci ic ones wit a tamper trouble
A tamper condition is present on one or Per orm a Module Placement est Section 04
more wireless de ices
iolate t en restore t e tamper:
I no test result t en replace wireless de ice
An open circuit is present on one or more emo e t e wire leads rom and C M terminals.
ones wit double end-o -line resistors
enabled Measure t e resistance o t e wire leads.
pen circuit indicates a break in t e wiring.
Connect a 5.6 resistor Green Blue ed across t e and C M
terminals.
eri y t e trouble condition clears.
rouble 7 Wireless De ice Low Battery Press 7 to toggle t roug speci ic de ices wit low battery trouble
1st press ne or more wireless de ices as a low eplace battery
Wireless ones battery
2nd press NOTE: Replacing batteries will cause a tamper. Replacing cover will
NOTE: The event will not be logged to
and eld eypads restore the tamper causing the associated reporting codes to be sent
the event buffer until the wireless device
rd press low battery delay time expires to the Central Station.
Wireless eys
Program Section 77 pt
IMP A
nsure you a e t e ollowing in ormation a ailable be ore contacting Customer Support
62
Appendix E: Template Programming
Common Group
63
PowerSeries - PC1616/PC1832/PC1864
Selected Troubles
Trouble [345] Alarms [346] Restoral
Battery FF FF
AC Failure 00 00
Bell Circuit FF FF
Fire, Alarm FF FF
Aux PS FF FF
TLM 00 FF
General System 00 00
General System Supervisory FF FF
FF = Communicate in automatic format , 00 = Disabled
1-64 00 00 00 00 00 00 00 00 [324]-[327]
00 = Disabled
64
Appendix F: Communicator Format Options
65
PowerSeries - PC1616/PC1832/PC1864
the duration of Post Dial Wait for Handshake timer. Once Telephone Line Monitoring (TLM)
the panel receives the handshake, it will emit an alarm tone When the TLM Enable option is selected, the panel will
over the telephone line for 20 seconds. If several alarms supervise the telephone line and will indicate a trouble con-
occur at the same time, only one call will be made to each dition if the telephone line is disconnected.
telephone number the panel is programmed to call. If the TLM Enable option is ON, the panel will check the tele-
phone line every 10 seconds. If the telephone line voltage is
Communicator Call Direction Options . . . .Section [361] to [368]
below 3V for the number of checks programmed in the TLM
Trouble Delay section, the panel will report a TLM trouble.
Pager Format The default number of checks is 10. Enter a number from
The Communicator Format option for either telephone (000) to (255) in the TLM Trouble Delay section to change
number can be programmed for Pager Format. If an event the number of checks before the TLM trouble is reported.
occurs and the Communicator Call Direction options Programming a delay means that a momentary interruption
direct the call to a telephone number with the Pager Format of the telephone line will not cause a trouble condition.
selected the panel will attempt to page. If the TLM Trouble Beeps When Armed option is enabled,
When calling a pager extra digits will be required to make it the panel will indicate a TLM trouble at the keypad while the
work properly.The following is a list of Hex digits and what system is armed. To activate the bell output in the case of a
function they perform: TLM trouble while the system is armed, the TLM Audible
Hex [A] - not used (Bell) When Armed option must be selected.
Hex [B] - simulates the * key on a touch tone telephone When the trouble condition is restored, the panel can send a
Hex [E] - two second pause TLM Restoral reporting code. Any events which occur while
Hex [C] - simulates the [#] key on a touch tone telephone the telephone line is down will also be communicated. If an
Hex [F] - end of telephone number marker alternate communicator is being used, the panel can be pro-
Hex [D] - forces the panel to search for dial tone grammed to report a TLM Trouble Reporting Code.
The panel will attempt to call the pager one time. After dial-
ing the digits in the telephone number the panel will send
the account number and reporting code followed by the [#]
key (Hex [C]).
There is no ringback when using Pager Format. The panel
has no way of confirming if the pager was called success-
fully; a failure to communicate trouble will only be generated
once the maximum number of attempts has been reached.
NOTE: Do not use the digit C in a reporting code when using
Pager Format. In most cases, the digit C will be interpreted as a
[#], which will terminate the page before it has finished.
NOTE: If the panel detects a busy signal, it will attempt to page
again. It will make the maximum number of attempts pro-
grammed in section [165].
Force dialing should be disabled when using Pager format.
When using Pager format, you must program two hex digit E’s at
the end of the telephone number.
Pulse Formats
Depending on the pulse format selected the panel will com-
municate using the following:
• 3/1, 3/2, 4/1 or 4/2
• 1400 or 2300 Hz handshake
• 10 or 20 bits per second
• non-extended
The digit ‘0’ will send no pulses and is used as a filler. When
programming account numbers enter four digits. When pro-
gramming a three digit account number the fourth digit must
be programmed as a plain ‘0’ which will act as a filler digit.
If an account number has a ‘0’ in it, substitute a HEX digit ‘A’
for the ‘0’. Examples:
• 3 digit account number [123]- program [1230]
• 3 digit account number [502] - program [5A20]
• 4 digit account number [4079] - program [4A79]
When programming reporting codes two digits must be
entered. If one digit reporting codes are to be used the sec-
ond digit must be programmed as a ‘0’. If a ‘0’ is to be trans-
mitted substitute a HEX digit ‘A’ for the ‘0’.
Examples:
• 1 digit reporting code [3] - program [30]
• 2 digit reporting code [30] - program [3A]
To prevent the panel from reporting an event program the
reporting code for the event as [00] or [FF].
66
Appendix F: Communicator Format Options
Use the following list as a guide to find a suitable place for this equipment:
• Locate the control panel near a telephone socket and a power outlet.
• Select a place that is free from vibration and shock.
• Place the alarm controller on a flat, stable surface and follow the installation instructions:
Do NOT locate this product where persons can walk on the secondary circuit cable(s).
Do NOT connect the alarm controller to electrical outlets on the same circuit as large appliances.
Do NOT select a place that exposes the alarm controller to direct sunlight, excessive heat, moisture, vapors, chemicals
or dust.
Do NOT install this equipment near water (e.g., bathtub, wash bowl, kitchen/laundry sink, wet basement, or near a
swimming pool).
Do NOT install this equipment and its accessories in areas where there is a risk of explosion.
Do NOT connect this alarm controller to electrical outlets controlled by wall switches or automatic timers.
AVOID sources of radio interference.
AVOID setting up the equipment near heaters, air conditioners, ventilators, and/or refrigerators.
AVOID locating this equipment close to or on top of large metal objects (e.g., metal wall studs).
• NEVER install this equipment and/or telephone wiring during a lightning storm.
• NEVER touch uninsulated telephone wires or terminals unless the telephone line has been disconnected at the network
interface.
• Ensure that cables are positioned so that accidents can not occur. Connected cables must not be subject to excessive
mechanical strain.
• For Direct Plug-in versions, use the transformer supplied with the device.
The power supply must be Class II, FAIL SAFE with double or reinforced insulation between the PRIMARY and
SECONDARY circuit/ENCLOSURE and be an approved type acceptable to the local authorities. All national wiring rules
shall be observed.
67
Limited Warranty
Digital Security Controls warrants the original purchaser that for a period of twelve months from the date of purchase, the product shall be free of
defects in materials and workmanship under normal use. During the warranty period, Digital Security Controls shall, at its option, repair or Items Not Covered by Warranty
replace any defective product upon return of the product to its factory, at no charge for labour and materials. Any replacement and/or repaired In addition to the items which void the Warranty, the following items shall not be covered by Warranty: (i) freight cost to the repair centre; (ii)
parts are warranted for the remainder of the original warranty or ninety (90) days, whichever is longer. The original purchaser must promptly products which are not identified with DSC's product label and lot number or serial number; (iii) products disassembled or repaired in such a
notify Digital Security Controls in writing that there is defect in material or workmanship, such written notice to be received in all events prior to manner as to adversely affect performance or prevent adequate inspection or testing to verify any warranty claim. Access cards or tags returned
expiration of the warranty period. There is absolutely no warranty on software and all software products are sold as a user license under the terms for replacement under warranty will be credited or replaced at DSC's option. Products not covered by this warranty, or otherwise out of warranty
of the software license agreement included with the product. The Customer assumes all responsibility for the proper selection, installation, due to age, misuse, or damage shall be evaluated, and a repair estimate shall be provided. No repair work will be performed until a valid
operation and maintenance of any products purchased from DSC. Custom products are only warranted to the extent that they do not function purchase order is received from the Customer and a Return Merchandise Authorization number (RMA) is issued by DSC's Customer Service.
upon delivery. In such cases, DSC can replace or credit at its option.
International Warranty Digital Security Controls Ltd.’s liability for failure to repair the product under this warranty after a reasonable number of attempts will be limited
The warranty for international customers is the same as for any customer within Canada and the United States, with the exception that Digital to a replacement of the product, as the exclusive remedy for breach of warranty. Under no circumstances shall Digital Security Controls be liable
Security Controls shall not be responsible for any customs fees, taxes, or VAT that may be due. for any special, incidental, or consequential damages based upon breach of warranty, breach of contract, negligence, strict liability, or any other
Warranty Procedure legal theory. Such damages include, but are not limited to, loss of profits, loss of the product or any associated equipment, cost of capital, cost
of substitute or replacement equipment, facilities or services, down time, purchaser’s time, the claims of third parties, including customers, and
To obtain service under this warranty, please return the item(s) in question to the point of purchase. All authorized distributors and dealers have injury to property. The laws of some jurisdictions limit or do not allow the disclaimer of consequential damages. If the laws of such a jurisdiction
a warranty program. Anyone returning goods to Digital Security Controls must first obtain an authorization number. Digital Security Controls will apply to any claim by or against DSC, the limitations and disclaimers contained here shall be to the greatest extent permitted by law. Some
not accept any shipment whatsoever for which prior authorization has not been obtained. states do not allow the exclusion or limitation of incidental or consequential damages, so that the above may not apply to you.
Conditions to Void Warranty
This warranty applies only to defects in parts and workmanship relating to normal use. It does not cover: Disclaimer of Warranties
• damage incurred in shipping or handling; This warranty contains the entire warranty and shall be in lieu of any and all other warranties, whether expressed or implied (including all implied
• damage caused by disaster such as fire, flood, wind, earthquake or lightning; warranties of merchantability or fitness for a particular purpose) and of all other obligations or liabilities on the part of Digital Security Controls.
• damage due to causes beyond the control of Digital Security Controls such as excessive voltage, mechanical shock or water damage; Digital Security Controls neither assumes responsibility for, nor authorizes any other person purporting to act on its behalf to modify or to
• damage caused by unauthorized attachment, alterations, modifications or foreign objects; change this warranty, nor to assume for it any other warranty or liability concerning this product. This disclaimer of warranties and limited
• damage caused by peripherals (unless such peripherals were supplied by Digital Security Controls Ltd.); warranty are governed by the laws of the province of Ontario, Canada.
• defects caused by failure to provide a suitable installation environment for the products;
• damage caused by use of the products for purposes other than those for which it was designed; WARNING: Digital Security Controls recommends that the entire system be completely tested on a regular basis. However, despite
• damage from improper maintenance;
• damage arising out of any other abuse, mishandling or improper application of the products. frequent testing, and due to, but not limited to, criminal tampering or electrical disruption, it is possible for this product to fail to perform
as expected.
Out of Warranty Repairs
Digital Security Controls will at its option repair or replace out-of-warranty products which are returned to its factory according to the following
conditions. Anyone returning goods to Digital Security Controls must first obtain an authorization number. Digital Security Controls will not
accept any shipment whatsoever for which prior authorization has not been obtained.
Products which Digital Security Controls determines to be repairable will be repaired and returned. A set fee which Digital Security Controls has
predetermined and which may be revised from time to time, will be charged for each unit repaired.
IMPORTANT - READ CAREFULLY: DSC Software purchased with or without Products and Components
is copyrighted and is purchased under the following license terms:
(f) Termination - Without prejudice to any other rights, DSC may terminate this EULA if You fail to comply with the terms and conditions of this
• This End-User License Agreement (“EULA”) is a legal agreement between You (the company, individual or entity who acquired the Software EULA. In such event, You must destroy all copies of the SOFTWARE PRODUCT and all of its component parts.
and any related Hardware) and Digital Security Controls, a division of Tyco Safety Products Canada Ltd. (“DSC”), the manufacturer of the (g) Trademarks - This EULA does not grant You any rights in connection with any trademarks or service marks of DSC or its suppliers.
integrated security systems and the developer of the software and any related products or components (“HARDWARE”) which You acquired. 3. COPYRIGHT - All title and intellectual property rights in and to the SOFTWARE PRODUCT (including but not limited to any images,
• If the DSC software product (“SOFTWARE PRODUCT” or “SOFTWARE”) is intended to be accompanied by HARDWARE, and is NOT accom- photographs, and text incorporated into the SOFTWARE PRODUCT), the accompanying printed materials, and any copies of the SOFTWARE
panied by new HARDWARE, You may not use, copy or install the SOFTWARE PRODUCT. The SOFTWARE PRODUCT includes computer soft- PRODUCT, are owned by DSC or its suppliers. You may not copy the printed materials accompanying the SOFTWARE PRODUCT. All title and
ware, and may include associated media, printed materials, and “online” or electronic documentation. intellectual property rights in and to the content which may be accessed through use of the SOFTWARE PRODUCT are the property of the
• Any software provided along with the SOFTWARE PRODUCT that is associated with a separate end-user license agreement is licensed to You respective content owner and may be protected by applicable copyright or other intellectual property laws and treaties. This EULA grants You no
under the terms of that license agreement. rights to use such content. All rights not expressly granted under this EULA are reserved by DSC and its suppliers.
• By installing, copying, downloading, storing, accessing or otherwise using the SOFTWARE PRODUCT, You agree unconditionally to be bound 4. EXPORT RESTRICTIONS - You agree that You will not export or re-export the SOFTWARE PRODUCT to any country, person, or entity
by the terms of this EULA, even if this EULA is deemed to be a modification of any previous arrangement or contract. If You do not agree to subject to Canadian export restrictions.
the terms of this EULA, DSC is unwilling to license the SOFTWARE PRODUCT to You, and You have no right to use it. 5. CHOICE OF LAW - This Software License Agreement is governed by the laws of the Province of Ontario, Canada.
SOFTWARE PRODUCT LICENSE 6. ARBITRATION - All disputes arising in connection with this Agreement shall be determined by final and binding arbitration in accordance
The SOFTWARE PRODUCT is protected by copyright laws and international copyright treaties, as well as other intellectual property laws and with the Arbitration Act, and the parties agree to be bound by the arbitrator’s decision. The place of arbitration shall be Toronto, Canada, and the
treaties. The SOFTWARE PRODUCT is licensed, not sold. language of the arbitration shall be English.
1.GRANT OF LICENSE This EULA grants You the following rights: 7. LIMITED WARRANTY
(a) Software Installation and Use - For each license You acquire, You may have only one copy of the SOFTWARE PRODUCT installed. (a) NO WARRANTY - DSC PROVIDES THE SOFTWARE “AS IS” WITHOUT WARRANTY. DSC DOES NOT WARRANT THAT THE SOFTWARE WILL MEET
(b) Storage/Network Use - The SOFTWARE PRODUCT may not be installed, accessed, displayed, run, shared or used concurrently on or from YOUR REQUIREMENTS OR THAT OPERATION OF THE SOFTWARE WILL BE UNINTERRUPTED OR ERROR-FREE.
different computers, including a workstation, terminal or other digital electronic device (“Device”). In other words, if You have several (b) CHANGES IN OPERATING ENVIRONMENT - DSC shall not be responsible for problems caused by changes in the operating characteristics
workstations, You will have to acquire a license for each workstation where the SOFTWARE will be used. of the HARDWARE, or for problems in the interaction of the SOFTWARE PRODUCT with non-DSC-SOFTWARE or HARDWARE PRODUCTS.
(c) Backup Copy - You may make back-up copies of the SOFTWARE PRODUCT, but You may only have one copy per license installed at any (c) LIMITATION OF LIABILITY; WARRANTY REFLECTS ALLOCATION OF RISK - IN ANY EVENT, IF ANY STATUTE IMPLIES WARRANTIES OR
given time. You may use the back-up copy solely for archival purposes. Except as expressly provided in this EULA, You may not otherwise CONDITIONS NOT STATED IN THIS LICENSE AGREEMENT, DSC’S ENTIRE LIABILITY UNDER ANY PROVISION OF THIS LICENSE
make copies of the SOFTWARE PRODUCT, including the printed materials accompanying the SOFTWARE. AGREEMENT SHALL BE LIMITED TO THE GREATER OF THE AMOUNT ACTUALLY PAID BY YOU TO LICENSE THE SOFTWARE PRODUCT
2. DESCRIPTION OF OTHER RIGHTS AND LIMITATIONS AND FIVE CANADIAN DOLLARS (CAD$5.00). BECAUSE SOME JURISDICTIONS DO NOT ALLOW THE EXCLUSION OR LIMITATION OF
(a) Limitations on Reverse Engineering, Decompilation and Disassembly - You may not reverse engineer, decompile, or disassemble the LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES, THE ABOVE LIMITATION MAY NOT APPLY TO YOU.
SOFTWARE PRODUCT, except and only to the extent that such activity is expressly permitted by applicable law notwithstanding this (d) DISCLAIMER OF WARRANTIES - THIS WARRANTY CONTAINS THE ENTIRE WARRANTY AND SHALL BE IN LIEU OF ANY AND ALL OTHER
limitation. You may not make any changes or modifications to the Software, without the written permission of an officer of DSC. You may WARRANTIES, WHETHER EXPRESSED OR IMPLIED (INCLUDING ALL IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A
not remove any proprietary notices, marks or labels from the Software Product. You shall institute reasonable measures to ensure PARTICULAR PURPOSE) AND OF ALL OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF DSC. DSC MAKES NO OTHER
compliance with the terms and conditions of this EULA. WARRANTIES. DSC NEITHER ASSUMES NOR AUTHORIZES ANY OTHER PERSON PURPORTING TO ACT ON ITS BEHALF TO MODIFY OR
(b) Separation of Components - The SOFTWARE PRODUCT is licensed as a single product. Its component parts may not be separated for use TO CHANGE THIS WARRANTY, NOR TO ASSUME FOR IT ANY OTHER WARRANTY OR LIABILITY CONCERNING THIS SOFTWARE
on more than one HARDWARE unit. PRODUCT.
(c) Single INTEGRATED PRODUCT - If You acquired this SOFTWARE with HARDWARE, then the SOFTWARE PRODUCT is licensed with the (e) EXCLUSIVE REMEDY AND LIMITATION OF WARRANTY - UNDER NO CIRCUMSTANCES SHALL DSC BE LIABLE FOR ANY SPECIAL,
HARDWARE as a single integrated product. In this case, the SOFTWARE PRODUCT may only be used with the HARDWARE as set forth in INCIDENTAL, CONSEQUENTIAL OR INDIRECT DAMAGES BASED UPON BREACH OF WARRANTY, BREACH OF CONTRACT,
this EULA. NEGLIGENCE, STRICT LIABILITY, OR ANY OTHER LEGAL THEORY. SUCH DAMAGES INCLUDE, BUT ARE NOT LIMITED TO,
(d) Rental - You may not rent, lease or lend the SOFTWARE PRODUCT. You may not make it available to others or post it on a server or web LOSS OF PROFITS, LOSS OF THE SOFTWARE PRODUCT OR ANY ASSOCIATED EQUIPMENT, COST OF CAPITAL, COST OF
site. SUBSTITUTE OR REPLACEMENT EQUIPMENT, FACILITIES OR SERVICES, DOWN TIME, PURCHASERS TIME, THE CLAIMS OF
(e)Software Product Transfer - You may transfer all of Your rights under this EULA only as part of a permanent sale or transfer of the HARDWARE, THIRD PARTIES, INCLUDING CUSTOMERS, AND INJURY TO PROPERTY.
provided You retain no copies, You transfer all of the SOFTWARE PRODUCT (including all component parts, the media and printed materials, WARNING: DSC recommends that the entire system be completely tested on a regular basis. However, despite frequent
any upgrades and this EULA), and provided the recipient agrees to the terms of this EULA. If the SOFTWARE PRODUCT is an upgrade, any testing, and due to, but not limited to, criminal tampering or electrical disruption, it is possible for this SOFTWARE
transfer must also include all prior versions of the SOFTWARE PRODUCT. PRODUCT to fail to perform as expected.
FCC COMPLIANCE STATEMENT
NOTE: CAUTION: Changes or modifications not expressly Equipment Maintenance Facility
approved by Digital Security Controls could void your authority to If trouble is experienced with this equipment PC1616, PC1832, PC1864 for repair or war-
use this equipment. ranty information, please contact the facility indicated below. If the equipment is causing
This equipment has been tested and found to comply with the limits for a Class B digital de- harm to the telephone network, the Telephone Company may request that you disconnect
vice, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable the equipment until the problem is solved. This equipment is of a type that is not intended
protection against harmful interference in a residential installation. This equipment generates, to be repaired by the end user.
uses and can radiate radio frequency energy and, if not installed and used in accordance with DSC c/o APL Logistics, 757 Douglas Hill Rd., Lithia Springs, GA 30122
the instructions, may cause harmful interference to radio communications. However, there is
Additional Information
no guarantee that interference will not occur in a particular installation. If this equipment does
cause harmful interference to radio or television reception, which can be deter-mined by turn- Connection to party line service is subject to state tariffs. Contact the state public utility
commission, public service commission or corporation commission for information.
ing the equipment off and on, the user is encouraged to try to correct the interference by one
Alarm dialling equipment must be able to seize the telephone line and place a call in an
or more of the following measures:
emergency situation. It must be able to do this even if other equipment (telephone, answer-
• Re-orient the receiving antenna. ing system, computer modem, etc.) already has the telephone line in use. To do so, alarm
• Increase the separation between the equipment and receiver. dialling equipment must be connected to a properly installed RJ-31X jack that is electrical-
• Connect the equipment into an outlet on a circuit different from that to which the ly in series with and ahead of all other equipment attached to the same telephone line. Prop-
receiver is connected. er installation is depicted in the figure below. If you have any questions concerning these
• Consult the dealer or an experienced radio/television technician for help. instructions, you should consult your telephone company or a qualified installer about in-
The user may find the following booklet prepared by the FCC useful: "How to Identify and stalling the RJ-31X jack and alarm dialling equipment for you.
Resolve Radio/Television Interference Problems". This booklet is available from the U.S.
Government Printing Office, Washington D.C. 20402, Stock # 004-000-00345-4.
IMPORTANT INFORMATION
This equipment complies with Part 68 of the FCC Rules. On the side of this equipment is
a label that contains, among other information, the FCC registration number and ringer
equivalence number (REN) for this equipment. If requested, this number must be provided
to the Telephone Company.
PC1864 Product Identifier US: F53AL01BPC1864
PC1832 Product Identifier US: F53AL01BPC1832
PC1616 Product Identifier US: F53AL01BPC1614
REN: 0.1B
USOC Jack: RJ-31X
Telephone Connection Requirements
A plug and jack used to connect this equipment to the premises wiring and telephone net-
work must comply with the applicable FCC Part 68 rules and requirements adopted by the
ACTA. A compliant telephone cord and modular plug is provided with this product. It is INDUSTRY CANADA STATEMENT
designed to be connected to a compatible modular jack that is also compliant. See installa- NOTICE: This Equipment meets the applicable Industry Canada Terminal Equipment Tech-
tion instructions for details. nical Specifications. This is confirmed by the registration number. The abbreviation, IC, be-
Ringer Equivalence Number (REN) fore the registration number signifies that registration was performed based on a Declaration
of Conformity indicating that Industry Canada technical specifications were met. It does not
The REN is used to determine the number of devices that may be connected to a telephone
imply that Industry Canada approved the equipment.
line. Excessive RENs on a telephone line may result in the devices not ringing in response to
an incoming call.
In most but not all areas, the sum of RENs should not exceed five (5.0). To be certain of the NOTICE: The Ringer Equivalence Number (REN) for this terminal equipment is 0.1. The
number of devices that may be connected to a line, as determined by the total RENs, contact REN assigned to each terminal equipment provides an indication of the maximum number of
the local Telephone Company. For products approved after July 23, 2001, the REN for this terminals allowed to be connected to a telephone interface. The termination on an interface
product is part of the product identifier that has the format. may consist of any combination of devices subject only to the requirement that the sum of the
US: AAAEQ##TXXXX. The digits represented by ## are the REN without a decimal point Ringer Equivalence Numbers of all devices does not exceed five.
(e.g., 03 is a REN of 0.3). For earlier products, the REN is separately shown on the label.
PC1616 Registration numberIC: 160A-PC1614
Incidence of Harm
PC1832 Registration numberIC: 160A-PC1832
If this equipment PC1864/PC1832/PC1616 causes harm to the telephone network, the tel-
ephone company will notify you in advance that temporary discontinuance of service may PC1864 Registration numberIC: 160A-PC1864
be required. But if advance notice is not practical, the Telephone Company will notify the This Class B digital apparatus meets all requirements of the Canadian interference-caus-
customer as soon as possible. Also, you will be advised of your right to file a complaint ing equipment regulations.
with the FCC if you believe it is necessary. Cet appareil numérique de la Classe B respecte toutes les exigences de règlement sur le
materiel brouilleur du Canada.
Changes in Telephone Company Equipment or Facilities
The Telephone Company may make changes in its facilities, equipment, operations or pro-
cedures that could affect the operation of the equipment. If this happens the Telephone
Company will provide advance notice in order for you to make necessary modifications to
maintain uninterrupted service.
The trademarks, logos, and service marks displayed on this document are registered in the United States [or other countries]. Any misuse of the
trademarks is strictly prohibited and Tyco International Ltd. will aggressively enforce its intellectual property rights to the fullest extent of the law,
including pursuit of criminal prosecution wherever necessary. All trademarks not owned by Tyco International Ltd. are the property of their respective
owners, and are used with permission or allowed under applicable laws.
Product offerings and specifications are subject to change without notice. Actual products may vary from photos. Not all products include all
features. Availability varies by region; contact your sales representative.