Power System PDF
Power System PDF
Power system I
2. Basic Concepts in Electric Power system
Tiruwork A.
Email: [email protected]
1
Power in single phase a.c. system
The instantaneous power in watts absorbed by an electrical load is the
product of the instantaneous voltage across the load in volts and the
instantaneous current into the load in amperes
Assuming the load voltage is
v(t ) Vmax cos t
2
The instantaneous power absorbed by the resistor is
pR (t ) v (t )iR (t ) Vmax I R max cos 2 t
1
2
Vmax I R max 1 cos 2 t
VI R 1 cos 2 t W
1
Note : cos 2 x 1 cos 2 x
2
3
Purely inductive loads
For a purely inductive load, the current lags the voltage by 90 degree,
V
IL , and
jX L
p (t ) VI cos 1 cos 2 t VI sin sin 2 t
Letting I cos I R and I sin I X gives
p (t ) VI R 1 cos 2 t VI X sin 2 t
pR ( t ) pX (t )
6
Complex Power
The Active power is the power that is dissipated in the resistance
of the load.
It uses the same formula used for DC (V & I are the magnitudes,
not the phasors):
2
V
P I 2R [watts, W]
R
The reactive power is the power that is exchanged between
reactive components (inductors and capacitors)
The formulas look similar to those used by the active power, but
use reactance instead of resistances.
2
V
Q I2X [VAR]
7 X
For circuits operating in sinusoidal-steady-state, real and reactive power
are conveniently calculated from complex power, defined below.
Let the voltage across a circuit element be V , and the current into
the element be I . Then the complex power S is the product of the
voltage and the conjugate of the current:
S VI * V I VI
*
P = real power
Q= reactive power and
cos Power factor
8
The magnitude S VI of the complex power S is called the apparent power, it
signifies the rating of equipments (generators,Transformers, etc)
9
Power Triangle
X
. C
10
Direction of Power Flow
Consider the current and voltage of figure (a) where a dc current I
is flowing through a battery.
If the voltmeter and ammeter both read upscale to show E=100 V
and I=10 A, the battery is being charged (absorbing energy) at the
rate given by the product EI= 1000 W.
On the other hand , if the ammeter connections have to be reversed in
order that it reads upscale with the current arrow still in the direction
shown , then I =-10 A and the product EI = -1000 W, the battery is
discharging (delivering energy)
11
The same considerations applied to the ac circuit relationships.
Figure (b) shows an ac system with an ideal voltage source with polarity
marks to indicate the terminals which is positive during the half cycle of
instantaneous voltage.
Similarly the arrow indicates the direction of current I into the box
during the positive half cycle of the current.
By definition the power absorbed inside the box is
13
Balanced three phase system
•Three sources connected to 3
loads using four-wire system
•Sources have EQUAL frequency
but DIFFFERENT phases
15
Positive (abc) Sequence Negative (acb) Sequence
Figure 2.1
17
The neutral impedance zn does not affect network behavior
For the reference phase a
Ea ( zG zL ) I a .............(2.1)
The current and the voltage in the other phases have the same magnitude
but progressively shifted by 1200
Equation 2.1 corresponds to the single phase network of figure 2.2 below
The solution of fig. 2.2 completely determines the solution of the three
phase network
Figure 2.2
18
Consider the case where a three phase transformer forms part of a three
phase power system
If the transformer is Y/Y connected as shown in fig. 2.3a, in the single
phase equivalent of the three phase circuit it can be obviously represented
by a single phase transformer (as in fig. 2.3b) with primary and secondary
pertaining to phase a of the three phase transformer
Figure 2.3
19
If the transformer is Y/∆ connected as in figure 2.4a below, the delta side
has to be replaced by an equivalent star connection as shown doted so as to
obtain the single phase equivalent of fig. 2.4b
When the load is balanced, the impedance of each leg of the Y is one third
the impedance of each leg of the ∆
Since both phase voltage and line current shift through the same phase
angle from star to delta side, the transformer per phase impedance and
power flow are preserved in the single phase equivalent.
20
Figure 2.4
22
Power in balanced three phase system
If the magnitude of the voltages to neutral 𝑉𝑝 for a Y-connected load is
𝗅𝑉𝑝 𝗅=𝗅𝑉𝑎𝑛 𝗅=𝗅𝑉𝑏𝑛 𝗅=𝗅𝑉𝑐𝑛 𝗅
and if the magnitude of the phase current 𝐼𝑝 for a Y-connected load is
𝗅𝐼𝑝 𝗅=𝗅𝐼𝑎𝑛 𝗅=𝗅𝐼𝑏𝑛 𝗅=𝗅𝐼𝑐𝑛 𝗅
then, the total three phase power and the total three phase var is,
P=3 𝗅𝑉𝑝 𝗅𝗅𝐼𝑝 𝗅𝑐𝑜𝑠𝛉𝑝 Q=3 𝗅𝑉𝑝 𝗅𝗅𝐼𝑝 𝗅𝑠𝑖𝑛𝛉𝑝
Where 𝛉𝑝 is the angle by which phase current lags the phase voltage.
• If the magnitudes of line-to-line voltage 𝑉𝐿 and line current 𝐼𝐿 are 𝗅𝑉𝐿 𝗅
and 𝗅𝐼𝐿 𝗅, respectively,
P= 3 𝗅𝑉𝐿 𝗅𝗅𝐼𝐿 𝗅𝑐𝑜𝑠𝛉𝑝 Q= 3 𝗅𝑉𝐿 𝗅𝗅𝐼𝐿 𝗅𝑠𝑖𝑛𝛉𝑝
The total volt-amperes of the load is
𝗅S𝗅 = 𝑃2 + 𝑄 2 = 3𝗅𝑉𝐿 𝗅𝗅𝐼𝐿 𝗅
23
Reading Assignment
Unbalanced three phase system
Voltage and current in unbalanced three phase system
Power in unbalanced three phase system
24
PER-UNIT REPRESENTATION
Computations for a power system having two or more voltage levels
become very cumbersome when it is necessary to convert currents to a
different voltage level wherever they flow through a transformer (the
change in current being inversely proportional to the transformer turns
ratio).
In an alternative and simpler system, a set of base values, or base
quantities, is assumed for each voltage class, and each parameter is
expressed as a decimal fraction of its respective base.
For instance, suppose a base voltage of 345 kv has been chosen, and under
certain operating conditions the actual system voltage is 334 kV: then the
ratio of actual to base voltage is 0.97.
The actual voltage may then be expressed as 0.97 per-unit. In an equally
common practice, per-unit quantities are multiplied by 100 to obtain
percent quantities: our example voltage would then be expressed as 97
percent.
Per-unit and percent quantities and their bases exhibit the same
relationships and obey the same laws (such as Ohm's law and Kirchhoff’s
laws) as do quantities in other systems of units.
25
A minimum of four base quantities is required to completely define a per-
unit system: these are voltage, current, power, and impedance (or
admittance). If two of them are set arbitrarily, then the other two become
fixed.
Base values can be determined by three ways
Taking the largest value
Taking the total sum
Any arbitrary
The per unit value of any quantity is the ratio of the actual value in any
units to the chosen base quantity of the same dimensions expressed as a
decimal.
Actual value in any units
Per unit quantity
Base or reference value in the same unit
In power systems the basic quantities of importance are voltage, current,
impedance and power. For all per unit calculations a base KVA or MVA
and a base KV are to be chosen.
Once the base values or reference values are chosen, the other quantities
can be obtained as follows:
26
Where base KVA and base MVA are the total or three phase values.
If phase values are used
base voltage
Base impedance in ohm =
base current
(base K V) 2 / 1000
base K V A per phase
In all the above relations the power factor is assumed unity, so that
27
Selecting the total or 3-phase KVA as base KVA, for a 3-phase system
(base KV (line-to-line) 2
Base Impedance in ohms = base MVA
28
Some times, it may be required to use the relation
actual Impedance in ohm = (Per unit impedance in ohms) (base KV) 2
(base MVA)
Very often the values are in different base values. In order to convert the
per unit impedance from given base to another base, the following relation
can be derived easily.
Per unit impedance on new base
29
In general :
Base current = base volt amperes/base voltage (in amperes)
Base impedance = base voltage/ base current (in ohms)
Per-unit voltage = actual voltage / base voltage (per unit, or pu)
Per-unit current = actual current / base current (per unit, or pu)
Per-unit impedance = actual impedance /base impedance (per unit. or
pu)
The impedances of transmission lines are expressed in ohms, but can be
easily converted to pu values on a given voltampere base using above
expressions.
30
Advantages of Per Unit System
1. While performing calculations, referring quantities from one side of
the transformer to the other side serious errors may be committed. This
can be avoided by using per unit system.
2. The p.u systems are ideal for the computerized analysis and
simulation of complex power system problems.
3. Voltages, currents and impedances expressed in per unit do not
change when they are referred from one side of transformer to the
other side. This is a great advantage'.
4. Per unit impedances of electrical equipment of similar type usually
lie within a narrow range, when the equipment ratings are used as base
values.
5. Transformer connections do not affect the per unit values.
6. Manufacturers usually specify the impedances of machines and
transformers in per unit or percent of name plate ratings.
31
Example
Solve for the current, load voltage and load power in the
circuit shown below using per unit analysis with an SB of
100 MVA, and voltage bases of 8 kV, 80 kV and 16 kV.
Original Circuit
8kV 2
Z BLeft 0.64
100 MVA
80kV 2
Z BMiddle 64
100 MVA
16kV 2
Z BRight 2.56
100 MVA