Application Note-IEC AC Short Circuit Contribution 230828

The document provides an application note on the short current contribution of Huawei SUN2000MA inverters, detailing specifications such as peak short-circuit current and initial short-circuit current according to IEC60909-0:2016. It includes a table listing various inverter models with their maximum apparent power, rated output voltage, and short-circuit current values. This information is essential for understanding the performance and safety of these inverters in short-circuit scenarios.

Uploaded by

Achraf AEP
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
22 views2 pages

Application Note-IEC AC Short Circuit Contribution 230828

The document provides an application note on the short current contribution of Huawei SUN2000MA inverters, detailing specifications such as peak short-circuit current and initial short-circuit current according to IEC60909-0:2016. It includes a table listing various inverter models with their maximum apparent power, rated output voltage, and short-circuit current values. This information is essential for understanding the performance and safety of these inverters in short-circuit scenarios.

Uploaded by

Achraf AEP
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Huawei SUN2000MA Inverters Short Current Contribution

Huawei Technologies Co., Ltd. Huawei Industrial Base Bantian, Longgang


Shenzhen 518129
People’s Republic of China

Application Note- Huawei SUN2000MA Inverters Short Current Contribution


Revision History
Version 1.0 March 31, 2022 – Initial release

Application
Application Note- Huawei SUN2000MA Inverters Short Current Contribution
Solution

Solution According to IEC60909-0:2016, the definitions of ip, I’’k and Ik is used for calculation of short-circuits
Description current of power generators.

Pmax Vac Ip I''k Ik


Model (kVA) (V) (A) (A) (A)

SUN2000-3KTL-M1 3.3 400 Vac 38.4 7.7 5.1

SUN2000-4KTL-M1 4.4 400 Vac 40.8 10.2 6.8

SUN2000-5KTL-M1 5.5 400 Vac 44.0 12.8 8.5

SUN2000-6KTL-M1 6.6 400 Vac 46.0 15.2 10.1

SUN2000-8KTL-M1 8.8 400 Vac 51.0 20.3 13.5

SUN2000-10KTL-M1 11 400 Vac 55.8 25.4 16.9

SUN2000-12KTL-M1 12 400 Vac 53.4 27.6 18.4


Solution
Diagram
SUN2000-8KTL-M2 8.8 400 Vac 52.2 20.1 13.4

SUN2000-10KTL-M2 11 400 Vac 55.8 25.5 17.0

SUN2000-12KTL-M2 13.2 400 Vac 55.8 30.0 20.0

SUN2000-15KTL-M2 16.5 400 Vac 63.0 37.8 25.2

SUN2000-17KTL-M2 18.7 400 Vac 67.8 42.8 28.5

SUN2000-20KTL-M2 22 400 Vac 74.4 50.3 33.5

SUN2000-20KTL-M3
22 202 Vac 196.6 94.8 63.2
(JP)
SUN2000-20KTL-M3
22 202 Vac 180.4 87 58
(Other)

SUN2000-29.9KTL-M3 29.9 400 Vac 134.4 64.8 43.2


Huawei SUN2000MA Inverters Short Current Contribution

SUN2000-30KTL-M3 33 400 Vac 149.0 71.85 47.9

SUN2000-36KTL-M3 40 400 Vac 180.4 87 58

SUN2000-40KTL-M3 44 400 Vac 198.5 95.7 63.8

SUN2000-50KTL-M3 55 400 Vac 247 119 79.4

SUN2000-100KTL-M2 110 400 Vac 498.8 240.5 160.4

SUN2000-115KTL-M2 125 400 Vac 566.8 273.3 182.2

(Pmax: Max.AC Apparent Power,Vac: Rated Output Voltage(line voltage),Ip: Peak short-circuit current)
(I''k :Initial short circuit current, Ik: Short circuit contribution)

Solution
1. This documents provides short-circuits information of Huawei SUN2000MA inverters.
Notes