Building A Semi-Anechoic Chamber
Building A Semi-Anechoic Chamber
Building A Semi-Anechoic Chamber
6/30/2006
Can I build what I need and want with low risk of failure? Yes - however you had better be sure that you know what you want. Be careful what you wish for as for every wish there comes a curse!
6/30/2006
Target specifications
Noise isolation - 10dB quieter inside than the levels that you want to measure Must conform to some, (often changing) ISO standard if the measurements are to be accepted. ISO3744 specifies the environmental criteria for sound power measurements.(in the UK most chambers will have been built
to BS EN 60704-1: 1997)
6/30/2006 4
It needs to be good enough but not necessarily any better than that! Historically the cost of construction of acoustic facilities has been high, perhaps too high. The high prices have reflected the high performance goals set by the designers and engineers involved. The desire to provide the best has not always been tempered by the need to build what the client can afford or what is strictly necessary. Size really does matter then!
6/30/2006
6/30/2006
Isolation at least 50dB Reflectivity/Absorption 10% / 99% But are they what they need?
6/30/2006
6/30/2006
How do the material work? Noise isolation. For all practical purposes the heavier and more impermeable the material the better its performance will be. Sound is carried in air and air is light and elastic while heavy concrete blocks, sealed with cement mortar, effectively divide any particle velocity by 10something large .
6/30/2006 9
What goes wrong? The devil is in the detail or rather in the designer and the builder! The sum of 1000 small building defects = poor acoustic performance. Noise, especially higher frequency, leaks in through small gaps. If a wall contains 6 inch blocks but the mortar between them is missing 50% of the time then the wall is effectively 5% open space. You have built a sound barrier with an open window in it!
6/30/2006 10
Effect of good solid door with excellent double seals = 44dB Some gaps and a door = disaster
6/30/2006 11
6/30/2006
12
What goes wrong? The Roof. Where the walls meet the roof can be a major problem. 1. Getting a good seal 2. Timber shrinkage causing gaps to appear over the next 2 years - Timber may shrink by 10% over two years and that can mean a large gap appearing.
6/30/2006
13
The Roof:
6/30/2006
14
Anechoic Treatments
Absorption coefficients Wedges and what they are made of ? Materials can absorb the energy in a sound wave using different mechanisms. But in all cases the key is to present a slowly changing acoustic impedance; any rapid change will cause a reflected wave. Wedges provide a graduated impedance change from air to the absorbing materials impedance over the length of taper.
6/30/2006 15
6/30/2006
16
After all the hard work only a few wedges needed to complete the project.
6/30/2006
17
6/30/2006
18
There are three areas; typically below 200Hz where the response is stiffness controlled. 2005000Hz where the response is Mass controlled and above 5000Hz where coincidence controls the transmission. 6/30/2006 19
Frequency in Hz
As always the construction of a barrier is a trade off but it does make sense to consider the energy levels of the incident spectra!
6/30/2006 20
6/30/2006
21
Basic calculations for the Mass lineThe general rule is that the Transmission Loss (R) is calculated as follows: R = 20 log (freq. x Mass per square metre) - 47 dB so if we are at 100Hz and our wall is 500kg per square meter of surface area we get: R= 20 log (100 x 500) -47 dB R = 20 x 4.7 - 47 dB R = 47dB
6/30/2006
22
Coincidence frequency
This means that there will be a number of frequencies where there will be strong coupling across the barrier. The exact frequencies that this coupling will occur will be determined by the relative speed of sound in the two media.
6/30/2006
23
Speed of sound ms-1 331.3 3500 3650 5100 5000 3850 5000
The first coincidence frequency for concrete assumes that bending waves of significant amplitude are present in a heavy concrete block wall - this I think is very unlikely! However in the case of barriers made of thin sheets of wooden board or metal sheets these waves will occur.
6/30/2006 24
6/30/2006
26
Isolation
Inside SPL=28dBA
6/30/2006
27
Avoidance measures
1. Make sure the chamber is big enough to get microphones out of the near field of the Device Under Test (DUT) and of the wedges. 2. Avoid the obvious room modes by having different length and if possible none parallel sides. 3. Survey the sound field and the ground vibration where the chamber is to be built and consult about further developments that are foreseen for the area. 4. Consider usability and in particular the need for repeated access through a potentially heavy door. 5. Remember the SUM of many small errors can = Disaster
6/30/2006
28