07 Technical Session Seven
07 Technical Session Seven
07 Technical Session Seven
Detailed Energy Audit Report on 11/0.4 kV Distribution Transformer and 33/11kV Power Transformer of Pushkar, Ajmer
Er. R.N.Vaishnawa & Er. P.C. Tiwari
Secondary winding: the winding where the principal load is connected. Usually this refers to Low Voltage
side in Distribution transformers.
No load loss: The losses taking place in a transformer when only primary winding is energized and all
secondary windings are open. They represent constant losses in a transformer.
Dielectric loss: The losses taking place in a stressed dielectric medium (insulation) subjected to stress
reversals.
Iron losses: The losses taking place in the magnetic core. There are two types; hysterisis losses and eddy
current losses.
Hysteresis losses: This loss depends upon the area of the hysteresis loop, which is depending upon the
maximum flux density, the type of material and frequency. It is independent of the waveform
Eddy current losses in core: This is loss due to circulating currents induced by voltage in the thickness of
core laminations. It depends upon thickness of lamination, path resistance which is depended upon the type of material, R.M.S. flux density i.e. waveform and square of frequency
Eddy losses in a conductor: For a thick conductor, the induced voltage within the conductor cross section
due to self linkage and due to current in other conductor varies. The difference in induced voltage in the local path in the thickness of the conductor causes extra eddy current loss : This loss varies with square of current and square of frequency.
Stray losses: All current dependant losses in a winding other than the basic I2R losses. Stray losses include
eddy loss in the conductor, eddy losses in structural paths in close proximity to outgoing conductor and the eddy loss in general in the structural parts. In dry type transformers, the last two mentioned types of stray losses are absent.
Form factor: It is the ratio of the r.m.s. value of a waveform to the average value over one half cycle. For a
sine wave the value of form factor is 1.11. For distorted waves with higher peak values, the form factor is higher.
Harmonics: Frequencies other than the main fundamental frequency of current or voltage which are present in
a distorted wave as multiples of base fundamental frequency.
Inception Report
Distribution transformers are very efficient, with losses of less than 0.5% in large units. Smaller units have efficiencies of 97% or above. It is estimated that transformer losses in power distribution networks are 15 billion kWh i.e. 3% of the total electrical power generated in India. Reducing losses can increase transformer efficiency. There are two components that make up transformer losses. The first is "core" loss (also called noload loss), which is the result of the magnetizing and de-magnetizing of the core during normal operation. Core loss occurs whenever the transformer is energized; core loss does not vary with load. The second component of loss is called coil or load loss, because the efficiency losses occur in the primary and secondary coils of the transformer. Coil loss is a function of the resistance of the winding materials and varies withthe load on the transformer. In selecting equipments, one often conveniently avoids the concept of life cycle costing. But the truth is that even the most efficient energy transfer equipment like a transformer, concept of life cycle cost is very much relevant. The total cost of owning and operating a transformer must be evaluated, since the unit will be in service for decades.
Estimation of transformer efficiency The total losses in a transformer at base kVA as well as at the actual
load are estimated. The losses in a transformer are as under. 1. Dielectric Loss 2. Hysteresis Losses in the Core 3. Eddy current losses in the Core 4. Resistive Losses in the winding conductors 5. Increased resistive losses due to Eddy Current Losses in conductors. 6. For oil immersed transformers, extra eddy current losses in the tank structure. From the rated output and measured output, transformer efficiency is calculated as follows.
Reduction of losses due to improvement of power factorTransformer load losses vary as square of current. Industrial power factor vary from 0.6 to 0.8. Thus the loads tend to draw 60% to 25% excess current due to poor power factor. For the same kW load, current drawn is proportional to KW/pf. If p.f. is improved to unity at load end or transformer secondary, the saving in load losses is as under. Saving in load losses = (Per unit loading as per kW)2 X Load losses at full load X {(1/pf)2-1)} Thus, if p.f is 0.8 and it is improved to unity, the saving will be 56.25% over existing level of load losses. This is a relatively simple opportunity to make the most of the existing transformer and it should not be missed. It should also be kept in mind that correction of p.f downstream saves on cable losses, which may be almost twice in value compared to transformer losses.
Core Material- Losses in Core:There are two important core materials used in transformer manufacturing. Amorphous metal and CRGO. It can be seen that losses in amorphous metal core is less than 25% of that in CRGO.
The objective of this study is to find out how the technical losses varies with the % loading as well as unbalancing and power factor in the 11/0.4kV Distribution Transformers and 33/11kV Power Transformers. The area for case study has been choosen is the Pushkar Sub-station. The 33/11kV Substation at Pushkar (Ganaheda) is having 4 nos. of 33/11kV Power Transformers of 3X3.15MVA + 1X1.5MVA Capacity. Total 9 nos. 11kV feeders are emanating from these power transformers feeding the area. _ Transformer No.1 of 3.15MVA o o 11 kV Banseli feeder 11 kV Budha Pushkar
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 _ Transformer No.4 of 1.5MVA o o 11 kV Leela Sevadi Feeder (24 Hrs.) 11 kV Ganahera (24 Hrs.)
The 33/11kV Sub-station is fed from 132/33kV MDSU Grid Sub-station, Ajmer.
Case Study #1
For the 56 nos. DTs studied, the total loss due to over/ under sizing and improper loading/ unbalancing as well as poor power factor is 1.47LU per year. The Power saving is around 34kW. The CO2 emission saving shall be around 300 tons per year. The national saving against power plant cost shall be Rs.27 Lacs. If these transformers are replaced by appropriate size amorphous core distribution transformers, then 1.83 LU of electrical energy can be saved. The CO2 emission saving shall be around 382 tons per year. The national saving against power plant cost shall be Rs.35 Lacs.
10
11
12
Case Study#2
A sample of 56 Transformers are studied for their phasewise % loading and neutral current due to unbalance loading is measured. Neutral current flows in the neutral conductor having some resistance depending on the size of the conductor. This current cause losses in the conductor in the form of heat and proportional to the square of the neutral current. The average value of neutral current in all 56 Transformers is found to be 15.4Amps. Assuming 500m length of neutral conductor per transformer, the calculation for losses occurring is as follows: 15.4AX15.4AX0.9116 ohm/kmX56 Nos. of DT X 0.5 km/TransformerX50%(Distribution factor)=3.026kW =3.026X8760 = 26514 kWh/annum This can save 53 tons of CO2/annum.
13
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 As the Discom as a whole, if this figure is calculated, it can be million of tons of CO2/ nnum that can be saved by proper balancing of transformers to some extent.
14
15
Case Study #3
Power Transformer #1 for 11kV Banseli & Budha Pushkar Feeder of 3.15MVA The no-load loss is 3kW and Copper loss is 16kW at unity power factor. The maximum efficiency of the transformer is achieved at the load where no load loss and copper loss are equal i.e. Loading for maximum efficiency of the transformer = (No load loss/Copper loss)1/2 For this transformer, the maximum efficiency is achieved at (3/16)1/2= 43.3% loading i.e. 1364kVA. The loading pattern of this power transformer for 26-7-10 to 22-09-10 (1503 Hrs) is as follows-
It is found that the loading average loading on the transformer is 722kVA and the transformer is loaded for only 20-30% of its rate capacity. The technical loss of the transformer at 23% loading and 0.9 PF is 0.59%. If the load of transformer #4 is connected with this transformer (225kVA) then the loading on this transformer shall be 950kVA, then loss of 1.5MVA Transformer will be saved which is equal to 1.9kWx8760 = 16644kWh per annum. This can save 33 tons of CO2 per annum. Also this will improve efficiency of the existing 3.15MVA Power Transformer.
16
Case Study #4
Power Transformer # 2 for 11kV Mela Feeder and Pushkar City Feeder of 3.15MVA
Capacity of Power Transformer # 2 is 3.15MVA. Two nos. 11kv Urban feeders emanates from this transformer namely 11kV Mela Ground Feeder and 11kV Pushkar City Feeder. The no-load loss is 3kW and Copper loss is 16kW at unity power factor. The maximum efficiency of the transformer is achieved at the load where no load loss and copper loss are equal i.e. Loading for maximum efficiency of the transformer = (No load loss/Copper loss)1/2 For this transformer, the maximum efficiency is achieved at (3/16)1/2= 43.3% loading i.e. 1364kVA. The loading pattern of this power transformer for 26-7-10 to 22-09-10 (1392 Hours) is as follows-
From the loading pattern, it is clear that the transformer is mainly have 70-80% loading for more than 45% period and average loading on the transformer is 2125kVA and maximum load is 3600kVA. The Technical losses at 0.9PF for 3.15MVA Power Transformer at 2125kVA (75%) loading is 0.56% while the loss for 5MVA Transformer for 2125kVA(42.5%) loading is 0.42% i.e. an improvement of 0.14% improvement in efficiency. It is therefore proposed to augment the 3.15MVA Power transformer by 5MVA Power Transformer. The total saving of Energy shall be ~34000kWh per year. It will save 68 ton of CO2 per annum.
17
Case Study # 5
Power Transformer #3 is 3.15MVA for 11kV Devnagar, Ganaheda and kishanpura feeder
Capacity of Power Transformer #3 is 3.15MVA. Three nos. 11kv Rural area feeders emanates from this transformer. The no-load loss is 3kW and Copper loss is 16kW at unity power factor. The maximum efficiency of the transformer is achieved at the load where no load loss and copper loss are equal i.e. Loading for maximum efficiency of the transformer = (No load loss/Copper loss)1/2 For this transformer, the maximum efficiency is achieved at (3/16)1/2= 43.3% loading i.e. 1364kVA. The loading pattern of this power transformer for 28-3-10 to 23-09-10 (4320 Hours) is as follows-
From the loading pattern, it is clear than for more than 11% of period, the Power Transformer is idle and around 3000kWh/annum are lost due to no load losses. This can be saved if GO switch is made OFF during idle period. Operating the ransformer beyond 1364kVA is due to mismanagement of Block Supply given to rural areas for 3-phase pump sets. It is proposed that whenever 3-phase supply is given to 11kV kishanpura feeder than other two feeders should not be operated in three phase block. For 31% time, the loadings are beyond the ideal loading condition resulting into excess copper losses of 30,000 kWh/ annum. The total saving possible is 33,000kWh/ annum which can result into 66 tons of CO2 per annum.
18
19
20
21
22
Case Study # 6
Power Transformer #4 is 1.5MVA for 11kV Leela Sevadi & Ganaheda (24 Hrs. supply) feeder
Capacity of Power Transformer #4 is 1.5MVA. Two nos. 11kV 24 hours supply feeders namely Leela Sevadi and Ganahera (U) feeders emanates from this transformer. The no-load loss is 1.9kW and Copper loss is 10kW at unity power factor. The maximum efficiency of the transformer is achieved at the load where no load loss and copper loss are equal i.e. Loading for maximum efficiency of the transformer = (No load loss/Copper loss)1/2 For this transformer, the maximum efficiency is achieved at (1.9/10)1/2= 43.59% loading i.e. 654kVA. The loading pattern of this power transformer for Study period 25-July-10 to 23-09-10 (1490 hours) is as follows
It is evident from the loading pattern of the transformer that all the time, the transformer is underloaded and the maximum loading on the transformer is 20% and mainly the % loading is 10 to 15%. This load can be shifted to transformer # 1 of 3.15MVA which is also under loaded. The possible saving is due to saving of no-load losses of this transformer and improving of efficiency of Transformer # 1. The total saving expected is 6650kWh/annum which can result into 33 tons of CO2 per annum.. This will also save the capital amount of 1.5MVA Transformer.
23
24
Abstract
A Study on Transformers to find out the losses due to loading on transformers. Out of 69 L.T. transformers based on loading record of few Months, 30 nos. heavily loaded transformers were selected for study .And calculation has been done for Transformers Losses and the results are as follows:Total Losses in Transformers of one unit of 210 MW are = 687KW or 0.33% of 210MW Contribution of Power Transformers in Losses per unit 210 MW = 659 KW Contribution of Service (L.T.) Transformers in Losses per 210 Mw = 29 KW Total Transformer Losses in Plant of 1240 MW = 4040 KW Annual Amount Loss due to Transformer Losses which could have been sent out = Rs.6.7 crores /year Overall Auxiliary Consumption of 1240 MW is 9.72 % and Excluding Power Transformer losses it is 9.39 %. (A) Savings for 1240 MW due to reduced Station Transformer Losses by P.F. Improvement = RS. 4.20 Lac/year (B) Savings for 1240 MW due to reduced Distribution Losses by P.F. Improvement = Rs.5.9 crores /year By Station Transformers Loading Adjustment one no. of Station Transformer can be put-off that will reduce the Total Losses of 44.50KW plus Service Transformers of EPT, WT, and DMT can also be put-off which will also reduce 16KW Losses. And by selecting G.T. of 350 MVA its Loading will reduce to 60% .Thus Total Losses reduction will be up to 136 KW. (C) Overall by Optimization strategy Annual saving @Rs.2.13/-will is (2.13*325*24*136) Rs.23 lacs.
25
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 Expected Total yearly saving on Improving Power Factor and Transformer optimisation for 1240 Mw Power Plant (A+B+C) = Rs.6.17 crore Expected Total Saving by improving power factor for 1240 mw Power Plant = RS. 5.95 crores Expected Total Investment including the installation = Rs. 1.19 crores Simple Pay back Period = 65 days Expected Total saving by improving power factor from .83 to .99 and loading optimization on transformers by distribution companies on 1240 Mw = Rs. 13 crores/year
Key Words: Overall Transformer Losses, Reduction in Transformer Losses by Optimisation, Savings by
improving power factor
1.0 Introduction
1.1 General Plant details
Kota Thermal Power Station is first major coal power station of Rajasthan. Its present installed capacity is 1240 MW. It is located on the left bank of Chambal River at Kota. KTPS has established a record of excellence and has earned meritorious productivity awards from the Ministry of Power, Govt. of India during 1984,1987,1989,1991 and every year since 1992-93 onwards. In 2008-09 its Gross Generation was 8874 MU at 94.76% PLF with Auxiliary Power consumption 9.37% and Sp. Oil consumption 0.43 ml/kWh.
1.2 Transformers Types of Transformers:Transformers are classified as two categories: power transformers and distribution transformers. Power transformers are used for transmission of power at high voltage i.e. 400 kV, 200 kV, 110 kV, 66 kV, 33 kV deployed for step-up and step down the power as per requirement. Distribution transformers are used for distribution of power at low voltage as a means of end user connectivity i.e. 11 kV, 6.6 kV, 3.3 kV, 440 V, 230 V.
26
27
28
S. No
SERVICES
Load KW AT 7.15PM 5
RATED KVA
% Loadi ng 7=3/6
No-Load LOSS KW 8
LOAD LOSS
TOTAL LOSSES KW
1 2
10
SSIVA/IVB
9136.00
11564.00
9621.25
50000.00
18.27
34.60
185.00
40.78
UAT7A
7884.00
3904.00
3162.24
15000.00
52.56
8.17
50.34
22.08
UAT7B
6630.00
8228.00
6664.68
15000.00
44.20
8.17
50.34
18.00
GEN.TRANS.
218000.0
219640.00
210000.00
250000.00
87.20
119.34
599.10
574.89
SUB-TOTAL
23650.0
23696.00
19448.17
TOTAL LOSS
655.74
CHP
338.00
338.00
287.30
TOTAL
23988.0
24034.00
19735.47
29
STATION TRANSFORMERS
S. No.
Unit No.
Unit Cap.
Input/Output Volt.
Make
Unit #1
110 MW
50 MVA
220/7/7 KV
Crompton Bombay
Unit #2
110 MW
50 MVA
220/7/7 KV
Crompton Bombay
Unit #3
210 MW
50 MVA
220/7/7 KV
BHEL Bhopal
Unit #4
210 MW
50 MVA
220/7/7 KV
TELK Kerala
30
S. No.
Unit No.
Unit Cap.
Input/Output Voltage
Make
Unit #1
110 MW
15 MVA
11/7 KV
BHEL Jhansi
Unit #2
110 MW
15 MVA
15.75/7 KV
BHEL Jhansi
Unit #3
210 MW
2*15 MVA
15.75/7 KV
BHEL Jhansi
Unit #4
210 MW
2*15 MVA
15.75/7 KV
BHEL Jhansi
Unit #5
210 MW
2*15 MVA
15.75/7 KV
Unit #6
195 MW
2*15 MVA
15.75/7 KV
BHEL Jhansi
Unit #7
195 MW
2*15 MVA
15.75/7 KV
BHEL Jhansi
GENERATOR TRANSFORMERS
S. No.
Unit No.
Unit Cap.
Input/Output Voltage
Make
Unit #1
110 MW
125 MVA
11KV/240 KV
BHEL Jhansi
Unit #2
110 MW
125 MVA
15.75KV/240 KV
BHEL Jhansi
Unit #3
210 MW
230 MVA
15.75KV/240 KV
BHEL Jhansi
Unit #4
210 MW
250 MVA
15.75KV/240 KV
BHEL Jhansi
31
Unit #5
210 MW
250 MVA
15.75KV/240 KV
Unit #6
195 MW
250 MVA
15.75KV/240 KV
BHEL Jhansi
Unit #7
195 MW
250 MVA
15.75KV/240 KV
BHEL Jhansi
32
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 17 18 19 20 21 22 23 24 25 26 27 28 29 30 EPT 6B CT-6A CHP-IIA CHP-IIIA WT-IIA AHT7A CTT7A CTT7B EPT7A EPT7B UST7B UST7A SST 5A SST 5B 45.00 40.00 20.00 40.00 40.00 21.00 47.00 56.00 6.00 9.00 56.00 53.00 39.00 38.00 514.00 457.00 229.00 457.00 457.00 247.00 547.00 649.00 73.00 108.00 650.00 602.00 455.00 427.00 1600.00 1600.00 2000.00 2000.00 2000.00 1600.00 2000.00 2000.00 2500.00 2500.00 2000.00 2000.00 2500.00 2500.00 TOTAL LOSSES 32.13 28.56 11.45 22.85 22.85 15.44 27.35 32.45 2.92 4.32 32.50 30.10 18.20 17.08 1.60 1.60 1.90 1.90 1.90 1.60 1.90 1.90 2.20 2.20 1.90 1.90 2.20 2.20 13.50 13.50 15.00 15.00 15.00 13.50 15.00 15.00 20.00 20.00 15.00 15.00 20.00 20.00 2.99 2.70 2.10 2.68 2.68 1.92 3.02 3.48 2.22 2.24 3.48 3.26 2.86 2.78 81.85 99.42 99.41 99.08 99.41 99.41 99.22 99.45 99.46 96.96 97.93 99.46 99.46 99.37 99.35
33
34
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 Expected Annual Saving by Distribution Company for 1240 Mw power plant is Rs. 11.46 crores. Expected Total year saving by Improving the Power Factor for 1240 Mw Power Plant (A+B) = Rs.5.94 crore Expected Total Investment including the Capacitor Bank installation = Rs. 1.19 crores Simple Pay back Period = 70 days
4.2 Transformers Losses Calculations and the results are as follows:Total Losses in Transformers of one unit of 210 MW are = 687KW or 0.33% of 210MW Contribution of Power Transformers in Losses per unit 210 MW = 659 KW Contribution of Service (L.T.) Transformers in Losses per 210 Mw = 29 KW Total Transformer Losses in Plant of 1240 MW = 4040 KW Annual Amount Loss due to Transformer Losses which could have been sent out = Rs.6.7 crores /year Transformer Losses contributes to share in Auxiliary power Consumption = 3.5 % Overall Availability of Plant has been considered 325 days in a year Overall Auxiliary Consumption of 1240 MW is 9.72 % and Excluding Power Transformer losses it is 9.39 %. By Station Transformers Loading Adjustment one no. of Station Transformer can be put-off that will reduce the Total Losses of 44.50KW plus Service Transformers of EPT, WT, and DMT can also be put-off which will also reduce 16KW Losses. Thus Total Losses reduction will be up to 60 KW. By selecting G.T. of 350 MVA its Loading will reduce to 60% and 76KW Transformer Losses will also reduce. (C)Overall by Optimization strategy Annual saving @Rs.2.13/-will be (2.13*325*24*136)Rs.23 lacs. Expected Total yearly Saving on Improving Power Factor and Transformer optimisation for 1240 Mw Power Plant(A+B+C) = Rs.6.17 crore Expected Annual Saving by Distribution Company on Improving Power Factor and Transformer optimisation for 1240 Mw power plant is Rs. 13 crores
5.0 Conclusion
5.1 Recommendations
Energy Conservation & Management
35
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 1) Equal loading shall be done on Service Transformers shall be done to avoid under loading and overloading 2) The transformers at minimum loading shall be replaced from high rated capacity to low required capacity or shall be switched off by transferring that load on other transformer to avoid losses and maintenance cost. 3) Routine and Preventive maintenance of transformers shall be carried out to avoid tripping. 4) By load analysis - Total losses can be reduced which will reduce the Overall Auxiliary Consumption of KTPS, and more power will be available to fulfil the gap between demand and supply. 5) Two transformers operating in parallel, should be technically identical in all aspects and more important both should have the same impedance level .This will minimize the circulating current between transformers. 6)Where the load is fluctuating in nature, it is preferable to have more than one transformer running in parallel, so that the load can be operated close to the maximum efficiency range by this operation.
36
6.0 References
The following books, Literature and websites were referred in preparing this report:-
Technical Specification Sheets of Transformers Tests Reports of Transformers Website of RRVUNL Guide Books for National Certification Examination on Energy Audit and Energy Management
37
Experimental Investigation & Analysis to Reduce Boiler Tube Failure in Thermal Power Plant.
Amol M. Andhare Assistant Professor in Industrial Engg.,SRKNEC, Nagpur Bhushan V. Lande, Lecturer in Mechanical Engg. , PCE, Nagpur
Abstract
Boiler tube failures continue to be the leading cause of forced outages in fossil-fired boilers. To get boiler back on line and reduce or eliminate future forced outages due to tube failure, it is extremely important to determine and correct the root cause. Experience shows that a comprehensive assessment is the most effective method of determining the root cause of a failure. In the modern World, requirement of power has become necessity for day to day activity. Todays power generation in the Country is dominated by thermal power plants to the extent of 65%. Boiler tube failures are conditions that utilities have been battling since the day boilers were invented. They amount to millions of dollars of lost generation and anything done in this field to aid root cause and solution determination would be of great benefit to the utility industry. Hence availability of boiler is very much essential for thermal power generating stations. One of the main reasons for boiler forced outages is boiler tube leakage. The plan was to carry out the experimental investigation and analysis of the boiler tube failure, and then run experiments with different power plants and failure techniques until it was considered effective. Improvements between the tubes failure could be measured and recommendations made to the management. This paper covers the major reason of tube Leakages and recommended remedies to avoid the same. Index term: leak detection; boiler tube failure root cause analysis system; solution determination; failure mechanism; physical failure appearance; Knowledge-based cause and effect diagrams; Koradi Thermal Power Station, Nagpur, Maharashtra, India. Keywords: Boiler failures; Economizer tube; Corrosion; Failure analysis; Metallurgical examination, Boiler tube leakage, experimental investigation & analysis, power generation unit.
Problem Identification
In Present Work, data of boiler tube Failure at Koradi thermal power station Collected for last ten years which is given below. From above data of boiler tube failure shows that maximum tube failure occurs in economizer and reheater, in reheater section most of the boiler tube failure occurs due to short term overheating and long term overheating. An accurate analysis of the deposits indicates the source of the problem and the steps needed for correction. Metallographic analyses are useful, at times, in confirming whether a short- or long-term exposure to overheating conditions existed prior to failure. Such analyses are helpful also when metal quality or Energy Conservation & Management
38
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 manufacturing defects are suspected, although these factors are significant only in isolated instances. If the problem is remains as it is then boiler performance will affect and result in following factors. Improper availability Increased forced outage costs. More cost to repair Minimum component life Repeated root cause analysis In determinant commonalities across the boiler fleet Repeated Plan for future outages Please refer table below for the data collection of boiler tube failure. Tube Failure instances from 1994-1995 to 2008-2009
UNIT NO.
ECO
WATER WALL
CAGE
PRISH/H
PLATEN S/H
SEC S/H
R/H
TOTAL
31
NIL
20
76
22
16
NIL
21
74
14
10
13
10
62
16
12
12
62
16
15
NIL
52
22
NIL
17
51
39
18
16
NIL
12
53
Introduction
The failure of industrial boilers has been a prominent feature in fossil fuel fired power plants. The contribution of one or several factors appears to be responsible for failures, culminating in the partial or complete shutdown of the plant. The use of high sulfur or/and vanadium-containing fuel, exceeding the design limit of temperature and pressure during operation, and poor maintenance are some of the factors which have a detrimental effect on the performance of materials of construction. A survey of the literature pertaining to the performance of steam boilers during the last 30 years shows that abundant cases have been referred to concerned with the failure of boilers due to fuel ash corrosion, overheating, hydrogen attack, carburization and decarburization, corrosion fatigue cracking, stress corrosion cracking, caustic embrittlement, erosion, etc. Corrosion problems in boiler tubes arisen due to overheating are quite common. This mode of failure is predominantly found in superheaters, reheaters and water wall tubes, and in the result of operating conditions in which tube metal temperature exceeds the design limits for periods ranging from days to years. The phenomenon of overheating is manifested by the presence of significant deposits, which impart a reduction in water flow and excessive fire-side heat input. Due to this rise in temperature, steel loses its strength, causing rupture or bulging of the tube due to internal pressure. In a recent investigation. The failures have been attributed to accelerated corrosion, hydrogen attack and overheating. In another study, corrosion of stainless superheater tubes occurred due to carburization resulting in intergranular wastage of steel near the exposed surface. The causes of the majority of failures are attributed to the upset in water quality and/or steam purity. The mechanisms of failures due to short term overheating & long term overheating. This paper presents the results of two separate investigations carried out to determine the causes of failure of boiler tubes of Koradi thermal Power station and Desalination Plants. The main aim of this paper to investigation and acquaint the operation and maintenance personnel with the different corrosion modes involved in failures of boiler tubes due to short term overheating & long term overheating, and to suggest some measures for preventing the recurrence of such failures. The objectives of today for any power plants are to increase the availability, efficiency and reliability of power generating systems. Boilers are considered heart of steam and power generation systems. Unpredictable failures in boilers can bring down operation of power and steam generation to a halt for many days based on the severity of failure / damage. Proper operation and maintenance of boilers can ensure prolonged and safe operations of the power / steam generation systems. However, during downtime of these equipment, inspection and repair at the fastest possible time play a major role in bringing back the power and generation systems. Inspection and repair time are very crucial as the failure down time of boilers directly affect other dependent plants in terms of supply of electric power and utility steam. Energy Conservation & Management
40
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 Koradi Thermal Power Station is the plant operated by Maharashtra State Power Generation Co. Ltd. Koradi Thermal Power Plant is 8 Km away from Nagpur. Total capacity of plant is 1110 MW. Plants consist of 7 units, 4 units of 120 MW & 3 units of 210 MW. The Boilers are used in power plant supplied by ABL & BHEL. The boiler used as front fired & corner fired. The material used for boiler tube is SA 210 T1 & SA213 C22 as per the unit capacity. In Koradi Thermal Power Plant boiler tube failure is the main reason for boiler forced outages. In this paper an attempt is being made to present failure analysis of boiler, corrective methods followed and inspection and repair execution to bring the boilers back to operation at the shortest possible time.
41
1 Stress Rupture
The term overheating failure often misused but generally means the failure resulting from operation of a tube higher than expected in design selection of the tube steel for a period of time sufficient to cause a stress rupture failure. Time and temperature is an important factor and these types of failure are often called short term and long term overheating failures.
42
3 Water side corrosion:Caustic gouging Hydrogen damage Acid Phosphate Corrosion Pitting Corrosion Graphitization Stress Corrosion Cracking
5 Erostion
Fly Ash erosion Soot blower erosion Coal particle erosion Falling slag damage
43
6 Fatigue
Thermal Fatigue Corrosion Fatigue Rubbing of tubes 7 Lack of quantity control Chemical cleaning damage Maintenance damage Material Flaes & Welding Flaws
Platen S/H
121
76
31
45
10
46
101
Graph 3 Total no of boiler tube failure (1994-95 to 2008-09) Energy Conservation & Management
44
Methodology
Boiler tube failures continue to be the number one cause of forced outages at power generating stations. Great strides are taken to identify where tubes are wearing so that preventative actions can be taken to avoid failures during peak operation, but failures still continue to occur. To operate at peak capacity, a plant needs to find ways to avoid tube failures, as well as to recover from them quickly when they caused forced outages. Fossil fired boilers of all sizes continue to experience boiler tube failures and if the boiler tube root cause and scope of damage is not identified repairs will be incomplete and worse a dangerous condition may exist. AIS Metallurgical Testing has a decade of experience with boiler tube failures including steam drums and water drums (mud drums) as well as boiler headers and economizer tubes. After identifying failure on tube sample, testing of failure tube sample was carried out in Metallurgy department of VNIT NAGPUR. Experimental investigation & analysis were carried out as per Indian Boiler Regulation act 1950.
45
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 Figure 3 Polished metallographic longitudinal cross-section showing oxide-filled groove and crack. Lightcolored material indicated by white arrows is oxide. Yellow arrow indicates crevice attack on part of tube rolled into tube sheet. (18X Original Magnification)
Figure 4 Microstructure of failed tube showing pearlite in equiaxed ferrite matrix. (2% nital etch) Original Magnification)
(125X
2 Flattening test: - This is usually applied to the boiler tube and involves flattening a sample of tube between two parallel faces without the tube showing flaws or cracks. The length of the test piece and degree to which it is to be flattened (i.e. the distance between the parallel faces) are specified. A section of the tube not less than 40 mm length shall be flattened cold between parallel plates. No cracks or breaks in the metal shall occur until the distance between the plates is less than the given by the following formula. Evidence of lamination or burnt material or incomplete penetration of the weld shall not develop during the testing. (1 + e) t H = ---------------e + (t /D) Where t = Specified thickness of tube (in mm) D = Specified outside diameter of tube (in mm) e = Flattening test constant as given below: 0.10 for tube grade WC 1 0.07 for tube grades WC2 & WC3. (ii) The weld shall be placed 90 degree from the line of direction of the applied force. (iii) Superficial rupture as a result of minor surface imperfections shall not be cause for rejection. adopted shall be specified. Energy Conservation & Management
46
3 Corrosion test: Various corrosion mechanisms contribute to boiler tube failure. Stress corrosion may result in either intercrystalline or transgranular cracking of carbon steel. It is caused by a combination of metal stress and the presence of a corrosive. A metallurgical examination of the failed area is required to confirm the specific type of cracking. Once this is determined, proper corrective action can be taken. 3.1 Caustic Embrittlement: - Caustic embrittlement, a specific form of stress corrosion, results in the intercrystalline cracking of steel. Intercrystalline cracking results only when all of the following are present: specific conditions of stress, a mechanism for concentration such as leakage, and free NaOH in the boiler water. Therefore, boiler tubes usually fail from caustic embrittlement at points where tubes are rolled into sheets, drums, or headers. The possibility of embrittlement may not be ignored even when the boiler is of an all-welded design. Cracked welds or tube-end leakage can provide the mechanism by which drum metal may be adversely affected. When free caustic is present, embrittlement is possible. The device, illustrated in Figure 5, was developed by the United States Bureau of Mines. If boiler water possesses embrittling characteristics, steps must be taken to protect the boiler from embrittlement-related failure.
Figure 5 Embrittlement related failure protecting device Sodium nitrate is the standard treatment for inhibiting embrittlement in boilers operating at low pressures. The ratios of sodium nitrate to sodium hydroxide in the boiler water recommended by the Bureau of Mines depend on the boiler operating pressure. These ratios are as follows:
Pressure,psi
Up to 250
0.20
47
Up to 400
0.25
Up to 1000
0.40-0.50
The formula for calculating the sodium nitrate/sodium hydroxide ratio in the boiler water is: NaNO3 = NaOH ppm M alkalinity - ppm phosphate (As CaCO3) (As PO4 3- ) ppm nitrate (as NO3 -)
At pressures above 900 psig, coordinated phosphate/pH control is the usual internal treatment. When properly administered, this treatment method precludes the development of high concentrations of caustic, eliminating the potential for caustic embrittlement. 3.2 Fatigue & Corrosion Fatigue: - Transgranular cracking primarily due to cyclic stress is the most common form of cracking encountered in industrial boilers. In order to determine the cause of a transgranular failure, it is necessary to study both the design and the operating conditions of the boiler. Straight tube, shell-and-tube waste heat boilers frequently develop tube and tube sheet failures due to the imposition of unequal stresses. 3.3 Stress-Induced Corrosion: - Certain portions of the boiler can be very susceptible to corrosion as a result of stress from mechanical forces applied during the manufacturing and fabrication processes. Damage is commonly visible in stressed components, such as rolled tube ends, threaded bolts, and cyclone separators. However, corrosion can also occur at weld attachments throughout the boiler (see Figure 6) and can remain undetected until failure occurs. Regular inspection for evidence of corrosion, particularly in the windbox area of Kraft recovery boilers, is recommended because of the potential for an explosion caused by a tube leak.
48
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 3.4 Caustic Attack:- Caustic attack (or caustic corrosion), as differentiated from caustic embrittlement, is encountered in boilers with dematerialized water and most often occurs in phosphate-treated boilers where tube deposits form, particularly at high heat input or poor circulation areas. Deposits of a porous nature allow boiler water to permeate the deposits, causing a continuous buildup of boiler water solids between the metal and the deposits. Because caustic soda does not crystallize under such circumstances, caustic concentration in the trapped liquid can reach 10,000 ppm or more. Complex caustic-ferritic compounds are formed when the caustic dissolves the protective film of magnetic oxide. Water in contact with iron attempts to restore the protective film of magnetite (Fe3O4). As long as the high caustic concentrations remain, this destructive process causes a continuous loss of metal. The thinning caused by caustic attack assumes irregular patterns and is often referred to as caustic gouging (see Figure 7). When deposits are removed from the tube surface during examination, the characteristic gouges are very evident, along with the white salts deposit which usually outlines the edges of the original deposition area.
Figure 7 Caustic Attack Causing the failure of caustic gouging The whitish deposit is sodium carbonate, the residue of caustic soda reacting with carbon dioxide in the air. 3.5 Acidic Attack: - This results in a visually irregular surface appearance, as shown in Figure 8. Smooth surfaces appear at areas of flow where the attack has been intensified. In severe occurrences, other components, such as baffling, nuts and bolts, and other stressed areas, may be badly damaged or destroyed, leaving no doubt as to the source of the problem.
Figure 8 Acidic Attack Causing the failure Energy Conservation & Management
49
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 3.6 Corrosion Due to Copper: - Pitting of boiler drums and tube banks has been encountered due to metallic copper deposits, formed during acid cleaning procedures which do not completely compensate for the amount of copper oxides in the original deposits. Dissolved copper may be plated out on freshly cleaned steel surfaces, eventually establishing anodic corrosion areas and forming pits very similar in form and appearance to those caused by oxygen. Copper deposits and temperatures over 1600F can cause liquid metal embrittlement. Weld repair of a tube containing copper deposits leads to the failure shown in Figure 9.
Figure 9 Failure due to metallic copper deposits 3.7 Hydrogen Attack: - Since around 1960, hydrogen attack, or embrittlement, has been encountered with increasing frequency in high-pressure, high-purity systems. It is not encountered in the average industrial plant because the problem usually occurs only in units operating at pressures of 1500 psig or higher. When contaminants lower the boiler water pH sufficiently, the acid attack of the steel generates hydrogen. If this occurs under hard, adherent, nonporous tube deposits, the hydrogen pressure within the deposit can build up to the point at which the hydrogen penetrates the steel tubing. Ruptures are violent and sudden, and can be disastrous (see Figure 10)
Figure 10 Hydrogen Attack Causing the Ruptures 4 Tensile Testing. Two 12-inch sections were processed through a typical infiltration brazing furnace cycle without the application of cladding material. One sample was subsequently normalized at 1,675 F and rapidly cooled (specific rates are proprietary). A third 12-inch control sample was cut and left in its original state. All three 12-inch tube sections were then sent to an independent laboratory for ASTM E8 tensile testing. Three samples from each of the three 12-inch sections, for a total of nine samples, were tensile tested. Energy Conservation & Management
50
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 5 Proximate Analysis Test: - Proximate Analysis test is carried out to determine the percentage of fixed carbon, moisture, ash, and volatile matter is coal
Fig.ure No 11 Microstructure at 100X (The above Microstructure shows Alternate Region of Normal ferrite & pearlite.)
51
2 Flattening Test Result: A section of tube of length equal to 1.5 times the outside diameter, but not less than 50 mm, shall stand being flared with a tool having 60 or 45 degree included angle until the tube at the mouth of the flare has expanded to the percentage given below without cracking.
Tube Grade
0.6 under
and
Over 0.8
WC1
12
15
19
WC1
12
15
19
WC3
10
12
17
d = inside diameter of tube. Table 3 flattering test results. Discussion:-The flatting test is performed as IBR act 1950. In this test calculate distance H = 32.84 mm indicates no cracks present on given tube. This indicates the given material of tube is ductile material and failure of the tube is not occur do to short term overheating. 3 Corrosion Test Result: Corrosion product is to found loose, brown in color. Pitting is not found on both the surfaces. Oxide film is not found on both the surfaces
52
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 Discussion The third result of corrosion test is directly related failure of tube is due to hydrogen damage in hydrogen damage failure damages occur due to heavy scales deposit on water/ steam side of boiler tube concentrate sodium hydroxide will remove the protective magnetic film. In hydrogen damage when the protective oxide layer destroyed from inner side and outer side of tube the reaction of iron with concentrate sodium hydroxide form sodium ferrite and atomic hydrogen. Fe + 2 NaoH Na2Feo2 + 2 H
When hydrogen trapped between steel a scale, hydrogen react with iron carbide formed methane. Methane Formation weakens the steel. It is necessary to avoid excessive water deposition & control Ph value the feed water. The given tube fail is due to hydrogen damage because of protective oxide layer from inner side and outer side is reduces. 4 Tensile Test Results: - Tensile test results of Tensile Testing and calculated Yield Strength are tabulated below. Results shown in the center section of the table indicate that subjecting the tubes to a typical brazing cycle reduced the tensile strength of the material to its minimum allowable level of 60 ksi, and reduced the material yield strength to below its minimum allowable level of 37 ksi.
Tensile
Yield
Elongation
Strength (ksi)
Strength (ksi)
(%)
Control sample 1
68
46.7
34.6
Control sample 2
69
46.5
35.2
Control sample
67
46.2
35
53
Average
68
46.5
34.9
Braze Sample 1
Cycle
59.5
33.4
33.5
Braze Sample 2
Cycle
60.5
33.1
32.9
Braze Sample 3
Cycle
60
32.8
31.6
Average
60
33.1
34.9
Average
60
37
34.9
Table 4 Tensile test result. The normalization heat treatment process, as shown in the bottom section of the table, increased the material yield strength to the minimum allowable level of 37 ksi
54
5.82%
40.25%
30.44%
23.49%
C.V. of Coal
3840Kcal
Chemical Composition (W / T %)
%C
% SI
% MN
%S
%P
0.19
0.26
0.48
0.014
0.016
Discussion:-The above value of moisture Ash, fixed carbon, and volatile matter in coal indicate the quality of coal is used in power plant is not inferior and there is no effect of coal quality on tube failure.
55
Conclusions
After carrying out failure analysis of boiler tube, it is found that major failure occurred in reheater, super heater and economiser tube. In reheater due to high temperature of steam, tube failure occurred. The reason for such failure is short term overheating and long term overheating. To avoid the failure of boiler tube due to short term overheating, the flow starvation due to low drum level is suggested. Also it is necessary to flush the boiler 2-3 times before hydraulic test. Another reason for tube failure is corrosion. To avoid the failure of boiler tube due to corrosion, it is suggested to maintain water chemistry, not to run the boiler in condenser leakage condition and also maintain PH value is 9.3. Presence of sulfur in the oil ash deposited on the fireside surfaces of the tube appears to be the main cause of the failure of the boiler tubes at Al-Khobar Power Plant.
References:
Reid, W. T. External Corrosion and Deposits - Boilers and Gas Turbines. New York :Elsvier 1971. Stringer, J. High Temperature Problems in the Electric Power Industry and their Solutions, in High Temperature Corrosion. Ed., R. A. Rapp. Houston : National Association of Corrosion Engineers, 1983, p. 389. French, D. N. Liquid Ash Corrosion Problems in Fossil Fuel Boilers, Porc, Electrochem Soc., (1983), 83-85, p. 68. Corrosion in Fossil Fuel Power Plants, in Metal Handbook, Vol. 13 ed. B. C. Syratt, Metals, Park, Ohio : American Society for Metals, 1987, p. 985. Porta R. D. and H. M. Herro, The Nalco Guide to Boiler Failure Analysis. New York : McGrawll Hill, 1991. Dooley, R B. Boiler Tube Failures - A Perspective and Vision, Proceedings International Conference on Boiler Tube Failures in Fossil Plants, Palo Alto, California : EPRI, 1992. Calannino J., Prevent Boiler Tube Calannino, J. Prevent Boiler Tube Failures Part II : Waterside Mechanisms, Chemical Engg. Progress, November 1993, p. 73.
56
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 Hendrix, D. E., Hydrogen Attack on waterwall Tubes in High Pressure Boilers, Materials performance, (1995), 32(8), p. 46. Public Works Technical Bulletin 420-49-21, Boiler Water Treatment Lessons Learned, Nov. 1999. 11. R. K. Dayal and N. Parvathavarthini, Hydrogen embrittlement in power plant steels, pp 431-451, Sadhana, Vol. 28, Aug. 2003. 12. Glenn N. Showers, PE, The importance of Burner Management Control, pp 39-41, HPAC, Dec. 1997. 13. S. Tuurna, O. Cronwall, L. Heikinheimo, M. Hanninen, H. Talja, O. Tiihonen, "State of Art Report Lifetime Analyis of Boiler Tubes, VTT Technical Research, Oct. 2003. M. N. Hovinga, G. J. Nakoneczny, Standard Recommendations for Pressure Part Inspection during a Boiler Life Extension Programme, International Conference on Life Management and Life Extension of Power Plant, May 2000. Darryl Rosario, Peter Riccardella and Thomas Sherlock, A Risk Management Approach for Boiler Waterwall Tube Failure, EPRI Maintenance Conference, June 1999.
57
Keywords:
Handbook of solar radiation by Anna Mani. Solar energy and surface metrology (NASA).
1. Introduction
Tata International Limited was established in 1962 as Commercial and Industrial Exports Ltd (CIEL) to promote exports of Tata Group products and services as well as those of other reputed Indian manufacturers. The company was renamed as Tata Exports in 1968 and has evolved to become an International Business Company. The company assumed the name Tata International Limited (TIL) in March 1998 to reinforce its evolution from an exporter to an internation0al business company. TIL is one of largest export houses in India with the status of Five Star Export House. The company has five Global Business Units namely Leather & Leather Products (L&LP), Steel, Minerals, Engineering and Bulk Commodities & Chemicals. The L&LP business started in 1975 with the establishment of integrated Leather Complex at Dewas; manufacturing Finished Leather, Leather Garments and Footwear. The business has since consistently grown and has taken a global shape with a subsidiary in Hongkong; front offices in Shanghai, Dong Guan, London; supply chain bases in Bangladesh, China and across India (primarily Chennai); and global sourcing of raw materials & other inputs. L&LP Dewas & Chennai operations are ISO-9001 certified and the own manufacturing set-up at Dewas ISO 14001 certified tannery, largest in India. L&LP operates its business through three business lines Finished Leather, Leather Garments & Articles and Footwear. The three businesses are lead by respective Global Business Heads. L&LP is largest exporter of leather & leather products from India since 1982, with 3.8% share. L&LP has consolidated its leadership in the industry as worlds largest producer of Goat & Sheep leathers, being among top 10 producers. Energy Conservation & Management
58
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 Of Finished Leather worldwide and has already strategic plans in place for an exponential growth of around 20% per annum in next 3 years. The Leather Garment and Footwear Business exports products to the leading brands of the world. The Articles business is integrated with the Leather Garments Business and includes wide range of products from Luggage & Portfolios to Wallets & Purses. Our association with best international designers and design studio in Italy and Spain enable us to produce value added and customized products in vogue with the latest International trends. The Company is committed to good corporate citizenship by being proactive, integral and responsible member of communities and environment in which it operates. The companys Environmental Policy demonstrates its commitment to the environment. The principal potential impact of the L&LP operations on society is from its Dewas manufacturing facility. L&LP has been certified with ISO 14001 at Dewas which ensures that systems and processes are implemented for improved environment management. It won the Rajiv Gandhi National award for environment protection in the year 2002 and MP State Award for Environment Conservation In 2004.
59
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 After the collection of Meteorological data different PV modules were compared according to their efficiencies and types. PV modules based on thin film technology are not considered as their efficiency is less and there is probability of breakage. Around 5 % of breakage has been reported as per different case studies. Only Mono crystalline and polycrystalline PV modules have been considered for the project. Both monocrystalline and polycrystalline modules were compared on the basis of their efficiencies and cost. A Chinese company has been considered to supply the modules. Only modules with rated power greater than 200W have been considered for the project. 2.3 Selection of inverters Different inverters of rating 500 kW are compared from different companies as per the information given by the vendors. As inverter is to be connected to grid, only grid connected inverters are considered for the project. Inverters are compared on the basis of following parameters. Efficiency Total harmonic distortion. IP protection rating. MPPT voltage rating. Software for control and monitoring. Technology used in the inverter. Isolation protection. Standby losses. Maximum DC input current and DC voltage. 2.4 PVSYST software simulation The calculations done in the software are based on following inputs. Planned capacity. Location. Type of system. Type of module and type of mechanism required for mounting of PV array. Energy Conservation & Management
60
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 Inverter capacity. For shadow analysis we have to give the distance between the rows. Although this distance can also be optimized. After giving these inputs all the necessary calculations regarding number of modules to be connected in series and number of strings to be paralleled are done by software and based on these necessary calculations for the energy output of the system are done by software.
Solar Radiation (kWh/m2/day) S.No Month Tilt angle =250 Tilt angle =400
Jan
6.44
6.97
Feb
6.74
7.02
Mar
7.32
7.23
Apr
7.27
6.24
May
6.71
5.89
Jun
6.27
5.86
Jul
4.44
Aug
5.3
4.91
61
Sep
5.6
5.38
10
Oct
6.66
6.81
11
Nov
6.42
6.91
12
Dec
6.25
6.85
13
Avg
5.85
6.32
S.No
Parameter
Specification
Unit
260
Modules in a string
18
Nos
4.691
kW
Strings in an array
108
Nos
Total arrays
10
Nos
507
kW
19440
Nos
62
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 Table 3.3 Area requirements with the help of shadow analysis for PV arrays corresponding to tilt angle 250 and 400
Tilt angle
25 o
40 o
54.04
73.86
11673
15953
58363
79768
14
19
Onth
Wp
(Tavg)amb
(NOCT)rated (C)
(Gavg) (W/m2)
(Tcell)avg
Power cell
at
temp
63
Jan
260
21.6
45
5.56
10.9
510
34.35
-0.5%
247.842
Feb
260
23.65
45
6.24
11.4
547
37.33
-0.5%
243.965
Mar
260
28.4
45
6.59
12
549
42.12
-0.5%
237.732
Apr
260
31.5
45
6.49
12.6
545
44.37
-0.5%
234.804
May
260
31.95
45
6.18
13.2
468
43.65
-0.5%
235.749
Jun
260
29.10
45
5.52
13.5
408
39.32
-0.5%
241.381
Jul
260
26.55
45
4.03
13.3
303
34.12
-0.5%
248.137
Aug
260
26.10
45
3.12
12.9
288
33.30
-0.5%
249.197
Sep
260
27.15
45
4.83
12.3
392
36.96
-0.5%
244.442
Oct
260
27.45
45
5.83
11.6
502
40.01
-0.5%
240.480
Nov
260
25.35
45
5.82
11
529
38.57
-0.5%
242.344
Dec
260
22.40
45
5.36
10.8
496
34.80
-0.5%
247.250
Avg
280
26.31
45
5.51
12.13
459
38.24
-0.5%
242.788
64
65
5. Conclusions
After theoretical calculations the simulation of Grid connected 5 MW solar PV Power Plant was done with the help of PVSYST software. The module, inverter and all the meteorological data is taken from the software database and also the weather data files are imported from NASA database. The different tables and reports generated according to the inputs given in the software are given on the upcoming pages. System can be sized as per the requirement. Orientation and tilt angle can be optimized for maximum power production. Shadow analysis can be done in the software. Different losses can be calculated with the help of software. Calculations for normalized performance coefficients Calculations for inverter losses. Solar pumping systems and stand alone systems can also be designed and simulated with this software Cost analysis can also be done with the help of software.
66
References
Solar Energy- Principle of thermal collection and storage by S P Sukhatme and J K Nayak, Thired Edition, Tata-McGraw-Hill Publication company ltd, Delhi. Planning and Installing Photovoltaic System by- A guide for installers, Architects and Engineers www.susdesign.com www.solarphotovoltaic.net www.wikipedia.org www.indiasolar.com/ www.pvresources.com/en/inverter.php www.solardirect.com/pv/inverters/inverters.htm www.automation.siemens.com/mcms/solar-inverter.aspx PVSYST Software- Simulation and Shading analysis.
Adaptation of New Technology on Carbon Capture, Sequestration and conversion of fly ash into artificial zeolites SP Singh Ex. Council Member, Institution of Engineers (I) Member (UPSEB)
Reference:
International Conference on Green Power GenerationVision 2020 organized by The Institutions of Engineers (India), Anpara Local Centre at HINDALCO (Renusagar Power Division) Renusagar, Distt. Sonbhadra (UP) on 10th to 12th December 2010.
67
68
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 RGTU will be Principal consultant to this project and Institution of Engineers (I) will coordinate the entire activity. Another new technology discussed by the I E (I) forum is the Conversion of Fly Ash into Artificial Zeolites had to be installed in one of the above plants in the existing power belt of Singrauli region.
69
Abstract
This paper presents a cost effective way of tracking of Solar PhotoVoltaic panel using electronic sensors. Solar PhotoVoltaic Panels are used to harness Solar Energy. The main objective of this work is to utilize the maximum of solar radiation by minimizing the angle between solar incident ray and the normal to the tilted surface i.e. to minimize angle of Incidence.
Introduction
Electricity generation is the process of creating electricity from other forms of energy. Solar power is the conversion of sunlight into electricity, directly using photovoltaics (PV). The photoelectric effect refers to the emission, or ejection, of electrons from the surface of, generally, a metal in response to incident light. A photo voltaic panel is a series combination of PN junction. When sun radiation full of photons falls on PN Junction, results in diffusion which starts power generation. PV converts light into electric current using the photoelectric effect. Photovoltaic power generation employs solar panels comprising a number of cells containing a photovoltaic material. Materials presently used for photovoltaics include monocrystalline silicon, polycrystalline silicon, amorphous silicon, cadmium telluride, and copper indium selenide/sulfide. Sun path refers to the apparent significant seasonal-and-hourly positional changes of the sun (and length of daylight) as the Earth rotates, and orbits around the sun.
70
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 As we know the earth is tilted at 23.5 on its pole-to-pole axis. Due to this there is seasonal variation found where sun travels back and forth from north to south. The sun comes overhead at the places which are in between Tropic of cancer and Tropic of Capricorn. Due to this variation there is a slight change in radiation coming on earth.
Solar PV Tracking
There are various tracking systems as- Concentrated Photovoltaic (CPV) Module Trackers, Single Axis Trackers, Horizontal Single Axis Tracker (HSAT), Vertical Single Axis Tracker (VSAT), Tilted Single Axis Tracker (TSAT), Polar Aligned Single Axis Trackers (PASAT), Dual Axis Trackers , Tip Tilt Dual Axis Tracker (TTDAT), Azimuth-Altitude Dual Axis Tracker (AADAT), Active tracker, Passive tracker, Chronological tracker.
LDR SENSORS
The major sections of this tracking are listed below and will be explained in detail. Sensor Ball Bearing PV panel Electronic Ckt. DC Motor
71
1.
6.18
7.4
2.
6.68
7.8
3.
6.72
7.9
4.
5.62
6.6
Conclusions
The system developed is found to be very easy to implement. The maintenance is very less. System complexity is very less. The concept can be extended to Concentrator tracking with further R& D.
72
Technical paper on Energy Saving Aspect in Boiler Feed Pump in Thermal power plant
Santosh M. Mestry and Paresh Kumar Parhi [email protected], [email protected]
Profile
Power Plant Name Location Power Plant Capacity Dahanu thermal Power Station Dahanu, Distt- Thane, Maharashtra 2*250 Mw
Introduction
In a thermal power plant, steam is produced and used to spin a turbine that operates a generator. Shown here is a diagram of a conventional thermal power plant, which uses coal, oil, or natural gas as fuel to boil water to produce the steam. The electricity generated at the plant is sent to consumers through high-voltage power lines.
73
BFPs FD FANS
LT MOTOR LOAD 5% MISC. 1%
IDFANS 2.37 2.78 PAFANS CEP 0.26 0.29 0.35 1.41 0.22 1.38 MILLS CHP AHP Comp.air 0.74 0.26 Others
There are 3-case study explained on Energy Saving Aspect in Boiler Feed Pump Replacement of pump cartridge Drum Level Controlled by BFP SCOOP operation in 3-Element mode instead of DP mode Replacement Of Recirculation Valve Of Boiler Feed Pump
74
Observation
The Boiler Feed Pump at DTPS is of multistage (three stage) type. It was observed that the BFP-2B is taking much higher current than other BFPs. From performance curve of the pump also it was clear that it is consuming much higher power corresponding to the flow. Technical & Financial analysis Three root causes shortlisted from technical analysis. Wear & tear of pump internals due to ageing Possible damage to internal gasket Short-circuiting of suction and discharge chambers It was concluded that loss is taking place due to interstage leakage or recirculation. Hence decision was taken to replace the cartridge of pump.
75
Impact of Implementation After replacing the cartridge the current drawn reduced by 70 Amp. Power saved per day = 3*V*I*PF* 24 = 1.73*6.6Kv*70amps*0.85 * 24=16304 KWH Power saved per year=5950960 KWH Saving of cost= 5950960*3.5= Rs2,08,28,360 Simple Pay Back Period: 70 days with 40 Lakh Rs. Investment
Case Study -2 :
Drum Level Controlled by BFP SCOOP operation in 3-Element mode instead of DP mode.
Background
Boiler drum level control is done by BFP scoop & feed water regulating station (FRS) control valve in two ways, DP mode Three element mode In DP mode BFP scoop maintain the DP across the FRS as per set point & control valve regulate feed water flow as per three element errors to maintain drum level as per set point. Whereas in three element mode, scoop maintain the drum level as per three element error keeping FRS control valve wide open.
76
Observation:
In most of units having MD BFP only, drum level control is accomplished through DP mode because it believed that is robust control. But it results in appreciable energy loss due to throttling of FRS valve. DP set point for scoop is observed between the range of 7-10 kg/cm2; hence same is the pressure drop across FRS valve. Reason of high DP set point to increase differential pressure to improves the control. Disadvantage of DP mode is increased pressure loss & Energy loss.
Pump Power
DP optimization in DP mode gives no substantial energy saving due to action of FRS valve. Further pressure drop reduction is only possible in three element mode scoop operation where FRS valve is kept fully open
Pump power (100- efficiency) Pump losses % = Generated Load In 250 MW capacity unit having overall efficiency of 38 % and for pump power = 7 MW, DP =7.5 kg/cm2, Total pr. Developed by pump = 180 kg/cm2,
------------------------------------
77
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 Energy saving potential & Calculated pump loss is given below which are unusually high figure. Energy saving potential =29 % Calculated pump loss = 1.736 % of Boiler Heat I/P As flow control by throttling in case of high power pump like BFP is inefficient, flow control by speed regulation by means of BFP scoop is adopted.
78
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 FLOW In the above system, pump system curve get shifted to lower efficiency region as throttling increases. Point A is the best efficiency point (BEP) where valve is full open at the pumps best efficiency point (BEP). But, in actual operation, amount of flow in valve full open condition is not necessary hence we throttle the valve. To point B to get desired flow. The reduction in flow rate has to be effected by a throttle valve. In other words, we are introducing an artificial resistance in the system. Due to this additional resistance, the frictional part of the system curve increases and thus the new system curve will shift to the left -this is shown as the red curve. So the pump has to overcome additional pressure in order to deliver the reduced flow. Now, the new system curve will intersect the pump curve at point B. At point B, pump head is increased the red double arrow line shows the additional pressure drop due to throttling. You may note that the best efficiency point has shifted from 82% to 77% efficiency. So what we want is to actually operate at point C which is on the original system curve for the same required flow. The head required at this point is reduced. What we now need is a new pump which will operate with its best efficiency point at C. But there are other simpler options rather than replacing the pump. The speed of the pump can be reduced or the existing impeller can be trimmed (or new lower size impeller). The blue pump curve represents either of these options. It is not feasible to replace pump or trimming of impeller, best solution is to reduce the speed. Hence flow control by speed control method is more efficient. DP control mode & three element mode schematic is given below. Scoop operation in DP mode Scoop operation in three element mode
79
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 Changeover philosophy from DP mode to three element mode. (SCOOP Operation- DP mode & Auto. FRS valve- Auto) Take SCOOP and FRS control Valve in MAN. Select three element mode of scoop operation. Put scoop in AUTO. Observe scoop operation. Gradually open the FRS valve fully.
AMP. Gain/Hr
KW saving/Hr
BFP-1A
10
97
83
BFP-1B
2.6
25
21
BFP-2A
4.2
40
35
BFP-2B
14.2
137
118
Changeover philosophy from Three element mode to DP mode. (SCOOP Operation- Three element mode & Auto. FRS valve- Manual) Set the required DP set point Gradually close the FRS valve so that DP across valve matches the DP set point Take SCOOP in MAN. Select DP mode from three element mode. Put SCOOP & FRS valve in AUTO. Observe the response. DP mode is suitable in case of emergency & fluctuating load condition whereas three element mode is suitable in steady load condition. Impact of Implementation:
80
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 In DTPS, BFP scoop operation successfully tested in three element mode for each BFP. Pressure drop across FRS valve is observed to be @ 3.5 kg/cm2 in valve full open condition. Ampere saving achieve is given above Table. Difference in energy saving may be due to change in vacuum, operating drum pressure & metering error. BFP hydraulic couplings response time and subsequent change in drum level shows that drum level control directly through BFP scoop operation in three element mode variation is quite feasible especially under steady operating condition. Simple Pay Back Period: Immediate with Nil investment
Case Study - 3 :
Replacement Of Recirculation Valve Of Boiler Feed Pump
Background
Boiler Feed pump is supplied with suction strainer, NRV on the pump discharge and modulating minimum flow re-circulation system. Recirculation line is provided before discharge valve with a pneumatic control valve, which maintains a minimum flow of 240 T/hr. This valve avoids dry run and overheating of pump.
Observation
It was observed that after certain running hours the suction flow of a loaded pump was much higher than the discharge feed water flow. Technical & Financial analysis When recirculation valve of the BFP was further closed, the difference got reduced. Hence the manual isolating valve was closed and it resulted in drastic reduction of suction flow . Now the suction flow was matching with the discharge feed water flow. Hence it was suspected that some flow is passing through valve seat. After due maintenance of the existing valve not much improvement was observed. Hence it was decided to replace the existing valve with an advanced class of drag technology valve.
81
Impact of Implementation:
After replacement of valve the current drawn by the motor of pump reduced by 60 amp. Power saved due to the reduction current drawn by motor = 6.6*60*1.73*0.85 Power saved= 582 KWH/HR Saving in cost/hr = 582*3.5= Rs 2037 Saving/year Investment =2037*24*365=1,78,44,120 = Rs 2500000
Simple Payback period = 2500000 / 2037 = 51days Same valve replaced in all the 4 BFP with an investment of 1 crore which resulted in saving of Rs 7,13,76,480.
Conclusion
Thermal power plants contribute 70% of Indias power generation installed capacity. It is not possible to meet the growing demand due to long gestation period of power plant. Only solution is to reduce auxiliary power consumption by energy conservation & energy efficiency practices. There is tremendous scope in power sector for reducing auxiliary power consumption (APC). In India, It is estimated that; reduction in APC by 1%, equvivalant of generation of 5000 Mu of energy per annum. Saved energy can be sold out. to minimize the gap between supply & demand. This changed scenario impacted the bottom line of power generation utilities. Hence the ways to retains ones competitive edge in the fiercely competitive industry.
82
Heat Recovery Hot Water Heater Desuperheater in Refrigeration System Vrajalal Kanetkar [email protected] www.refreconmagic.com
Process Industries / hospitality Industries requiring hot water Hospitality Industry Hospitals Chemical and Pharmaceutical Industries Economiser for Boiler water Pre-heater Dairies and milk processing plants Engineering Industries Compressor Heat Recovery for Air Compressor Waste heat recovery to make hot water from air conditioning compressor (use of our Desuperheater ) is one the major tools available for Hospitality industry in general. Hospitality, Pharmaceutical, Dairies, and Process Industries have also adopt this in recent past. Techno-commercial advantages of this heat recovery are incredible and this is why international institutes like ASHRAE, CADDET, AEE, DOE in USA and now number of Indian users are strongly supporting this concept. Dairies and Hotels are bulk consumers of hot water at 500 to 700C. Invariably this hot water is generated using prime energy either fuels or using electricity. In recent past good number of users meet their requirement through solar hot water heaters. . Using high-grade waste heat to generate hot water for boiler was a common practice adopted by users as well as manufacturers for decades. There are number of good manufacturers to supply this system for industrial application. We are discussing here commercial success of low-grade heat in reciprocating or screw compressors to generate hot water. At REFRECON we have now more than 100 successful installations saving crores of rupees for our customers (Aggregate savings withal installations put together.)
83
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 Users or refrigeration systems and air compressors are at great advantage to offset their hot water heating cost by implementing heat recovery. Users of REFRECON system have reduced 50 to 70% of hot water heating cost along with number of other benefits. Successful heat recovery normally has several cascaded hidden benefits. Refrecon has several success stories of recovery of this low-grade heat. Adiabatic compression process generates high temperatures depending upon type of compressors used. Reciprocating compressors have higher temperature after compression where as screws normally have lower delivery gas temperature. But both have potential to deliver usable hot water for process need. Dairies and Star Hotels are potentially large consumers of refrigeration and hot water. Cascading heat recovery with cooling effect has great advantage for the system efficiency improvement along with reduction of energy cost by adopting this heat recovery. Retrofitting old systems or installing new systems with hot water desuperheater gives great advantage of operating cost reduction as well as stable and efficient operation of refrigeration system. Superheat in refrigeration is necessity for stable and safe process operation. Same superheat is also cause to reduce operation efficiency of compression. Heat Recovery Hot Water Heater - Desuperheater installation with refrigeration is boost to dairy and hotel industry in general saving operating energy cost and avoiding pollution due to fuel use. This also has added advantage of eco-friendly image building when globally every one talks of green gas emission reduction. All compressors deliver hot gas/air at outlet and this gas is either condensed or cooled after compression rejecting heat to atmosphere. Converting this hot gas into hot water substantially reduces heating cost to generate hot water. Enclosed schematic technically explains mode of connecting this heat recovery system. Material of Construction (MOC) will depend upon the type of gas/air handled by compressor. While SS is most safe for water some times comer also can be deployed to optimise cost of manufacturing. Some built in safeties are essential to ensure We will discuss two specific applications in this paper.
Dairy and milk Processing Hotels, hospitals or hospitality industry 1. Dairy and milk Processing
Refrigeration and boiler constitute more than 75 % of operating energy cost of dairy. As much as dependability of these systems is important, operating plant efficiency and consistency in performance is also required to limit processing cost of milk. Built-in improvement in operating efficiency constitutes major saving opportunities in dairy utility system. Installation of desuperheater for recovery of waste heat is major step in this direction.
84
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 REFRECON has several successful desuperheater installations in operation since past eight years. The technology is successfully implemented for various systems using ammonia and R 22 refrigerants.
85
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 ADS series of REFRECON desuperheater is specifically designed for ammonia compressors. MOC and process parameters are appropriately matched for life long consistency in performance. The fully welded construction of desuperheater has complete safeties required for installation and infinite life of operation. The desuperheater is capable to withstand 40 bar pressure and is tested for bubble-tight leak-proof performance at 25 bar pressure in the manufacturing process. The perfected design results in flaw less commissioning during field installation. The performance consistency has been proven with number of installations. Though available heat potential for reciprocating compressors is large REFRECON has successfully installed desuperheaters on ammonia screw compressors (180 TR and 250 TR) and proved its commercial viability.
86
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 1 kWh of electricity delivers 28 liters of hot water at 550C Hotel uses 200 to 300 liters hot water per occupied room Dairy needs 0.5 to 0.75 liter hot water at 600C for general sanitation per liter of milk processed. There are hundreds of success stories of heat recovery desuperheater. Every year Beuro of Energy Efficiency (BEE) under Ministry of Power gives energy conservation awards for outstanding efficiency improvement performance in India. Since 2006 award winners in dairy sector successively have been honored who have been users of REFRECON desuperheater and it is proud moment for us to say that each of these award winners have praised for REFRECON desuperheaters in their presentation to BEE as well as expressed same opinion on their website. Needles to say we are proud of our customers for this action.
87
Cold storage design and operational parameters influencing energy consumption in composite climate of Indore
R.K. Singh, S.P. Singh, R.L. Sawhney [email protected] Abstract
With high economic growth rates India is a significant consumer of energy resources. Like the other sectors, cold storages are also the significant consumers of electrical energy. In this paper, few energy influencing parameters of cold storages were discussed. The study is based on the survey results of the actual potato cold storages and it is able to explain the energy consumption patterns and energy consumption levels of cold storages. The trend analysis and regression methods were used in the study to explain the influence of the parameters on specific energy consumption. The results show that the capacity utilization factor, aspect ratio and overall heat transfer coefficients of cold storages significantly affect the energy consumption of the cold storages.
Key words: Cold storage, Energy consumption, Energy efficient building Introduction
With high economic growth rates and over 15 percent of the worlds population, India is a significant consumer of energy resources. In 2009, India was the fourth largest oil consumer in the world, after the United States, China, and Japan. Despite the global financial crisis, Indias energy consumption has risen remarkably in the past few decades. As the energy demand increases, energy conservation has been included on the agenda of the developing countries like India [1]. Like the other sectors, cold storages are also the significant consumers of electrical energy and will increase in future. Potato is a most eatable vegetable and used throughout the year in human diet. The perishable nature of potato forces to keep it in a controlled environment. India is one of the countries where potato is grown in large quantities. Being a second largest producer of potato, India produces about 30 million tons of potato every year. The huge quantity of potato has gone wastage every year due to lack of sufficient storage facility in the country [2]. Therefore, it is urgent need to develop the sufficient storage facility for reducing wastage and emergences the opportunity to the producers for selling out their potato commodity at good value. Energy saving potential in Indian potato cold storages was reported earlier [3]; however, there is no clear cut indication of energy consumption pattern of cold storage. In this situation, it becomes very significant to identify and figure out the parameters those influence energy consumption of potato cold storages to further development of new energy efficient cold storages, so as to put forward the corresponding energy saving measures.
88
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 In this study, the impact of aspect ratio and effective overall heat transfer coefficient on the energy consumption of potato cold storages were discussed using the trend analysis. Also, the variation in energy consumption with capacity utilization factor was analyzed. Results arising from this study provide important reference materials for the cold storage designers, architects, consultants, owners and operators in assessing electricity energy consumption patterns and selecting a more accurate approach to estimate future energy demand. However, study is limited for a small cluster of the composite climate in the country and results may influence in other part of the same climate or in other climatic conditions. Therefore, similar study for other parts of the country would be more significant for better results.
Study region
The surveyed cold storages are located in Indore region, which is a big chunk of cold storages. Indore is located in the mid western part of India South of the Tropic of Cancer (latitude 22.71N, longitude of 75.91E). About 52 cold storages are functioning for preserving perishable items like potato and help greatly to regulate the demand and consumption of these items throughout the year. The climate of Indore is composite having three distinct seasons summer, monsoon and winter.
89
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 Data of energy consumption and storage pattern for 10 cold storages were collected for four consecutive years (2001-2004). The Specific energy consumptions (SEC) for four consecutive years (2001-2004) are given in Table 1. The respective storage patterns of cold storages are shown in Figure 1. Table 1. Annual Specific Energy Consumption (SEC) of Potato cold storages
Cold Storage
Y-2004
Y-2003
Y-2002
Y-2001
10.07
10.86
10.77
10.49
10.01
9.92
12.33
13.69
9.00
9.90
12.79
13.00
14.63
14.96
13.67
21.47
12.79
13.38
11.30
12.58
9.47
9.92
10.17
9.66
9.70
10.84
10.38
10.61
15.56
16.82
9.64
10.80
11.35
12.05
26.08
13.81
12.15
8.90
11.93
12.38
90
Figure 1. Annual potato storage patterns for years 2001-2004 Buildings of cold storages still remain the second largest consumer of energy and will be singled out for the present study as a target for energy conservation. In general, the factors that affect cooling energy consumption in a cold storages building include thermal conduction gains through building envelop and infiltration. The amount of thermal conduction gain mainly depends on aspect ratio; envelop orientation, exterior colour, construction materials as well as shape of buildings [4-7]. The survey was done for all described parameters of building envelop of cold storages. The buildings were insulated and rectangular in size with sloping roofs. A false flat ceiling were constructed and sloping roof works as shading device, which restricts the direct solar radiation from the roof. Building envelope for all cold storages were constructed in similar manner and bricks, and RCC used as construction materials. The walls and roof consists of a number of layers with different thicknesses and construction materials. The arrangement patterns of layers used in construction of buildings of surveyed cold storages are given in Table 2. Table 2. Construction pattern of false ceiling and walls
Construction layers
False ceiling
Wood
Tarcol Sheet
Thermocole
Plaster
Wood
Walls
Plaster
Brick
Plaster
Thermocole
Iron net
Plaster
91
Refrigeration units require to controls the indoor storage environment at required temperature level and maintain the quality and flavour of stored produce. Surveyed storages were maintaining at 20C and 80-95% humidity using the conventional vapour compressor refrigeration systems. The major components of a vapor-compression refrigeration system include a reciprocating compressor, a condenser, receiver, expansion valve and an evaporator. The compressors room of a cold storages refrigeration unit is shown in Figure 3.
Figure 3. Compressors room of a refrigeration unit in a cold storage Two types, i) bunker type and ii) fan coil units (FCUs), of air-handling units (AHUs) were used in the cold storage for inside air circulation (Figure 4). About 80 percent cold storages were using bunker type air handling units and other 20% fan coil unit type. The air handling units were kept in the top of the cold storages chambers and cool the inside air by re-circulating the indoor air continuously. The indoor air removes completely in the morning hours every day and fills fresh air into the chambers accordingly.
92
The specific energy consumption is the only suitable and sufficient parameter to explain the energy consumption pattern of cold storages. It can be seen from Table 1, the specific energy consumption is varying between 9-25 kWh/ton/year that clearly indicates the sufficient potential for reducing it. The variation in specific energy consumption defiantly influenced by various buildings as well as refrigeration parameters. The trend analysis focuses on the impact of individual predictors on SEC acting alone.
17 Specific energy consumption(kWh/ton) 15 13 11 9 7 5 0.2 0.3 0.4 0.5 0.6 0.7 Capacity utilization factor(ton/ton) y = -14.163x + 17.907 R2 = 0.6267
93
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 The average negative slope of the SEC with changes in CUF was 14.163 kWh/ton that mean the increase in CUF by 0.1 decreases the energy consumption by 1.46 kWh/ton. Beyond a CUF of 0.35, the change in SEC is marginal and before 0.35 value of CUF, the SEC increases significantly. This indicates that the specific energy consumption is affected a little for capacity utilization factor above 0.35; however, lower value of capacity utilization factor is one of the significant causes for higher energy consumption. It is recommended to the owners and operators, to operate the cold storages for higher value of CUF or they should use the partial volume of the cold storages for efficient operation.
H/L 0.4 17 Average specific energy consumption(kWh/ton/year) 16 15 14 13 12 11 10 0.20 0.21 0.33 W/L 0.43 0.59 0.64 0.37 0.8 0.63 0.91 1
Figure 6. SEC vs. aspect ratios The minimization of the external surface area for a specified volume will reduce the heat gain through the building envelope and ultimately energy consumption. As clear from the Figure 6, the specific energy consumption of cold storages vary with aspect ratio and found the building having W/L=0.64, H/L=1 values of aspect ratio is better from the energy efficiency point of view. However, the values of aspect ratios for lower energy consumption may change with location and climatic conditions. efficient cold storage in future. Therefore, further studies for other climates and locations would strengthen the concept and helpful to setup the guidelines for designing energy
94
Effect of U value
Overall heat transfer coefficient of building envelope is one of the most important thermophysical properties affect the thermal performance of the building envelope and it is easy to control by minor modification or adopting energy efficient designs. The values of overall effective heat transfer coefficients were calculated for each cold storage from the collected data and correlated with respective specific energy consumption as shown in Figure 7. The expected pattern of energy consumption can be observed from the Fig. 7. Higher the effective heat transfer coefficients, higher the energy consumption. The optimization of effective overall heat transfer coefficient values are recommended for composite as well as other climatic conditions for minimizing the energy consumption of the cold storages.
0.35
0.4
18 Average specific energy consumption(kWh/ton) 16 14 12 10 8 6 4 2 0 0.03 0.031 0.032 0.033 0.034 0.035
Figure 8. SEC vs. Specific refrigeration capacity Energy Conservation & Management
95
18 Average specific energy consumption(kWh/ton) 16 14 12 10 8 6 4 2 0 2.35 2.4 2.45 2.5 2.55 2.6 2.65 y = -0.5681x + 13.662 R2 = 0.0007
Figure 9. SEC vs. Specific AHU capacity The trend indicates the minor increment in the specific energy consumption with increase in specific refrigeration capacity, on the other hand negative slope in the trend line indicates the specific energy consumption decreases with increase in specific capacity of AHU. However, the correlation coefficients are not so strong and needs further study of greater number of samples. The study is based on a small cluster of composite climate and results may vary for other climates and locations, therefore, further study for other climatic zones of India would be helpful to set the guidelines for setting up new energy efficient cold storages.
Conclusion
Based on survey of 10 cold storages in composite climate of Indore, the parametric study was performed for analyzing the impact on energy consumption. The trend analysis method is used to identify the factors of cold storages that affect the specific energy consumption of cold storages. The factors, namely capacity utilization factor, aspect ratio and overall heat transfer coefficients of cold storages are found to be significant parameters. The purpose of this study was to establish a help for architects, engineers, consultants, owners and operators to take into account the impacts of design and operation choices on energy consumption while designing and operating the potato cold storages. Also, some recommendations were made for energy efficient operation and designs of cold storages.
96
References
Bureau of Energy Efficiency, Ministry of Power, Government of India (www.bee-india.nic.in) www.indiastat.com Ramkishore Singh, Singh, S.P., Singh R.N.(2010). Energy saving potential in Indian cold storages. 2ndBharatiya Vigyan Sammelan held on 1-3 December, 2010, DAVV, Indore. Kaur, J., Singh, S.P., Sawhney, R.L. and Sodha, M.S. (1991) Optimum Layered Distribution of masonry and insulation of building component. International Journal of Energy Research, 15, 11-18. Kumar, A. Ashutosh, S. and Sodha, M.S. (1989) Optimum distribution of insulation over various components of air-conditioned building, Building & Environment, 24(2), 169-178. Bansal N.K., Shail and Garg S.N. (1997) Calculation of solar radiation intercepted by Nubian Vault and Dome Shaped Building. International Journal of Energy Research, 21, 723-736. Sodha, M. S., Jagjit Kaur and Sawhney, R. L. (1992) Effect of orientation on thermal performance of a building. International Journal of Energy Research, 16, 709-715
97
Present Scenario:
Economic growth, industrialization and growing population in the developing countries of Asia especially India demand a huge growth in energy supplies in the region while global environmental problems call for cuts on fossil fuel use, which keeps Power sector in continuous focus. Today the sustainable world energy policy is based on end-use-oriented energy strategy technically called Demand Side Management (DSM). If fusion of proper DSM models and mechanisms with proper technology can be achieved then the shortfall in the energy production can be compensated to a greater extent by efficient use of energy. This energy-useoriented approach leads to an energy efficient future that is much-less capital and resource intensive and more environmentally benign which is the need of the hour for countries like India. As per an estimate about 17% of total power generated in INDIA is consumed for lighting alone and use of energy efficient lighting itself can make a big difference in the total energy scene of the Nation (estimated total generation of the country is 150000MW and if even 15% of lighting load can be saved means 3825MW). At present the scope for energy saving in lighting sector, especially in community light is up to 50%. Electromagnetic Induction Light is the most energy efficient light source so far known to mankind for highway lighting, but we are unable to explore the benefits of this light source. This paper will discuss the barriers (Technological, commercial and policy intervention) in promoting the Electromagnetic Induction Light in the country and also attempt to address the likely policy intervention for up scaling the use of Electromagnetic Induction Light including the need of institutional/research capacity enhancement and public awareness.
98
Demerits:
Very high recurring energy usage costs and low power factor maintenance despite the initial low procurement cost. Very less life ( Only 10000 to 12000 Hours of useful life) Poor illumination at the ground level for HPSV, LPSV, Metal Halide and CFL lamps. Severe degradation in Lumen Output after first 4000 Hours of operation (Up to 40%). Poor Color Rendering Index (CRI) Well below the national and international standards for HPSV, LPSV and Metal Halide Lamps. Very long start and re strike time (8 to 10 minutes) for HPSV, LPSV and Metal Halide Lamps. Generate excess amount of heat. Presence of UV radiation and liquid mercury poses environmental threat.
So the demerits of these lamps outweigh their merits in a big way. Energy Conservation & Management
99
Demerits:
Very high initial cost of procurement. Very low life of the ballast or driver of the lamp primarily due to excess heat generation and high current dependence for more light.( Up to 12000 Hours only) LED lamps of higher capacity (>18W) are very bulky and in certain cases rendered unfit for pole mounting. LED lamps of capacities higher than 100W are not available easily and are very costly and LED lamps of lower capacities are not suitable for outdoor street lighting. LED Lamps produce enormous glare at the top but provide very low lumen output at the ground level.
So the LED Lamps also prove to be a gloomy replacement option for the conventional lighting products. With the above mentioned scenario and the analysis of presently available lighting solutions, the stage is now set to look for such an option that addresses the present concern for energy efficiency, while accommodating the mentioned merits and at the same time negating the demerits of the available conventional lighting systems as well as much hyped LED lighting systems. The first question that arises now is that Does such a lighting solution like this exist? Our answer is- YES The second question that arises is that What is that option? The obvious answer is- ELECTROMAGNETIC INDUCTION LIGHTING
100
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 In the following sections, we would like to highlight the details, advantages and disadvantages of Electromagnetic Induction Lighting, its applications and its future commercial viability in a power hungry country /economy like India.
Nikolas Tesla
The dream of lighting inventors has been to produce a lamp with no internal electrodes so as to eliminate these common failure modes. In an electrodeless lamp the envelope [bulb] is completely sealed and thus there is no chance of atmospheric contamination due to seal failure and no electrodes to wear out over time. In June of 1891, Nicholas Tesla was granted a US patent to cover a very early form of Induction lamp. Nikol a s Tesla demonstrated wired and wireless transfer of power to electrodeless fluorescent and incandescent lamps in his lectures and articles in the 1890s, and subsequently patented a system of light and power distribution on those principles. Noting the diagrams in Tesla's lectures and patents, a striking similarity of construction to electrodeless lamps that are available in the market currently is readily apparent. Further, a statement in 1929 by Tesla, published in The World : Surely, my system is more important than the incandescent lamp, which is but one of the known electric illuminating devices and admittedly not the best. Although greatly improved through chemical and metallurgical advances and skill of artisans it is still inefficient, and the glaring filament emits hurtful rays responsible for millions of bald heads and spoiled eyes. In my opinion, it will soon be superseded by the electrodeless vacuum tube which I brought out thirty-eight years ago, a lamp much more economical and yielding a light of indescribable beauty and softness.
101
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 ballast, is sent through wires, which are wrapped in a coil around the ferrite inductor, creating a powerful magnet. The induction coil produces a very strong magnetic field which travels through the glass and excites the mercury atoms in the interior which are provided by a pellet of amalgam (a solid form of mercury). The mercury atoms emit UV light and, just as in a fluorescent tube, the UV light is up-converted to visible light by the phosphor coating on the inside of the tube. The system can be considered as a type of transformer where the inductor is the primary coil while the mercury atoms within the envelope/tube form a single-turn secondary coil.
Applications of Electromagnetic Induction Light In hard-to-reach locations that make maintenance costs high, such as street lighting and tunnels, or in high ceilings where there is continuous operation. Cold environments, such as supermarkets, walk-in coolers and freezers. Where high-quality lighting is required or highly desirable. Where reliability is highly valued. Where high lumen output is required. In areas that require lamps to reach full illumination immediately. In industrial factories, workshops, mines, backyard, sport, high security areas, etc.
They are also ideally suited for such applications where the advantages of fluorescent lighting are sought but a light source is needed that can start and operate efficiently in extremely cold temperatures. As a result, induction lighting is a suitable for a wide range of applications, including not only warehouses, industrial buildings, cafeterias, gymnasiums, etc., but also signage, tunnels, bridges, roadways, outdoor area and security fixtures, parking garages, public spaces, and freezer and cold storage lighting.
102
103
104
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 is called Pupil Lumens or Visual Acuity Lumens and is now being considered as the most important factor in deciding the energy efficiency and quality of the light in addition to CRI and CCT. Electromagnetic Induction Lamps score significantly here as they achieve very high P/S ratio of 2.0, whereas low pressure sodium vapor and high pressure sodium vapor lamps achieve a low P/S ratio of 0.38 and 0.76 only respectively eventually degrading their effective lumen output resulting in poor visibility. The economics of using Induction lamps is favorable over life cycle.
Conclusion:
Electromagnetic Induction Light sources pose technical challenges, most of which have been addressed by vendors now that the technology is nearly a decade old. Early systems faced concerns about electromagnetic interference from the field generators, but today's products meet FCC 47CFR Part 18 Non-Consumer certification, and complaints are just about nonexistent.
GOVERNMENTAL CONSERVATION
INTERVENTION
REQUIRED
FOR
ACHIEVING
ENERGY
Unlike many other energy efficient gadgets, Electromagnetic Induction Light fails to attract the attention of Government policy makers for a Electromagnetic Induction Light promotional scheme on National level as in the case of Compact Fluorescent Lamp-CFL (National scheme of Bachat Lamp Yojna is launched to promote use of CFL) In order to promote efficient use of available energy sources specially in lighting sector followings are the suggestions for Energy efficiency measures under DSM:
Government should make a Nation Wide Energy Efficiency-Demand Side Management (EE-DSM) plan to promote use of Electromagnetic Induction Light where ever it is possible.
Government should make stringent standards for quality Electromagnetic Induction Light gadgets, may be Energy Star labeling be done on Electromagnetic Induction Light products to ensure the quality of the gadget.
For hoardings and signboards use of Electromagnetic Induction Light must be made mandatory. A National body that addresses the new research and carries quality testing for Electromagnetic Induction Lighting gadget is also suggested.
From the details given above it becomes very clear that the option of Electromagnetic Induction lighting is one of the most energy efficient way and will help in National Demand Side Management program. By keeping in view the supply demand gap in the energy requirements of our country, Electromagnetic Induction lighting is the need of the hour and it deserves due promotion and recognition from the government. Use of Electromagnetic Induction lights is economical and environment friendly. With the help of Government
105
FIRST INDIA INTERNATIONAL ENERGY SUMMIT-2011 intervention use of Electromagnetic Induction lights can be made multifold and this will conserve energy which can be used to bring the new era of lighting to those villages that are still away from even a light source.
106